HomeMy WebLinkAboutEVALUATION REPORT POLYGLASS ROOF UNDERLAYMENTS�lTwNmrIERD EVALUATION REPORT Polyglass USA, Inc. 150 Lyon Drive Fernley, NV 98408 (570)384-1230 EXTERIOR RESEARCH & DESIGN, I.I.C. Certificate of Authorization #9503 IV 353 CHRISTIAN STREET, UNIT#13 OXFORD, Cr 06478 (203) 262-9245 Evaluation Report FLS259-R26 Date of Issuance: 02/24/2009 Revision 22: 03/13/2017 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code and Florida Building Code, Residential Volume. The products described herein have been evaluated for compliance with the 5th Edition (2014) Florida Building Code sections noted herein. DESCRIPTION: Polyglass Roof Underiayments LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report Is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product changes or the referenced Quality Assurance documentation changes. Trinity] ERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report number preceded by the words "TrinitylERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety. INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the Job site at the request of the Building Official. This Evaluation Report consists of pages 1 through 14. Prepared by: �4;,�S4ag•hy - i4 - =' '� . • • t= The facsimile seal appearing was authorized by Robert Nleminen, P.E. on 03/13/2017. This does not serve as in electronically i3O r .,:.. T r.�, Robert J.M. Nieminen, P.E. y,�,�e�q;°,•• signed document. Signed, sealed hard copies have been Florida Registration No. 59166, Florida DCA ANE1983 I';M N� �+` transmitted to the Product Approval Administrator and to the named client . CERTIFICATION OF INDEPENDENCE: 1. TrinitylERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. TrinitylERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial Interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 4. Robert Nieminen, P.E. does not have, norwiil acquire, a financial interest in any other entity involved in the approval process of the product. 5. This is a building code evaluation. Neither TrinityjERD nor Robert Nieminen, P.E. are, in anyway, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. File COPY V TRINITYIERD ROOFING COMPONENT EVAWATION: 1. SCOPE: Product Category: Roofing Sub -Category: Underlayment Compliance Statement: Roof Underlayments, as produced by Polygiass USA, Inc., have demonstrated compliance with the following sections of the 5th Edition (2014) Florida Building Code through testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set forth herein. 2. STANDARDS: Section Property ndard Year 1504.3.1 Wind Uplift FM 4474 2004 1SD4.3.1 Wind Uplift UL 1897 20D4 2504.6 Accelerated Weathering ASTM 6354 2006 1504.6 Accelerated Weathering . ASTM G155 2005 1507.2.3,1507.3.3,1507.5.3,1507.7.3, Physical Properties ASTM D226 2006 1507.8.3,1507.9.3 3SO7.2.4,1507.2.9.2,1507.5.3,1507.7.3 Physical Properties ASTM Di970 2009 3507.11.2 Physical Properties ASTM D6164 2005 2507.11.2 Physical. Properties ASTM D6222 2008 1507.3.3 Installation Practice FRSA/TRI April 2012 2012 1523.6.5.2.1 Physical Properties TAS 103 1995 3. REFERENCES: Entity Examination Reference Date FM Approvals (TST 2867) Wind Uplift 3004091 01/12/2000 j PRI (TST5878) Physical Properties PRIOI121 04/08/2002 . PRI (TSTS878) Physical Properties PUSA-005.02-01 01/31/2002 PRI (TSTS878) Physical Properties PUSA-013-02-01 12/23/2002 PRI (TSTS878) Physical Properties PUSA-013-02-02 12/23/2002 PRI (TSTS878) Physical Properties PUSA-013-02-03 12/23/2002 PRI (TSTS878) Physical Properties PUSA-018-02-01 07/14/2003 PRI.(TST5878) . Physical Properties PUSA-028-02-01 07/13/2005 PRI (TST5878) Physical Properties PUSA-033.02-01 01/12/2006 PRI (TST5878) Physical Properties PUSA-035-02-01 09/29/2006 PRI (TST 5878) Physical Properties PUSA-055-02-02. 