Press Alt + R to read the document text or Alt + P to download or print.
This document contains no pages.
HomeMy WebLinkAboutSetup & Installation ManualSCANNED cotBwlt
BY ST LUCIE COUNTY Homes, Inc. -
Setup Instructions
Installation Manual
W
M
M
O�G
JUNE 29.2004
CLCL
6
Fedaal NSoa od
And 3dety SWd'dt
Multi -Section Units
Revised: June 3, 2004
Please keep a copy of this manual with this home at all times for reference of possible future ffomeowners.
SU-1
WBIR Homes, Inc
Table of Contents
Chapter I - Introduction
.............................................................. .......... ...... S[}-3
Foreword............................ .............
�-----_^`.~_."---------..----.-^_...-.'3\J�
- ---------'------------------^_.----.-----Su'o
u-iformuuou........... —.... ^....
-.-.................................. ..^'-`-----^--------'
�u��y,_^__________._.____.____^_______~____' .___---_.-...-'_8D'3
Consumer Record Card
.................... ........................................................... ......................................... .... 0lJ'4
Homeowner's Manual .............................................................. .............. `^--'--__-----,-^,Heat Duct Connection'
Ow
��
��°���Q�UU�H��U��% IK��
Chapter I - Introduction
1 a) Foreword
This ScotBilt home was engine
constructed, and inspected in confom
with the National Manufactured He
Construction and Safety Standards Act
"Act") and the regulations issued thereun
effect on the date of manufacture.
standards set forth minimum requiremer
the design and, construction of manufa(
homes designed to be used as dwellings.
Your new home is furnished with a Ec
Manual and Home. Owner's Manual. C
the most important things you as a home
can do is familiarize yourself with
manuals and CHECK FOR PROPER SE1
It is recommended that licensed ,
personnel do all the work in accordant
the set-up manual. However, it is stil
responsibility to check the work, regardli
who does it.
Your dealer can assist you in to
experienced personnel. Failure to follow
instructions could result in serious prol
which would not be the responsibility
manufacturer.
I lb) Using this nwnual
This, manual contains detailed inst
instructions, including specification
procedures for the proper support and i
of your manufactured home. It discus:
setup of the home from preparing tl
through final inspection. It includes
tables and figures giving important d
proper setup. Careful adherence 'I
manual by the installation crew will ass
of a quality, safe, and affordable ho
many years to come. Consultation
registered professional architect or engir
those unusual circumstances not cove
this book is required.
10 Pre -Setup InfornWlon
red, The design criteria for this home may be
nice found on the data plate (see figure ,1.1), which
sing also contains other essential information such
(the as where this home was manufactured,
:r in- factory -installed equipment, and heating and
The cooling information. This data plate may be
for found attached to the home in- one of the
fired following locations:
Jp 1. Inside Master Bedroom Closet
Of 2. Utility Area
er 3. Inside Kitchen Cabinet Door
UP. Please crosscheck the data plate supplied
:t-up with your home with the roof load, wind and
with heating / cooling zone maps to assure that
your your home is built for the proper location.
's of These maps indicate the acceptable areas of
the United States where your home may be
sting safely located. Prior to locating or relocating
lese your home, contact the local authority having
gms, jurisdiction over home installation to see if
the permits , for such procedures as blocking,
anchoring, or utility connections are required.
Inspections may be required during installation.
On private property, zoning or development
ation covenants may apply and should be taken into
and consideration. (NOTE: Preparation of the site,
okup when accomplished by other than the home
the installer, may not be in accordance with these
site instructions.)
for
this I d) Safety
you This manual is intended to be used by
for licensed installers who are property trained and
h a qualified to install manufactured housing and
r for associated equipment. Certain operations
i in described he risks of possible
injury or even geath if performed without
SU-3
Scot9lft Homes Inc
Chapter 1. Introducti®n
proper skills and knowledge and such
:operation should not be attempted by anyone
other than a 'licensed installer. The following
"Warning" format, is used throughout this
:manual to describe many of those hazards:
WARNING.
Hazards inherent to the installation of the
manufactured 'home may' present risks of injury
or death. Only a professional installer should
perform operation.
THIS HOME MAY WEIGH IN EXCESS OF
30,000 POUNDS
USE ADEQUATE 'TEMPORARY WOOD
BLOCKING TO SUPPORT THE • HOME
DURING SETUP.
No one should be allowed under the home
unless it is securely supported.
1 e) C*nsumeer ,Record Card
Refer to the Homeowner's manual and fill
out the CONSUMER INFORMATION CARD.
Retum it to. the home's manufacturer, so that
you may be notified of revised instructions or
new products.
If) Home Owner's Manual
After the installation of your home, it is
important that you understand how to maintain
it in order for you to enjoy many years of
trouble free. living. The homeowner's manual
will help you, understand how to care for your
home and will describe basic preventative
maintenance procedures.
Is) Recommended Smp Tools (MIN.)
- Claw hammer', 3-10Ton Hydraulic Jacks,
12' 'step ladder, yankee screwdriver or Y4"
powered screw gun (with standard blade,
phillips bit, square bit, and Y4" hex
attachments), ' utility knife, wire strippers, -2-10"
crescent wrenches,- 4" -Brush (to apply roof
coat), foundation supports (shims,_.etc... ), steel
measuring tape, 6", carpenter level, sheet metal
snips, combination cross -cut or rip hand saw,
4-1 M ton jacks (doubl,ewides), and 4'x8'
sheets'of luaun paneling:(doublewides).
NOTE: All shipping material shall be
removed. All penetrations, holes ,-in exterior
are to `be:. repaired and sealed jLngludling
.shingles).
:NOTE: -The materials shown in .Scot8ilt's
setup manual are typical ,in nature., and may be
substituted for equivalent : materials.
(Examples: tie -down straps, tie -down anchors,
etc...
SU-4
THIS INSTALLATION MANUAL IS WRITTEN TO ASSIST ALREADY QUALI1IED AND TRAINED
PERSONNEL IN SETTING UP YOUR HOME. IT IS NOT INTENDED TO ENABLE AN UNTRAINED
INDIVIDUAL TO SET-UP YOUR HOME. MANUFACTURED HOMES WEIGH SEVERAL ICONS.
ALWAYS ENSURE HOMES ARE ADEQUATELY SUPPORTED TO PROTECT WORKERS.
ATTEMPTS TO REPAIR OR SIET-UP A HOME BY UNTRAINED INDIVIDUALS COULD RESULT IN
SERIOUS INJURY OR DAMAGE TO THE HOME.
ScAl t Homes, Inc,
Chapter 1 t. Introduction
'figure 1.1—
Data Plate
- MagYlBatYlOr AdtlrOgB
mufacturar HUD No,
nu actunil a Serial um ran M0 .0
oar gn pprova . Y P A.P,.I.AJ
Hllborn Werner. Carter & Associates
This m,ndMurW IIonN 4 dlsipmd b owrWY whh lho IWael nuMadurad liglm
consirwI06 and so" alerWad In forgo al 094 d rmmrfadur•.
(For adddbnW Imormation, ddrisulI "WA manual)
The factory Inatallod equipment Includes:
Equipment Manufacturer Model Designalbn
Hosting
Cooking
Refrigerator
Water Heater
Dishwasher
Fireplace
store0 -
Lwo,s ilia home and he adiakg ud (aw"an ayaom Mrs ban designed rot the Iwassed n-
ownerda spadAeO la,E.Vown 0 to Mill 7.0.
Thishamh■s' '.ias Nt_pot boon woppadwllh dOmi.b..OfL
protedlw oowdngs for wincim and odonor door opordnga. For homes designed to be Idwiod in
WNie ZoM fl uW Itl wrdch hew rat Oe•n p WO*d with Womors. or "Ulvalsm coydring dovimi, Is Is
strongly ro ss ad 1hN Ua'tidta W made ready to egdpped with time devise in daor-
dnraa wiNtin mettad'roarrrnarWod b manubdar" prkdad InsN+gtloro. ,
Y4 9ASICVWNDZONE MAP
ZONI81 .
-ZON 8
ZOMBI .,
_"'" "' ah��i 2 NC ■ :ON)d tI � ONE M!I .
NOTE: age Soctlon 5280406(c) (2)
LION ROOF LOAD ZCNE MAP
COMFORT HEATING
This mamdeduod Tome aasboonthomalprinsulalaetd eomorrawlNlho foqukom■ntt dlhoiad,ral
maroAedturod llorn0 tonekudlon mW sdoyalsndWp/or o0 bcettont
within dimato zona '
Hooting pulpmsm mD. o as lid at Ia111
The above hosting epuornml has the capacity to rml in aawrage70e Ftompaatieobi Ns .
home at ouldoot tomparahxa of __F. ,.
To madmiss lurmce opentirg •oonwny sari "l "o (07 .) energy, h ru Nndod Out hate home
W Imuitsd M+on Ua outdoor wNnr nmpordun g7 K is not tuA
depre•a F.
oar emu obton eaiwlalod osaumingamdximumwlnd vebcityd/3mph alstandard
■w"OlThemprets".
COMFORT CCOLINO
❑ Air canditbning pdyided at factory (alternate I) ,
Air conditlonei mom last" and modal ("a that at ton)
CaNned aped 9.TU.I for, In oecordowe whn the Fppopiata air
'anddlaVna aWoo,ld unuq systeGon m ' TM anbd air ern evicted in this home has boon sized ■swrkq on
orionlollon dthe framlhhch eria)dgw laim facing
'this basis the system s dotiytW to tnskdoin N Indoor ramporoan a ro- r wanwnmgr
tonVoraturos am_ Fdrybidbsnd Fwet butt.
-The lomperlinlowNdithis home can becoobCwill dingodov aNuponIhiianotaitof
Now
'es>o of dm (No ham the m 's rodent
eat. oorrl�nsHn'r'inf* hwmprot Edit
•,pn�Ul orydsFa�lmrq N• ottadetlon d codhq kad• at vaiou, locofbm, wiMon7
Hipown, ind shodrfo provided in Cheater 22 of the 107 edition of fMASHAAE
HarWhook d Fundorroman. .
Ipovl'doidkt spec tgpmo'M l0000ting lN�mmtiaipwlloWlo orbmations is
❑ Alt gandlloning not prsividad At Wall` ~116141 01
The ICutOn system a No homes ow for tied Instdlsllan. of oamfrnl air
The v** ok distroxion sworn lnitollW in Nsliane Is eizodfora mamdahoadhonb
rrbsrpibsat air which
lap to up W vn conditionN and
mf ctjil. row
ry WWI a whin the air dro - d such air eondtiomm •- noise d
O.S Tndt wag odm�u�mp�•yelolie pne,uro err preMor la the oodirq Alt dwverod to the
mnmdsch rod harm t � sir and eyaem
Womutbn nooeosry o calwtato ppdtrqg beds N varlcus locatbm and atamabns b pro
~Wdw In"s We odrdan cooling-vfarm■,WnpsrWt v Wwith ids mwWladuW home.
❑ Air co"d`0oq*dmm nd raoroironandW (alematg III1
Tm akdlWlbdbNb�r�i ssyyssism d Ns holm Tw rot bases doslgrad inantdps6on dhs user wilh o
salmi air oororaonttp system.
