Loading...
HomeMy WebLinkAboutEvaluation Report Modified BitumenTRINITY1 ERD EVALUATION REPORT TRI-BUILT Roofing Products 9050 Louisiana Street Merrillville, IN 46410 RECENED NOV 0 6 2017 PERMITTING St. Lucie County, FL EXTERIOR RESEARCH & DESIGN, LLC. Certificate of Authorization #9503 353 Christian Street Oxford, CT 06478 PHONE: (203) 262-9245 FAX: (203) 262-9243 Evaluation Report A42970.10.12-111 FL16027-R1 Date of Issuance: 10/23/2012 Revision 1: 03/23/2015 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for compliance with the 5th Edition (2014) Florida Building Code sections noted herein. DESCRIPTION: TRI-BUILT Modified Bitumen Roof Systems LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. TrinityJERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 4, plus a 27-page Appendix. Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCA ANE1983 The facsimile seal appearing was authorized by Robert Nieminen, P.E. on 03/23/2015. This does not serve as an electronically signed document. Signed, sealed hardcopies have been transmitted to the Product Approval Administrator and to the named client CERTIFICATION OF INDEPENDENCE: 1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. Exterior Research & Design, LLC, d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. File C� I-_ -_ �Y ROOFING SYSTEMS EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Modified Bitumen Roof Systems Compliance Statement: TRI-BUILT Modified Bitumen Roof Systems, as produced by Allied Building Products Corp. / TRI-BUILT Roofing Products, have demonstrated compliance with the following sections of the Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Property Standard Year 1504.3.1 Wind FM 4474 2004 1504.7 Impact FM 4470 1992 1507.11.2 Physical Properties ASTM D6163 2000 1507.11.2 Physical Properties ASTM D6164 2005 1507.11.2 Physical Properties ASTM D6222 2008 3. REFERENCES: Entity Examination Reference Date ERD (TST6049) Physical Properties P10490.10.08-2 10/30/2008 ERD (TST6049) FM 4470/4474 P13760.09.09 09/10/2009 ERD (TST6049) FM 4470/4474 P13770.09.09 09/10/2009 ERD (TST6049) FM 4470/4474 P30540.11.09-R1 11/30/2009 ERD (TST6049) FM 4470/4474 P30550.12.09 12/02/2009 ERD (TST6049) Physical Properties P33960.12.10 12/30/2010 ERD (TST6049) FM 4470/4474 P33970.03.11 03/15/2011 ERD (TST6049) Physical Properties P37590.03.13-3A 03/06/2013 ERD (TST6049) FM 4470/4474 P39680.03.13 03/04/2013 ERD (TST6049) Physical Properties P37590.03.13-1-R1 06/26/2013 ERD (TST6049) Physical Properties P37590.03.13-2-R1 07/01/2013 ERD (TST6049) Physical Properties P37590.07.13-2 07/01/2013 ERD (TST6049) Physical Properties P37590.03.13-5-R1 07/01/2013 ERD (TST6049) Physical Properties P37590.07.13-1 07/02/2013 ERD (TST6049) Physical Properties P45940.09.13 09/04/2013 ERD (TST6049) Physical Properties P44370.10.13 10/04/2013 FM Approvals (TST1867) FM 4470 2W7A7.AM 08/04/1994 FM Approvals (TST1867) FM 4470 0D3A3.AM 04/04/1997 FM Approvals (TST1867) FM 4470 2DOAO.AM 12/23/1998 FM Approvals (TST1867) FM 4470 2D5A9.AM 06/22/1999 FM Approvals (TST1867) FM 4470 3006646 01/04/2000 FM Approvals (TST1867) FM 4470 3001334 01/25/2000 FM Approvals (TST1867) FM 4470 3001334 02/15/2000 FM Approvals (TST1867) FM 4470 3000857 01/12/2000 FM Approvals (TST1867) FM 4470 3004091 01/12/2000 FM Approvals (TST1867) FM 4470 3006115 05/02/2001 FM Approvals (TST1867) FM 4470 3012321 07/29/2002 FM Approvals (TST1867) FM 4470 3014692 08/05/2003 FM Approvals (TST1867) FM 4470 3014751 08/27/2003 FM Approvals (TST1867) FM 4470 3007170 01/13/2004 FM Approvals (TST1867) FM 4470 3019317 06/30/2004 FM Approvals (TST1867) FM 4470 3020703 07/30/2004 FM Approvals (TST1867) FM 4470/4474 3018332 01/31/2006 FM Approvals (TST1867) FM 4470/4474 3023368 03/20/2006 FM Approvals(TST1867) FM 4470/4474 3024594 05/23/2006 FM Approvals (TST1867) FM 4470/4474 3023458 07/18/2006 FM Approvals (TST1867) FM 4470/4474 3030668 09/12/2007 FM Approvals (TST1867) FM 4470/4474 3032172 06/12/2009 PRI(TST5878) Physical Properties PUSA-062-02-01 