HomeMy WebLinkAboutStructural Design 6-28-22AFCFIVFO JUN - 8 20 sr ��2 Pe����; tt�9 n4Y STRUCTURAL DESIGN ENCLOSED BUILDING EXPOSURE 1PB B " Y c044 MAXIMUM 30'-0" WIDE X 20'-D" EAVE HEIGHT- BOX SAVE FRAME AND BOW FRAME 29 July 20211 Revision 6 M&A Project No. 16022S/17300S/20352S Prepared for: Tubular Building Systems, LLC 631 SE Industrial Circle Lake City, Florida 32025 Prepared by - Moore and Associates Engineering and Consulting, Inc. 1009 East Avenue North Augusta, SC 29841 401 S. Main Street, Suite 200 Mount Airy, NC 27030 MOORE AND ASSOCIATES ENGINEEFFING ANC CO NSI.LLTING NO 57170 �'p • STATE OF : 40 e,9* /O�NALSt .; JAW 1 1 2022 ORO� o Fa G,� ,. } No. SE0005T0 STRUCTURAL 1iC 9j FNGINEE`� tiF S. MC�JE� ugrr,,��, .�`�NN`4���o E AR �''• No 18W R. ,`,uuinnun,,,� CAR ' MOOR E 1IT n AND r 'rn %ASSOCIATES, INC. = No. CO2968 h 3f ,/�,• `,t��llleee�� 13 :;F : NO. 33416-E 4 ; PROFESSIONAL �— k5k, 4aINEE�`. pQ. ....•Mp JAIL 1 1 2022 Ida ®® h90 57170 r C041 po STATS OF �. MOORE AND ASSOCIATES DRAWN BY, JG TUBULAR BUILDING SYSTEMS ENGINEERING AND CONSULTING, INC. CHECCIEEB BY, PDH 30'-0"x20'PE ENCLOSED BUILDING EXP. B PE SEAL COVER SHEET TlQS Da11ETIi LS THE PFMPERTY OF NXME AND ASSDCiA7ES O AND PROJECT NGRt WSN JOB 16b 16022S/ CMCLUM T►E IBUU MMM REPR1mUCTla, COPYBG, DR QTIEAVISE l7SE iF TD 7-29-21 SCALE, NTS 17300S/2M52S 7= nXM ENT IS STFaMy PR Hmrnm AND ANY B'FRIIJ�A7ENT TFF7tEIptH MAY BE SUBJECT M LEGAL ACT= CLD=NTi TBS 1 NOt SK-3 .- 6 DRAWING INDEX SHEET 1 PE SEAL COVER SHEET SHEET Z DRAWING INDEX SHEET 3 INSTALLATI❑N NOTES AND SPECIFICATIONS SHEET 4 TYPICAL SIDE AND END ELEVATI❑NS SHEET 5 TYPICAL RAFTER COLUMN END AND SIDE FRAMING SECTIONS (BOX EAVE RAFTER) SHEET 5A TYPICAL RAFTER COLUMN END AND SIDE FRAMING SECTIONS (BOX EAVE RAFTER) SHEET 5B TYPICAL RAFTER COLUMN END AND SIDE FRAMING SECTIONS (BOX EAVE RAFTER) SHEET 6 TYPICAL RAFTER COLUMN CONNECTION DETAILS (LACED COLUMN) SHEET 6A TYPICAL RAFTER COLUMN CONNECTION DETAILS (DOUBLE COLUMN) SHEET 613 TYPICAL RAFTER COLUMN CONNECTION DETAILS (SINGLE COLUMN) SHEET 7 TYPICAL RAFTER COLUMN END AND SIDE FRAMING SECTIONS (BOW RAFTER) SHEET 7A TYPICAL RAFTER COLUMN END AND SIDE FRAMING SECTIONS (BOW RAFTER) SHEET B TYPICAL RAFTER COLUMN CONNECTION DETAILS QOUBLE COLUMN) SHEET BA TYPICAL RAFTER COLUMN CONNECTION DETAILS (SINGLE COLUMN) SHEET 9 BASE RAIL ANCHORAGE ❑PTIONS FOR LOW AND HIGH WIND SPEED SHEET 9A OPTIONAL FOUNDATION ANCHORAGE FOR LOW AND HIGH WIND SPEED SHEET 93 BASE RAIL ANCHORAGE OPTION SHEET 9C BASE RAIL ANCHORAGE OPTIONS SHEET 10 BOX EAVE RAFTER END WALL AND SIDE WALL OPENINGS SHEET 11 BOW RAFTER END WALL AND SIDE WALL OPENINGS SHEET 121 CONNECTION DETAILS SHEET 13 CONNECTION DETAILS SHEET 14 BOX EAVE RAFTER LEAN—TO ❑PTIONS SHEET 14A BOX EAVE_ RAFTER LEAN—TO OPTIONS SHEET 15 BOW RAFTER LT —AN —TO OPTIONS S�BYNED SHEET 16 VERTICAL ROOF/SIDING OPTION SHEET 17 HEATAIL ST LUCRE SHEET 1B FLOAL OD VENT COUNry SHEET 19 STAND—ALONE STEM WALL DETAIL SHEET 20 VERTIC,AL SLIDING WIND❑W DETAIL JAN 1 1 2022 SHEET ?1 STRIP FOOTING OPTION MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. DDC WNT = THE PROPERTY W NOORE A!m ASSDC nM OM103 �iG Alm LTDIG THE UMtlOQt�p REPRQTIIETD71, COPYO�G, DR QiHERVME USE OF DOCUMENT Ci STRD;TLY PROHM TED AND ANY MUNGENENT THEREUPON MAY m,ECT TO LEtr1L ACTml `asIII rrA ..... * : ItR0 57170 q O• STATE OF ®•40 AN 41, 'ON A HMAMN HT, JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED We PDH 30'-0"x20'-0" ENCLOSED BUILDING EXP. B I I JOB NDA 160223/ 2 IDWG. NE+ SK-3 IREW 6 INSTALLATION NOTES AND SPECIFICATIONS 1. DESIGN IS FOR A MAXIMUM 30-0' WIDE x 20'-0' EAVE HEIGHT ENCLOSED STRUCTURES. 2. DESIGN WAS DONE IN ACCORDANCE WITH THE 2020 FLORIDA BUILDING CODE (FBC) 7TH EDITION, 2012 INTERNATIONAL BUILDING CODE (IBC), 2015 IBC, AND 2018 IBC. 3. DESIGN LOADS ARE AS FOLLOWS: A) DEAD LOAD = 1.5 PSF B) LIVE LOAD = 12 PSF C) GROUND SNOW LOAD = 10 PSF 4. LOW ULTIMATE WIND SPEED 105 TO 140 MPH (NOMINAL WIND SPEED 81 TO 108 MPH): MAXIMUM RAFTER/POST AND END POST SPACING = 5.0 FEET 5. HIGH ULTIMATE WIND SPEED 141 TO 170 MPH (NOMINAL WIND SPEED 109 TO 132 MPH): MAXIMUM RAFTER/POST AND END POST SPACING = 4.0 FEET. 6. END WALL COLUMNS (POSTS) AND SIDE WALL COLUMNS ARE EQUIVALENT IN SIZE AND SPACING (UNLESS NOTED OTHERWISE). 7. RISK CATEGORY I. 8. WIND EXPOSURE CATEGORY B. 9. SPECIFICATIONS .APPLICABLE TO 29 GAUGE METAL PANELS FASTENED DIRECTLY TO 2 1/2' x 2 1/2' - 14 GAUGE TUBE STEEL (TS) FRAMING MEMBERS. FOR VERTICAL PANELS, 29 GAUGE METAL PANELS SHALL BE FASTENED TO 18 GAUGE HAT CHANNELS (UNLESS OTHERWISE NOTED). 10. AVERAGE FASTENER SPACING ON -CENTERS ALONG RAFTERS OR PURLINS, AND POSTS, INTERIOR = 9' OR END = 6', (MAX.) 11. FASTENERS CONSIST OF #12-14x3/4' SELF -DRILLING FASTENER (SDF), USE CONTROL SEAL WASHER WITH EXTERIOR FASTENERS. SPECIFICATIONS .APPLICABLE ONLY FOR MEAN ROOF HEIGHT OF 20 FEET OR LESS, AND ROOF SLOPES OF 14' (3:12 PITCH) ❑R LESS SPACING REQUIREMENTS FOR OTHER ROOF HEIGHTS AND/OR SLOPES MAY VARY. ROOF SLOPES LESS THAN 3:12 REQUIRE USE OF JOINT SEALANT 12. STANDARD ANCHORS SHALL BE INSTALLED THROUGH BASE RAIL WITHIN 6' OF EACH COLUMN. 13. STANDARD GROUND ANCHORS 'SOIL NAILS) CONSIST OF #4 REBAR W/WELDED NUT x 30' LONG IN SUITABLE SOIL CONDITIONS MAY BE USED FOR LOW ( < 108 MPH NOMINAL) WIND SPEEDS ONLY. ❑PTIONAL ANCHORAGE MAY BE USED IN SUITABLE SOILS AND MUST BE USED IN UNSUITABLE SOILS AS NOTED. COORDINATE WITH LOCAL CODES/ORDINANCES REGARDING MINIMUM LENGTH FOR FROST DEPTH PROTECTION. 