INFORMATION PROVIDED BY THE MANUFACTURER
NECESSARY TO CALCULATE SENSIBLE HEAT GAIN
Wags lwivaW wirldOWa end doom) 'U'
Calling$ and rods of light ulor
Coirugs and rod$ d"oobr Y'
Ak duds In poor 'v
Air duds In alkg ... 'U .
Air duds fastaud outside to hams %r
The following ate the duct areas in this home.
At dud, In hoar w. h.
Nr dudsin dolling � ea.a
Air duct Oulsido No OoiM 80. R
To aatamlm to roquved Rollo* d .oQl!ipment to coel.ei;hon; umdemly and 0aoigmoslly, ra
cooling load (hat gam) uWation Is rogtitrod The oodihg bod id dtpaidad d th• aNntation
locagm am CM slnrdirra d t $'lame Central ark=WRlonare opanta most sffalomb ■ A P&*
IMpotleYart ShMl befloodin 00,ordnas VAt cheater p2 of theA eras gba*L of He .
ark nxrWhbrar ►�guW ho •ilea N aegordanea wdth Cheater 22 d to Amadmn Saeiory d Hoaeg,
ROhjgaalrg aW Alr CmdluadrO Engines IASHRAEI HorWaook d Fuidoraeias anoe alp.
leaden aM odomollai onW�odn
U/O Value Zone Map
for Manufactured Housing
ti v, n ai,11m 4 40.0
SU-5
ScotBift Homes, Inc
J_
Chapter Site Trep
7,apidon
A,
-2a) Vfind, Root. and Climate,, Zones
To ensure that this home's location is within
its specified boundaries., refer to the home's
data plate and to the zone maps (figure 2.1)
lnchriari in this rnnn"nl
2b) PraInage and Grading of Site:
m thatknot- it is i Oortan't, water does,run-,
,underneath a h6n4_'JheWore.1he'_ h'drhd site%--.
should
Id be Properly graded and - l'0'6;i6d-_awci ..Y.;
from streams and r'1v6ri.,-- -Excessive water and
Moisture will affect the home's, stability, and.
could void the home s* , .warranty:.(S. 6e-1`ii6Ur6_
2.2).
,2c) Ground Cover
if the home is to be skirted.,---- etc.,"- the
.ground underneath the.. _-home,_.,*-is' to,,be
c' - polyethylene sheeting
completely covered with I
or t equivalen minimum inimum.6 m' "ils t (If -footing
_
Is to be Plaoed-ben'e-ath. „grade 6 l6vel.,_ place
ground cover ben0ath�fq.pt!ngj._:
2d) Land In
;Branches, buthes:add other -de H6Sthat are
in a location In which. they could rub against
walls or roof when 'home is getup should be
removed. Also, any 'plant life should be
.removed from underneath- the home prior 'to
time of setup
as, well.
2e) Home Hook -Ups
,Note 'the location of water,gas, and
electrical inlets. Be sure that these
connections can be made with any prior utility
,connections at the .'home site, if any, without
obstruction
Figurd 24 —
Zone Maps
, : 1:
t/0 Value Zone Map for Manufactured Housing
0.11 6 0.0%
SU-6
RAN HomerN Inc
Chapter 2 - Site
Figure 2.2 —
Proper Land Grading
DO:
GRADE SITE TO ALLOW.WATER
TO SLOPE AWAY FROM HOME,
DO NOT:
GRADE SITE TO SO THAT WATER
COLLECTS AND REMAINS UNDERNEATH
HOM$.
_,
ScotBIR Homes, Inc
IL
Chapter 3 - Foundation
3a) "Foreword ; blocking is required within 24`', of all shearwall
One of the most .important `parts of; a Mobile tiedown straps:
Home setup is the foundation. In areas where In some instances, there are also shearwall
the soil is .subject to: freezing and thawing; .the: . � fiedown , 'anchors located at various spans
foundation must be. designed 'in compliance ialong, the marriage line of -the home.
with local . ;building , rules;, therefore, ,always
:check- local building codes for -'footing'--, depth,
block sizes., etc...3e) Removal of organic material
Your dealer can also help in recommending Remove all decayable: - -material such .,as
the proper anchoring system ''to "be used and ' grass, roots, arid wood scraps from beneath
also assist you in obtaining qualified personnel the 'home, especially in areas where footings
to install your anchoring system in a ate -,.to be placed, to minimize settling. of
professional method. footings and insect damage: ' Remove shrubs
and overhanging'.branches.frorri the immediate
vicinity of the homesite to prevent windstorm
36) F"Ongs damage.
If your :local building official has no'
requirement for footing thickness in your area,.
then a minimum thickness of 4" should be
,used. The footing should extend below the
"frost line" in; climates where soil is subject -to .
'freezing and thawing; movements: :(See .figure
Provided in' this manual are tables to aid" in
footer size and pier 'specifications. (Table 3,2,
3:3, & '3.4).
30 Pier Bloeidng
Pier blocking. is- required: at. each end of all
exterior doors. I' (See Figure !3.5 for typical pier
blocking system.) See drawings at the end of
this chapter for pier blocking specifications_ on
anything other than standard construction
(examples: angle bay window, cottage box
'bay, etc...).. .
3d) Btocidng . o1F Shearwait -and Marriage
Wall Tiedowns
Shearwall anchors are,identified at sidewall
locations with orange or.. green paint. Pier
Figure 3.1 —
Typical Footing
SOLID OR . CELEE
CONCRETE BLOCK!
FOOTER.
SINGLE-. TIERED
WOOD SHIM,
SOLID OR CELLED
,CONCRETE BLOCKS
D SHIMS
ScotBilt Homes, Inc.
'LbOR SYSTEM
# BETWEEN TOP OF THE PIER AND THE I —BEAM MAY BE A WOOD PLATE
NOT EXCEEDING 2" IN THICKNESS) AND/OR SHIMS. (NOT EXCEEDING 1" IN '
'HICKNESS). SHIMS, SHALL BEAT LEAST 4" WIDE AND C LONG, FITTED
D DRIVEN_ TIGHT BETWEEN WOOD PLATE OR PIER AND THE I —BEAM,
:AP — WOOD C2 X6'iX1Ei` S—Y-P ,2 P.T. WITH SOLID BLOCK BELOW OR
,CONCRETE ' 4"XB'-'X1 E' SOLID CONCRETE CAP BLOCK.
;INGL.E OPEN OR, CLOSED CELL CONCRETE 'BLOCKS 1rkft1,E' (OPEN CELL
'U1 m VERTICALLY ON THE FOOTER) SHALL, BE ILLE NSTAD WITH THE .19,
IWENSION PERPENDICULAR TO THE I —BEAM.
OCTING — 'I 6''X11j N-C MINIMUM. SOL16 CONCRETE OR DTHER PRODUCT .
APPROVED FOFt: THE PURPOSE .(SEE TABLE FOR LOAD AND SIZE)
IORIZONTAL .GRADE
© zw4g >
W `D
aAUG 112004 C
c. p m
SYSTEM
BETWEEN TOP OF' THE PIER AND . THE I —BEAM MAY BE ' A WOOD PLATI
EXCEEDING r IN THICKNESS) AND/OR SHIMS (NOT r EXCEEDING 1' Its
CHESS). SHIMS Sv
HALL BE AT LEAST 4 WIDE AND ' LONG, FITTED
DRIVEN TIGHT, M-TWEEN WOOD. -PLATE OR -PIER -*NO THE -1-Bt4M: -
— WOOD (2 XG) X1Ir S-Y—P #2 P.T. WITH SOUR. BLOCK BELOW OR
CONCRETE 1lrXl-rX4' SOUD CONCRETE CAP BLACK.'
UZ OPEN OR, CLOSED CELL CONCRETE BLOCKS B`XB"X1 ' (OPEN CF11
:ED VERTICALLY. ON THE , FDOTER) SHALL BE INTERLOCKED AND CAPPEE
►PECIFIEO ABOVE.
'ING — I Wxl6"Xc'MINIIJUM SOLID CONCRETE 'OR 'OTHER PRODUCT
16VED FOR THE PURPOSE (SEE TABLE FOR. LOAD AND. SIZE),
GRADE
icuT • FOOT3 GS TO BE P=CED ON FZZiM MM=TQR>9m
STABLE son, WM ALL. ORM=C iYmmMarnr. VM,
WITH THE BOTTOM OF THE F0OTZN0 LOCATEDBOTH A
MIAT7MOM OF 12 n;mm BE w (MADE m BpLow THE
YMST DEPTH nQ Tm AREA THE SU; MG IS IACATM.
NQTE: PIERS SPBCIS m .nm ARE TO SE na STACI® ERCEPT
WHEN THS PIER HEIGHT ASOYE THE room G I E7GCE w 48"
THE BLOCKS MUST BE PLACED IN TYPE 6 MORTAR. ALL
CONCRE= BLOCKS MAST COMPLY WITH ASTM q-90 OR C-145.
tit k'• �� � P, ,,, �� :± �
act 3
t
SU-8A
EXTERIOR WALL OPENING. SHEARWALL STUD, OR 'COLUMN SUPPORT POST.
GAP BETWEEN TOP OF '7HE PIER AND 714E FLOOR MAY BE A ' W000 PLATE
.(NOT EXCEEDING 2" IN THICKNESS) AND/OR SHIMS (NOT EXCEEDING 1" IN
THICKNESS). SHIMS SHALL BE AT LEAST 4' WIDE AND 6' LONG, FITTED
AND DRIVEN TIGHT BETWEEN WOOD PLATE OR PIER AND THE FLOOR SYSTEM
CAP — WOOD (2 X13)X16" S—Y=P 2 'P.T. WITH. SOLID BLOCK BELOW OR
CONCRETE ;CWX16" SOLID CONCRETE CAP BLOCK.
SINGLE OPEN OR CLOSED CELL CONCRETE BLOCKS 8"X8'X16" (OPEN CELLS
PLACED VERitCALLY ON THE FOOTER) SHALL BE INSTALLED WITH THE 16'
DIMENSION PERPENDICULAR TO THE I —BEAM:
FOOTING — 16"X16" XC MINIMUM SOLID CONCRETE OR OTHER PRODUCT
APPROVED FOR THE PURPOSE (SEE TCA6LE 'FOR LOAD AND SIZE)
HORIZONTAL 'GRADE
0 awe
>
AUG 112004
C3
C
. n" Prilcn2 Mamilicm,sd
' Nov. Conmwtk a
�
And Stay Suam,a.
EXTERIOR WALL OPENING, SHEARWALL STUD, OR COLUMN SUPPORT POST.
GAP BETWEEN TOP. OF THE PIER AND THE FLOOR MAY BE A WOOD PLATE
(NOT EXCEEDING Z AN THICKNESS) AND/OR SHIMS .(NOT, EXCEEDING, 1" IN.
THICKNESS). SHIMS SHALL mBE AT LEAST d WIDE AND 6' LONG, FITTED
AND DRIVEN TIGHT BETWEEN WOOD PLATE OR PIER AND THE FLOOR SYSTEM
CAP — WOOD (2 'XG).XI6" S—Y—P J2 P.T. WITH SOLID BLOCK -BELOW OR
CONCRETE IVX•16"U'SOUD CONCRETE CAP BLOCK.