12/04/2007 PRI(TST5878) Physical Properties PUSA-061-02-02 01/28/2008 PRI(TST5878) Physical Properties PUSA-064-02-02 02/27/2008 Exterior Research and Design, I.I.C. Evaluation Report A42970.10.12-111 Certificate of Authorization #9503 FL16027-R1 Revision 1: 03/23/2015 Page 2 of 4 Ent! PRI (TST5878) Miami -Dade (CER3592) Miami -Dade (CER1592) UL LLC (QUA9625) UL LLC (QUA9625) UL LLC (QUA9625) 4. PRODUCT DESCRIPTION: S. Examination Reference Physical Properties PUSA-062-02-02 HVHZ Compliance Various NOAs Proposal for Review 10-0823 Quality Control MI -Agreement Quality Control ML Correlation, R27202 Quality Control Service Confirmation, R14571 Date 12/04/2008 Various 10/12/2010 02/27/2012 08/20/2012 Exp.06/27/2016 This Evaluation Report covers TRI-BUILT Modified Bitumen Roof Systems installed in accordance with Allied Building Products Corp. / TRI-BUILT Roofing Products published installation instructions and the Limitations / Conditions of Use herein. The following membranes make up the subject systems. a� F Tab{e 1 RoN Goods for TRI BUILT Modrfred ertumen Roof Systems 3 Type Product Specification Reference Grade Type SBS Membranes TriBuilt SA SBS Base ASTM D6163, Table 2 S I TriBuilt SBS Granular ASTM D6164 G I TriBuilt SA SBS Cap ASTM D6164 G I APP Membranes TriBuilt APP Smooth ASTM D6222 S I TriBuilt APP Granular ASTM D6222 G I TriBuilt SA APP Cap ASTM D6222 G I LIMITATIONS: 5.1 This is a building code evaluation. Neither Trinity] ERD nor Robert Nieminen, P.E. are, in anyway, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for use in HVHZ. 5.3 Refer to a current Roofing Materials Directory for fire ratings of this product. 5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance with FBC 2603.4 unless the exceptions stated in FBC 2603.4.1 and 2603.6 apply. 5.5 Unless otherwise noted in Appendix 1, roof decking and its attachment shall be specified and installed to meet project design criteria to the satisfaction of the AHJ. 5.6 For recover installations, the existing roof shall be examined in accordance with FBC 1510. 5.7 For mechanically attached insulation or membrane or strip -bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16. Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are RAS 117 and FM LPDS 1-29. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.1.5.1(a) of FM LPDS 1-29 for Zone 2/3 enhancements. 5.8 For fully -adhered insulation, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No rational analysis is permitted for these systems 5.9 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with TAS 105 or ANSI/SPRI FX-1. 5.10 For bonded insulation or membrane over existing substrates in a re -roof (tear off) or recover installation, the existing deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If any surface conditions exist that bring system performance into question, field uplift testing in accordance with ASTM E907, FM LPDS 1-52, ANSI/SPRI IA-1 or TAS 124 shall be conducted on mock-ups of the proposed new roof assembly. 5.11 For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the AHJ, as documented through field uplift testing in accordance with ASTM E907, FM LPDS 1-52 or TAS 124. Exterior Research and Design, I.I.C. Evaluation Report A42970.10.12-Ri Certificate of Authorization #9503 FL16027-R1 Revision 1: 03/23/2015 Page 3 of 4 5.12 Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with FBC Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES-1 or RAS 111, except the basic wind speed shall be determined from FBC Figure 1609. 5.13 All products in the roof assembly shall have quality assurance audit in accordance with the FBC and F.A.C. Rule 61G20-3. 6. INSTALLATION: 6.1 TRI-BUILT Modified Bitumen roof systems shall be installed in accordance with Allied Building Products Corp. / TRI-BUILT Roofing Products published installation instructions, subject to the Limitations / Conditions of Use noted below. 6.2 System attachment requirements for wind load resistance are set forth in Appendix 1. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FBC 1609 for determination of design wind loads. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. S. MANUFACTURING PLANTS: Contact the noted CA agency for information on product locations covered for F.A.C. Rule 61G20-3 CA requirements. 9. QUALITY ASSURANCE ENTITY: UL LLC—QUA9625; (314) 578-3406, k.chancellor@us.ul.com - THE 27-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT - Exterior Research and Design, LLC. Evaluation Report A42970.10.12-111 Certificate of Authorization #9503 FL16027-R1 Revision 1: 03/23/2015 Page 4 of 4 ")OTRINITYIERD 5.12 Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with FBC Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES-1 or RAS 111, except the basic wind speed shall be determined from FBC Figure 1609. 5.13 All products in the roof assembly shall have quality assurance audit in accordance with the FBC and F.A.C. Rule 61G20-3. 6. INSTALLATION: 6.1 TRI-BUILT Modified Bitumen roof systems shall be installed in accordance with Allied Building Products Corp. / TRI-BUILT Roofing Products published installation instructions, subject to the Limitations / Conditions of Use noted below. 6.2 System attachment requirements for wind load resistance are set forth in Appendix 1. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FBC 1609 for determination of design wind loads. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. H. MANUFACTURING PLANTS: Contact the noted QA agency for information on product locations covered for F.A.C. Rule 61G20-3 QA requirements. 9. QUALITY ASSURANCE ENTITY: UL LLC—QUA9625; (314) 578-3406, k.chancellor@us.ul.com - THE 27-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT - Exterior Research and Design, I.I.C. Evaluation Report A42970.10.12-111 Certificate of Authorization #9503 FL16027-RI Revision 1: 03/23/2015 Page 4 of 4 Table Deck Application Type Description Page 1A-1 Wood New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 4 3A-2 Wood New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 5 1B Wood New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 5 1C Wood New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 1D=m.,.,UW Wood New, Reroof (Tear -Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover Wood New or Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 3E-2V ood New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 1F Wood New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover 2A Steel or Conc. New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 9 2B Steel or Conc. New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 10 2C Steel or Conc. New, Reroof (Tear -Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover 11 3A-1 Concrete New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 12-14 3A-2 Concrete New or Reroof (Tear -Off) A-1 Bonded Temporary Roof, Bonded Insulation, Bonded Roof Cover 15 3B Concrete New or Reroof (Tear -Off) F Non -Insulated, Bonded Roof Cover 15 4A LWIC New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 16-17 4B LWIC New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 17 4C LWIC New or Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 18-20 5A CWF New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 21 5B CWF New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 22 5C CWF New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 22 5D CWF New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 23 5E CWF New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 23 6A Gypsum New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 24 6B Gypsum New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 25 6C Gypsum New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 25 6D Gypsum New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 25 7A Various Recover A-1 Bonded Insulation, Bonded Roof Cover 26-27 7B Various Recover F Non -Insulated, Bonded Base Sheet, Bonded Roof Cover 27 The following notes apply to the systems outlined herein: 1. The roof system evaluation herein pertains to above -deck roof components. Roof decks and -structural members shall be in accordance with FBC requirements to the satisfaction of the AHJ. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 2. Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement: ➢ Wood: Minimum 0.75-inch penetration. ➢ Steel: Minimum 0.75-inch penetration and engage the top flute of the steel deck. ➢ Concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions. 3. Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate, polystyrene, wood fiberboard, perlite, Dens Deck, Dens Deck Prime, SECUROCK Gypsum -Fiber Roof Board or SECUROCK Glass -Mat Roof Board that meets the QA requirements of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC 2603.4.1 or 2603.6, when installed with the roof cover. Exterior Research and Design, LLC. d/b/a Trinity I ERD Evaluation Report A42970.10.12-R3 for FL16027-R1 Certificate of Authorization #9503 Revision 1: 03/23/2015 Prepared by: Robert Nieminen, PE-59166 Appendix 1, Page 1 of 27 TOR II�I�tY j ESQ 4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover), whereby the base sheet fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the AHJ. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 5. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published instructions. ➢ HA (HA): Full coverage at 25-30 Ibs/square. ➢ Dow Insta-Stik Roofing Adhesive (D-IS): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c. ➢ Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c. ➢ OMG OlyBond 500 (OB500): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c. (PaceCart or SpotShot). Note: OlyBond Green may be used where OlyBond 500 is referenced., ➢ OlyBond Classic (OB Classic): Full coverage at 1 gal/square. ➢ 3M CR-20: Continuous 2.5-3.5-inch wide ribbons, 12-inch o.c. ➢ Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, adhesive ribbons shall be staggered from layer -to -layer a distance of one-half the ribbon spacing. ➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing. 6. Unless otherwise noted, all insulations are flat stock or taper board of the minimum thickness noted. Tapered polyisocya n u rate at the following thickness limitations may be substituted with the following Maximum Design Pressure (MDP) limitations. In no case shall these values be used to 'increase' the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then the thinner board listed below may be used as a drop -in for the equivalent thicker material listed in the table: ➢ Millennium One Step Foamable Adhesive (M-OSFA): ➢ OMG OlyBond 500 (OB500): ➢ OMG OlyBond 500 (013500): ➢ OMG OlyBond 500 (OB500): ➢ OMG OlyBond 500 (OB500): ➢ 3M CR-20: MDP -157.5 psf (Min. 0.5-inch thick) MDP -45.0 psf (Min. 0.5-inch thick Multi -Max FA-3) MDP -187.5 psf (Min. 0.5-inch thick ISO 95+GL) MDP -315.0 psf (Min. 0.5-inch thick ENRGY 3) MDP -487.5 psf (Min. 0.5-inch thick ACFoam II) MDP -117.5 psf (Min. 1.0-inch thick) 7. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft. 8. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are RAS 117 and FM LPDS 1-29. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.1.5.1(a) of FM LPDS 1-29 for Zone 2/3 enhancements. 9. For fully bonded assemblies, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is permitted. 10. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with TAS 105 or ANSI/SPRI FX-1. 11. For existing substrates in a bonded recover installation, the existing roof system shall be examined for compatibility and bond performance with the selected adhesive, and the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the AHJ, as documented through field uplift testing in accordance with ASTM E907, FM LPDS 1-52, ANSI/SPRI IA-1 or TAS 124. 12. For Recover Applications using System Type D, the insulation is optional; however, the existing roof system shall be suitable for a recover application. 