14 WIND FORCES GOVERN OVER SEISMIC FORCES, SEISMIC PARAMETERS ANALYZED ARE: SOIL SITE CLASS = D RISK CATEGORY I R= 3.25 L-= 1.0 SDs= 1.522 D V= CSW SDI= 0.839 D MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. lac MID EOF 1 MAY AN 1 1 2022 lk ,....4.40 .. ate` ��NeC E 1v � * ; No 57170 • lk r. a. P �• STATE OF .•�v �L . I��o�< O R 1 o P �\�®oR Q4YA' `SXN,,o� DRAWN BYi JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED BY, PDH 30'-0"x2O'-O" ENCLOSED BUILDING EXP. B JDB N0 16022S/ 3 JDVG. Na SK-3 PEV., 6 17 BOX SAVE FRAME RAFTER ENCLOSED BUILDING ROLL -UP DOOR (AS APPLICABLE) PERSONNEL DOOR DESIGN PRESSURE (AS APPLICABLE) LOW = (18.5 PSF, -20.9 PSF) DESIGN PRESSURE HIGH = (27.6 PSF, -31.2 PSF) LOW = (18.2 PSF, -19.8 PSF) HIGH = (27.2 PSF, -29.7 PSF) l2 �3 6' (TYP.) - FLASHING IMAXIMUM RAFTER SPAN (V) TYPICAL END ELEVATION SCALE: NTS BOW FRAME RAFTER ENCLOSED BUILDING ROLL -UP DOOR (AS 4?PLICABLE) PERSONNEL DOOR DESIGN PRESSURE (AS APPLICABLE) LOW = 11B.5 PSF, -23.9 PSF) DESIGN PRESSURE HIGH = 27.5 ?SF, -31.2 PSF) LOW = (18.2 PSF, -19.8 ?SF') HIGH = (27.2 PSF, -29.7 PSF ) 12 Q3 ) MAXIMUM RAFTER SPAN (W) TYPICAL END ELEVATION SAL NTS F WINDOW CAS APPLICABLE) DESIGN ?RESSURE LOW = (19.1 ?SF, -20.7 PSF) HIGH = (28.5 'Sr, -31.0 PSF) LENGTH VARIES DEPENDING ON NUMBER AND SPACING OF RAFTERS TYPICAL SIDE ELEVATION SCALE NTS MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. 7= MDCMW 13 7W PROPERTY IF NM E AND ASSOCMM EMMEMM ING Na CRISILTIWti iFE IJliMlifQt�D REPR®UC7�1, COPT01G, Ot QiIERVISE USE IF 714S DOC11Elli S STRIC7LT PROH®IIED AND ANT DFiiDil}]QlT 7fESlIIPs� may WINDOW (AS APPLICABLE) DESIGN PRESSURE LOW (19.1 PSF, -20.7 PSF) HIGH = (28.6 PSF, -31.0 PSF) LENGTH VARIES DEPENDING ON NUMBER AND TYPICAL SIDE ELEVATION SCALE: NTS S C sTz�c /\ n JAN 1 1 2022 Igills# GE No 57170 .q • R /yr A y • : 4r � STATE OF' BRAWN HY1 JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED BY, PDH 30'-0"x20'-0" ENCLOSED BUILDING EXP. B -- --I I .JDH NO YOM/ . 4�NO SK-3�,, 6SK-3�,, 6 29 GA. GALVANIZED METAL ROOF AND WALL PANELS FASTENED TO RAFTERS AND POSTS Il IS ROOF RAFTER 13 12 l2'-0' Q3 TS COLLAR TIE n IS LACED COLUMN (TYP) 29 GA. GALVANIZED METAL ROOF AND WALL TS ROOF RAFTER PANELS FASTENED TO RAFTERS AND POSTS 12 24' IS GA. U-CHANNEL BRACE FASTENED TO RAFTER WITH (4) U12-14x3/4' SDF'S AT EACH END (9 PER BRACE) IS LACED COLUMN (TYP.) 6 IS BASE RAIL 6 TS BASE RAIL <TYP.) (TYP.) 1'-0' (TYP.) 1'-0' CTYP.) 24'-0' ( W ( 30-0' MAXIMUM RAFTER SPAN W ( 24'-0' MAXIMUM RAFTER SPAN TYPICAL RAFTER/COLUMN END FRAME SECTION TYPICAL RAFTER/COLUMN END FRAME SECTI❑N SCALE NTS SCALE: NTS sEE l) T-S SPACING OF RAFTERS TYPICAL RAFTER/COLUMN SIDE FRAMING SECTI❑N NTS MOORS AND ASSOCIATES ENGINEERING AND CONSULTING, INC. JAN 1 1 2022 ®e®® airs yt ; No 57170 STATE OF <v: s O R 1 o ��I, a0N A118 is l `�N`,� TUBULAR BUILDING SYSTEMS By, JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 D BY, PIN 30'-0"x20'-0" ENCLOSED BUILDING E3M. B .1�8 NI, 16022S/ r Nab vsN TE, 7-2s-21 SCALE, NTS JOB NM 16OW TBS . 5 to SK-3 LEW 6 29 GA. GALVANIZED METAL ROOF AND WALI PANELS FASTENED TO RAFTERS AND POSTS TS ROOF RAFTER IS COLLAR TS DOUBLE COLUMN (TYP.) 12 Q3 29 GA. GALVANIZED METAL ROOF AND W� IS ROOF RAFTER PANELS FASTENED TO RAFTERS AND POS 12 Q3 24' lB GA. U-CHANNEL BRACE FASTENED TO RAFTER WITH (4) N12-14x3/4' SDF'S AT EACH END (B PER BRACE) TS DOUBLE COLUMN (TYP.) 6A (T IS BASE RA[L 6A (TYP.) IS BASE RAIL PJ -JI. 24'-0' ( W K. 30'-0' MAXIMUM RAFTER SPAN V S 24'-0' MAXIMUM RAFTER SPAN TYPICAL RAFTER/COLUMN END FRAME SECTION TYPICAL RAFTER/COLUMN END FRAME SECTION SCALE+ NTS SCALD NTS SEE NOTES 'SHEET 3) TS ;RAFTER/COLUMN FUR MAXIMUM ASSEMBLY SPACING LENGTH VARIES BE?ENDING ON NUMBER AND SPACING OF RA-TERS TYPICAL RAFTER/COLUMN SIDE FRAMING SECTION SCALE NTS MOORS AND ASSOCIATES ENGINEERING AND CONSULTING, INC ST400, B, Fr, JAN 1 1 2022 ®� Ili®►r� NS'• E •.9 S * No 57170 s r • �i O' STATE OF . W: �� e'l /ONAL���`�� �118111110® BY, JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 D BY, PDH 30'-0"x20'-0" ENCLOSED BUILDING EXP. B .IIIB N1 16022S BE SIA.ECT M LEGAL AC IML ,- -- - - I CLIENT. THS ISHT. SA IDV& to SK-3 IREV i 6 29 GA. GALVANIZED METAL ROOF AND WAI PANELS FASTENED TO RAFTERS AND POST O TS ROOF RAFTER 13 12 12'-0' Q3 12 TS COLLAR TIE - 29 GA. GALVANIZED METAL ROOF AND VALI PANELS FASTENED TO RAFTERS AND POSTS TS ROOF RAFTER 12 Q 3 24' IS GA. U-CHANNEL BRACE FASTENED TO RAFTER VITH (4) 412-14z3/4' SDF'S AT EACH END (B PER BRACE) TS COLUMN IS COLUMN 2 p x (TYP) Jo x o (TYP.) o sr x iIW Q tix E I N x 6B TS BASE RAIL SB TS BASE RAIL (TYP.) (TYP.) 2a'-0• ( V < 30-0' MAXIMUM RAFTER SPAN V L 24-0' MAXIMUM RAFTER SPAN TYPICAL RAFTER/COLUMN END FRAME SECTI❑N TYPICAL RAFTER/COLUMN END FRAME SECTI❑N SCALE: NTS SEE NOTES LENGTH VARIES DEPENDING DN NUMBER AND SPACING OF RAFTERS TYPICAL RAFTER/COLUMN SIDE FRAMING SECTI❑N SCALE: NTS MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. nm =mff IS THE PR pom IF "xw AND ASSETi m ENoEE m Mm �ISULTDMG THE Il1AUitQi�D RFPR®IA:T�1, COPYOE. OR Qi1ERVISE USE OF U4S DQ111ElTI IS STRDCTLT PR�IIED AND ANY QFRIIICf?EMT TFEREIIPON MAY SCALE: NTS ., ST �Gc B� JAN 1 1 2022 1111e1 ...:..4100, Rio ��e�S,�••�,\C, E N SF••; �F �•o No 57170 33 o ®. STATE OF W? .A.( D .