DOUBLE OPEN OR CLDS€D CELL CONCRETE BLOCKS 8'X8'X16" (OPEN CELL
PLACED VERTICALLY ON THE FOOTER) SHALL BE INTERLOCKED AND CAPPED
AS SPECIFIED ABOVE.
FOOTING — 16"X16`X4" MINIMUM 50LID CONCRETE OR OTHER PRODUCT
APPROVED -FOR THE PURPOSE (-SEE TABLE FOR LOAD AND SIZE)
HORIZONTAL. GRADE
41 ,-• - --
NOTE: FOOTINGS TO BE PLACED ON FIRM MWISTORBED
STABLE SOIL WITH ALL ORGANIC MATERIAL REMOVED,
WITH THE BOTTOM OF THE FOomr- LOCATED ,BOTH A
KnYlblbN OF 3.2 INCHES BELOW MWE AND BELQW THE
FROST DEPTH IN THE AREA THE'BU= NG IS LOCATED.
NOTE: PIERS SPECIFIED ABOVE ARE TO BE DRY STACKED EXCEPT
WHEN THE PIER HEIGHT ABOVE THE FOOTING EXCEEDS 48"
THE BLOMW MUST BE PLACED IN TYPE S mcRTAR. ALL
CONCRISm BLOCKS MAST COMPLY VM ASTM C-90 OR C-145.
d¢
Chapter 3 - Foundation
Table 3.2 -
-Steel Beam Pier Loads and Footing
Required.
1W' floor width (W wide) W 10" max. ove 4mv
Sa ffi Zanel iMad U_ 10 ndDLl
I
�. ♦.
. ♦.,
�- rON "76
♦
�i
179' floor width (32 wide) W 10" max OvQiwV
South Zane) (20 Od LL.10 qsf DU
'NORM
,SU-9
ScotBilt Homes, Inc.
Chapter 3 fbuudaddn -
Fable 3.3 -
Sidewall Pier Loads & Footing Areas
(Opening Studs)
166" floor width.(23'.wide) vi+1.10" max. overhang (Sidewall Pier Loads)
South 7nnar /2A ngf i I -4A not ni
OPENING WIDTH.
(CLEAR SPAN)
PIER
LOADS
(LBS)
MINIMUM FOOTING AREA (Z. IN.) PER SOIL PRESSURE SPECIFIED
1000 psf :
'_ 1500 psf
2000 psf
2500 psf
3000 psf
4'
450,
120 •
-•78
: 57
45
38
6'
675
156,
101.
74;
59.
49
8'
900 .
193
124
91
72 '
60-
10'
• 1125 ..
228
147
109 .
' .. '. 86. ,
71
12'
1350
265-
`170-
126�
99
82
14'
1575
300 -
193.
143
113
94
16'
1800
336,
: ' 217
159 .
.127
105
18'
12025
373°
239
176
140
116
20'
2250
:•.,408
263'
194
-154
127
22'
247S....445
286
211
167
138
24'
2700
= 480;
309
228.
181
149
26'
•2925
516 '
333-
245
-194
161
28'
'3150
553
355
262'
208
172
30'
3375, _.
588
379
'.279 .
221 _
183
32'
3600:
625'
.401
296.1.
235.. .
194
34'
.-3825
660 -
425
313 .
-
248
205
' 36'
4050
696
448
330
... 262.
217
38'
4275-
733
.471
.347
'275 • ;
228
40'
�ni.w•.-rn
4500
768
' 494
365 '. -
288
238
n.v.rvrw rv� vvwivnv rn i n �rLC11I[ JCMIV VIV VIVt )IUC VNLT,
WHEN CLEAR SPAN EXISTS' BOTH SIDES OF COLUMN, ADD BOTH SPANS TOGETHER BEFORE
REFERRING TO TABLE.•
NOTE:.CHECK LOCAL BUILDING OFFICIAL FOR FOOTING THICKNESS IN YOUR AREA
178" floor width-(32- Wide) W/ 10" max .•overhang (Sidewall Pier Loads)
South: nnn 00'nnf 1_1__ 4I1 risfI ni 1
OPENING WIDTH
(CLEAR SPAN)
PIER '
LOADS
(LBS)
MINIMUM FOOTING AREA (Sd. IN.) PER SOIL PRESSURE SPECIFIED
-
; 1 uop psf
1600 psf
2000 psf,
_ 2500 psf
3000 psf
4'
.505
-129,
83.-
62
48
- 41
6'
758,
169
110
81
64
53
8'.
.1010
.:'210
135'
99
79
66
10'
' 1263
251 :
161 ' .
119 ,
94
78
12'
1516
291.
187:
138
110
91
14.'
1768
"332,
214
157
124
103
'16'
1 . 2021
.372
239
17.6
.140
115
18,
2273'
413
265'
.195 ..
155
1 129
20'
2526
453
291
214
: ' 170
141
22'
2779
493
318
:-234
'185
154
24' .
3031'
534
343,
` 253. ,
200
166
26'
3284
574
,369
272
'216
178
28':
3536'_
614
395 •
291
231 '
191
30'..
3789
655
422
310 '
246.
203"
32'
4042
695.
.447..
330
261
.216
34'
4294
736
473
349
-277 --,.
229
36'
4547.
778
..499
368
. ,291 - •
242
.'38'
4799
816
525
'387
'307
254
40'A
5052
857
551
406
.. 321.
266
vv n.v wrw rvn vvwrvm rn In C?r-MIV VIV UNM 04UC. VIVLT,,
WHEN CLEAR SPAN EXISTS BOTH SIDES OF COLUMN, ADD BOTH SPANS TOGETHER BEFORE
REFERRING TO TABLE,
NOTE: CHECK LOCAL BUILDING OFFICIAL FOR FOOTING THICKNESS IN YOUR AREA
'SU-10
'ScotBilt Homes, Inc,
Chapter 3 - Foundation
Table 3.4 -
Marriage Wall Pier Loads & Footing Areas
(Opening Studs)
156" floor width (28' wide) w/ 7
max. overhang (Marriage Wall Pier Loads.)
ijn -.f 1 1 4 n ncf 111 1
OPENING WIDTH
(CLEAR SPAN)-
PIER
LOADS
MINIIu�UM FOOTING AREA (SQ. IN,) PER SOIL PRE66URE SPECIFIED
f
2000.psf
o
.
3000 psf(LBS)
4' '
390
111
71
63
42
35
8'
685.
'142
- 92
68
64
44
6'.
780
174
112:
83
85.
64
10
976
205
131•
87
77
64
12'
1170
236
152-
112 :
89 •`
74
14'.
-1365
267: '
172; '.
127. '
100
.83
16'
1680
298
- 192
142
112
93
18'
1766
.329
212
156
123 ..
103
20'
1950
360
.232
171"`
136
112
22'
2145
392.
252
186
147
122
24'.
2340
423
272-
20I
169
132
,26'
'2535
454
292
.215
170
141
28'-
2730
485
312
230
183.
161
30'
2925-
516
.333
245
194
161
32'
3120
547i
352
259.
206
170
34'
3316
670
-372
274- -
217
480
36'
3510 • ••
610
393
289:
229 --
190
36'
3706
649
412
304
241
.199
40'
3900
673
432
318
253
1 209
42'
4095
7041
463,
333
264
219
44'
4290
735-
473
346
276.
n , nu
228
c nC All
IiiDLC IIYw Ment V 1 nG rvvl I,.v , - - ......---.--•- -- --•- --- ----- •
WHEN CLEAR SPAN EXISTS,BOTH SIDESIOF COLUMN, ADD BOTH SPANS TOGETHER
BEFORE REFERRING TO TABLE.
'TABLE ASSUMES MARRIAGE WALL CONSTRUCTION IN ONLY ONE HALF OF THE
DOUBLENIIDE HOME (ONLY');. IF SUPPORT COLUMNS OCCUR•IN BOTH'HALVES AT THE SAME
LOCATION (I.E.. WILL_BE,SUPPORTED BY THE SAME .PIER) ADD THE LOADS FROM EACH HALF
TOGETHER (USEITHE,METH,OD,DESCRIS D ABOVE, FOR EACH HALF) TO DETERMINE THE '
TOTAL LOAD SUPPORTED BY THE. PIER.
NOTE: CHECK LOCAL BUILDING OFICIAL FOR FOOTING THICKNESS IN YOUR AREA.
178" floor width (32'.wide) w/ 10,' m x. ove.thang (Marriage Wail NO Loads) .
n_..1�. v...-vin—fI 1 4n.,efn11
OPENING WIDTH
(CLEAR SPAN)
PIER _
LOADS'
(LBS)
^MINIUM FOOTING AREA (8Q. IN.) PER SOIL PRESSURE SPECIFIED .
1000 psf
1500.,psf
2000,pst
2600 psf
3000 psf
4'
- 446
-1191
78
57
45
-38
6'
_ 668
155
.100
`.74
69
48.
.8'
890
1911
123.
- 91
72
-69 -.
10'
1113
."2261
146
A 08 '
85 .
71
- 12'
1336
2631
169
726
98
82
14'
1558
298
191
:'142'
112'
93
16'
1781 ..
334-
215!
=.158
126
104
18'
2003
3691
237 ; •
176
138
115
20'
2228
.4051
260
192
152
126
22'
-2449
4401
283
209
166..K203
37
24'
2671. -
4761
108 •
226 '
17948
26'
2894 , -
' . -5121
329
243
19259'
28'
3116
547
1
362 ;
269: • .
108 '70
30'
' 3339. •
5831
:. 374
276.
':21882
32'
3662
618
'
398 '
1 •: 293 '
23292
34' _
:3784;
654
•
421
: 310
245 '
36'
4007
6891
-443
327 '-
269
215
38'...
4229'.
725
467
344:.
272
226
40'
'4462
•761
.489
361
286
238
42' .
4875`
". 798.
'513
377
.298 ,
248
�44'
'4897
832
_ _
_' 535
_' 394
_11n
312
.,c
258
InC A411 V
'1 AD"= IP/UIVAI Gq 1 nC ryy i u.v I.vr.v , y,. vvw... ,.- ... ... -. - -.- ---- -�- - - . .
WHEN- CLEAR SPAN EXISTS BOTH SIDES IOF COLUMN, ADD BOTH SPANS TOGETHER
BEFORE REFERRING TO'TABLE.
TABLE ASSUMES MARRIAGE WALL CONSI RUCTION IN ONLY ONE HALF OF THE
DOUBLEWIDE HOME (ONLY); IF SUPPORT COLUMNS OCCUR IN BOTH HALVES AT THE SAME
LOCATION ,(I.E., WILL BE_SUPPORTED BY -THE SAME PIER) ADD THE LOADS FROM EACH HALF
TOGETHER (USE THE METHOD DESCRIBED ABOVE FOR EACH HALF) TO DETERMINE THE
TOTAL. LOAD SUPPORTED BY T,HE'PIER.
NOTE: CHECK LOCAL BUILDING'OFF CIAL FOR FOOTING THICKNESS IN YOUR AREA.
SU-11.1
Scotfilt Homes, Inc.
Chapter 3 - Foundation
Figure 3.6 —
Typical Pier Blocking Diagram
.SUPPORT PIER SLOCKINc RFf)LIIRFn
TYP. SHEARWALL
ENDWALL
SUPPORT PIER BLOCKING
TYP. SHEARWALL
SU-12
Scot8llt Homes, Inc.