13. LWIC shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWIC is referenced, refer to current LWIC Product Approval for specific deck construction and limitations. For systems where specific LWIC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness is 2-inches. For LWIC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1. Exterior Research and Design, LLC. d/b/a Trinity) ERD Evaluation Report A42970.10.12-R1 for FL16027-R1 Certificate of Authorization #9503 Revision 1: 03/23/2015 Prepared by: Robert Nieminen, PE-59166 Appendix 1, Page 2 of 27 \\JTR1N1TYjEk ki 14. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications. TAsiI liTRl-BUILT 6--Covens Reference Layer Material Application BP -AA Base FBC Approved ASTM D4601, Type II HA at 20-40 Ibs/square Ply FBC Approved ASTM D2178, Type IV or VI (Base and Ply sheets, Asphalt -Applied) SBS-AA Cap ThBuilt SBS Granular HA at 20-40 Ibs/square (SBS, Asphalt -Applied) SBS-TA Cap TriBuilt SBS Granular Torch -Applied (SBS,:Torch-Applied) oQs — . : SBS-SA` B's_ee. "�TciB It SA-5 SB Base v (SBS, SelfAdhering)A T Self`Adhering Tr Capes Tr _;Built S� BS Cap APP-TA f _ _ Base or Ply _. TriBuilt APP Smooth Torch -Applied Cap TriBuilt APP Smooth, ThBullt APP Granular (APP, Torch -Applied) APP SA Cap TdBuilt SA APP Cap Self -Adhering (APP, Self -Adhering) 15. The following represent priming requirements for gypsum -based coverboards: ➢ Dens Deck and Dens Deck Prime shall be field -primed with ASTM D41 primer prior to self -adhering or torch -applied membrane application. No priming is required for hot -asphalt membrane applications. ➢ SECUROCK Gypsum -Fiber Roof Board does not require field priming for any membrane application. 16. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads. Exterior Research and Design, L-C. d/b/a Trinity) ERD Evaluation Report A42970.10.12-R1 for FL16027-R1 Certificate of Authorization 49503 Revision 1: 03/23/2015 Prepared by: Robert Nieminen, PE-59166 Appendix 1, Page 3 of 27 TABLE 1A-1: WOOD DECKS — NEW CONSTRUCTION OR REROOF (TEAR -OFF) SYSTEMTYPEA-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System Deck Anchor Sheet Base Insulation Top Insulation Roof Cover MDP No. (See Note 1) Type Fasteners Attach Type Attach Type Attach Base Ply Cap (psf) Min. 0.25-inch Dens 8-inch o.c. in 4- Deck, Dens Deck Prime, Polyglass G2 Base, 32 ga., 1-5/8- inch lap and 8- (Optional) FBC SECUROCK Gypsum - Min. 19/32- CertainTeed Glasbase, inch diameter inch o.c. in Approved, Fiber Roof Board, Min. SBS-AA, W 1 inch plywood Firestone MB Base, tin caps with 11 three, equally ASTM C1289, HA 0.75-inch FescoBoard HA BP -AA (Optional) SBS-TA, .60.0 max. Tamko o a annular ringspaced, g ' p type II of iso- Yp p y (homogeneous) or min. ( g ) BP � APP-TA in inch spans spans or Glass Base or GlassPermBase shank nails staggered cyanurate 0.5-inch Structodek GAFGLAS 475 center rows High Density Fiberboard Roof Insulation 8-inch o.c. in 4- Polyglass G2 Base, 32 ga., 1-5/8- inch lap and 8- (Optional) FBC (Optional) Min. 19/32- CertainTeed Glasbase, inch diameter inch o.c. in Approved, Min. 0.25-inch Dens One or SBS-SA, W 2 inch plywood Firestone Base, tin caps with 11 three, equally ASTM C1289, HA Deck, Dens Deck Prime, HA SBS-SA more SBS- APP-SA, -60.0 at max. 24- Perma-Ply , Tamko 28 ga. annular ring spaced, type II polyiso SECUROCK Gypsum- SA or SBS-TA or inch spans Glass Base or shank nails staggered cyanurate Fiber Roof Board APP-TA APP-TA GAFGLAS #75 center rows 6-inch o.c. in 4- Min. 2-inch D-IS, OB500, Min. 19/32- 32 ga., 1-5/8- inch lap and 6- ACFoam II, III, CR-20 or M- Min. 0.25-inch Dens DAS, inch plywood Polyglass Elastobase inch diameter inch o.c. in H-Shield, H- OSFA, atop Deck, Dens Deck Prime OB500, (Optional) SBS-AA, W-3 or Polyglass tin caps with 12 four, equally BP -AA SBS-TA, -60.0 at max. 24- Elastobase Poly ga. annular ring spaced, Shield CG, fastener or SECUROCK Gypsum- CR-20 or BP -AA APP-TA inch spans Multi -Max FA3 rows, 7-inch Fiber Roof Board M-OSFA shank nails staggered center rows or ENRGY-3 oc 6-inch o.c. in 4- Min. 2-inch D-IS, OB500, 32 ga., 1-5/8- inch lap and 6- (Optional) Min. 19/32- Polyglass Elastobase