• N TUBULAR BUILDING SYSTEMS 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 30'-0"x20'-0" ENCLOSED BUILDING EXP. B JOB N01 1602M 7-29-M SCALD NTS 17300S/20352S 5B M SK-3 imv., 6 TS LACED COLUMN BOX EAVE RAFTER COLUMN CONNECTION DETAIL 1 F❑R HEIGHTS W-0' < T❑ < 20'-0' SCALE: NTS L 18 Pik U-CHANNEL BRAG= =AST-NED TO THE COLUMN AND ROOF RATER, VITy ;4) NL-14x3/4' SD;'S AT EACH ? 1/2• END 'B ?=R BRACE( BRACE SECTION SCALE: NTS MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. 18 GA. U-CHANNEL BRACE FASTENED TO THE COLUMN AND RAFTER SLEEVE TO BASE RAIL (— RAFTER COLUMN/BASE RAIL CONNECTION DETAIL SCALE NTS S�, (30 lG ti� C'i� y JAN 1 1 2022 ,o k areee,e 0 0, A ono •G. �® O No 57170 e �r STATE OF [1/0 Z O R %o. `�,e sseaeeee DRAIN BY1 JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED BY1 PDH 30'-0"x20'-0" ENCLOSED BUILDING EXP. B .JOB NO 16CM/ .c �wwu��—•�� • ,mr,y„ lmmf, GUFTING. UR UT ERV= USE OF - - - - - -- TFdS =UeNi LS S =my PRMWnED AND ANY pFRIIICE NEWT THERELpM NAY BE SUB.= TD LEGAL ACTmu T, TBS 6HT. 6 6waHl SK-3 a 6 SECURE WITH— (4) N12-14x3/ S➢F'S (EACH END) TS ROOF RAFTER CONNECTOR 3/]6 SLEEVE 12 TO RAFTER 3/]6 (T YP.) 3 i 6' QS• 0 MINIMUM 6LONG, ' MINIMUM 15 GA., CONNECTOR SLEEVE. SECURE WITH (4) / »12-14x3/4• SDF'S —18 GA. U-CHANNEL BRACE FASTENED TO THE COLUMN AND RAFTER 3-1L 11 1 1 1 `TS DOUBLE COLUMN BOX EAVE RAFTER COLUMN CONNECTION DETAIL 1 Fr HEIGHTS 13'-0' < TO SCALE: NTS NOTE: COLUMN HEIGHTS 12'-3' < TO < IS-0— FOR HIGH WIND. ::::I l8 -.A. U-CHANNEL BRACE FASTENED TO THE COLUMN AND ROOF RAFTER, WITH (4) 412-14x3/4" SDF'S AT EACH END (8 PER BRACE) 9-- ) BRACE SECTI❑N SALE: NTS MOORS AND ASSOCIATES ENGINEERING AND CONSULTING, INC. 3-12 TS DOUBLE COLUMN 3-12 MINIMUM 6• LONG, CONNECTOR SLEEVE MINIMUM 15 GA., CONNECTOR 3/16 SECURE WITH (4) SLEEVE TO M12-14x3/4' SDF'S BASE RAIL 3/16 4 IS CONTINUOUS BASE RAIL I -I 11=+11' in 11 11 :111-111-111-111= RAFTER C❑LUMN/BASE RAIL 2 C❑NNECTI❑N DETAIL SCALE: NTS JAN l 1 2027- ,aaaa 1 ��0 Q` ••• C.. . 00 poi No 57170 :. ®; STATE OF• • s�,�•.•� � s lv�o �tt`'.•O 10.' ��` NS,aAa ENOa°°� DRAWN BYI JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED BY, PDH 30'-0"x20'-0" ENCLOSED BUILDING EXP. B _ JDB NO 160225/ IR OF 1/rNllrrirn IDIH�Y�i �E -� 7ZL JNnLLnIJ 1/dWJ/GVS RT LEGA IOKT P�17ED Atm ANY RFRIIiCiDQti 7fQtE7F0i� MIRY CLIENTI TBS 6HT. 6A N01 SK-3 a 6 CONNECTOR 3/16 SLEEVE TO RAFTER 3/16 6' MINIMUM 6' LONG. MINIMUM 15 GA.. CONNECTOR SLEEVE. SECURE WITH (4) 412-14x3/4' SDF'S , SECURE WITH— (4) #12-14x3/4' SDFI (EACH END) TS ROOF RAFTER 12 18 GA. U-CHANNEL BRACE FASTENED TO THE COLUMN AND RAFTER iS COLUMN `TS ? l/4'x2 l/4'-l4 GA 2E[NFORC[NG. SECURE WITH N12-14z3/4' SDF'S ? B' O.C. MAX. 7N BOTH SIDES OF COLUMN TS 2 1/4'x2 1/4-14 GA. C7LUMN INSERT BOX EAVE RAFTER COLUMN C❑NNECTI❑N DETAIL lA FDR HEIGHTS 10'-0' < T❑ < SCALE NTS NOTE MAXIMUM :OLUMN 'EIGHT IS 12'-0' FOR HI6H WIND. f ITS C71 UMN III// MINIMUM 6' L ON:i, ::Z ZEI ��, CONNECTDR SLb MINIMUM 15 3ASc_URE WITH (4) a12-1ax3/4' SP'S TS C7NTIN000S /— BASE RAILI�—���—��� -1 I I —I I I I I-111- RAFTER COL UMN/BASE RAIL 2 CDNNECTI❑AIL SCALt NTS MOORS AND ASSOCIATES ENGINEERING AND CONSULTING, INC. MW IIOCIIME f IS 7K PROPERTY OF MTIW IMm ASS=TES BGBEE 24 &w CTI O LTDG, TIE TIMUT UUM R0RTB7UCMM COPYDG• M TITIERI = UZ TIP 'MM DOMM T IS STRICTLY PR[JH ED IMDI MY D&WOMeff TiE7iE1M MAY IE SUBJM M LEGM_ eT nm CONNECTOR 3/16 SLEEVE TO RAFTER 3/l6 6' MINIMUM 6' LONG, MINIMUM 15 GA., CONNECTOR SLEEVE. SECURE WITH (4) 012-14z3/4' SOF'S TS COLUMN-/ TS ROOF 12 3� i QS• 20 SECURE WITH (4) 012-14x3/4' SDF'S (EACH END) IS GA. U-CHANNEL BRACE FASTENED TO THE COLUMN AND RAFTER BOX EAVE RAFTER COLUMN C❑NNECTI❑N DETAIL 1B F❑R HEIGHTS S 10'-0' SCALE NTS m ;u 18 GA. U-CHANNEL BRACE gSTENE2 TO THE C7LUMN AND ROOF-A=TEZ, WITH (4) 412-14x3/4' SD='S AT EACH L END (3 PER BRACE) BRACE SECTI❑N SCALE: NTS JAN 1 1 2022 �08®® kuf.?i e��,�,5� • •�` G E N g �0�((,,,� • ` �® • � No 57170 �A9• c• rr ice, � STATE OF •:�( op ,'ONAb ,S 0 ee 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 30'-0"x20'-0" ENCLOSED BUILDING EXP. B NQ 1 1b022S/ EI 7-29-21 SCALES NTS 1730.1®40222E . 6B wr- M SK-3 �V, 6 29 GA. GALVANIZED METAL ROOF AND WALI PANELS FASTENED TO RAFTERS AND POSTS 11 TS ROOF RAFTER 13 12 Q 3 12 IS COLLAR TIE 13 r. x w x TS DOUBLE COLUMN (TYP) 29 GA. GALVANIZED METAL RDOF AND WALL IS ROOF RAFTER PANELS FASTENED TO RAFTERS AND POSTS 12 Q3 24' IS GA. U-CHANNEL BRACE FASTENED TO RAFTER WITH (4) -12-14x3/4' SDF'S AT EACH END (B PER BRACE) TS DOUBLE COLUMN (TYP ) B TS BASE RAIL I� 8 IS BASE RAIL (TYP, f (TYP.) 24-0' C V ( 30-0' MAXIMUM RAFTER SPAN W ( 24-0' MAXIMUM RAFTER SPAN TYPICAL RAFTER/COLUMN END FRAME SECTI❑N TYPICAL RAFTER/COLUMN END FRAME SECTION SCALE NTS SCALE: NTS sEE NDrs TYPICAL RAFTER/COLUMN SIDE FRAMING SECTION SCAL NTS MOORS AND ASSOCIATES ENGINEERING AND CONSULTING, INC. TM a m S C T� CSC BNNFO �Fcov, JAN 1 1 2022 still ®®0 �s�e��••�\G E AIS�..; No 57170 oO° STATE OF : Qj e % ®111A` 1EN;o 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 30'-0"x20'-0" ENCLOSED BUILDING EXP. B JOB NO 16022S/ El 7-29-21 SCALD NTS 1730CS/20352S . 7 NOS SK-3 REV, 6 29 GA. GALVANIZED METAL ROOF AND WALL PANELS FASTENED TO RAFTERS AND POSTS TS ROOF TS COLLAR TS COLUMN (TYP ) 12 Q3 TS ROOF RAFTER t3 J = �u IS COLUMN o (TYP.