RE: Permit # 1711-0144
D.R. Horton Homes
Creekside Lot 111
Model 2432-D-R
Please see below for responses to building dept. comments for the above listed project:
Comment 1: SEE DETAIL NUMBER TWO ON PAGE D3, CENTER OF DETAIL
CALLS OUT A DETAIL NUMBER FIVE, NO DETAIL FIVE LISTED ON PAGE D3.
PLEASE CORRECT.
Response 1: Detail reference has been revised to 7B/WA2 on drawing D3, for
Detail 1 and 2.
Comment 2: DETAIL 3 SHOWN ON PAGE D3 FOR EXTERIOR TO STRAPPING
FROM WOOD FRAMING TO BLOCK. STRAPPING IS BEING INSTALLED ON
THE EXTERIOR THE STRUCTURE OVER THE PLYWOOD DOWN TO THE
BLOCK ON THE TWO STORY STRUCTURES. PLEASE CLARIFY IF THIS IS
ACCEPTABLE APPLICATION OR REVISE THE DETAIL TO ACTUAL
CONDITIONS BEING INSTALLED ON SITE.
Response 2: Partial sheathing has been added to the detail to clarify that the
strapping is attached after the sheathing has been applied.
Comment 3: DETAIL NINE SHOWS NOT USED ON PAGE D4. DETAIL NINE
SHOWS WOOD TO WOOD STRAPPING NOT TO EXCEED 36", THIS DETAIL
DOES NOT APPLY. PLEASE SUBMIT THE CORRECT DETAIL ON PLANS FOR
THE TWO STORY L.B.W. SEE SECTION 107 OF FLORIDA BUILDING CODE.
Response 3: Detail 9/D4 is "NOT USED". Details 1&2 on drawing D3 are
applicable to this project for reference.
1441 N. Ronald Reagan Blvd. • Longwood, FL 32750 • Phone: (407) 774-6078 • Fax: (407) 774-4078
AA0003325
www.abdesi2naroun.com
A R C H I T E C T S
Design
Group Inc.
Comment 4: PLEASE SEE DETAIL 8 AND 8B ON PAGE D-4. PERMIT
APPLICATION SPECIFIES TWO STORY STRUCTURE AND THE DETAILS ARE
FOR A SINGLE STORY STRUCTURE. PLEASE SUBMIT DETAIL FOR A TWO
STORY INTERIOR BEARING WALL, AND TWO STORY TYPICAL INTERIOR
WALL. SEE SECTION 107 OF 2014 FLORIDA BUILDING CODE.
Response 4: Revised Details 8 and 8B on Drawing D4 state "1st Floor" and not "1
Story." Those bearing walls support the floor trusses only. The 2nd story trusses are
bearing on the Ext. Walls not on the 1st Floor Walls.
Comment 5: SEE DETAIL 9 ON PAGE D-4. DETAIL IS MARKED NOT USED
PLEASE CORRECT. SEE SECTION 107 OF THE FLORIDA BUILDING CODE.
Response 5: So noted. For additional clarity, unused details have also been marked
out with an "X".
Comment 6: NO DETAIL FOR INTERIOR TWO STORY WALL DETAIL AT
GARAGE LOCATION. PLEASE SUBMIT. SEE SECTION 107 OF 2014 FLORIDA
BUILDING CODE.
Response 6: Refer to the added Detail "A" on Drawing 2, for the Interior 2-Story
Wall at the Garage Wall, as requested.
Comment 7: NO CUBIC VOLUME ON PLANS. PLEASE ADD THE CUBIC
VOLUME OF THE CONDITIONED SPACE TO THE INFORMATION BLOCK
CONTAINING THE SQUARE FOOTAGE INFORMATION. SEE CHAPTER 1,
SECTION 107 OF THE 2014 FLORIDA BUILDING CODE.
Response 7: Cubic Footage of the Conditioned Space has been added to Drawing
2, as requested.
Comment 8: SUBMITTED PRODUCT APPROVAL NUMBER FL 12147-R1 IS
OUTDATED. PERMIT WAS APPLIED FOR AFTER EXPIRATION DATE LISTED
ON SUBMITTED PRODUCT APPROVAL (10/01/2017). PLEASE SUBMIT
CURRENT PRODUCT APROVAL FOR THE ZIP WALL SYSTEM SHEATHING.
SEE SECTION 107 OF THE 2014 FLORIDA BUILDING CODE.
Response 8: So noted. The revised Zip System Wall Sheathing Product Approval
number has been revised on drawing D5: "FL17147-112".
1441 N. Ronald Reagan Blvd. • Longwood, FL 32750 • Phone: (407) 774-6078 • Fax: (407) 774-4078
AA0003325
www.abdesi2n2roun.COM
A R C H I T E C T S
Design
Group Inc.
Comment 9: PLEASE SEE ZIP SYSTEM SHEATHING PRODUCT APPROVAL
NUMBER ON PAGE D-5. PRODUCT APPROVAL NUMBER IS A GENERAL
NUMBER. PLEASE SUBMIT SPECIFIC PRODUCT APPROVAL NUMBER ON
THE PRODUCT APPROVAL AFFIDAVIT. SEE SECTION 107 OF 2014 FLORIDA
BUILDING CODE.
Response 9: The correct current Zip System Sheathing Product approval number
is "FL17147-112", which has been revised on the product approval affidavit.
Comment 10: PLEASE NOTE THAT ALL COMMENTS ARE FOR
CLARIFICATION OR CORRECTION OF THE SUBMITTED DOCUMENTS.
ADDITIONAL REVIEW MAY BE REQUIRED AFTER CORRECTED
DOCUMENTS.
Response 10: So noted.
Comment 11: SUBMITTED DOCUMENTS MUST BE IN DUPLICATE. SEE
SECTION 107.1 OF THE 2014 FLORIDA BUILDING CODE.
Response 11: So noted.
Should you have any questions, please feel free to contact me.