22/10/2007 PRI (TST 5878) Physical Properties PUSA-061-02-02 01/28/2008 PRI (TST 5878) Physical Properties PUSA-076-02-01 02/22/2008 PRI (TSTS878) Physical Properties PUSA-083-02-01 04/14/2008 PRI (TST 5878) Physical Properties PUSA-088-02-01 07/29/2009 MTI (TST 2508) Physical Properties 1X20H7A 04/01/2008 MTI (TST 2508) Physical Properties RX14ESA 01/29/2009 ERD (TST 6049) Physical Properties 11752.09.99-1 02/08/2000 ERD (TST 6049) Wind Uplift 11757.08.01-1 08/13/2001 ERD (TST 6049) Wind Uplift 11776.06.02 01/16/2003 ERD (TST 6049) Physical Properties 02200.07.03 07/14/2003 ERD (TST 6049) Wind Uplift P1740.01.07 01/04/2007 ERD (TST 6049) Physical Properties P5110.04.07-1 04/11/2007 ERD (TST 6049) Wind Uplift P9260.03.08 03/21/2008 ERD (TST 6049) Physical Properties P134SO.08.09 08/13/2009 ERD (TST 6044) Wind Uplift P30540.11.09-R7 22/30/2009 ERD (TST 6049) Physical Properties P11030.11.09-1 11/30/2009 ERD (TST 6049) Wind Uplift P11030.11.09-2 11/30/2009 ERD (TST 60491 Physical Properties P11030.11.09-3 11/30/2009 ERD (TST 6D49) Physical Properties P33360.06.10 06/25/2010 ERD (TST 6049) Physical Properties P33370.03.11 03/02/2011 Exterior Research and Design, LLC. Evaluation Report P12060.02.09-R22 CerWicate of Authorization #9503 FBC NON-HVH2 EVAW ATION Polyglass USA, Inc FL5259-R26 Revision 22: 03/13/2017 Page 2 of 14 �I I j�INITYIERD Entity Examination Reference Date ERD (rST 6049) Physical Properties P33370,04.11 04/26/2011 ERD (TST 6049) Physical Properties P37300.10.11 10/19/2011 ERD (TST 6049) Physical Properties P40390.08.12-1 08/06/2012 ERD (TST 6049) Physical Properties P40390.08.12-2 08/07/2012 ERD (TST 6049) Physical Properties C41420.09.12-3 09/11/2012 ERD (TST 6D49) Wind Uplift P39680.03.13 03/04/2013 ERD (TST 6049) ` Physical Properties P45370.04.13 04/26/2013 ERD (TST 6049) Wind Uplift P3738.02.07-112 04/29/2013 ERD (TST 6049) Wind Uplift 11757.04.01-1-R1 04/30/2013 ERD (TST 6049) Wind Uplift P41630.08.13 08/06/2013 ERD (TST 6049) Wind Uplift P11751.05.03-R1 11/26/2013 ERD (TST 6049) Wind Uplift P11781.11.03-R3 11/26/2013 ERD (TST 6049) Physical Properties P45270.05.14 05/12/2014 ERD (TST 6049) Physical Properties 6020.07.14-1 09/08/2014 ERD (TSr 6049) Physical Properties 6020.09.14-2 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-3 09/08/2014 ERD (TST 6D49) Physical Properties 6020.09.14-4 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-5 09/08/2014 ERD (TST 6049) Physical Properties 6020.09.14-6 09/08/2014 ERD (TST 6049) Physical Properties P46520.10.14 10/03/2014 ERD (TST 6049) Physical Properties P44360.10.14 10/07/2014 ERD (TST 6049) Physical Properties P43290.10.14 10/17/2014 ERD (TST 6049) Physical Properties PLYG-SC7550.03.15 03/24/2015 ERD (TST 6049) Physical Properties P40390.04.15 04/03/2025 ERD (TST 6049) Physical Properties PLY13-SC8080.05.15-1 05/20/2015 ERD (TST 6D49) Wind Uplift PLYG-SC8905.05.16-1 05/17/2016 ERD (TST 6049) Physical Properties PLYG-SC8080.07.16 07/16/2016 ERD (TST 6D49) Wind Uplift PLYG-SC12025.10.16 10/12/2016 ERD (TST 6049) Physical Properties PLYG-SC11900.03.17 03/10/2017 ICC ES (EVL 239f) IBC Compliance ESR-1697 11/01/2014 Miami -Dade (CER 1592) HVHZ Compliance NOA 14-0717.08 01/22/2015 Polyglass USA Manufacturing Affidavit Products Current 02/18/2009 Polyglass USA P/L Affidavit Mule -Hide Cross Ltg 03/01/2008 Polyglass USA Materials Affidavit Polystick SA Compound 08/18/2011 UL, LLC. (QUA9625) Quality Control Service Confirmation Exp. 04/24/2018 4. PRODUCT DESCRIPTION: 4.1.1 Elastobase is a fiberglass reinforced, SBS modified bitumen base sheet. 4.1.2 Elastobase P is a polyester -reinforced, SBS modified bitumen base sheet. 4.1.3 Polyglass G2 Base is a fiberglass -reinforced, asphaltic base sheet. 4.1.4 Polyglass APP Base is a fiberglass -reinforced, APP modified bitumen base sheet. 4.2.1 Polystick MTS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, surfaced with polyoleflnic film surface; meets TAS 103. 4.2.2 • Polystick MTS PLUS is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, surfaced with poly -film surface; meets TAS 103. 4.2.3 Polystick IR-Xe is a nominal 60-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with an aggregate surface; meets ASTM D1970. Exterior Research and Design, U.C. Evaluation Report P12060.02.09-R22 Certificate gfAutfwrtrarion R9S03 F8C NON-HVHZ EVALUATION FL5259•1126 Polyglass USA, Inc. Revision 22: 03/13/2017 Page 3 of 14 TRINITY I ERD 4.2.4 Polystick TU Plus is a nominal 80-mil thick rubberized asphalt waterproofing membrane, glass fiber reinforced, with a polyester fabric surface; meets ASTM D1970 and TAS 103. 