> 29 GA. GALVANIZED METAL ROOF AND W PANELS FASTENED TO RAFTERS AND POS 12 Q 3 TI GA. U].ANN. BRACE FASTENED TO RAFTER WITH (4) k12-14x3/4' SDF'S AT EACH END (8 PER BRACE) =53 ZO= u u Qo u �F J< _ Q o� � ! W N= gA IS BASE RAIL TS BASE RAIL �'> V (TYPJ BA (TYP) 24-0' < V K. 30-0' MAXIMUM RAFTER SPAN V < 24--0- MAXIMUM RAFTER SPAN TYPICAL RAFTER/COLUMN END FRAME SECTION TYPICAL RAFTER/COLUMN END FRAME SECTI❑N SCALE: NTS SCALE: NTS N II _ sEE NOTES I SPACING Z37 RATERS J TYPICAL RAFTER/COLUMN SIDE FRAMING SECTION SZALE NTS MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. TM MOCtM T IS TIE PROPERTY OF MOW R M ASSOCIATES OIGOEEm " COOLTM THE 11iAUT MOM R04M CMX COPYW2. M an*WISE USE OF n= MOCMVff M STRMMY PROMUM OW MY DFRMMM THMPM MAY BE SUD.WT TD MGM. ACTOR s ciF y/ I O �OV jo 1 1 2022 °w I Id ® � � No 57170 : o op: z �/� � R STATE OF .'Q 4: s � AL i 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 PDH 30'-0"x2O'-O" ENCLOSED BUILDING EXP. B JOB NO 16022S/ VSM DATEI 7-29-21 SCALES NTS 173ODS/20352S 7A DVM NO) SK-3 REVa 6 SECURE WITH C4) #12-14x3/4' SDF'S (EACH END) TS BOW RAFTER 12 3�NO SCREWS REQUIRED IN BOW END 9. R,yO O 4g. 3-12 TS DOUBLE COLUMN 3-12 n �° °1 CONNECTOR SLEEVE ° MINIMUM 15 GA., 3/16 SECURE: WITH '4) 18 GA. U-CHANNEL BRACE SLEEVE CONNECTOR #12-14x3/4' SDF'S FASTENED TO THE COLUMN BASE RAIL 3/16 AND RAFTER r �r� MINIMUM 6' LONG, MINIMUM 15 GA., CONNECTOR SLEEVE. I �i SECURE WITH (4) I TS CONTINUOUS #S 12-14x3/4' S➢F'BASE RAIL 3-12/11111 `—TS DOUBLE COLUMN 3-12 BOX EAVE RAFTER COLUMN CONNECTION DETAIL 1 F❑R HEIGHTS 13'-0' < To < 16'-0' s ALE: NTs NOTE: COLUMN HEIGHTS 12'-0' < TO < 16' 0' FOR HIGH WIND. :u E418 GA. U-CH.ANNEL BRACE FASTENED TO THER, COLUMN AND ROOF RAFTEWITH (47 #12-14x3/4' SDF'S AT EACH 2 1/2' END (9 PER BRACE) BRACE SECTION SCALE: NTS MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. -I 11=1 11=1 11=1 11= RAFTER COLUMN/BASE RAIL 2 C❑NNECTI❑N DETAIL SCALE: NTS S' ^ey��o JAN 1 1 2022 �'c E NSF•.9�,® e NO 57170 �. • a STATE OF (U %*®dam®�c��,'�< O Rlittle 1110,00 UMVN HYR JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED BY, PDH 30'-0"x2O'-O" ENCLOSED BUILDING EXP. B --- •_-- --- _ ._--I I JOB NO 16022S/ B WG. Na, SK-3 (REW 6 SECURE WITH TS BOW RAFTER (4) #12-14x3/4' l2 SDF'S (EACH END) 3------- i TS BOW RAFTER NO SCREWS REOUIRED IN 12 '/ BOW END 3 NO SCREWS REUU(RED IN BOV END SECURE WITH 4g. (4) 412-14x3/4' p SDF'S (EACH END) N 6 1 IS GA. U-CHANNEL BRACE FASTENED TO THE COLUMN Fk13. a m ! e! AND RAFTER L I ,I I °1 MINIMUM 6' LONG, L MINIMUM 15 GA., IS GA. U-CHANNEL BRACE CONNECTOR SLEEVE. FASTENED TO THE COLUMN SECURE WITH (4) TS COLUMN AND RAFTER H12-14x3/4- SDF'S MINIMUM 6' LONG, MINIMUM 15 GA., CONNECTOR SLEEVE, SECURE BOW RAFTER AND COLUMN TO SLEEVE l WITH (4) M112-14x3/4' SDF'S B❑X EAVE RAFTER COLUMN CONNECTION DETAIL TS COLUMN iB)_�REIGHTS0'-0'TS TS 2 l/4-x2 1/4-14 :34. REINFORCING. SECURE WITH n12-14x3/4' SDF'S 2 B' O.L. MAX. 3.1 11311 SIDES 3F COLUMN IS 2 1/4'x2 1/4-14 34. 91END 8 G4. U-CHANNEL BRAG_COLUMN INSERT 'AST-NED TO THE COLUMN AND 277E R4FTE2, WITH C4)N12-14x3/4- SD;'S AT =4CH (8 PER BRACE, BRACE SECTI❑N BOX EAVE RAFTER COLUMN SCALE: NTS C❑NNECTI❑N DETAIL lA FpR HEIGHTS 10'-0T❑ 13'-0'ALE NTS7TE MAXIMUM SI]LUMN HEIGHT IS 12-0' FDR HIGH WIND. ` ! 1 i--rS COLUMN CONNECTOR MINIMUM 6' L7NG, 3/16 CONNECTOR SLEEVE SLEEVE TO �� MWIMUM 15 3A., BAS= 24IL 3/l6 SECURE WITH ,4) k12-14x3/4• SBF'S /-TS .3NTINU7US BASE RAIL 1(- RAC❑LUMN/BASERAI�'� I❑N DETAILSCA MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. 7w L ff m ANY JAN 1 1 2Qa2 oaaAro s * No 57170cc •e -o STATE OF .•C ,o �it�•• �Ri lee. 4,0611111� %%% IWAVN HT, J5 1 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED BY, PDH 30'-0"x2O'-0" ENCLOSED BUILDING EXP. B - - - - JOB to l6wm 3/ . SA Ma Na, SK-3 iREVJ 6 BASE RAIL ANCHORAGE OPTIONS FOR LOW AND HIGH WIND SPEED INSTALL 1/2'x6 3/4' EXPANSION VWF OR FIBERGLASS ANCHOR THROUGH BASE RAIL FIBERS WITHIN 6' OF EACH COLUMN. (ALSO APPLICABLE TO END WALLS) VARIES w a ° Q a ° GRADE _ A A ° d -11 1 I I I=I I II_ I I E 17 —_1 " MINIMUM 3 1/4' I Q EMBEDMENT '� I A• I I I E (TYP.) MONOLITHIC CONCRETE FOOTING (3000 PSI MIN.)( - REINFORCED WJTH (2)-k4'5 CONTINUOUS 1•-p• C❑NCRETE M❑N❑LITHIC SLAB 3A BASE RAIL ANCH❑RAGE SCALE: NTS MINIMUM .ANCHOR EDGE DISTANCE IS 4' ( COORDINATE WITH LOCAL CODES/ORD. REGARDING MINIMUM FROST DEPTH RED. GENERAL NOTES NOTE CONCRETE MONOLITHIC SLAB DESIGN ON MINIMUM SOIL BEARING CAPACITY OF 1,503 PSF. CONCRETE, CONCRETE SHALL HAVE 4 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF 3,300 PSI AT 28 DAYS. COVER OVER REINF❑RCING STEEL, FOR FOUNDATIONS, MINIMUM CONCRETE COVER OVER REINFORCING BARS SHALL BE PER ACI-318: 3 INCHES IN FOUNDATIONS WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY IN CONTACT WITH THE EARTH OR EXPOSED TO THE EARTH OR WEATHER, AND 1 1/2 INCHES ELSEWHERE, REINF❑RCING STEEL, THE TURNDOWN REINFORCING STEEL SHALL BE ASTM A615 GRADE 60 THE SLAB REINFORCEMENT SHALL BE WELDED WIRE FABRIC MEETING ASTM .4185 DR FIBERGLASS FIBER REINFORCEMENT. REINF❑RCEMENT MAY BE BENT IN THE SHOP OR THE FIELD PR❑VIDED, 1. REINFORCEMENT IS BENT COLD. 2 THE DIAMETER 0= THE BEND, MEASURED ON THE INSIDE OF THE BAR, IS NOT LESS THAN SIX -BAR DIAMETERS 3. RE N-DRCEMENT PARTIALLY EMBEDDED IN C3NCRETE SHALL NOT BE MELD BENT HELIX ANCHOR NOTES, I F3R VERY DENSE .AND/OR CEMENTED SANDS, C74RSE GRAVEL AND COBBLES, GAUCHE, PRE DADED SILTS AND CLAYS USE MINIMUM :2) 4' HEL[ ES WITH MINIMUM 33 INCHEMBEDMENT 2 FGR CORAL USE MINIMUM '2) 4' HELICES WITH MINIMUM 30 INCH EMBEDMENT. 