This structure has been designed in accordance with the requirements of the 2014 Florida
Building Code, Fifth Edition - Residential, Chapter 3, Section R301.2.1. The following
wind load requirements, in accordance with 2014 Florida Building Code, Fifth Edition -
Building, Chapter 16, Structural Design, Section 1609 and ASCE 7-10 were employed in
the design of the structure:
Ultimate Design Wind Speed (V„ It): 150 MPH
3-Sec6nd Gust Wind Speed (Vasa): 116 MPH
Risk Category: I
Wind Exposure Category: B
Applicable Internal Pressure Coefficient: +/- 0.18 (Utility Shed)
Design Pressure for Exterior Components & Cladding:
• Walls = +21.8/-25.6 PSF
• Roof = +8.5/-26.8 PSF
Applicable Internal Pressure Coefficient: +/- 0.00 (Carport)
Design Pressure for Exterior Components & Cladding:
• Walls = N/A
• Roof = +/-15.0 PSF
Applicable Internal Pressure Coefficient: +/- 0.00 (Screen Room)
Design Pressure for Exterior Components & Cladding:
• Walls = +/- 18.6 PSF
• Roof = +/-15.0 PSF
TNg§# PLANS AN8 ALL PROPOSED WORK
4NE @U®JSC7 rO ANY CORRECTIONS K
AVf3- SVFIELD INSPECTORS THAT
comp
SS NECESSARY IN ORDER TO
�aAi�LY Y" ALL APPLICABLE CODES.
CONCEg160
fASTFNEqe,�
,
ARETN,FgES�,ONSIBILliyOF
�R�ENTS
CONTR,gCTOR OFREC080 T HE
Davis & Cleaton Engineering, Inc.
260 Wekiva Springs Road
Suite # 1060
Longwood, FL 32779
FL P.E. License # 35816
�Jd - a/0 9
S'T. LUC?F' ANTY BL'ILnL!'C'DIVISION
R.EVIER'ED FOR C Le
REVIEWED Y�GJy
DATE
PLA\S A\ PERMIIT M ST BE KEPT ON JOB
OR NO INSPECTION WILL BE yiADE.
olZ� mie copy
345 Seahorse Terrace
Ft. Pierce, FL
WIND LOADS ON EXTERIOR OPENINGS
OPENING SIZE TOTAL TOTAL POSITIVE NEGATIVE LENGTH OF LOAD PER LIN.
AREA LOAD WIND LOAD WIND LOAD BUCK ATTACHMENT FT. OF BU.
(Ft.2) (Lbs.) (PSF) (PSF) (In.) (LB. per FT.)
Window 3'-0 x 3'-0" 9.0 312 25.9 34.7 108.00
Door T-0" x 6'-8" 20.0 648 24.7 32.4 196.00
1.) For exterior windows, use 1x4 P.T. buck on jambs and head.
2.) For exterior doors, use 2x4 (Min.) P.T. buck on jambs and head.
3.) For garage door use minimum 2x6 P.T. buck for jambs and required spring pads.
4.) Provide enough fasteners of type used to equal or exceed stated loads on table.
Fasteners are required no closer than 2" or more than 4" from ends and spaced
equal in distance along balance of buck.
Minimum fasteners for top buck is 2.
** Minimum fasteners for side buck is 3.
Approved Fasteners:
3/16 Tapcon with 1 %" penetration = 230 lb. of holding power.
%4" Tapcon with 2" penetration = 380 lb. of holding power.
See manufacturers specification for required fasteners to attach garage door, entry doors, patio doors and
windows to building. Note: Garage door "bucks" shall be attached to studs with 3/8"x4" lag bolts. Spaced
each 24" o.c. with minimum of 3 bolts.