3-
Figure 3.6 -
Angle Bay Blocking Requirements
MAIN BEAM
MAIN STEEL I BEAM
HEADER
PIER
Front Angle Bay
(At Header)
MAIN T BEAM
(SPACING 95 1/2')
PERIMETER RAIL
Rear Angle Bay
PIER BLOCKING
SU-13
ScotBilt Homes, Inc.
Chapter. 4 - Setup .Procedures
4a) Positioning
When site preparation. is complete, you can
begin positioning and installation of the home.
Be sure ,that any work that should be done
prior to placing, the home. ,in .'its final .,resting=
position is complete..
WARNING
A manufactured home weighs several tons:
Getting under a 'home when it is jacked up
and/or improperly supported is, VERY
dangerous. Be sure that the jacks) you are
using are safe and supported properly. Do
NOT over jack.
4b) Leveling and Blocidng•
There are many different ways to level a
home. We have included two of the more
popular procedures. Using a*. .water level
(Figure 4.1) and using a bubble level (Figure
4.2). (Refer to figure 4.3 for proper jacking
procedures.).
1) Using a water level. (Figure 4.1)
First, pre -determine the height that all
pier supports will be. •Then, place.a
container, with long ' plastic tubing
attached to the bottom, off to the .side.
;Next, fill the container with colored water
to the _ pre=determined . pier height.
Blocks beneath -the container may be
necessary to _reach desired height. Be
sure to remove any air bubbles from the
Plastic tubing before using. Hold the
opposite end of the. ' plastic '. tubing
approximately a foot above the pier you
are measuring" and open the valve
attached to the end of the plastic tubing.
Using the level of water visible through
the plastic tubing, adjust the support pier
'to the desired height. Measure each pier
using this method and then lower section
onto adjusted piers.,
.2). Using a bubble level. (Figure 4.2)
First, place bonne on piers. Then, check
the level of the floor from front to rear
'.then from -side. to side. Check, level of
sidewall. Make any necessary
adjustments to piers using a jack and
pier wedges; Repeat until entire home is
completely level.
40 Multi -section_ installation , - -
'.When installing anything other .than a
single -wide home, complete all work done in
section : , 4a) and 4b), . then proceed to this
section.
♦ .Place the next section as;.near; as possible
to the first section.
♦ Be sure. to remove all plastic from the
marriage wall side of the home and/or any
other objects that could obstruct proper
mating of the two sections.
♦ Seal at floor, walls, or roof with foam, carpet
pad, or equivalent.
Draw the two sections together using come-
alongs, rollers, or skid -boards.
Check the floor line to ensure that it is flush
horizontally and vertically.
♦ Repeat leveling and blocking procedures
same as first section.
4d) Floor Connections
'Once 'the two ' sections have been
.positioned and blocked, fastening may begin.
Using either of the methods shown in figure
4.4, begin fastening the two sections together
along the marriage line.
If the floors are flush at both ends, but the
SU-14
ScotBilt Homes, Inc,
Chapter 4 - Setup Procedures
top of the heavy half is sticking out in front of
the light half and the .rear 'ends are the
opposite, the ceiling strips will not line up. This
must be corrected before the top is b Ited
together. To eliminate' this problem, put�one
jack under the outside front corner of the, half
sticking out. Place the ' other- jack under the
rear outside corner of the ,opposite half. Mack
up both corners at the same time until the
ceilings line up and then,strap the center beam
together before removing the jacks.
EXTERIOR WALL -
4e) Roof Connections
If the home haS-"f=oam$ealR" or egwvalent,
installed along the ridge beam of either half, no
other air -infiltration treatment is required at time
of setup along the roofline at the marriage wall.
Level the ceiling between the two halves . so
that they are flush with each other. Strap the
'''roof with. galvanized straps: provided, in, setup
kit. (See figure 4.5)
WARNING
A protective, covering material (polyethylene
held in -place with plywood or O.S.B. strips)
was installed at time of manufacture to <eep
the shingles from blowing off of the roof d ring
transit. Any holes from any .fasteners MUST
BE SEALED to prevent water damage i the
roof.
4f) Interior and Exterior Finishing
Once floor, roof, and wall connections I
all been made, finishing may begin.
ROOF DECKING
RIDGE BEAM.
SEAL AT THESE CONNECTIONS
(WALLS, FULL LENGTH OF FLOOR,
AND FULL LENGTH OF ROOF) PER
SECTION 4c.
FLOOR
FOR RIDGE SET -UP OF SHINGLE ROOF, INSTALL THE ROOFING FELT
STRIP, CUT THE CAP SHINGLES PROVIDED INTO THIRDS AND INSTALL
WITH ROOFING NAILS OR STAPLES..
FIBERGLASS OR
SHINGLE
SS -OR ASPHALT
RIDGE CAP
'-FIBERGLASS OR
ASPHALT SHINGLES
INGLE UNDER LAYMENT
SHEATHING
BEAM
SU-15
ScotBilt Homes, Inc,
Chapter .4 Setup _Procedures
Figure 4.1 —
Using a water level
VALVE
DESIRED PIER
WATER LEVEL HEIGHT
CLEAR TYPICAL PIER
PLASTIC
Figure 4.2 -
Using a bubble- IeVel (recommended areas
to check for leveling of home)
TYPICAL SIDEWALL
TYPICAL ENDWALL C G C C
B
TYPICAL MARRIAGE WALL MATING LINE
;NOTE
-CHECK AREA •c' VM11CALLY ALONG SHE S10EWALL SU-] 6
ScotSllt Homes, Inc,
Chapter 4 - Setup Proced
Figure 4.3 —
Proper Jacking Procedures
TYPICAL JACKk F _&_J
FRONT' Hew
REARMFRONT WIMP
W MO HANGER MUMMM-7
HAM
TYPICAL
MIL2*Xrxl6' BLOCK JACK
Starting with one side, place first jack just forward of the front
spring pring hanger under main I -Bea m and the'secoAd jack just next
to the rearmost spring hanger,
NOTE Always locate Jackson or near as,po.ssible, where cros,9member
Are connected to main 11 Be 'am Minunum.TWO jacks per I-beam.
SU-17
ScotBilt Homes, Inc.
I
I Chapter 4 Setup Procedures
i Figure 4.4
i,
Floor Fastening
FLOOR
DECKING S
RAIL OOR
OIST_—S
FLOOR 'FASTENING
.Figure 4.6 —
Roof Fastening
BEAM
ROOF FASTENING
#10 x 4" SCREWS 12" O.G. OR 318" x 3'/:" LAG 24" O.C.
�S STAGGERED FROM SIDE TO SIDE AT 45° ANGLE FROM
VERTICAL.
26ga x 1'/2" STRAP SPACED 32" O.C.•WITH ONE (1) 318" x 3'/2" LAG
SCREW OR FIVE (5) #10 x 1%" SCREW$ EACH END OR ONE (1)
269a. X 2'/2" STRAP 48' O.C. WITH TWO (2) 3/8" x 3 1/2" LAG
SCREWS EACH END. (ALL SCREWS MUST PENETRATE INTO
FLOOR JOISTS.)
© CONTINUOUS WOOD BLOCKING EACH HALF (MAY BE FULL
HEIGHT RIDGE BEAM - NOT SHOWN.,)
® #10 x 5" SCREWS 12"• O.C. STAGGERED"FROM SIDE TO SIDE AT
300 ANGLE FROM VERTICAL.
® 26ga. x 1%" STRAP LOCATED ABOVE TRUSS FASTENED TO
TRUSS WITH TEN (10) 15ga x VA' STAPLES OR FOUR (4) #10 x
1 %" SCREWS EACH END SPACED AS FOLLOWS.'
WIND ZONE 1: 96" O.C.
WIND ZONE 2: W. O.C.
WIND ZONE 3: 80O.C..
IN LIEU OF O AND Q ABOVE, MAY INSTALL CONTINUOUS
30ga. x 6" MINIMUM STEEL ROOF CAP OVER 16# FELT WITH:
TWO (2) #8 x 1%s° SCREWS EACH TRUSS AT 16" O.C. OR
THREE (3) #6 x W SCREWS EACH TRUSS AT 24" O.C.
SU-18
ScotBilt Homes, Inc.
FASTENERS:
UNLESS OTHERWISE STATED, ALL FASTENERS
ON THIS DRAWING SHALL BE 16ga. x 7/16" x 1-1/2"
STAPLES. FASTENERS ARE TO BE DRIVEN INTO
FRAMING MEMBERS.
STARTER STRIP:
FASTEN STARTER STRIP TO UNIT AT 8" O.C.
CORNER POSTS:
ALLOW APPROXIMATELY 1/4" CLEARANCE
AT TOP END. FASTEN IN CENTER OF SLOTS
AT APPROXIMATELY 12" O.C.
HORIZONTALSIDING:
SNAP FIRST (BOTTOM) COURSE INTO THE
STARTER STRIP. FASTEN IN CENTER OF
SLOTS AT 16" O.C. OVERLAP PIECES ON
SAME COURSE APPROXIMATELY I".
OVERLAPS MUST BE FROM REAR TO FRONT
ASSUMING THE HOME IS TO BE TOWED FROM
FRONT. SEE DETAIL'A'.
TOP COURSE:
IF NEEDED, TOP COURSE MAY NEED TO BE
TRIMMED IN ORDER TO FIT. USING A PUNCH,
CUT SLOTS IN THE TRIMMED PANEL AND
FASTED IN -CENTER OF THE SLOT AT 1.6" O.C.
TOP TRIM:
INSTALL TOP TRIM OVER TOP COURSE @ 16" O.C.
DOORS:
INSTALL J-CHANNEL ALONG VERTICAL AND
HORIZONTAL, EDGES OF DOOR OPENINGS.
THE J-CHANNEL ABOVE THE OPENINGS' SHOULD
EXTEND OVER THE SIDES. NOTCH AND BEND
DOWN THE TABS ON THE J-CHANNEL OVER THE
DOORS. SEE DETAIL'S'.
WINDOWS:
IF WINDOWS 50 NOT HAVE A VINYL RECEIVING
FLANGE, THEN INSTALL J-CHANNEL USING
SAME METHOD AS DOORS LISTED ABOVE.
DETAIL 'A'
'DETAIL 'B'
DRAWING NO.
S�MC
CL
SU -18 A
CR SS. A 3
N'AYCROSS,OA 71)0!
VINYL SIDING
W
DATE: 07 27 04
INSTALLATION
.'DETAILS
LAST REVISION DATE: N/A
Chapter 5 - Tiedowns
Tledowu
The following pages of this chapter pettain to
typical tiedown installation. Please refer 'to the
page(s) pertaining to the size, configuration,
and wind zone location of the unit to be set.
Periodically, 'you should check for releveling of
the home, and tensioning of the. tie -down
,straps.
SU-19
ScotBilt Homes, Inc.