3. =3R MEDIUM DENSE -:]ARSE SANDS, SANDY 5RAVELS. VERY STIFF SILTS, AND CLAYS USE MINIMUM (2) 4' HELICES WITH MINIMUM 30 INCH EMBEDMENT. 4 FOR LOOSE TO MEDIUM DENSE SANDS, FIRM TO STIFF CLAYS AND SILTS ALLUVIAL FILL USE MINIMUM (2) 6' HELICES WITH MINIMUM 50 INCH EMBEDMENT 5. FAR VERY LOSE TO MEDIUM DENSE SANDS, FIRM TO STIFFER CLAYS AND SILTS, ALLUVIAL FILL USE MINIMUM (2) 8' HELICES WITH MINIMUM 60 INCH EMBEDMENT, MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. MS MMMff IS ME PM-EM OF M W NO ASS0=7n EMG a_Mjlfi ATm M=Ln i THE tl"DM= R04MMCTDK M"ri. OR UrHMWM UZ W MS >lGC ma m STRICTLY PRI>im rm mm IWf aFR01l11 m TFam m MAY E SULECT M LEGAL &-rM . 2' WASHERS TOP OF ASPHALT PAVEMENT OR GROUND SURFACE F—( t I I � I E_d I I_� I 114 III= TS CONTINUOUS liL BASE RAIL Al HELIX EYE ANCHOR (SEE NOTES BELOW) DRILL 5/8' DIAMETER HOLE THROUGH THE BASE RAIL AND SECURE TO ANCHOR EYE WITH 1/2' ➢IAME TER THROUGH BOLT (3B )_GROUND BASE HELIX ANCH❑RAGE NTS :CAN BE USED FOR ASPHALT) COORDINATE WITH LOCAL CODES/ORD. REGARDING MINIMUM FROST DEPTH REQ, ST4 0c/F JAN 1 1 2022 P a VV �,VY o S \, ss®® � • e 46� %• C� si * ; No 57170 • 6-0®: STATE ' .Q • s Jlc� AI .00 R I'188��♦ 11111 DRAWN ST1 JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED BY, PDH 30'-0"x2O'-O" ENCLOSED BUILDING EXP. B I JOH NO 1602PS/ 9 IDW& NQ1 SK-3 (REV., 6 OPTIONAL FOUNDATION ANCHORAGE FOR LOW AND HIGH WIND SPEED INSTALL 1/2'0 ANCHOR ROD THROUGH BASE RAIL WWF OR FIBERGLASS WITHIN 6' OF EACH FIBERS POST (SEE DETAIL 'E') (TYP,) 1 1 1/2, V a o GRADE III — a _ d _ MINIMUM 6'I EMBEDMENT (TYP.) a MONOLITHIC CONCRETE FOOTING (3000 PSI MIN.) REINFORCED WITH (2)-44'5 CONTINUOUS 1•-p• CONCRETE M❑N❑LITHIC SLAB 3C BASE RAIL ANCHO RAGE SCALE: NTS MINIMUM ANCHOR EDGE DISTANCE IS 1 1/2' COORDINATE WITH LOCAL CODES/ORD. REGARDING MINIMUM FROST DEPTH RED, GENERAL NOTES NOTE: CONCRETE MONOLITHIC SLAB DESIGN ON MINIMUM SOIL BEARING CAPACITY OF 1,500 PSF. CONCRETE, CONCRETE SHALL HAVE A MINIMUM SPECIFIED COMPRESSIVE STRENSTH OF 3,300 PSI AT 28 DAYS. COVER OVER REINF❑RCING STEEL, FOR FOUNDATIONS, MINIMUM CONCRETE COVER OVER REINFORCING BARS SHALL BE PER ACI-318: 3 INCHES IN FOUNDATIONS WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY IN CONTACT WITH THE EARTH OR EXPOSED TO THE EARTH OR WEATHER, AND 1 1/2 INCHES ELSEWHERE. REINF❑RCING STEEL, THE TURNDOWN REINFORCING STEEL SHALL BE ASTM .A615 GRADE 60 THE SLAB REINFORCEMENT SHALL BE WELDED WIRE FABRIC MEETING ASTM A185 OR FIBERGLASS FIBER REINFDRCEMENT. REINF❑RCEMENT MAY BE BENT IN THE SHOP OR THE FIELD PR❑VIDED, 1 REINFDRCEMENT IS BENT COLD. 2. THE DIAMETER OF THE BEND. MEASURED ON THE INSIDE OF THE BAR, IS NOT LESS THAN SIX -BAR DIAMETERS.. 3. R_INF7RCEM_NT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. • z � o U W 7 O a 1/2'0 A36 THREADED ROD T/CONCRETE w W 1/6 HEAVY HEX NUT ANCH❑R R❑D THR❑UGH BASE 3D RAIL DETAIL SCALE: NTS s���c eyNFo z COCi JAN 1 1 2022 eo®it# yf No 57170 OT••.STATE p� • �� '��: '*;If N-A 4SO °°°v DRAWN BYI JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED BY, PDH 30'-0"x2O'-O" ENCLOSED BUILDING EXP. B _---_--I liaB N6 1602PS/ LIME Alm 9A PM 10 SK-3 IREW 6 BASE RAIL ANCHORAGE OPTION DRILL 5/B' DIAMETER HOLE THROUGH THE BASE RAIL AND SECURE TO ANCHOR EYE WITH 1 1/2' WASHERS 1/2' DIAMETER THROUGH BOLT 2 1/2'x2 1/2'x2 1/2'xl/4' ANGLE TOP OF ASPHALT OR r GROUNDISURFACE TS CONTIN BASE RAIL 3/40 x 30' :MIN.) LONG A529 GRADE 50 2'x3/4'xl/B' A36 BARBS :MIN. 4) ASPHALT BASE ANCHORAGE (HP 9 BARBED DRIVE ANCHOR) S -.ALL: iV I S :CAN BE USED FOR ASPHALT) x COORDINATE WITH LOCAL CODES/ORD. REGARDING MINIMUM FROST DEPTH RED. MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. JAN 1 12022 rrrrrro • •� I No 57170 L A STATE OF ft oioo®ZArLo0',e®s UKAVN SYN JU 1 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED BY, PDH 30'-0"x2O'-O" ENCLOSED BUILDING EXP- B I I JOB NO 16022S/ Bmm =Muff 1s snmcnY R�ITm � 7wr riFRnm�ir nQ�PW lay HE SULE1CT M � � CLO]NTi TBS kHT. 9H W& NOi SK-3 6 BASE RAIL ANCHORAGE OPTIONS 4' EDGE OF CONCRETE 1/2'0 EXPANSION ANCHOR i I I I I TS 2 1/4x2 1/4-14 GA. q I OR TS 2 1/2x2 1/2-14 GA. ix I I I I I I I I EDGE OF SK-9 I I CONCRETE X I I � I I SECTION 1 TYP SCALE, NTS K-9� 3/16 I I I TS COL'UMN (LEG) TYPICAL ANCHOR DETAIL WHEN BASE RAIL IS NEAR EDGE OF CONCRETE SCALE: NTS SCB yNED ST C Uc/F COUN ly JAN 1 1 2022 sees®�ao� IV e` * N0 57170 ° e v r r � r STATE OF •o °��: �®o�07�V �i p 8� Reid l U LS U LtiA n u ILL IN li J Y J 1 C.MJ MOORE AND ASSOCIATES DRAWN BYj JG 631 SE INDUSTRIAL CIRCLE 32025 ENGINEERING AND CONSULTING, INC. cHEcKED BY, PIN 30'-o°X 0 OK ENCLOSED BUCITY,DILDING EXP. B 7M DOCUOIr M THE PROPERTY OF M W NO ASSMIA7 S ENGOEERDIG M M JOB W, 16022S/ CMinLTM THE lIiINJ H== R0nWR CnM COPYM 0R an*RVM = IF PROJECT HM WSM TES 7-29-21 SCALE, NTS 173=/2=2S TF4S EGC11Eif� is STRDM PRE M AM ANY WRDIMOU TIEWFM MAY HE SUB ECT TO LEGAL ACTU CLMENT. TES ISHT, 9C hmaNrh W-3 LEV.. 6 BOX EAVE RAFTER END WALL AND SIDE WALL OPENINGS fFF NnTVI TYPICAL BOX EAVE RAFTER END WALL FRAMING SECTI❑N SCALE: NTS SEE NOTES CSHEET 3) BOX EAVE RAFTER/COLUMN FOR MAXIMUM T4SS_MBLY JIE 7l- l2 OPENWG FOR ERSONNEL DOOR WITH HEADER 14 12 I9 13 l3 TYPICAL BOX EAVE RAFTER SIDE WALL ❑PENINGS FRAMING SECTI❑N SCALE: NTS MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. nm