4.2.5 Polystick TU P is a nominal 130-mil, thick rubberized asphalt waterproofing membrane, glass-fiber/polyester reinforced, with a granular surface; meets ASTM D1970 and TAS 103. 4.2.6 Polystick TU Max is a nominal 60-mil thick rubberized asphalt waterproofing membrane with a 190 g/m2 polyester fabric surface; meets ASTM D1970 and TAS 103. 4.2.7 Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR) are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222. 4.2.8 Polystick Dual Pro"' is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM D1970. 4.2.9 Polystick Tile Pro"' is a nominal 60-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polyester fabric surface; meets ASTM D1970 and TAS 103. 4.2.10 Polystick MU-X is a nominal 54-mil thick dual -layer rubberized asphalt waterproofing membrane, fiberglass reinforced, with a polypropylene film surface; meets AC188 and physical requirements of ASTM D1970 (See Section 5.8). 4.3.1 Elastoflex G TU is a polyester reinforced, modified bitumen tile underlayment composed of an sand -surfaced SBS modified bitumen back -side and granule -surfaced APP modified bitumen top -side. Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM 06380, Class M) In the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered the roof systems. 4.3.2 Elastoflex S6 G and Elastoflex S6 G FR are polyester reinforced, SBS modified bitumen cap sheets, meet ASTM D6164. Elastoflex S6 G and Elastoflex S6 G FR are for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. Elastoflex S6 G Is for use as an alternate to Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered file roof systems. Elastoflex S6 G FR is for use as an alternate to Hot Asphalt applied "Cap Sheet' in the "Two Ply System" from FRSA/TRI April 2022 (04-12) beneath mechanically fastened tile roof systems. 4.3.3 Polyflex G and Polyflex G FR are polyester reinforced, APP modified bitumen cap sheets; meet ASTM D6222. Polyflex G Is for use as an alternate to Heat Applied "Cap Sheet° in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. Polyflex G FR is for use as an alternate to Heat Applied "Cap Sheet" in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems. S. LLMiwtow 5.1 This is a building code evaluation. Neither Trinity(ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained spetaficallyfor that purpose. 5.2 This Evaluation Report is not for use in the HVH2. 5.3 Fire Classification is not part of this Evaluation Report; refer to current Approved Roofing Materials Directory for fire ratings of this product. 5.4 Polyglass Roof Underiayments may be used with any prepared roof cover where the product is specifically referenced within FBC approval documents. if not listed, a request may be made to the Authority Having Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof covering. Exterior Research and Design, U.C. Evaluation Report P12050.02.09-1122 Cert&afeo/Authorkat on OR503 FBC NON-HVHZ EVALUATION FL5259-R2d Polygbss USA, Inc Revision 22:03/13/2017 Page 4 of 24 �i�vl-nrlERD 5.5 Allowable Roof Covers: Underlayment Asphalt Shingles Nall -On Tile Foam -On Tile metal Wood Shakes & Shingles Slate Elastobase Yes (son Sheet Y2.14system) Yes Iftse Sheet In 2-pty system) Yes yes Yes Elastobase P Yes Yes (am sheet In 2-ptV system) Yes (Bew Sheet in 2-Ov system) Yes Yes Yes Polyglass G2 Base No Yes (Base Sheet in Z­PV system) yes (Sm Sheet In 2-*SVMM) No No No Polyglass APP Base No Yes Sheet in 2-piv system) Yes (Base sheet in 2-* sperm) No No No(am Polystick MTS Yes Yes No Yes Yes Yes Polystick MTS PLUS Yes Yes No Yes Yes Yes Polystick IR-Xe Yes No No No -yes Yes Pold*Tu P Yes Yes Yes (See 5.5.1) No Yes Yes PalystlekTUPu Yes yes Yes (See S.S.1) Yes Yes Yes —Polystick TU Max No Yes Yes (See 55.1) Yes No NO Potystick Dual Pro Yes Yes No Y6 Yes Yes Polystick Tile Pro Yes Yes Yes (See 55.1) yes Yes Yes PoWck MU-X Yes No No yes yes Yes Elastoflex SSG Yes Yes Yes (See S.S.1) No Yes Yes Elastoflex SIS G Fit Yes Yes No No Yes yes Elastoflex G TU Yes Yes Yes (See S.S.1) No Yes Yes Polyflex G Yes Yes Yes (See 5.5.1) No Yes Yes Polyflex G Fit Yes Yes No No Yes Yes Polyflex SAP or SAP FR Yes Yes Yes (See 55.1) No yes