TYPICAL DOUBLE -WIDE TIEDOWN INSTALLATION
STANDARD IIEDOM 117 TION
(STANDARD PEDOWN I I STALLATION NOT AT SHEAR WALLS)
WIND z I
(15 Fes)
INSTALL VUMC&L TM6M STRAPS AND/OR im
,e.VERTICAL MEDOWN STRAPS 7MO C90M ANCHORS AT EACH
nm� J.'. A�
NOOK -FROM GME 11D TOP WALL DPEN1140 STUD FOR OPSOM DMEEDING
ftINIMM
OF STEEL BM SPECRW ON WAM VZMCAL -OMOYN STRAPS ARE IN
Dw sw-cr-3 B07H NALYM AT THE SAME LOCATION, C014NWT BOTH
MAPS 713 THE SALE DDLIBLE WAD ANCHOR VM RMUS
CUP
.035. TED"M
�STANDARD CH!jj� (Typ)
PIM cnp
)
NORrZONTAL INSTALL ALL %__,W0UND ANCHOR
I" txtADEq1.
(TYMN L)
ANMORS BELOW 7CAL)
4 F
�WAI.L VE7MCALLY AS stiom
COCK ANGM FOR ALL MIX410 ANMM EXCEPT AT S14M WALL VERTICAL TIMOMM INSTALL
NUMIM TO SINWALL FRAME 1010ONS
A FRWE MEDDWN STRAP AT EACH WR7)CAL WM
'PER Dwo SW-4-3 tm)
AND CWNECT THE FRME ItMOYM STRAP To
THE SAME DOUBLE HEAD GROUND ANCHOR AS IM
EKCEPrr AT SHEAR WU %MCAL 71MXYWIM INSTALL :.1,vmQQ TIMM STRAP (n?.EACH SIDEWALL)
A FRAME MEDOWN MAP AT A SPACING -Fo
THE VALUE SPECnED 00 -DRAWN( ; SW
C=EN AL 14015SI
.
INSTALL VMC& 1M-SMMAPS 'AN%=`Wff t ALL
VMGAL'ED0"STRAPS T0CROUNDANO.T 7tED0WN'STRAPS AND .CONNECTING HARDWARE MUST
41W
DPEHNG STUDS WHEN 7HE OPENING VADTH' 4ir CWIF BY A'PROFESSIONAL ENQNEER OR A PMX)MM
(TYPICAL EACH MEVAtL) IMMG LABORA7M 70 ADEQUA7MY ;WPPOff A. 315*
AIMMAE LOAD MRWM (1.101MAX LOADQ251 M[MLIIA)
AND/OR ID COIAPLY W?H ASW D30539L
Z ALL GROUND ANCHORS W=016 ON THIS DRAMNO MUST BECER7FW
BY A ENGNEEP OR A RECOGN2W
IESIING LABDRATM TO ADEOUATMY SUPPORT A 31501
='U VATHDMV& TAUMIN_(ULMWATE LOAD 4725f MIU4
00ADED
BOTH PARALLM WITH IM ANCHOR SHAFT AND
AT A 4V ANGLE FROM IM ANCHOR SHAFT,
M. AHM E FROM GRAD9 TO FRAU TIEWAt
d.W? TO BE 46..vEa (LOCATE aftmm ANc3ft 'FULL
I THE. GROUND ANCHORS UM BE RM&M TO 7HEIR
AS REQUIRED TO WAIN T111S ANGLE) DEPTH IN A=)RDAI= VITH ME MANUFACTURERS INSTRU=DNS
(IM APPROVED FOR OWN.LAIIDN IN IM SOIL 7YK VMCH
N DM'
DWM AT THE SITE.ETM) AM MUST EXTM BaM'ffE FROST
INI SPWFIED OTHERWISE ON CTM DRAWNGS, IM AND- BE AT LEAST 1Z ABOIC THE WATER TABLE-
ALL 7WOM4 STRAPS AND GROUND ANCHORS
WWW ON INIS DRAWING ARE IN ADDITION 4. ALL GROUND ANCHORS CONNMYED 70 7W WEWALL FRAME
M IM MED,001 STRAPS AND IIRDUND ANCHORS IMMG ULW BE PROVIDED WrM STABiUZER PLA7ES To
RWRED AT 7HE SHEAR WAU.S. MINIMIZE HORIZONTAL MOVEMENT.
THIRD PARTY
REVISIONS
MBB41 <6\
DAM mm
V_�17m_i . SW-FI-2
0=1k,
Li awe
Lu
>
0 -JUN 2 9 Z004
0.
TYPICAL DOLMEWIDE TIEDOWN INSTALLATION
(STAN[�ARD`J TIEO.OWN INSTALLATION =- NOT AT SHEAR - 'WALLS
•
WIM0 ONE 2 4 3
•
INSTALL. VDt?ICAL IIEDOWN STRAPS. AND/OR SECURE THE
VERTICAL TIEDOWN $TRAPS TO GROUND ANCHORS AT EACH
LiEYf4IT FRW GRAM R TO TOP MARRIAGE WAIL OPENING STUD FOR OPENINGS E ZW)ING
-OF STEEL BEAU SPECOE D ON 48" IN WIDTH, WHEN VERTTCAL TIEDOWN STRAPS ARE IN
DN 3 BOTH HALVE'$ AT THE SAME LAGATIDN. CONNECT• BOTH
ST AP5 TO THE Z6NIE DOUBLE HEAR ANCHOR WITH RAUIU5
- 1 i /�' x .03 -5' 7TEDOYYN
STANDARD CHASSISSTRRAP (TYP)..
PIER (TYP)
HORIZONTAL 1N5TA11 A1.L GRouNO OUNO ANCHOR
GRADE ANCHORS BaW MARRIA(� (T! IOAr).
WALL VERTICALLY AS SHOWN
BACK 1IN(YE:FOR ALL GROUND ANCHORS DWALL MARRIAM WALL FRAME TIEDIDUa BELOW IMS'MARRIAGE
LINE WITHIN S=0' •OF,EACH ENDWALL. ANDAT A SPACING NOT
CWJNECTED 7D StpEWALL FRAME tIEDOYItiS
PER 0*0' SIN-0-3 (iYP) 70 EXCE L .7NE DISTANCE SPEgF7F� .ON DRAWING S4SF-�G-3;
CONNECT. THE STRAPS FROM EACH STEEL BEAM TO THE SAME
DOUBLE HEAD GROUND ANCH.M(TYP•EACH HALF)
D(CEPT AT $HEAR WALL VERTICAL TIEDOWNS, •INSTALL .A e
AIAGONAL. FRAME 'iEDOM STRAP AT.EAUI VE'RTIC& TIEDOWN
CONNECT THE FRAIJE 11EDOW STRAP TO
S�ZMD
DOtIBLE•HEAD- GROUND ANCHOR AS THE.TrEi10vM
STRAP (TYP EAc51 SIDEWALL) C- N 4L NQIE—S:
LIM LL VERVCAL TEDDWN 5IRAPS AN6/dt SECURE; THE
'VERTICAL TEDOWN STRAPS TO GROUND -ANCHORS AT 1. ALL 'I11:DOWN ,STRAPS AND..CONNECTING HARDWARE MUST
,OPENING STUDS ,NiEN 7HE `aPENING IMDTH EkCEEDS 4r . CE RTIRED BY A PRW'�ESSIONAL ENGINEER OR A RECOGNIZED
AND AT A SPACING NOT 70 bc�n THE VALUE TESTING LABORATORY TO ADEQUATELY SUPPORT A S.lWf
EIED ON DRAWING SYi-G-3. ALLOWABLE LOAD MINIIAUM .(ULTIMATE LDAD d725# MINIMLW)
,AND
AND/OR TO COMPLY 41H ASTM ID3953-LTt.
'Z ALL GROUND ANCHORS SPWFIE.D ON THIS DRAWING MUST BE
CE RT1M BY -A'PROFESSIONAL ENGINES! OR A , RErA3PN129D
'TESTING LABOPATOi2Y T) `ADEQUATELY SUPPORT A '31500
ALLOWABLE VYMMAWAL LOAD: .(I T04ATE COO 4725J) MW-
WHEN LOADED AT A 45•.ANGIE FROM ME ANCHOR SHAFT AND A
4000 ALLAWABLE YHTIIDRAWAL LOAD (ULTIMATE LOAD 6000f)MIN.
WHEICLOMED PARALLEL. TO V E ANCHOR SHAFT:
3 THE GROLIND ANCHORS MUST BE INSTALLED 10 THEIR FULL
DEPTH IN A=RDANCE YHVH THE MANUFA=RERS INSTRUCTIONS
(IG. APPROVED FOR INSTALLATION IN THE SOIL TYPE WWCH
AT THE SM ETr--) AND MUST EXTEND BELOW IHE FROSTSS
SPEMED OTHERWISE ON OTHEIt BRAWWGS, LINE AND BE AT LEAST 1r ABOVE THE WATER TABLE
RECOWN SIRAP5 AND GROUND ANCHORS
E11J)DLOSISTS
MEDON 'IBIS -DRAWING DIRE IN AODITWN' 4. ALL GROUND ANCHORSCONNECTED TD THE FRAME
HE'TiEDDWN STRAPS AND GROUND ANCHORS M DOIdNS MUST'BEPROVI= WaH STApIL1ZBR PLA IES TO
IRED AT THE SHEAR WAlIS. MINIMIZE HORIZONTAL !MOVEMENT.
P. v ISF..L
THIRD PARTY
REVISIONS
L'I
W.
DAM
f�ro�ir»s3�L`..
p►WOHORAGE SYSTEM
•'
�.
1VE�4R MI M n4fin
DnAtM+ BY: tc • '
tow tm.
m N.TSW�-FI-2
r STI<TE GP 7
�'�.• "l:0It1�?l;•a.
V 1/4w
�;1 illnl cI 0 )nnA
LL 1EDOWN; 5Y,
FQNI IN Q1W,HALF' TM (4) f1D x i 1,W SCREWS
A7, EACH �.
FOR FULL MMrrH, SHED$ MALL% LOOP STRAP; WRWGH
SLOT IN sNEAtz. WALL vfxncu..nmaKx. IWCHOR AND
/ C01tNEC7 EeWi END TO DWBLB BEAD CRI WW ANCH¢IL
,,,IKWALL PM qE1 W EDGE JOIST OPPOME SHEAR WALL
WHEN ViEAR WALL 7mmm Om Xw CAMfq.EVf L
NOTE;
ALL 71EDOVM STRAPS AND ,CDNN=NG H.Alt>aMW LUST
C�R7iFgEZ] BY A PROFMO NAL FBdt�'f.8 OR A
iE''da Nc LASORA7DRY 7D ADEQUAIELY SUPPORT A 3150#
ol
LLOWABLE LOAD MNUM (ULT"IE WAD 47M# WNIMUM)
AND/OR 70 COMPLY ,%M ASW 03053-M.
ALL CH011l>D AWHMM$ WWO ON INS DR WRG JAW BE
CER1M BY A PROFESSIONAL k o*m OR A W W =W
`1ES MS LABORATORY 7D ADE WEI.Y SUPPORT A 40OW
AUDWABLE IbT6.1DRAUL LOAD 1QH..(LfL'lUME L01AD 6000# AWL)
WEN LOADED P/41te M llM ANCIM SHAFT:
A
TRIM -PARTY
REVISIONS.
&ell
NonuS9Rt1�
t ,srAroF �
+,•• �
ANCHORAGE SYSTEM
'FIELD, INSTALLED.'