inch diameter inch o.c. in ACFoam II, III, CR-20 or M- D-IS, One or SBS-SA, W 4 inch plywood Polyglass tin caps with 12 four, equally H- H-Shor OSFAPaste atop (Optional) Additional OB5CR-2 0, SBS-SA more SBS- APP-SA, -60.0 at max. 24- Shield C, Shield CG, fastener layers of base insulation CR-20 or SBS-TA or inch spans Elastobase Poly ga. annular ring spaced, Multi -Max FA3 rows, 7-inch M-OSFA SA or APP-TA shank nails staggered APP-TA center rows or ENRGY-3 oc Exterior Research and Design, LLC. d/b/a Trinity) ERD Certificate of Authorization #9503 Prepared by: Robert Nieminen, PE-59166 Evaluation Report A42970.10.12-RS for FL16027-R1 Revision 1: 03/23/2015 Appendix 1, Page 4 of 27 TABLE IA-2: WOOD DECKS — NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER SYSTEMTYPEA-2: MECHANICALLY ATTACHED ANCHOR SHEET, BONDED INSULATION, BONDED ROOF COVER System Deck Anchor Sheet Base Insulation Top Insulation Roof Cover MDP No. (See Note 1) Type Fasteners Attach Type Attach Type Attach Base Ply Cap (psf) 12-inch o.c. in 4- Min. 0.25-inch Dens Deck, Min. 19/32- Polyglass OMG Flat inch lap and 12- (Optional) FBC Dens Deck Prime, SECUROCK inch plywood Elastobase or Bottom Plates inch in two, Approved, Gypsum -Fiber Roof Board, (Optional) SBS-AA, SBS- W-5 max. Polyglass (square) with equalllyly spaced, ASTM C3289, HA Min. 0.75-inch FescoBoard HA BP -AA BP -AA TA, APP-TA -60.0 in inch spannss Elastobase Roofgrip #12 staggered center type II polyiso- (homogeneous) or min. 0.5- Poly cyanurate inch Structodek High Density rows Fiberboard Roof Insulation Polyglass 12-inch o.c. In 4- (Optional) FBC (Optional) Min. 19/32- Elastobase or OMG Flat inch lap and 12- Approved, Min. 0.25-inch Dens Deck, One or SBS-SA, APP- W 6 inch I plywood Polyglass Bottom Plates inch o.c. in two, ASTM C1289, HA Dens Deck Prime, SECUROCK HA SBS-SA more SBS- SA, SBS-TA -60.0 at max. 24- Elastobase (square) with equally spaced, type II polyiso- Gypsum -Fiber Roof Board SA or APP- or APP-TA inch spans Poly Roofgrip #12 staggered center cyanurate TA rows TABLE 1B: WOOD DECKS —NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER SYSTEM TYPE B: MECHANICALLY ATTACHED BASE INSULATION, BONDED TOP INSULATION, BONDED ROOF COVER System Base Insulation Layer Top Insulation Layer Roof Cover MDP No. Deck (See Note 1) Type Fasteners Attach Type Attach Base Ply Cap (psf) Min. 0.75-inch FescoBoard (Optional if using Min. 19/32-inch Min. 1.5-inch Dekfast Hex with 1 per (homogeneous) or min. 0.5-inch (Optional if AA Base) One or SBS-AA, SBS-TA, W 7 plywood at max. 24-inch ENRGY 3, H-Shield Dekfast #12 or Tru Fast z HA using AA Ply) -60.0 1.33 ft Structodek High Density Fiberboard more BP -AA or APP-TA spans or Polytherm MP 3 with TruFast DP Roof Insulation BP APP-TA Exterior Research and Design, LLC. d/b/a Trinity) ERD Certificate of Authorization #9503 Prepared by: Robert Nieminen, PE-59166 Evaluation Report A42970.10.12-R1 for FL16027-RI Revision 1: 03/23/2015 Appendix 1, Page 5 of 27 TABLE 1C: WOOD DECKS —NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION, BONDED ROOF COVER System Base Insulation Top Insulation Layer Roof Cover MDP No. Deck (See Note i) Layer (Psf) Type Fasteners Attach Base Ply Cap Min. 19/32-inch (Optional) Min. 0.5-inch Structodek High Density Dekfast Galvalume (Optional if (Optional if using AA W-8 plywood at max. One or more layers, Fiberboard Roof Insulation or min. 0.25- Steel Hex with 1 per 1.33 P Z using AA Ply) Base) One or more BP -AA SBS-AA, SBS-TA, APP- -82.5 24-inch spans any combination, inch Dens Deck, Dens Deck Prime Dekfast #12 DP ft BP -AA or APP-TA TA loose laid Board SECUROCK Gypsum -Fiber Roof Board (Optional) Dekfast Galvalume W-9 Min. 19/32-inch plywood at max. One or more layers, Min. 1.5-inch ENRGY 3, H-Shield or Steel Hex with Dekfast #12 DP or 1 per 1.33 Z SBS-SA (Optional) One or more SBS-SA, APP-SA, SBS- -82.5 24-inch spans any combination, Polytherm TruFast MP-3 with ft SBS-SA or APP-TA TA or APP-TA loose laid TruFast DP TABLE 113: WOOD DECKS —NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER SYSTEM TYPE D: PRELIMINARILY ATTACHED INSULATION, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System Insulation Layer(s) Base Sheet Roof Cover MDP No. Deck (See Note 1) Type Attach Base Fasteners Attach Ply Cap (psf) Polyglass Elastobase, Polyglass OMG Flat Bottom Plates Min. 19/32-inch Elastobase Poly, Polyglass G2 Base, (square) with Roofgrip 12-inch o.c. in 4-inch lap and 12- (Optional) One SBS-AA, W-10 plywood at max. One or more layers, Prelim. CertainTeed Glasbase, Firestone MB #14, Dekfast Hex with inch o.c. in two, equally spaced, or more BP -AA SBS-TA, -52.5 24-inch spans any combination Attached Base, JM Perma-Ply 28, Tamko Glass Dekfast #14 or TruFast staggered center rows or APP-TA APP-TA Base or GAFGLAS #75 MP-3 with TruFast HD Min. 19/32-inch One or more layers, Prelim. Polyglass Elastobase or Polyglass Dekfast Hex with Dekfast 12-inch o.c. in 4-inch lap and 12- One or more SBS-SA, APP-SA, ; W-11 plywood at max. any combination Attached Elastobase Poly with poly top surface #14 or TruFast MP-3 with inch o.c. in two, equally spaced, SBS-SA SBS-TA or -52.5 24-inch spans TruFast HD staggered center rows APP-TA Min. 19/32-inch One or more layers, Prelim. Polyglass Elastobase or Polyglass OMG Flat Bottom Plates 12-inch o.c. in 4-inch lap and 12- (Optional) One SBS-AA, W-12 plywood at max. any combination Attached Elastobase Poly (square) with Roofgrip #12 a inch o.c. in two, equally spaced, q y P or more BP -AA SBS-TA, -60.0 24-inch spans staggered center rows or APP-TA APP-TA Min. 19/32-inch One or more layers, Prelim. Polyglass Elastobase or Polyglass OMG Flat Bottom Plates 12-inch o.c. in 4-inch lap and 12- One or more SBS-SA, APP-SA, , W-13 plywood at max. any combination Attached Elastobase Poly with poly top surface (square) with Roofgrip #12 inch o.c. in two, equally spaced, SBS-SA SBS-TA or 60.0 24-inch spans staggered center rows APP-TA Exterior Research and Design, LLC. d/b/a Trinity) ERD Certificate of Authorization #9503 Prepared by: Robert Nieminen, PE-59166 Evaluation Report A42970.10.12-R1 for FL16027-R1 Revision 1: 03/23/2015 Appendix 1, Page 6 of 27 TABLE 3E-1: WOOD DECKS —NEW CONSTRUCTION OR REROOF (TEAR -OFF) SYSTEM TYPE E: NON -INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System Base Sheet Roof Cover MDP No. Deck (See Note 1) Base Fasteners Attach Ply Cap (Psf) W-14 Min. 15/32-inch plywood at max. 24- Polyglass Elastobase Simplex MAXX Cap 9-inch o.c. at 2-inch la and 18-inch o.c. in two, P (Optional) BP -AA or SBS-TA -45.0* inch spans equally spaced, staggered center rows APP-TA or APP-, or APP TA Min. 15/32-inch 9-inch o.c. at 2-inch la and 12-inch o.c. in two, P (Optional) BP -AA or SBS-AA, SBS-TA W-15 plywood at max. 24- Polyglass Elastobase Simplex MAXX Cap equally spaced, staggered center rows APP-TA or APP-TA -52.5 inch spans Min. 19/32-inch Polyglass Elastobase, Polyglass Elastobase (Optional) One or Poly, Polyglass G2 Base, CertainTeed 32 ga., 1-5/8-inch diameter tin caps 8-inch o.c. in 4-inch lap and 8-inch o.c. in three, SBS-AA, SBS W-16 plywood at max. Glasbase, Firestone MB Base, JM Perma- with 11 ga. annular ring shank nails equally spaced, staggered center rows more BP -AA or TA, APP-TA 60.0 24-inch spans Ply 28, Tamko Glass Base or GAFGLAS #75 APP-TA Min. 19/32-inch Polyglass Elastobase or Polyglass 32 ga., 1-5/8-inch diameter tin caps 8-inch o.c. in 4-inch lap and 8-inch o.c. in three, (Optional) One or SBS-SA, APP- W-17 plywood at max. Elastobase Polywith of to surface poly P with 11 a. annular ring shank nails g g equally spaced, staggered center rows q Y P gg more SBS-SA or SA, SBS-TA or -60.0 24-inch spans APP-TA APP-TA W-18 Min. 15/32-inch plywood at max. 24- Polyglass Elastobase Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in two, (Optional) BP -AA or SBS-AA, SBS-TA -90.0 inch spans equally spaced, staggered center rows APP-TA or APP-TA Min. 19/32-inch Polyglass Elastobase or Polyglass 32 ga., 1-5/8-inch diameter tin caps 4-inch o.c. in 4-inch