Yes Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Yes Yes Yes (See 5.5.1) No Yes Yes 5.5.1 "Foam-OnTile" is limited to use of the following Approved tile adhesives / underlayment combinations. Adhesive Florida Product Underlayments Approval Convenience Products' Touch In FL14506 Polystick TU Plus, Polystick TU Max Seal StormBond Roof Tile Adhesive Dow TileBond- FL717 Polystick TU P, Polystick TU Plus, Polyflex SAP or The Pro Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, 1CP Adhesives Polysee AH-160 FL6332 Elastoflex G TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) Polystick TU P, Polystick TU Plus, Polystick TU Max, Polystick Tile Pro, ICP Adhesives Poltisetl RTA-1 FL6276 Elastoflex.6 TU, Elastoflex S6 G, Polyflex G, Polyflex SAP, Polyflex SA Cap FR, Mule -Hide SA-APP Cap Sheet or Mule -Hide SA-APP Cap Sheet (FR) Polyglass PolyLok RoofT11e FL1785S I Polystick TU Plus or Polystick TU Max I Adhesive t Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance. Exterior Research and Design, ULC. Evaluation Report P12060.02.09-R22 Certificate ofAu thodia rio n #903 FBC NON-HVH1Z EVALUATION FL5259426 Polyglass; USA, Inc. Revision 22:03/13/2017 Page 5 of 14 TRINITY I ERD 5.6 Allowable Substrates: Direct -Bond to Deck: Polystick (all variations), Dual Pro, Tile Pro, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ New untreated plywood; ASTM D41 primed new untreated plywood; Existing plywood; ASTM D41 primed existing plywood; New or existing, unprimed OSB; ASTM D41 primed OSB; Southern Yellow Pine; ASTM D41 primed Southern Yellow Pine; ASTM D41. primed structural concrete; Huber Engineered Woods "ZIP System" Panels (designed and installed to meet wind loads for project). Note: Polyglass does not require priming of new or existing plywood or OSB sheathing. New or existing plywood or OSB sheathing should be cleaned of all dirt and debris prior to application of Polystick membranes. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D41 primed structural concrete. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete. 5.6.2 Bond -to -insulation: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) self -adhered to: ➢ ASTM C1289, Type 11, Class 1 polylsocyanurate or Type V polyisocyanurate-composite insulation; Dens Deck DuraGuard; Dens Deck Prime; or SECUROCK Gypsum -fiber Roof Board. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ' Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. Polyflex G or Polyflex G FR torch -applied to: ➢ ASTM D41 primed structural concrete; Dens Deck Prime or SECUROCK Gypsum -Fiber Roof Board. For installation under mechanically attached prepared roof coverings, insulation shall be attached per minimum requirements of the prepared roof covering manufacturers Product Approval. For installations under foam -on tile systems, insulation attachment shall be designed by a qualified design professional and installed based on testing of the insulation/underlayment system in accordance with FBC Section 1504.3.1. 5.6.3 Bond to Mechanically Attached Base Laver: Polystick (all variations), Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) Dual Pro or Tile Pro self -adhered to:. ➢ ASTM D226, Type I or II felt; Elastobase; Elastobase P or Mule -Hide Nail Base. Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt to: ➢ ASTM D226, Type I or li felt; Elastobase; Elastobase P, Mule -Hide Nail Base or Polyglass G2 Base. Polyflex G or Polyflex G FR torch -applied to: ➢ Elastobase; Elastobase P, Mule -Hide Nail Base, Polyglass G2 Base or Polyglass APP Base. For installations under mechanically attached prepared roof coverings, base layer shall be attached per minimum codified requirements. For installations under foam -on tile systems, base layer shall be attached per minimum requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in Section 5.6.4 herein, or as tested in accordance with FBC Section 1504.3.1. 5.6.4 Wind Resistance for Underlavment Systems in Foam -On Tile Applications: FRSA/TRI April 2012 (04-12) does not address wind, uplift resistance of all underlayment systems beneath foam -on tile systems, where the underlayment forms part of the load -path. The following wind uplift limitations apply to. underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in foam -on tile applications. Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04- 12), Appendix A, Table 1A or FBC 1609 for determination of design wind loads. ' Exterior Research and Design, I.I.C. Evaluation Report P12060.02.09•R22 Cerrift ate afAuthaN:otbn p9503 FBC NON4PMZ EVAWATION F15259-R26 Polyglass USA, Inc Revision 22:03/13/2017 Page 6 of 14 QOTRINITYIERD 5.6.4.1 Maximum Design Pressure = -90 off. Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: None Base Ply: (Optional) Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. 5.6.4.2 Maximum Design Pressure = -97.5 psf.* Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga. x N" ring shank nails through 32 ga.,1-5/8" diameter tin caps spaced 12-inch o.c. 5.6.4.3 Maximum Design Pressure = -105 psi: Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: WB-3000 Base Ply: (Optional) Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered and back -nailed within the selvedge -edge side laps using 12 ga, x 1Y." ring shank nails through 32 ga.,1-5/8" diameter tin caps spaced 12-inch o.c. 5.6.4.4 Maximum Design Pressure = -135 psf: Deck:. Min.15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer: (Optional) PG100 or ASTM D41 Joints: Min. 4-inch wide strips of Elastoflex SA-V over all plywood Joints. Base Ply: (Optional) Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. 5.6.4.5 Maximum Design Pressure = -315 psf: .Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer. PG100 or ASTM D41 Base Ply: (Optional) Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Poytstick TU Plus, Polystick TU Max, Tile Pro, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. 5.6.4.6 Maximum Design Pressure - -622.5 pd: Deck: Structural concrete to meet project requirements to satisfaction of Authority Having Jurisdiction. Primer. P6100 or ASTM D41 Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. 5.6.4.7 Maximum Design Pressure = -30.0 psf* Deck: Min.15/324nch OSB to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Eiastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.254nch long x 1-inch head diameter round metal cap nails Spacing: 6-4nch o.c. at the 3-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Pius, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. 5.6.4.8 Maximum Design Pressure = -37.5 psf*: Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS PLUS, self:adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. Exterior Research and Design, U.C. Evaluation Report P12060.02.09-R22 Certykate of Aurhar@atton #9503 FBC NON•HVHZ EVALUATION FL5259•11126 Polyglass USA, Inc Revision 22:03/13/2017 Page 7 of 14 TRINITY ( ERD 5.6.4.9 Maximum Design Pressure =-37.5 psf*: Deck: Min.19/32-inch plywood to meet. project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) or two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch long x 1-inch head diameter round metal cap nails Spacing: 6-inch o.c. at the 3-inch wide side laps and 124nch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt. 5.6.4.10 Maximum Design Pressure =-45 psf*: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: One (1) layer ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch x 3/8-inch head diameter annular ring shank roofing nails at i-5/8-inch diameter tin caps Spacing: 4-inch o.c. at the 2-inch wide side laps and 4-inch o.c. at two (2) equally spaced staggered center rows. Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Pius, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU, applied in full mopping of hot asphalt. 5.6.4.11 Maximum Design Pressure =-45 psf*: Deck: Min.19/32-inch plywood to meet project requirements' to satisfaction of Authority Having Jurisdiction. Base Sheet:. Two (2) layers ASTM D226, Type II felt Fasteners: 11 ga. x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-S/8-inch diameter tin caps Spacing: 9-inch o.c. at the 2-inch wide side laps and 9-Inch o.c. at two (2) equally spaced'staggened center rows. Base Ply: (Optional; for use with self -adhering underlayment only) Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered or Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot' asphalt. 