GRNIN 'B'� 7b " oiwu tidy • _ 4
Lu00C
0 J'UN 2 9 2004
n..
pDU5LEUJlDB -5HEAR tLALL TIED©WN SY'STIEM
VIND
ZONE
2 4
3
WAILS, QtSTALL
WN SIIiAP OYFR S[F:Et.
m A tioue<�
SHEAR WA♦; %
09
TI®OWH "ANCHOR
W/ RADIUS CUP
I EDGE OF HOUSE .
+.; OR CHASSIS BEAM
.. .. ;
•'CONTIh1U0U5
71EDOWN STRAP
��L a►4°
GRADE
TIEDOWN STRAP .
1NSYALLA7IQN
DOUBLE HEAD
:
-GROUND ANCHOR
4 STRAPS ON TRUSS ABOVE SI4 m WALL TD
w ovm HALF wrnH .(+);*o x t/z! sews
FULL Wia7H SP a' 7Rm THROUGH
'IN SLiEAR WALL VERTICAL UIDDWN ANCIiOR AND
=-EAW END 78 DOUME HM OfiCN1+1O ANlrHM
=Au PIER BF, m EDGE mw OPPOSITS SI;Em WALL
VMEN SHEAR WALL MUIINATEB OVER •JOIST CANTMEVER.
GROUM JWCHOR PIER W7HIN it OF
(t mAI,) WALL BELOW EDGE JDLSS (TYPICAL.
SHEAR -
NOTE
'
ALL T0MBK SIRAPS_AND CONUMINO HARDWARE MUST BE ,
LDDP SRAP 77HROUCN SLOT IN SHEAR W)U. VERTICAL
f.'ERTiFa BY,ATROFMONAL,ENCINMR-OR A REODGN12M
7E671NG L4BO TMY TD ADE QUA*nLY SWPDiT-'A 3!
TlODD18Rd ANCHOR AND ,CONNECT EAdi ENQ.TD. DOME
EAIL'A'. -70 D
A=WAM LOAD,WNIUUII (ULYWA'tE LWO 251 NINDJUM)
HEAD GROUND ANCIM SFUrr
;AND/OR m COWLY WITH AM D3253-OL
ALL GROUND ANCHORS ON INS DRAWN© MUST -BE
CE3t7MM BY A PROFESSIONAL ENGWW OR A REDO NaO
-TESTING LABORAMW 70 ADEAUA'IEU' SUPPORT ,-A,4OW
ALIMWBLE.W=RAW& LOAD YIN»(ULTlh1ATE LOAD 6000t MIN.
• ;.
WHEN LOADED PARALIBL Wl1H ANCHOR SHAFT. ,.
RE SEAL
THIRD PARTY
-REVISIONS
�-`�_ I��n„A��41�CH0SRAG
z
wC
OYt
,.SYS, E
MAW" *1 a
7; I"
MT4I1 *YY .
K7a. SIN--F%-4
J U N 2 9 2004
TYF_J.CAL-VQU5L�UJlQE TiEDOUN p LAC
NOTE: FOR TRIPLEWIDE OR LARGER DESIGNS INSTALL ALL THE VERTICAL 11EDOMS AT
EACH SHEARWALL, SIDEWAl1 AND MARRIAGE WALL AS SHOWN ON THIS DRAWING.
UND ZONE
VMUIRED ON SIDV OF OPEWNGS
GRFAIM THAN 4Er IN WI)TH
(7VrUl EACH SIDEWAW AND MARRUGE WALL) WHEN ENDWALL SHEARWAU.
LDrA7ED iN TM HW. WrAL wr
UMTAIN NORMAL. CHASSIS FRAME IIEDDYN CKA= TP.AME 7EDOYM WITHIN A
SPACING ACROW ALL VERTICAL =MCE EOUAL 'M 1/2 W NORMAL
TMDMN (rmoQ SPACING FROM END OF FLOW (TYPE
Z421 SIDMALL AT EACH ENMAU-)
� - ;ITEDDibNS AT EhIDS OF FJ►C'FI "
[WALL SH]EARWAL%Sn
s S s
A
Vaal)
SVARAIED -FOR CLARITY,
WHEN MOW41 SiEARVALL, IS NOT
ulm LOCATED IN.7W 144F.. INSUI ISr
(EM IWX 48-) t FRAME TM XYhN WTH]N 2'
Or EACH SIDE-
LrAT%T MEMDWALI-)
s s S,
ZEXCEPT FOR PULL WD7H SHEAR %K ON
l� IN ALL
UARRIAGE,WALL FRW; IISDOWN INSIALL CHAS58 FRAhlZ.tEDOMM
SIM OFAM CLASEST10 TZ IdAMUAGE ALONG. SIDEWALL VM AN AVaLAZE
WALL BELOW SHEAR. WALL "CAq SPACING NDT 70 EXCEED ME VALUE -
SPWFIED ON MANING SWG;-&
4101 S
(DID NOr INSTALL. FRAME TEDOWNS
AT SHEARWALL VOMMAL V=01
L=T0NS)(TVP EACH =EWAU)
� =SHEARWALL VancAL, TmowK EXCEPT AT OPEMO WIDIMS LARGM TITIAN
0 -STANDARD VERTICAL VEDM 41r. STANDARD 7=006 ARE
Vmm
S -0HASS8 FRAM(NOT REQUIRED) IN "NO ZONE 1.
2 wMAII WALL. FRAME UMDWN
SEAL THIRD PARTY REVISIONS pp
UO:, ft I I)AM
ANCHORAGE SyslEm
FIELD INSTALLED.
IWAV* I DAM Olik.
p fam Ilam" I= K-M SW—c-2
LU T
> , 0
0 JUN 2 !9 2004
TTP1G,4L. DDUE3L�I.IJIDE TE�DOLLIf<1 i`'L,4C1"1f�T
NOTE: FOR TRIPLEMDE OR LARGER DESIGNS INSTALL ALL THE VERTICAL TIEDOWNS AT
EACH SHEARWALL, SIDEWALL .AND MARRIAGE- WALL AS SHOWN ON THiS DRAWING.
STANDAM VE1 CAL 'RMO KS aRa: ltJihlD OI 2 3
REOUIRM ON FACH SIDE OF OPEMGS
IM THAN 4W IN iMD*M
CAL. EACH SIDEWALL AND MARRIAGE WALL)
WALL VERtICA[. TIEDONNS MUST 6E WHEN AN ENDWALL:IS A SHEARWAU„ INSTALL
WITHIN 2e OF OPENING STUDS) • 4ST SfAWDAF0 •VOM AL: TIEDOWN VAH7IN A
MAINTAIN NORM CIV FRAi.iE 11EDOY4Rd DISTANCE EQUAL 7Q 1/2 7w NOIZAIAL
SPACING AMSS SHEARWALL VEEnCAL SPACING.SPECIFiED ON DRAWS SW-G-3
TiEDDWN (;I1fP W) WROU END OF":FLODR.
_r-.(TYP EACH SIDEWALL AT EACH RIDWALL) .
INSTALL SHEARWALL WiTiCAL.
'i»Dll* AT ENDS OF r4kcH
SHEAftWALL AS SHOWN
CM ALL SHEMWAL.L.S)
M apma M
M oa o , M
H
I)DUBL£VM FLOOR SHOWN
. SEPARA1ED FOR Ct.ARiTY
BEiLOW NARRIAGE JUNE INSTALL IolAWAGE
WALL FRAME TIEDDWHS VMIN SOF EACH
END WALL. AND AT A •SPACING NOT TO E(CEED
THE DISTANCE SPECIFIED ON nlraWrrlG SW--G-3
(I)FICAL EACH HALF]
jvj Iv1
:Z-
' VW�EN ETIDWAI.L IS NOT A SWEARWALL
S
S
iNSi'JW. IST STANDARD VERTICAL TEDOWN
VNM 2' FRDM WE END OF'FLOOR. .
q
PTYP FACH S MALL AT EACH ENDWA 4
EXC£Pr FOR FULL YRDTH SHEAR WAILS, IIWALL
y=CAL, Fps ;SON ON •IyIE
INSTALL FRAME TIEDDWNS AT ALL STANDARD '
STEEL, MM CLpSW TO THE MARRIAGE WALL
TM
VERTICAL VEDOWN LOCATIONS ALONG, SIDEWALL
mww WALL .(T WAp)(� SILT-FI-4).
(00 NOT QtSTIl1.L FRAIAE • TI£DOWAS
'f o
T' SHEAILWI►l.l. VER;tCAL TimOY,N
LOCATIM)(TYP CAM SIDEWALL)
M=MAR WALL. DIAGONAL Fiwz "tmDWN
• asllEARWALL VEtCiiCAL'REOQIHN
RW LL STANDARD VERMC& MEDOYMS
'0 -6 ANDAN.D VZRTICAL 11EDM
ALONG SIDWALL NRTN -AN-AVERAGE SPACING
S -61ASO QIAGDNAI. FRAME 10MM
NDT'Tb EXM THE VALUE SPECIFIED.
0-VOMrAL. FTC TMa 1
ON OtiNW11R9 SYR-G�3 .
t
�;..;.'� •• :im CAM
AN G S
NEAR BEAM METHOD _
w' •� f ht SIC eLTS JrW G"" '
Ole,
r
Ltj
0. JUG! 2 9 2004 0
MAXIMUM TIEDOWN SPACINGS
FIELD INSTALLF-0-
i QW; I i
ALL GR01" ANCHM SPEMFMD ON THIS MWWAW MUST BE
CER"FIED BY A MCFESMONAL ENWEER CR A FtECMrM)
TESM LASUMTORY TO ADEUMTELY ZLWPORT A 3150*
ALLOKABLE WMIDPAWL LOAD CLUMTE Law 4725W) Mgt
W"6NIOADED AT A 451 ANGLE FROM THEAMCM SHAFT AND A
31" AME WLr(LT=41250 MIN.
MEN To MM�_
NOTE Du tm ALL TZEDOM IWAUATIcM
PRoTmnoN MUST BE nZOMED TO ALL
TUM STRAPS AT ALL MgW,coMEM
REF. CALC
LC - 0 -JUN 2 9 2004-
0A = MAX. SO)EWALL ROW OVEINAW
Far flv,4r ZZar
HE MW FMIM GRUE 'M
TOP OF STEEI- MAK
4A, 2 ,
Mrx-ICATIUM' ON THIS DRAWING SLFERSEDE
Me ALL UTHM &PECIRCATIMS SHOM ON OTHM
DRAWINGS ANDIOR IN TIDE SET-UP MANUAL_Lt 4CF
0R ANCHORAGE SYSTI
3.��SYern�E no INK
Lu
-0
>;
T
0
JUN 2-9-2004
033
CL
Federal Mobile
m
<
Home Construction
m
An d
MAXIMUM TIEDOWN SPACINGS
FIELD INSTALLED ..
MIAI M,•
OUT.,
®�®
..
0K= MM-SIDEWALL ROOF OV6il1 G
ALL'ANCHORS MVCMED ON 7W MAW M = BE
CERTIFIED BY A PR�1. Sd61tt OR �C0&NII�.
# FEK,'FJT FROM GRADE TD
TOP OF STD BM%
7ESi1N6.f ftMT W TIO ADE=TEW StfPCRT-A 3W#
AUMAKE WMEPAWL LOAD 0MMA7E LOAD 47251P)_MIPt-
Wt*N L WM AT A ANGLE PROM! TFEANUM SITAR AMA
",
-
'. ��ALLeOWABtEWIiF�RA)!B.LOAD.EU-TMA7El.OAD'f.�?'M16J:,..
