HomeMy WebLinkAboutTDH Calculation WorksheetSimpltified Total ma=c Head (TDH )C'J `rulation Worksheet Minimum Flow Rate Required: 35 GPM Per Skimmer. ( Required: 1 Skimmer per 800 Square Feet of Surface Area) Determine Maximum System Flow Rate 1. Calculate Pool Volume 336 4.5 * 7.481 (Gal/Cubic Foot) = 11,311 (Surface Area) (Avg. Depth) (Vol. In Gallons) 2. Determine Preferred Turnover Time in Hours: 6 * 60 ( Min./Hou) = 360 ( Hours) (Turnover In Mlns. ) 3. Determine Max. Flow Rate 11,311 / 360 + N/A = 35 (Vol. In Gallons) (Turnover InMins.) (Feature Flow) (System Flow Rate) 4. Spa Jets N/A N/A GPM Per Jet = N/A (No.OfJets) (Jet Flow) (Total Jet Flow) For single pump pool/spa combo, use the higher of No. 3 or No. 4 in the following calculations for pool & Spa Determine Maximum System Flow Rate Branch Piping to be 1.5" Inch to keep velocity at 6 FPS max at 35 GPM Max. System Flow Rate Trunk Piping to be 2" Inch to keep velocity at 8 FPS max at 35 GPM Max. System Flow Rate Return Piping to be 1.5" Inch to keep velocity at 10 FPS max at 35 GPM Max. System Flow Rate Determine Simplified TDH 1. Distance From Pool to Pump in feet 50 TDH Calculation Options Simplified Total Dynamic Head (STDH ) Complete STDH Worksheet- Fill in all blanks ❑ Total Dynamic Head (TDH) Complete Program or other Calcs. Fill in required blanks on worksheet & attach calcs. Maximum Flow Capacity Of the new or replacement pump Notes 1. If a variable speed pump is used, use the max. pump flow in calculations 2. For side wall drains, use appropriate side wall drain flow as published by manufacturer. 3. Insert manufacturer's name and approved maximum flow. 4. See installation instructions for number of ports to be used. 5. In -Floor suction outlet cover/grate must conform to most recent edition of ASME/ANSI Al 12.19.8 and be embossed with that edition approval. 6. Pump, Filter & Heater make and model cannot change, and equipment location cannot be moved closer to the pool without submitting a revised plan and TDH calculation worksheet for approval. 2. Friction Loss ( In Suction Pipe) In 2" Inch Pipe per 1 Foot at 35 GPM = 0.10 ( From Pipe Flow/Fricton Loss Chart) 3. Friction Loss ( In Return Pipe) In 1.5" 4. 50 * 0.10 = 5 ( Length of Suction Pipe) (Ft. of Head 5. 50 0.21 - 10.5 ( Length of Retum Pipe) ( Ft. of HeacD Determine Simplified TDH Pump Selection Main Drain Cover Champ-215, 1.5 HP CMP 25215 Inch Pipe per 1 Foot at 35 . GPM = 0.21 ( From Pipe Flow/Fricton Loss Chart) TDH In Piping 15.5 Filter Loss In TDH ( From Filter Data Sheet) 28.0 Heater Loss In TDH ( From Heater Data Sheet) N/A Total All Other Losses N/A TOTAL DYNAMIC HEAD 43.5 Using Pump Curve for TDH & System Flow Rate ( System Flow Rate must not exceed approved cover flow rates) Note: Minimum System Flow Rate based on minimum flow per skimmer of 35 GPM. Determine The Number & Type of Required In -Floor Suctions ( Check all that apply) ^a rhi O� 3.