5.6.4.12 Maximum Design Pressure = -45 osf: Deck: Mina 15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase/(sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 94nch o.c. at the 2-Inch wide side laps and 18-Inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. 5.6.4.13 Maximum Design Pressure = -525 Psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing: 9-inch o.c. at the 2-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. 5.6.4.14 Maximum Design Pressure = -S2.5 psf: Deck: Min,15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: Simplex Original Cap Nails Spacing: 64nch o.c. at the 3-inch wide side laps and 6-Inch o.c. at four (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. 5.6.4.15 Maximum Design Pressure =.52.5 psf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex Original Cap Nails Spacing: 64nch o.c. at the 3-inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. Exterior Research and Design, U.C. Evaluation Report 1332060.02.09-1122 CerbJkate o/Audrorimdon N9503 FBC NON-HVHZ EVALUATION FL5Z5"26 Polygiass USA, Inc. Revision 22: 03/13/2017 Page 8 of 14 TRINITY ! ERD 5.6.4.16 Maximum Design Pressure = -60 ttsf: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface forhot-asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: 11 ga. x 1.25-inch long x 3/8-Inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 8-inch o.c. at the 4-Inch wide side laps and 84nch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. 5.6.4.17 Maximum Design Pressure = -60 osf: Deck: Min.19/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet. Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip with OMG Flat Bottom Metal Plates Spacing: 124nch o.c. at the 4-inch wide side laps and 12-inch o.c. at two (2) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. 5.6.4.18 Maximum Design Pressure =-67S asf: .Deck: Min. 15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underloyment) Fasteners: 12 ga. x 1.25-inch long x 3/8-inch head diameter annular ring shank roofing nails at 1-5/8-inch diameter tin caps Spacing: 84nch o.c. at the 4-Inch wide side laps and 84nch o.c. at four (4) equally spaced staggered center rows. Underlayment; Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. 5.6.4.19 Maximum Design Pressure = -75 osf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underlayment) Fasteners: Dekfast R14 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, CMG Roofgrip #14 with OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-inch Insulation Plates or Simplex MAX( Cap Fasteners Spacing: 10-inch o.c. at the flinch wide side laps and 10-inch o.c. at three (3) equally spaced staggered center rows. Underlayment- Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. 5.6.4.20 Maximum Design Pressure=-90asf: Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap fasteners Spacing: 64nch o.c. at the 2-inch wide side laps and 6-inch o.c. at two (2) equally spaced staggered, center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Poiyflex G, torch -applied. 5.6.4.21 Maximum Design Pressure = -90 asf: Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3" Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: ' 6-inch o.c. at the 4-inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. 5.6.4.22 Maximum Design Pressure = -90 DO, Deck: Min.15/324nch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface) Fasteners: Trufast #12 DP or Trufast 014 HD with Trufast 3" Metal Insulation Plates Spacing: 6-inch o.c. at the 4-Inch wide side laps and 6-inch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt Exterior Research and Design, LLC. Evaluation Report P12060.02.09-R22 CerHJrcate of Authorization N9So3 FBC NON-HVHZ EVALUATION FLS259•R26 Polyglass USA, Ine., Revision 22: 03/13/2017 Page 9 of 14 ��TRINITYJERD 5.6.4.23 Maximum Design Pressure=-90 osf: Deck: Min.1S/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Polyglass G2 Base or Polyglass APP Base (requires use of torch -applied underloyment) Fasteners: Dekfast f114 with Dekfast Hex plates, OMG #14 HD with OMG 3" Galvalume Steel Plates, OMG Roofgrip #14 with OMG Flat Bottom Plates (AccuTrac), Trufast HD with Trufast 3-Inch Insulation Plates or Simplex MAXX Cap Fasteners Spacing 9-inch o.c. at the 4-inch wide side laps and 9-Inch o.c. at four (4) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or torch -applied or Polyflex G, torch - applied. 