.
-
�iwiuu
- _
VIt8+1 I n PARMIEL Td THE Atil MOW.
; •;
Js
5 1 L'i
:.
FF ` -e{•
-` .
' -S*G'3 VIEW
:..
e- MR= ALL TEDOM WrALLATIOMt�.:
. _ ._
NOTE . ICATWNS ON TM1S DRAS W SUPtB
OiFIE R SPECSCATIONS'SiiON ON OiiiEst
' - oF_
ANd ►6E SYSTEM
PI MEMON MUST' BE PROYM TO A!1
MEDG MH STRAASAT All Si(W COBS.
ALL
ORAWMS AMIOR IN ME SET-W MAM _
v
�,14 f
R%*
1Lu -v
REF: CALL
CL Federal Mobild ICI
Home Coustruction'
A.nd Safety Standards
LONSTUDINAL. FiRAME TIEDOWN INST LLATIoN
ONLY REQUIRED Wl iEN, LONGTUD..INAL � EDOWN ANCHORS INSTALLED ON. BOTTO�1 OF STEEL BEAM)
oNB a Out: Txzym i[wl olwwo Gaon Hoar
HS.IlL9TJi11.G[)'Obl S71CII' IArIfl. Txb�o3altl litiC110& N,Em=
3�0 SnLin01 OF FiRCK' 8TS6C , I16M. D MPHCC FJ 4 anm!
Dn" TO Vmuxr TOR RmaxRED XNCUCut xoc�rioNs. STA4JOAk1) 5
PIER .(LlpGAnco MAY
VAR)o .
' - 1.IONGnUDINAL TIEDOWN-
saal:..�nomla sir >u6ap . amr .
nm ab xa nay. � m" �t smart as : BEAdI $ ANC ,QR (5M DETAIL
swan _ „m., m cad xa mm cras as --i xc=. °'A"; HE7SINj
s�oosrg sslnoul4 , xlls su:laa �' .. ,
"All
(1YY_ 8C7i7 Atd+x.CQfG: '87 ►PS ADID ALIC1&]A9) S! /i 1!
:Q3s x 1-114" TIEDOWN
70' MAP- (SEE,DETAIL -e
(,gyp) BELOW FOR INSTALLAWN
MUMM'XMG. rzMaaH'hrtC 0W AM laZ= ro fiN57R11C71QNS)
OF gual'sTJ;iiI.Mm AT AN Am=. amna OF 1 , o.c. DOUBLE HEAD
mwm mc31 E ml of repair (m tines axa>a. iox) GROUND ANCHOR
r 3 LA1 YIW "BCTIdN- uA--pit'
AlWAM Wom cup JUN" g 20Ia4
c•�►o ANGiOR Leo rREF .CA►LC' #
STEM �
Tumum a+A,sts t ~ t ta»oaN s>�w ru�F» 3t eta C�I71 W= STRAP tI QC3LUlti! iZ.d►1�lLly CI_1f'
m (UrATION ,1HR X;GH' MDT IN
AR'o SQiAP AS spt 1ED FOR �•_ LONON ANCIM
smut. t�tAUE tamov>tts) WIN m tiro OF saw uotic.•'TMDM ANaM
t iHRFM MMDUGH ORO=!
1..a1 ANL`IIOR BOLT sum,
7 ' 4WE
�1a: I(A=fa
DETAIL 11,4u FIFJIDGmmo ANCHtNt sAUE
eula�os AS SPECM F SlaEtsrAu. � ! 1.
a nowNs . - T M p
IMAUM;TO FABRICATE R=S IxlPBy'
Ala.-rj=aazxlc63i=
.tzmD FAP 6 D:J41cla BS SIRAlcu 31 UNCH1 OF 1-1//4' *.OW ' OVW uSTMp
TS! Piinps»sb tiil�7t ST98T•.TT� iti a98S TQ 1 IN ANCHOR SL XT AND IrIA ALLY RENIUN01m STRAP ,
Itolis2oaexnz tervmae�er. • 0 ?w cmummoN sltotift
,�,�``;`•`�` `' �a``,;�af,.. THIRD PARTY RE S- 10hlS
AV
ANCHORAGE � S
FIELDINSTAL1LED
3, `. ' "r �; ; y, .i : . t : ti; • POW
j ! oRAs�o� elr: 11 1""
NIL
N.>s SW—EI--5
,cc JUN 2 9 2004 I•
2x4 SYPA 571FFD ERE W7kDN .e,,-`'
OF TOP AND SOTFOU OF OPEMNG' "'
AND 16' dC (MAXI SEE NOT£ 7
PI.YwtioO smRw+ cow* ..
- INST'AIl. VIRTIi FACE GRAIW
PLACED NORRGrNT&
SEE TAME SIIAW FOR
PLYWOOD SPF.gFICA7)0NS «»
uOcatE PLYWOQI7 SEAMS ovER .:...»,
►� aF � sTi�IrR C'�'.
FA701 PLYWOOD 37M COVQt
.ID, TNNDOW VEnC,AL M4MNQ .."..
Wliii (1) dnd x 2-1/f Paz— ......
51IFF7NER B� � OF y..«..
n
710P PLATE
FOR-NANDOWIDdOR WDEit 7HAN Be
SEE NOTE 6
;r'tiPtcat Scm, INSTAlUM014
SEE DETAIL 0*47 (DWG SLt-VJ2)
TYPICAL S'IIftm- INSTAU' AMON
0'01SEE DET•AL' 1174r (DWG SU-W2)
WMOW/booR WM/WALL FRAU)NO
BMIND SroRIII COVER
,14NDOWIDOOR OPENING %WTH
N
MM�
CON?INI1E •STORM OWM •AND STIFFENERS
TO FLOOR IF DOOR OPENI14 (NOT SHOYM
i�0"i�C"1'It�i FOR •�.tJ�U�1115�� ]
PIAIE
I I r 1 17.Y. 11 � 11 7
41
a r vs.l 1 1 /..��� � -
Ctt.'NOII�81 '
1/ 1NSTALl.ER 1dUST RRIDYE ALL, DECORAZIVE SHuilEttS;SOQtS JSS;3IfiE STCft NA S SU85lDIDEriORM
1 ALL
FROM WINDOWS AND ADDIi.S PRIOR :fO,INSTAWNG THE 'PitOTa!'17DFI,COVEtiS i1US? pa{AFbIAT£LY REMOVED
•5i0RM COMERS SPE)CM ON THIS URAWlNC: BERD[iE OCCUPANCY, OP'I}!l 8lllLpM1S I?.
Z YJHEh1 HURRICANE OR SSW IMNQ 51DRN5 B. ALL WOOD SCRI:i4F NOTES, 1i6UL11NG. FRDltd THE :.CORM
APPROACH, THE VWDW .AHD DOOR PitO7EC1iDD1 COVERS . C04ER RWALLA71pN , WT.SC 81e, FILLED SIG'FH CtOOD
SPWFIED ON INS ORA.WING sHouCD eE INSiALLm nvAT:nY EXTERIOR •GRADE CAULK,
3. Clil>IlEQ1A'ILY A!"tER� IN5Ti4t11NG 7FIE5E C4� '►K 7/ yn'IEM„ OpENMD IIIMTTi .EXI�FDS 84' UP TO A AIA>fl6dUM
BUILDING !<dUST' BE VACAYi"b AND/OR NO dDCPANTS • OF; 'i20'1 REPLACE 2x� S1IFFENERS Wl7I'i 2x6 SPF*2 AM
SHOi1ID RIwLWN IN1ME 57iiUCy3)RE USE 3/4!' PLYWOOD 147W SPAN INDDC OF 48f2C ALL ,
NOTE: 71ii><55 $7nC6d PRO:E>r'ITON SY57i31 DOLES NOT 07NFR:.IH57'AL4A'ilOr! 9PF.MCA710N5 RE7AAIN t1NCHlWGM
PERtli7' lxEiF: S FROA1 'JHE gU1LDiHG UNDRi FIRE '& FDR'Oi?io1+I1NG`1M1BDER 7FIAtt @o'. L;DCA7E S1'DRU• COVER
PER CALC
OR f7THhR DoGLsA1CY GONDLiIONs:I ' BUTT.:.X11N'f-sWlnilN 3D'.OF:,VER7ICAL S1UDS AND WSiall
"I't' CLIPS 9E711Vr?P]�1 W►IBfR s'f1FEENERS AS SHOIYN.
P.E. SEAL
THIRD PARTY
REViSI4NS
r
ININDOW/D00R. STaRM ,PROTECTfO
FIELD' INSTAL�D
mwl+ sr: 740
L" t+a: SU— W1
u-
,JUIV 7, y LUU4 0
PLYWOOD STORM COVER UU5r
La(TIr?JD LON 3` BEYOND EDGE
OF WINDOW/ODOR FRAME AS
SHOWN (TYP)
PLYWOOD STORM COVER (MIN)
)OW/DOOR FRAME
TYLE MAY VARY) `
JAW/WALL STUD
I
WINDOW/DOOR NOT SHOWN
(TYPICAL STI
THIRD PARTY
NDTla
INSTALLER MUST LOCATE WOOD 9CREWs 3/4`
FROM EDGE OF VANDOW/bOOR FRAME AND k(UST
VERIFY THAT WOW SCRLV PLACEMENT PROPEItLY
ENGAGES LUMBER FRAMING
1- 2:I 2• M of
31DID B' o.G. {SEE HDTE ]tf3ovE7
STEM WASHER
METAL 1118E/MNDER
/(OR PLYWOOD SPACER)
IJBBER WASHER
' VINYI�L stalNa w/ I:xrEl:toR st Ia:s►T1�Lc (AS SHOWN)
OR MMIOR HARDBOARD WiNG (HoT SHOWN)
i`t (SMTIUN . UOMR SL�OCKtNc
"r'lnNl HA - All
REF. CALL # IJUN 2 9 ZOOM
.3/s' x 3-y ' LAO
WITH 1-11t DIAMETER
WASHER AT EACH END
STIFFENER (TYPICAL)
2x4 51ftER ENTIRE WIDYH
OF STORM COVER
PLYWOOD STORM COVER
Ox3'SCREW rO.m
IMP ENTIRE LENGTH OF
°Jo1� tt�_�tI •
INER INSTALLATION)
SI ONS
oAT� �' i� i•.L�`
en 70 1 DA'Lk 40- SU—W2
Imp iscl -T.
rr
Chapter 6 - utility Connections
Secure cap supply inlet when not
6a) Plumbing / Gas Connections
The gas system of this home has .been
tested for leaks before leaving the factory.
However, prior to connection of the gas supply,
another pressure test is recommended to'
ensure that the gas piping system is free from
leaks after the home has been setup.
First, close all gas appliance shut-off valves.
Then attach the gas test fitting, gauge. Pump in
air until 5 oz. of air pressure is reached.. This
pressure must remain for 10 minutes without
any indicated pressure loss.
aE
WARNING
DO NOT over -pressure the gas system as
damage may result. The gas piping supply
system has been designed for a pressure not
exceeding 14" water column ('/a PSI) and not
less than 7" water column ('/4 PSI).