LOc!!!E CMC=7m Tm Doc= DE SuLwT IG mm USE IF Im MY SEE NOTES TYPICAL BOX EAVE RAFTER END WALL ❑PENINGS FRAMING SECTI❑N SCALE NTS OPENING FOR WINDOW WITH r1E4DER AND WINDOW RAIL :ALSO APPLICABLE TO END WALLS) OOR JAN 1 1 2022 f '• M "'®. •Y t No 57170 0. STATE•:40� • AN ;p'p LlE le®oll®es TUBULAR BUILDING SYSTEMS JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 h PDH 30'-0"x20'-0" ENCLOSED BUILDING EXP. B ---I I JOB N31 1602P3/ 10 IMM NO SK-3 KVa 6 BOW RAFTER END WALL AND SIDE WALL OPENINGS SEE NOTES TYPICAL BOX EAVE RAFTER END WALL FRAMING SECTION SCALE NTS SEE NOTES :SHEcT 3) BOX SAVE RAFTER/COLUMN FOR MAXIMUM ASSEMBLY SEE NOTES TYPICAL BOX EAVE RAFTER END WALL OPENINGS FRAMING SECTION SCALE: NTS ON I' i 9 12 7 � 1? OPENING FOR t2 L ROLL -UP IOR WITH HEADER (SEE SHEET 16) OPENING FOR OPENING FDR WINDOW PERSONNEL DOOR WITH HEADER AND WITH HEADER WINDOW RAIL ALSO 11 APPLICABLE TO END `3 14 12 LIZALLS)W TYPICAL BOX EAVE RAFTER SIDE S ST c WALL OPENINGS FRAMING SECTION C/� Y SCALE. NTS JAN 1 1 2022 e111111 000a ; � o 57170 t s Ns s � • a • e Z/ ® : STATE OF �� 'OJYAo MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. BRAWN BY' 1000LPLM L5UILIJ11N17 6 Y J I t:MJ 631 SE INDUSTRIAL CIRCLE CITY, FLORIDA 32025 30'-o"x 0 OK ENCLOSED BUILDING EXP. B cHEc= BY. PBH PROJECT WiRI WSM TEI 7-29-21 SCALEI NTS JOB NOI 160M/ 173=/20352S THIS MOM" T s THE PIMERTY IF NZWE NM ASSOMATES ENMNEMM Alm CONSILTMM THE UMNJTHWJM RFPRODUC7M COPYM OR G11ERW= USE OF TM DOMM T 1s ST EM PROHOW EB JVM ANY B*FRR1t GW THERaFM MAY BE SUBJECT M LEGAI. ACTB7L CLIENTI TBS RiT. U WCs m SIC-3 6 CONNECTION DETAILS TS RAFTER TS COLUMN (CORNER) TS COLUMN MINIMUM 6' LONG, MINIMUM OR END COLUMN 15 GA., TS CONNECTOR 2'x2'x2' 16 GA. ANGLE SLEEVE. SECURE WITH CLIP SECURE TO COLUMN (4) #12-14x3/4' SDF'S AND EITHER TOP OF CONNECTOR 2'x2'x2' 16 GA. CLIP ANGLE HEADER, OR BOTTOM OF WINDOW RAIL WITH 2'x2'x2. 16 GA. ANGLE CLIP SECURE TO COLUMN 3/16 SLEEVE TO l-I SECURE TO RAFTER COLUMN I I AND BASE RAIL V/(4) #12-14 x3/4' SDF'S AND RAFTER WITH BASE RAIL 3/16 I I 412-14x3/4' SDF'S I #12-14x3/4' SDF'S (2) ON TOP AND (2) ON SIDE TS END COLUMN TS HEADER OR I I I I I I I I I I- VINDOW RAIL I I I I I I I I I I I TS CONTINUOUS BASE RAIL HEADER OR WINDOW END COLUMN/RAFTER CONNECTION DETAIL END COLUMN/BASE RAIL RAIL TO COLUMN 4 SCALE CONNECTION DETAIL 6 CONNECTION DETAIL NTS 5 SCALE, NTS SCALE: NTS TS TRUSSED RAFTER CHORD, TS COLUMN OR HEADER OR END COLUMN 16 CONNECTOR 2'x2'x2' l6 GA. ANGLE 16 SLEEVE TO HEADER CLIP SECURE TO COLUMN AND EITHER TOP OF 2'x2'x2' 16 GA. ANGLE HEADER, OR BOTTOM OF WINDOW RAIL WITH TS END COLUMN =LIP SECURE TO COLUMN #12-14 x3/4" SOr 'S DR 000R WMDOW FR4ME POST (EACH SIDE) AND RAFTER CHORD/RAIL %,3, WITH 412-14x3/4' SDF'S ,2) ❑N BOTTOM AND (2>MINIMUM ONS[DE 6' LON`u, I MINIMUM l5 GA.,TS TSHE40ER, B4SE NOTEAT 2DLL-UP DOORCONNECTOR SLEEVE. RA1L, OR VINOOW OPENNGS,POST SHOULDSECURE E4CH VITH TS DOUBLE HEADER .FAIL BE FLUSH VITH RAIL(4) END. CLIP POST TO #12-14x3/4' SDF'S �3-12 RAIL ONLY ON SIDE TS COLUMN OPPOSITE THE OPENING. 3-12 DOUBLE HEADER COLUMN TO HEADER, �ONNEC!ION BLE HEADER/COLUMN TO COLUMN BASE RAIL, OR DETAIL CONNECTION DETAIL WIND❑W RAIL 8 , NT 6A SCALE: C 7 C❑NNECTI❑N DETAIL SCALE+ NTS I CONNECTOR 3/15 IS COLUMN HETO HEADER 3/16 MINIMUM 6' LONG, Sc _R ro MPIIMUM L5 GA., IS I CONNECTOR SLEEVE. I SECURE WITH (4) I I #12-14x3/4' SOPS 4it TS DOUBLE HEADER �-12 —, r ��� 2022 COLUMN/DOUBLE HEADERea�®p�� C❑NNECTI❑N DETAIL 9 SCAL-+ NTS o••AA•e�o• /!Q® No 5 170 so ° w ® � 1 • o N w • ' w m pro ; STATE OF XN P • ` ®� e • `i � % ®,�,'Oe1VP�gi Ear,. TUBULAR BUILDING SYSTEMS MOORS AND ASSOCIATES DRAWN BY, JG 631 SE INDUSTRIAL CIRCLE 32025 ENGINEERING AND CONSULTING, INC. CHECK BY, PDH 30'-0"x LAKE Nc ENCLOSED BIUDILDING EXP. B T1DS BDcakxr is THE PROPERTY DF AIm ASsoaArEs olmXaw MIDI J® NO 16022S/ CDNSULTDII-i TIC UNAUTH M" REPRaUCTBII, COME, DJ On*RWISE USE DF PROJECT MGR, VSM TTu 7�29-21 SCALE, NTS 173005/203525 THIS DDCIJgMr lS STRICTLY PROKM ED Alm ANY DlRtII1 DOff THMWffl 1 NAY BE SUBJECT TD I EfiAL ACTmi CLD]dT1 TBS . 12 M SK-3 a 6 CONNECTION DETAILS TS COLUMN CONNECTOR MINIMUM 6' LONG, SLEEVE TO 3/16 MINIMUM 15 GA., TS BASE RAIL 3/16 CONNECTOR SLEEVE. I I I SECURE EACH WITH (4) N12-14x3/4' SDF'S TS CONTINUOUS BASE RAIL I—III—III—III—i -III-III-III-I I COLUMN/BASE RAIL (10 CONNECTION DETAIL SCALE NTS VTSF RAFTER 3/l6 TS CHORD 3/IG RAFTER TO CHORD 11�6NNECTETAiL CALE NTS IS TRUSSED RAFTER CHORD, OR HEADER TS COLUMN I i TS ENO COLUMN I I OR DO02 VIGV I MINIMUM S' LONG, MINIMUM S' L3N3 FRAME POST J MINIMUM 15 3A., TS "7NNE=i7R 3/16 MINIMUM 15 GA., TS _� CONNECTOR SLEVE• C3NNE=TOR SLEEVE BASE RAIL 3/16 I S-_URE E4Ci WIT4 :a) SLEEVE. SECURE E4CH WITH (41 N12-14x3/4' SDF'S I Nl2-14z3/4' SDF'S I TS 4E4DER, BASE �IS CONTINUOUS B4SE 2A[L 24IL. ]R WINDOW RAIL I I I I -III -I I i COLUMN/BASE RAIL 13 C❑NNECTI❑N DETAIL SCALE NTS COLUMN TO HEADER, BASE RAIL 14 C❑NNECTI❑N DETAIL SCALE NTS MOORE AND ASSOCIATES I BRAWN BY, JG ENGINEERING AND CONSULTING, INC. ICHECKM BY1 PIN TS ROOF RAFTER TS COLLAR TIE 3. COLLAR TIE 12 C❑NNECTI❑N DETAIL SCALE NTS S`1 co�� JAN 1 1 2022 0A901�� NO 57170 STATE OF �(I: O,111''0NA� R 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 W-0" ENCLOSED BUILDING JOB N01 16022S/ TO IRSE OF mm NAY w N01 SK-3 ItEW 6 BOX EAVE RAFTER LEAN-TO OPTIONS ROOF EXTENSION