lap and 4-inch o.c. in four, (Optional) One or SBS-SA, APP- W-19 plywood at max. Elastobase Polywith of to surface poly P with 11 a. annular ring shank nails. g g equally spaced, staggered center rows q Y P gg more SBS-SA or SA, SBS-TA or -97.5 24-inch spans APP-TA APP-TA W-20 Min. 15/32-inch plywood at max. 24- Polyglass Elastobase Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in three, (Optional) BP -AA or SBS-AA, SBS-TA 105.0 equally spaced, staggered center rows APP-TA or APP-TA inch spans Min.19/32-inch Polyglass Elastobase or Polyglass 32 ga., 1-5/8-inch diameter tin caps 6-inch o.c. in 4-inch lap and 6-inch o.c. in four, (Optional) One or SBS-AA, SBS- W-21 plywood at max. Elastobase Poly with 11 ga. annular ring shank nails equally spaced, staggered center rows more BP -AA or TA, APP-TA -112.5 24-inch spans APP-TA 32 ga., 1-5/8-inch diameter tin caps Min. 19/32-inch Polyglass Elastobase or Polyglass with 11 ga. annular ring shank nails. 6-inch o.c. in 4-inch lap and 6-inch o.c. in four, (Optional) One or 585-SA, APP- W-22 plywood at max. Elastobase Polywith of to surface poly P Note: Tin caps are to be rimed with P P equally spaced, staggered center rows q Y P gg more APP-TA SA, SBS-TA or 112.5 24-inch spans ASTM D41 primer. APP-TA Exterior Research and Design, LLC. d/b/a Trinity) ERD Evaluation Report A42970.10.12-R1 for FL16027-R1 Certificate of Authorization 49503 Revision 1: 03/23/2015 Prepared by: Robert Nieminen, PE-59166 Appendix 1, Page 7 of 27 TABLE 3E-2: WOOD DECKS - NEW CONSTRUCTION, REROOF (TEAR -OFF) OR RECOVER SYSTEM TYPE E: NON -INSULATED, MECHANICALLY ATTACHED BASE SHEET, BONDED ROOF COVER System Base Sheet Roof Cover MDP No. Deck (See Note 1) Base Fasteners Attach Ply Cap (psf) Min. 19/32-inch Polyglass Elastobase, Polyglass Elastobase OMG Flat Bottom Plates (square) with 12-inch o.c. in 4-inch lap and 12-inch (Optional) One or W-1 plywood at max. Poly, Polyglass G2 Base, CertainTeed Roofgrip #14, Dekfast Hex with Dekfast #14 o.c. in two, equally spaced, staggered more BP -AA or SBS-AA, SBS- -52.5 24-inch spans Glasbase, Firestone MB Base, JM Perma- or TruFast MP-3 with TruFast HD center rows APP-TA TA, APP-TA Ply 28, Tamko Glass Base or GAFGLAS #75 Min. 19/32-inch Polyglass Elastobase or Polyglass Dekfast Hex with Dekfast #14 or TruFast MP- 12-inch o.c. in 4-inch lap and 12-inch One or more SBS- SBS-SA, APP- W-2 plywood at max. O.C. in two, equally spaced, staggered SA, SBS-TA or -52.5' 24-inch spans Elastobase Poly with poly top surface 3 with TruFast HD center rows SA APP-TA Min. 19/32-inch 12-inch o.c. in 4-inch lap and 12-inch (Optional) One or W-3 plywood at max. Polyglass Elastobase or Polyglass OMG Flat Bottom Plates (square) with o.c. in two, equally spaced, staggered more BP -AA or SBS-AA, SBS- -60.0 24-inch spans Elastobase Poly Roofgrip #12 center rows APP-TA TA, APP-TA Min. 19/32-inch Polyglass Elastobase or Polyglass OMG Flat Bottom Plates (square) with 12-inch o.c. in 4-inch lap and 12-inch One or more SBS SBS-SA, APP- W-4 plywood at max. Elastobase Poly with poly top surface Roofgrip #12 o.c. in two, equally spaced, staggered SA SA, SBS-TA or -60.0' 24-inch spans center rows APP-TA TABLE IF: WOOD DECKS -NEW CONSTRUCTION ORREROOF (TEAR -OFF) SYSTEM TYPE F: NON -INSULATED, BONDED ROOF COVER System Roof Cover MDP No. Deck Primer (psf) Joint Treatment Base PI Cap IVlin. 1J 5%32 ch plywood uy� (Optional) SBS-SA or SBS-SA, APP-SA, SBS-TA W-5 it-�chspans (Optional) ASTM D41 None SBS-SA APP-TA orY APP-TA �� 90. �f `-W-6 Min. 15/32-inch p ood � i Plywood joints-are-caveredwith•4_ nch wide strips.ofTriBuiffSA r- :�-_- ' r(Aptiona1) SBS-SA or ySBS-SA, APP=SA, SBS-TA at max. 24-inch spans -(Op ioh'alrZiS M D41 SBS Base, rolled into place to create continuous bond. TrIBUIIt`5A SBS Base APP-TA or APP-TA -97.5 Exterior Research and Design, LLC. d/b/a Trinity I ERD Certificate of Authorization #9503 Prepared by: Robert Nieminen, PE-59166 Evaluation Report A42970.10.12-R3 for FL16027-RI Revision 1: 03/23/2015 Appendix 1, Page 8 of 27