A) Gas Lines.
➢ This gas piping system is designed for
use of either liquefied petroleum gas or
natural gas. LOCATE "Quick -
Disconnect" and . connect where
applicable. Quick -Disconnect is located
under the floor where the halves come
together.
CAUTION: Do NOT use tools to
separate the Quick -Disconnect
device.
CAUTION: Before turning gas on,
be certain appliances are designed
for the gas connected and are
equipped with correct or
connected for use.
Vo� CAUTION: Before turning gas on,
Make sure all gas connections have
been made tight, all appliances are
turned off, and any un-connected
outlets are capped.
15 CAUTION: After turning gas on, test
gas. piping and connection to
appliances for leakage with soapy
water or bubble solution, and light all
pilots.
B) Water Supply Lines
➢ ,Check water and drain systems to
assure that vibration during
transportation has not . loosened . any
joints.. (For models with baths in both
halves, connect hot and cold water
supply lines provided under center
walls; where two halves meet, turn,
water on, and check for leaks.)
CAUTION: Do not ,power on to
electric water heater until the tank is
filled with water. The water supply
system is designed for a maximum
inlet water pressure of 80 PSI, if the
local water supply pressure to which
the home 'is being connected
exceeds 80 PSI, a pressure reducing
valve should be installed to limit the
supply pressure. A master shut off
valve shall be installed at the water
supply inlet.
Homes, set in areas subject to freezing
temperatures shall. have exposed water
supply pipe,protected. An electrical
SU-31
ScotBilt Homes, Inc.
Chapter: 6 - Utility C®ni ections
receptacle shall be located nearby Ifor the
use of electrical heat tape. Heat tap ie used
shall be listed for use with mobile ho es.
A) Drain Lines
➢ For models that have baths in both
halves — install drain lines and fitting'
between the stub -downs unde neath
each unit. Care should be to en to
assure compliance with local plu bing
code.
NOTE: Refer to plumb drawing fo field
installation of DWV. (Some field
installations may have been don at
Factory.).
6b) Electrical Connections (See Table 6A )
:For proper feeder conduct sizes I and
junction box size to be used in main electrical
hook-up refer to local electrical and buikng
codes. A qualified electrical serviceman using
approved electrical test equipment , should
perform the required continuity, polarity, and
high potential system tests.
WARNING
Always remember that electricity is
potentially the single most dangerous aspec I of
any home. Always take extra precautio s
when dealing with any electrical problems jor
jobs and always use a bonded and certifi d
electrician to do them.
A) Electrical System
This home is' wired according 'to HU
specifications for mobile homes.
CAUTION: Do NOT remove ground
wires or clamp connections Do
NOT cut ground,wires.
CAUTION: Do NOT turn power on
to electric water heater- until tank is
filled with water.
NOTE: The- following refers :'to doublewides
only.
B) ' Inter -Connection between halves. (See -
Figured 6.2)
.1) Lighting circuits.
a) Locate junction box along the
mating line.
CAUTION: Be sure all
Wires have been run inside the
junction boxes before beginning
hook-up. Never hook wires together
outside of'the junction box.
(b) Connect the conductors in the
junction box as follows:
(a) Bare copper conductor to
bare copper conductor.
(b) White insulated conductor to
white insulated conductor.
(c) Black, insulated copper
conductor 'to black insulated
conductor.
(c) Install junction box cover.
NOTE: Small appliance circuits (if any) will
also be marked to correspond with its matching
wire of the other half. Follow the same steps
as for the lighting circuits discussed above.
60 Heat Duct Connections
A heat duct crossover is included in the set-
up kit for joining the heat ducts of multisection
SU-32
ScotSilt Homes, Inc.
Chapter 6 - Utility Connections
homes. touching the ground at any point. Also, the
A. Crossover Duct Hook -Ups for Double vent must extend completely to the exterior of
Wides the home extending 1" to 2" from the'base. Do
1. Slide each end of crossover duct NOT . leave. dryer vent open underneath the
-over the dropout underneath each half. home. The end of the duct should be equipped
Secure by method provided. with an approved damper.
2. Wrap/Cover all seams and joints with
duct tape to reduce leakage.
3. Wrap/Cover exposed metal with
fiberglass insulation to reduce heat loss.
4. Be' sure to strap and -support
support
_crossover duct in such a way as to keep
1t off of the ground. (With galvanized
straps, etc...) See figure 6.3.
B. Furnace
1. For future installation or changes in
the heating and cooling system and for
possible additions of dampers, etc...;
refer to furnace manufacturer's
instructions included With home..
CAUTION: Inspect furnace
for physical signs of damage.
C. Gas Furnace Models _
CAUTION: Chimney must be
in place and completely installed
with accessories before turning
gas on and lighting pilot.
t� CAUTION: Do NOT turn
power to furnace on until it has
been inspected and leakage test
conducted. .
D. Electric Furnace Models
1. Furnace is completely wired. No
further connections need to be made.
CAUTION: Do NOT turn
power to furnace on until furnace
has been inspected.
6c) Dryer Vent
When installing dryer vent, be sure that duct
is strapped in manner preventing it from
MANUFACTURERS EXHAUST
OR EQUIV.
DIST
AMING
SU-33
ScotBilt Homes, Inc,
Chapter 6 . - Utility Conn ctioi
Table 6.1 I
Electrical Feeder and Equipment:Sizes . .
ELECTRICAL FEEDER AND EQUIPMENT SIZES (COPPER).'
MAIN BREAKER
SIZE IN PANEL
BOX (AMPS)
COPPER CONDUCTORS
MAXIMUM
CALCULATED
NEUTRAL
FEEDER LOAD
(AMPS)
MIN. SIZE
RACEWAY
CONDUIT
DIAMETER IN.
FEEDER CONDUCTOR /SIZES
I
RED AND BLACK
(POWER)
WHITE (NEUTRAL)
GREEN
" GROUNDING
30
1
#101THW
410 THW
#8 THW
30
50
1
#6 THW
46 THW
48 THW _
50
100
1 1/4
#2 OR #3 THW
#2 OR #3 THW
#8:THW
125
1 1/2
#1 OR #,1/0 THW
#2 THW
#6 THW.
.100
1.15
150
1 1/2
#1/0 OR #2/0 THW
42 THW
.#6.THW
115
200
2
#0/0 ".
#2 THW
#6 THW
'115
ELECTRICAL FEEDERIAN® EQUIPMENT SIZES (ALUMINUM)
MAIN BREAKER
SIZE IN PANEL
BOX (AMPS)
ALUMINUM CONDUCTORS
MAXIMUM
CALCULATED
NEUTRAL
FEEDER LOAD
AMPS
MIN..SIZE
RACEWAY
CONDUIT
DIAMETER IN.
I FEEDER CONDUCTOR /SIZES
RED AND BLACK
POWER
WHITE (NEUTRAL)
GREEN
(GROUNDING),
30
1
#10 THW
#10 THW
#6 THW
;30 '
50
1
#6 THW ,
#6 THW
#6 THW
so
100
1 112
#1 THW
#1 THW
46 THW
-
100
125
2
#2/0.THW
#1/0 THW
#4 THW
115
150
2
#3/0 THW
#1/0 THW
44 THW
115
200
2
#250 MCM THW
41/0 THW
.#4 THW
115
ScotBllt Homes, Inc,
Chapter 6 -(Utility Connections
Figure 6.2 —
Electrical Crossover Connections
Lyle
wrSAW u Sl "B" SIDE
ExnyaoR wAu.
MARRIAGE WALL MARRIAGE WALL MARME MARRIME WALL
»A" SIpE "B" 51 .... Ncnoir eoxWPM
CON EM" (GRO GROND LW) CM
:... /
ELECTRICAL CROSSOVER METHOD Awpm.I102 1,, � &Mw UM)MUfMNY, No BRAL E REQUIRED
ALT. ELECTRICAL CROSSOVER WIRING
( DLSTRIBUTION PANEL LOCATED ON ETTHER 'A' SIDE OR 'B' SIDE OF HOME
'(s) CROSSOVER PROPER WE JiRJCW BOX CAN BE LOCATED ON 'K. 'B' OR V
SIDE OF HOME
(3) aECTrsiA CGNitUMS WILL BE M.ADE INSIDE OF MOM BOX.
(4) CROSSOVER WIRE COVER WM BE USED TO COVER OR PROTECT LOOSE WM:ES,
WHICH WILL BE, SECURED TO THE BOIM OF 'FLOOR JOISTS, WO WILL BE
"M AUM ON THE SIDE ONLY, BUT IN SOME GISTS MAY BE USED ON
'BOTH SIDE.
(5) FRAWEGROW IDES SMUST BE CONNECTED PRIOR TO EiECM
�E
(6) PROPER EIECTRIGL CONNECTION Mt .BE MADE, SUCH. AS WIRE IDENTIFIED '
AT FACTORY MUST BE (NICHED AND ACCORDMG TO COLOR CODE :
BLACK (HOT WIRE); WHITE (NEUTRAL); BARE WARE (GROUND 00
(7) WAR WILL BE.IMSTAU.ED ON THE JUMCTKIN BOX, , PftOMCEED FROM
THE ELEMEW BY PAINTING, SEAUNC OR MWA W—
(B) HEATER HAS BEEN FILED WITH WATER, THIS MU5f Et DONEE TO PPRWff
DAMAGE TO WATER HFATM
(g) PRa AND UTo ra TALL wwE LIGHT FIXTURE, *WALL FIRE RIM BETWEDI S DMO
E.
(10) ENSURE WIRES ARE NOT MOWED OURM SETUP AND WALL PROTECTIVE COVER.
-SU-35 4
5cotsilt Homes, Inc.
Chapter 6 0 Utility Conn' cti®ns
'Figure 6.3 —
Crossover Duct Securement
TYPICAL EXTERIOR TYPICAL EXTERIOR
i WALL
FURNACE (MAY BE
LOCATED EITHER HALF,) TYPICAL MARRIAGE
WALL
iM.
( (�� N� N(((EWC
CROSSOVER DUCT SUPPORTS ( HEAT DUCT
(MINIMUM TWO (2) PER HALF.) �
I FLEXIBLE ROUND
CRCSSOVER;DUCT
Figure 6.4 —
Bottom Board Repair
% xLi . 1• STAPLE
I
REPAIR PANEL
PANFI--' "
. BOTTOY eOj
WATER PROOF TAPE (O M, 9DARD T BOTTOM BOARD OPENING (16* x 16 )
1 BOTTOM BG!tRD Mtw BE SEISED TO RESIST RODENTS
4 BOTTOM BOARD TAPE MUST BE APPRM BOTTOM DWAD TAPE;
INSULATION MST BE REPIACED PROPERLY. \
WHEN EXPOSURE T PLYWOOD IS USED, TT a NOT Tt Y To \ \ \ \ \\ \ \\ TYP FLOOR JOIST
OW FOR PROTOMION FROM THE\ \ %
�� \\
\
5) A "L LENGTH WY BE REAAiiDD MINT \ \�; \\ \
SU-36
BOTTOM BOARD
;COVER HOLE WITH BOTTOM BOARD
TAPED WITH MIN. 2 PIECES DOUBLED
APPROVED BOTTOM BOARD TAPE ALL
AROUND
ScotBllt Homes, Inc.