OPTION MAIN STRUCTURE STANDARD LEAN—TO OPTION TYPICAL BOX EAVE RAFTER LEAN-TO OPTIONS FRAMING SECTI❑N (BOTH ❑PTIONS SHOWN) SCALE: NTS MAIN BUILDING COLUMNS WITH LEAN—TO OR ROOF EXTENSION ATTACHED)ARE REQUIRED TO BE LACED COLUMNS FOR EAVE HEIGHTS 16'-0' < TO < 20'-0'. MAIN BUILDING COLUMNS WITH LEAN—TO OR ROOF EXTENSION ATTACHED ARE REQUIRED TO BE DOUBLE COLUMNS FOR EAVE HEIGHTS 13'-0' (12'-0' FOR HIGH WIND) < TO < 16'-0'. MAIN BUILDING COLUMNS WITH LEAN—TD OR ROOF EXTENSION ATTACHED ARE REQUIRED TO BE SINGLE COLUMNS FOR EAVE HEIGHTS 10'-0' ( TO < 13'-0' (12'-0' FOR HGH WIND) :WITH 4'-4' INSERT). MAIN BUILDING COLUMNS WITH LEAN—TO OR ROOF EXTENSION ATTACHED ARE REQUIRED TO BE SINGLE COLUMNS FOR EAVE HEIGHTS < KNEE BRACES MUST BE 4'-0- '5'-0' FOR HIGH WIND) WHEN LEAN—TO'S ARE ADDED. TS BOX EAVE RAFTER 071NE- TO.R 3/16 SL='EVE TO 3/16 L' L :RAFTER 7NG TS LS 3A. CONNECTOR SLEEV'. SECURE COLUMN TO SLEEVE WI7H '4) i k12-14x3/4' SDF'S J TS EXTENSION RAFTER .MINIMUM 6' LONG, - MINIMUM 15 SA., CONNECTOR SLEEVE. TS COLUMN SECURE COLUMN TO NIP' LE WITH (4) .2-14x3/4' SDF'S SIDE EXTENSI❑N RAFTER/COLUMN DETAIL 15 FOR RAFTER SPANS < 15'-0- SCALE NTS TS BOX EAVE RA=TER CONNECTOR\ 3/16 SLE= VE TO RAFTER 3/l6 12' LONG TS IS 3A. CONNECTOR SLEEVE SLEEVE WITH ;4) q12-14x3/4SDF'S e+ J Ii. I 6 L- MINIMUM 6' LONG, TS DOUBLE MINIMUM 15 'A., EXTENSION RAFTER / CONNECTOR SLEEVE. J SECURE COLUMN TO NIPPLE WITH (4) 2'x2'x2' 14 GA. ANGLE N12-14x3/4• SDF'S EL1P SECURE TO TS COLUMN COLUMN AND RAFTER CHORD/RAIL WITH ',4) 412-14x3/4' SDF'S SIDE EXTENSION RAFTER/COLUMN DETAIL (15A FOR RAFTER SPANS 15'-0' < TO S 24'-0' SCALE NTS MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. s� T��c/ ey�Fa �n JAN I I ®®v®® ,fitful# • o ' No 57170 • s i ®ta STATE OF ova®,'-46s►SO'NA9 0��� ®a®s 9mwn HY' JG 1 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED BY1 PDH 30'-0"x2O'-0" ENCLOSED BUILDING EXP. B I IJOB NMm 16022S/ BE Alm 14 P)WG. We SK-3 BOX EAVE RAFTER LEAN-TO OPTIONS 2'x2'x2' 16 GA. ANGLE CLIP SECURE TO COLUMN AND RAFTER WITH R12-14x3/4' SDF'S (2) ON TOP AND (2) ON BOTTOM /--TS RAFTER COLUMN LEAN-TO RAFTER TO RAFTER N C❑NNECTI❑N DETAIL 16)IC&U;NIT AFTERSPANS<15'-0'SCALE.S MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. 2'x2'x2' 14 GA. ANGLE CLIP SECURE TO COLUMN AND RAFTER WITH 1/4'x3/4' S➢F (2) ON TOP AND (2) ON BOTTOM ,- TS DOUBLE RAFTER TS COLUMN 3-12 LEAN-TO RAFTER TO RAFTER COLUMN C❑NNECTI❑N DETAIL F❑R RAFTER SPANS 16A 15'-0• < T❑ 24'-0' SCALE NTS Sc JAN 1 1 2022 °® 0O'ooi ��r• No 57170 '�.. o • 0 cc • STATE OF W 0. ®I��ld�ll01 41 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 30'-0"x20'-0" ENCLOSED BUILDING EXP. B RE AND ASSOCIATES ET1GtilmtpJG AND PROJECT NGR� VSM JOB ID 16022S/ :TOI6 COPYO�i, OR QIFQt: USE OF TES 7-29-21 SCALES NTS 1730CS/20352S MID ANY QFRDI M 7NDa M NAY CLIENT, TBS _ . 14A VCi Na SIC-3 6EVi 6 BOW RAFTER LEAN-TO OPTIONS TYPICAL BOW RAFTER LEAN—TO ❑PTI❑NS FRAMING SECTI❑N (BOTH ❑PTI❑NS SHOWN) SCALE: NTS MAIN BUILDING COLUMNS WITH LEAN-TO OR ROOF EXTENSION ATTACHED ARE REQUIRED TO BE DOUBLE COLUMNS FOR EAVE HEIGHTS 13'-0' <12' 0' FOR HIGH WIND) < TO < MAIN BUILDING COLUMNS WITH LEAN-TO OR ROOF EXTENSION ATTACHED ARE REQUIRED TO BE SINGLE COLUMNS FOR EAVE HEIGHTS 10'-0' < TO ( 13-0' (12'-D' FOR HIGH WIND) :WITH 4'-4' INSERT). MAIN BUILDING COLUMNS WITH LEAN-TO OR ROOF EXTENSION ATTACHED ARE REQUIRED TO BE SINGLE COLUMNS FOR EAVE HEIGHTS < 10'-0'. KNEE BRACES MUST BE 4-0- 15-0' FOR HIGH WIND) WHEN LEAN-TO'S ARE ADDED. 2'x2'x2' 16 54. ANGLE CLI? SECURE TO COLU.M,u� AND RAFTER WITH it12-14x3/4' SU'S (2) ON TOP AND '2) 3N BOTTOM TS LEAN-TO iS COLUMN RAF TER LEAN—TO RAFTER TO RAFTER C❑LUMN C❑NNECTI❑N DETAIL,F❑R RAFTER SPANS < SCALE NTS 2"x2'x2' 1634 ANGLE - CLI? SECURE TU _]LUMN AND RAFTER WITH N1-14x3/4' SOF'S ;R) ON TO? 4N0 '2) 3N BOTTOM TS DOUBLE Lc- AN -I RA.-T-1 if 3-12 TS DOUBLE --X 3-12 COLUMN Ai LEAN—TO RAFTER TO RAFTER COLUMN C❑NNECTI❑N DETAIL F❑R RAFTER SPANS 17A 15'-0' < T❑ 24'-0' SCALE: NTS MOORS AND ASSOCIATES ENGINEERING AND CONSULTING, INC. 18 ME PRQPERTY ff NZW 40 � Pr�1MMX'n A C SCq sT�uc/ ey�Fo F COVN JAN 1 1 2022 lifillll II •••• ®w®�Q �� C E AJ q n®••O����� i •i � � • O No 57170 o • u � r o � r s � •• : it 4 r STATE OF soal�aeoa DRAWN BYl JG 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED DYl PDH 30'-0"x20'-0" ENCLOSED BUILDING EXP. B -� _-- ---- - __--I I JOB NO MOM/ 15 JDWG. Na. SK-3 BOX EAVE RAFTER VERTICAL ROOF/SIDING OPTION TYPICAL END ELEVATION VERTICAL R❑❑F/SIDING OPTION SCALE: NTS TYPICAL SIDE ELEVATION VERTICAL ROOF/SIDING OPTION SCALE: NTS I ROOF PANEL ATTACHMENT (ALTERNATE FOR VERTICAL RDDF PANELS) SCALE: NTS MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. c 29 G,`GALVANIZED METAL ROOF WALL PANELS FASTENED TO HAT CHANNELS AND GIRTS 1 1/2'-18 GAUGE HAT CHANNEL TYPICAL SECTION VERTICAL ROOF/SIDING ❑PTION SCALE: NTS SEE NOTES 1 1/2'-18 GAUGE HAT CHANNEL SPACED AT (SHEET 3) �4' 0' O.C. AND FASTENED TO EACH RAFTER FOR MAXIMUM WITH (2) ltl2-14x3/4' SDF'S TYPICAL FRAMING SECTION VERTICAL R❑❑F/SIDING OPTION SCALE NTS NOTE: TS WALL GIRTS CAN BE USED AS AN OPTION IN ?LACE OF HAT CHANNELS. TS GIRTS MUST BE SPACD AT 4' 0' (MAX.) O.C. v JAN 1 I /0 < loll • No 57170 a �• STATE OF o;'O/: s� • s,��o�Ss� .0 R a Aa® 01�® DRAM DYl JG 1 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED We PDH 30'-0"x20'-0" ENCLOSED BUILDING EXP. B --- --- ---- - ----I I JOD M 16022S/ M LEGAL ACTMPL CLD7�To TBS ISHT. 16 IDvm Na. sK-3 kva 6 SIDE WALL HEADER OPTIONS TS HEADER Eir HEADER DETAIL FOR DOOR OPENINGS < 10'-0' SCALE: NTS 2 1/2x2 1/2-14 GA. (TYP.) 3/16 TYP 3/16 HEADER DETAIL FOR DOOR ❑PENINGS 10'-0' < LENGTH < 15'-0' SCALE: NTS END WALL HEADER OPTIONS 2 1/2x2 1/2-14 3A. (TYP.) TS HEADER 3/16 TYP 3/16,O-- HEADER DETAIL FOR DOOR ❑PENINGS < 12'-0' SCALE: NTS MOORS AND ASSOCIATES ENGINEERING AND CONSULTING, INC. HEADER DETAIL FOR DOOR OPENINGS 12'-0' < LENGTH < 15'-0' SCALE: NTS ST -`.q/l zoo/ 4 y JAN 1 1 �oeaaee® s ee s•• 0 e No 57170 r r � r .