�0 CMP 25215 Suction Outlets At 175 GPM Max. Flow ( See Note 2 ) LLL❑JJJ O O O Suction Outlets At GPM Max. Flow ( See Note 3 ) 0 Suction Outlets At GPM Max. Flow ( See Note 4) ANSIIAPSP--72006 Species three methods for determining the maximum system flow rate. The following TDH calculation is one of the methods specified. Date Contractors Signature Contractors Printed Name Contractors Telephone Total Head In Feet Conversion Chart Inches Mercury (Vacuum Gauge) 0 2 1 4 8 1 8 1 10 1 12 14 16 1 18 0 0 2.3 1 4.5 .6.8 9 11.3 13.6 15.8 18.1 20.3 1 2.3 4.6 5.8 9.1 11.4 13.6 15.9 18.1 20.4 22.7 2 4.6 6.9 6.1 11.4 13.7 15.9 18.2 20A 22.7 25 3 6.9 9.2 11.5 13.7 16 18.2 20.5 22.8 25 27.3 4 9.2 11.5 13.8 16 18.3 20.5 22.8 25.1 27.3 29.6 5 11.5 13.8 16.1 18.3 20.6 22.8 25.1 27A 29.6 31.9 6 13.9 16.1 18.4 20.6 22.9 25.2 27.4 29.7 31.9 34.2 7 16.2 18.4 1 20.7 23 25.2 Y�32 34.3 36.5 8018.5. 34A 36.6 38.8 �L 36.6 38.9 41.1 Ft � Il '? 36.7 38.9 41.2 43.4 41.2 43.5 45.8 2 9 41.3 43.5 45.8 48.1 .3 34.5 36.8 39.1 41.3 43.6 45.9 48.1 50.4 14 323 34.6 1 36.9 39.1 41.4 43.6 45.9 482 50.4 52.7 15 34.6 36.9 392 41A 43.7 .45.9 48.2 50.5 52.7 65 16 37 39.2 41.5 43.7 46 48.3 50.5 52.8 55 57.3 17 39.3 41.5 43.8 46.1 48.3 50.6 528 55.1 57.4 59.6 18 41.6 43.8 46.1 48.4 50.6 52.9 55.1 57A 59.7 61.9 19 43.9 46.2 48.4 50.7 62.9 55.2 57A 59.7 62 64.2 20 46.2 48.5 50.7 53 55.2 57.5 59.8 62 1 64.3 66.5 21 1 48.5 50.8 1 53 55.3 57.6 59.8 621 64.3 66.6 58.9 22 50.8 53.1 55.3 57.6 1 59.9 1 62.1 64.4 66.6 68.9 71.2 23 53.1 55A 57.7 59.9 62.2 64A 66.7 69 71.2 73.5 24 55.4 57.7 60 62.5 64.5 66.7 69 71.3 73.5 75.8 25 57.8 60 62.3 64.5 66.8 69.1 71.3 73.6 75.8 78 26 60.1 62.3 64.6 66.8 69.1 71.4 73.6 75.9 78.1 80.4 27 62.4 64.6' 66.9 69.2 71A 73.7 75.9 782 90.5 82.7 28 64.7 66.9 69.2 71.5 73.7 76 78.2 80.5 82.8 85 29 6714MEAM707P.3 90.5 a2.8 85.1 87.3 30 69.3 1 71. 76.1 .QII 9.6 31 71.6 73. 65.2 .7 89.7 42 32 73.9 762 94.3 33 76.2 78.5 80.7 94.3 96.6 34 78.5 80.8 83.1 85.3 87.6 89.8 921 94A 96.6 '98.9 35 80.9 83.1 85.4 87.6 89.9 92.2 94.4 96.7 98.9 101.2 ` NOTE: FIELD TDH MUST BE EQUAL TO OR HIGHER THAN THE CALCULATED TDH. "GAGES TO BE INSTALLED AT THE TIME OF FINAL INSPECTION FOR VERIFICATION. Flow and Friction Loss Per Foot TERMITE TREATMENT REQUIRED Schedule 40 PVC Pipe Velocity - Feet Per Second Pipe Size 6 FPS 8 FPS 10 FPS 1" 16 GPM 0.14' 21 GPM 0.23' 26 GPM 0.35' 1.5" 37 GPM 0.08' 50 GPM 0.14' 62 GPM 0.21' 2" 62 GPM 0.06' 82 GPM 0.10' 103 GPM 0.16' 2.5" 88 GPM 0.05' 117 GPM 0.09' 146 GPM 0.13' 3" 138 GPM 0.04' 181 GPM 0.07' 227 GPM 0.10' 4" 234 GPM 0.03' 313 GPM 0.05' 1392 GPM 1 0.07 6" 1534 GPM 0.02' 712 GPM 0.03' ST. Li C?E �V(4___1AX_C_rPjS1P_NUN REVIEWED'FOR LU REVIE.�'ED ' DATE r1 f u.. )�T1 P .RM it� � - B TaPT ON JOB OR NO INSiPECTIO`i WILL BE 1 SWIMMING POOL SPECIFICATION FOR: Hernandez Residence 8000 Penny Lane, Fort. Pierce, FL. 34951 ^^ Niq ?Vr�(4J • ^T''I o ^W' �}W�1 CZ �I UM V •�, ^�I W U 00 00 82 A Q) o �z o� [0 Fi N bo q C0 u � Zke w 0. • a F v � .f{ Revision Date Date: September 23, 2016 Drawn bv: zJ0 File COPY