•� i • tri _� o STATE OF ®dB1QA 9 DRAWN BYt Ai 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 CHECKED BYi PDH 30'-0"x20'-O" ENCLOSED BUILDING EXP. B --- •_-- --- - ----I I JOB NO 160Mn/ 17 P)W& NO SK-3 FLOOD VENT DETAIL GRA FRAME ❑PENING FOR FLOOD VENT WITH TS 2 1/2"x2 1/2" MEMBERS (MATCH ADJACENT RAFTER POSTS AND BASERAIL) 1/2"-18S OR F EXPANDED METAL. ATTACH W/ McNICH❑LS SQUARE FASTENERS ❑R APPROVED EQUAL AT 6" D.C. ATTACH W/ METAL TEK SCREWS. L TYPICAL FLOOD VENT DETAIL SCALE: NTS 1. MINIMUM VENT SPACE REQUIRED = 1 SQ. INUH OF OPEN VENT AREA PER SD. FOOT ❑F BUILDING AREA. 2. THERE SHALL BE A MINIMUM OF TW❑ ❑PENIN,GS ON DIFFERENT SID=S FOR EACH ENCL❑SED BUILDING. 3 APPLY 1.3 FA T❑R WHEN (ADULATING TOTAL OPEN AREA WHEN USING 1/21-ISSA S OR F EXPANDED METAL 4 TOTAL OPEN AREA OF VENT = LXH(MIN. 12'). 5 FLOOD VENT DETAIL--DMPLI-S WITH FEM,A/NFIP 6 ?REFABRICATED FLOOD VENTS MEETIiN—j THE REUUIR'-M-NTS OF F-MA/NIFIP MAY BE USED. MOORE AND ASSOCIATES ENGINEERING AND CONSULTING, INC. BY, . D Bri z _ 2: iu TS POST TS BASE RAIL GRq Sc'q sTc��� ;q/it/ _ JAW 1 1 2022 ® 9 illiiii C o 2 No 57170 0 � r do STATE OF �e 40 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 20'-0" ENCLOSED BUILDING EXP. B AB N11 16022S OR NI71 SK-3 FtEVa 6 STAND -ALONE STEM WALL DETAIL 2' FOR CAST IN PLACE 4' FOR EXPANSION ANCHOR INSTALL 1/2'0 — ANCHOR ROD OR (3000 psi MIN.) 4' THICK (MIN.) J-BOLT THROUGH SLAB -ON -GRADE BASE RAIL WITHIN 6' OF WWF OR FIBERGLASS EACH POST FIBERS III�IIIIIII�I� �-��. _ #4 L DOWEL @ 48' O.C. IIICOMPACT II —I SUBGRADE IIIII� III 4' o ¢ 8' --MU BLOCK in E 44 @ 48' O.C. #4 L DOWEL @ 48' O.0 a ' ° a 3-#4 CONT. FOR I'-G' WIDE 0 � a In G 414 S a G 4 a 2'CLR J J 1'-5' 'FDR BLDG WIDTHS < 40 -Y) in STAND—ALONE CONCRETE MASONRY UNIT (CMU) FOUNDATION STEM WALL DETAIL SCALE. NTS MOORS AND ASSOCIATES ENGINEERING AND CONSULTING, INC. PM D *Off IS 7W PROPERTY OF MOORS NM ASSMUTES ENGB6Qm AND amLnm 7NE Ui anutun Rmnmm nm COPYM OR UrHMWM UZ OF W= OOCWOff IS SVWXY PRONO3= AND ANY WRDSWOU 74EREPM MAY w_ 51mjm 7G l rm. wrax ST "IV, l &C y JAN 1 1 Zan a No 57170 •� ,� ' Or jr r r p : STATE OF 1 W r O r e• o • 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 30'-0"x20'-0" ENCLOSED BUILDING EXP. B JQB NO 16022S/ El 7-29-21 SCALES NTS 17300S/20352S 19 DWG W SK-3 REV-, 6 VERTICAL SLIDING WINDOW DETAIL u 31.75' MAX. OVERALL FIN. WIDTH 30.00' MAX. OVERALL FRAME WIDTH 1 SK-20 ELEVATION VIEW SCALE NTS TS POST OR RAIL 14 GA. i'TYP.) INTERIOR L E EXTERIOR #12x3/4' SELF -DRILLING FASTENERS lTYP) SECTION 2 SCALE 3'=1'-D' SK-20 TS POST DR RAIL L4 GA. (TYP.) INTERIOR EXTERIOR #12x3/4' SELF -DRILLING FASTENERS 'TYR.) SECTION 3 SCALE: 3'=1'-0' SK-20 MOORS AND ASSOCIATES ENGINEERING AND CONSULTING, INC. IWS DOCUl W 1S 7W PROPM" ff MOW AND ASSOCUI7ES E1dWOR M0 AMD MNSU-M4 7ME UiMliMM= R04MEnM CWYM OR 07fER = USE ff n1 n B=MW M SUMMY PRGHM= AND MY WRIIGE M 7FiRF pM MAY iE SUD.IOCT M LEGAL ACTmL #12x3/4' SELF - DRILLING FASTENERS (TYP.) IF EXTERIOR INTERIOR a SK-20 TS POST OR RAIL 14 GA. 'TYP.) 3 SK-?0 SECTION 1 SCALE: 3'=1'-0' SK-20 NOTE KINRD SERIES 18000-R VS OR EDIVALENT WINDOW IS REQUIRED POSITIVE WALL PRESSURE: +40.0 PSF NEGATIVE WALL PRESSURE: -40.0 PSF JAN 1 1 2022 .aadAa1QY10sv ,o" "'• Iy @� oe•esee•ea e 0 ® No 57170 e. s ®:ee STATE OF .• s®®JVALA� a�%% oleee�i~� 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 30'-0"x2O'-0" ENCLOSED BUILDING EXP. B JOB Ma 16022S/ 7-29-21 SCALE. NTS 173ODS/2M2S 20 D a NOj SK-3 IREV, 6 OPTIONAL CONCRETE STRIP FOOTING INC BASE SCALD iN 1 S rS RAFTER .�L UMN 3-tta :CANT �,� T3B /— 7S BASE RAIL EXPANSION ANCHDR FOOTING I • • B I`SUBGRADE ca PACT SECTION(:1 SCALE NTS SK-21 x COORDINATE WITH LOCAL CODES/ORD. MOORS AND ASSOCIATES ENGINEERING AND CONSULTING, INC. 1. STRIP FOOTING DESIGN BASED ON MINIMUM SOIL BEARING CAPACITY OF 1,500 PSF. 2. CONCRETE SHALL HAVE A MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF 3,000 PSI AT 28 DAYS. 3, FOR FOUNDATIONS, MINIMUM CONCRETE COVER OVER REINFORCING BARS SHALL BE PER 401-318: 3' IN FOUNDATIONS WHERE THE CONCRETE IS CAST AGAINST AND PERMANENTLY IN CONTACT WITH THE EARTH OR EXPOSED TO TIE EARTH OR WEATHER, AND 1 112' ELSEWHERE. 4. THE STRIP FOOTING REINFORCING STEEL SHALL BE ASTM 4615 SRADE 60, 5. REINFORCEMENT MAY BE BENT IN THE SHOP OR IN THE FIELD PROVIDED: 4) REINFORCEMENT IS BENT COLD. B) THE DIAMETER OF THE BEND, MEASURED ON THE INSIDE OF THE BAR, IS NOT LESS THAN SIX -BAR DIAMETERS. C) REINFORCEMENT PARTIALLY EMBEDDED IN CONCRETE SHALL NOT BE FIELD BENT. SC sT� j ey4�0 1�' " JAN 1 1 2022 as�o�s® Ire. E � eee No 57370 q e � N � STATE OF All ��✓. ®®°°ss'� AL 15"�� des 631 SE INDUSTRIAL CIRCLE LAKE CITY, FLORIDA 32025 30'-0"x2O'—O" ENCLOSED BUILDING EXP. B J® NO 160M Es 7-29-21 p:Vr& E) NTS 17300&/20352S 21 NO SK-3 6EV, 6