5.6.4.24 Maximum Design Pressure =-97.5 osf. Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly4rn top surface) Fasteners-. 11 ga. x 1.25-inch x 3/84nch head diameter annular ring shank roofing nails at 1-5/8-Inch diameter tin caps Spacing: 44nch o.c. at the 4-inch wide side laps and 4-Inch o.c, at four (4) equally spaced staggered center rows. Base Ply: (Optional) Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. 5.6.4.25 Maximum Design Pressure = -105 Psf: Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: Simplex MAXX Cap Fasteners Spacing 64nch o.c. at the 2-inch wide side laps and 64nch o.c. at three (3) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. 5.6.4.26 iMaximum Design Pressure = -112.5 Dsf, Deck: Min.19/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase or Mule -Hide Nail Base (poly -film top surface) Fasteners: 11 ga. x 1.25-Inch x 3/8-Inch head diameter annular ring shank roofing nails at 1-5/84nch diameter tin caps Spacing: 64nch o.c. at the 4-Inch wide side laps and 6-inch o.c. at four (4) equally spaced staggered center rows. Primer: PG100 or ASTM D41 primer at all tin -caps Base Ply: Polystick MTS PLUS, self -adhered Underlayment: Polystick TU P, Polystick TU Plus, Polystick TU Max, Polyflex SAP, Polyflex SAP FR, Mule -Hide SA-APP Cap Sheet and Mule -Hide SA-APP Cap Sheet (FR), self -adhered. 5.6.4.27 Maximum Design Pressure =-120 osf. Deck: Min.15/32-inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet: Elastobase (sanded top surface for hot -asphalt or torch -applied cap or poly -film surface for torch -applied cap) Fasteners: OMG #12 Standard Roofgrip or OMG #14 Heavy Duty with OMG 3' Round Metal Plates or OMG Flat Bottom Metal Plates Spacing: 64nch o.c. at the 44nch wide side laps and 64nch o.c. at five (5) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex 56 G, applied in full mopping of hot asphalt or Polyflex G, torch -applied. S.6.4.28 Maximum Design Pressure =-120 ast Deck: Min.15/32-Inch plywood to meet project requirements to satisfaction of Authority Having Jurisdiction. Base Sheet Elastobase (sanded top surface) Fasteners: Trufast #12 OP or Trufast #14 HD with Trufast 3" Metal insulation Plates Spacing: 6-inch o.c. at the 44nch wide side laps and 64nch o.c. at five (5) equally spaced staggered center rows. Underlayment: Elastoflex G TU or Elastoflex S6 G, applied in full mopping of hot asphalt. 5.6.4.29 All other direct -deck, adhered Polyglass underlayment systems beneath foam -on the systems carry a Maximum Design Pressure of -45 psf. Exterior Research and Design, ULC. Evaluation Report P12060.02.09-1122 CearrateofAuthorimtlon09503 FBCNON-HMEVAWATiON . FL5259•R26 Polyglots USA, Inc Revision 22: 03/13/2017 Page 10 of 14 TRINIIY (ERD 5.6.4.30 For mechanically attached Base Sheet, the maximum design pressure for the selected assembly shall meet or exceed that required under FRSA/TRI April 2012 (04-12), Appendix A, Table IA. Alternatively, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC 1609. In this case, Zones 2 and,3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117, Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 5.7 Exposure Limitations: Elastobase, Elastobase P, Polyglass G2 Base or Polyglass APP Base shall not be left exposed for longer than 30-days after installation. Polystick IR-Xe or Polystick MU-X shall not be left exposed for longerthan 90-days after installation. Polystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Dual Pro, Tile Pro or Elastoflex G TU shall not be left exposed for longer than 180-days after installation. Polyflex SAP or SAP FR, or Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR) does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile, in which case the maximum exposure is 30 days. Elastoflex S6 G or Elastoflex S6 G FR or Polyflex G or Polyflex G FR does not have an exposure limitation, unless the prepared roof covering is to be adhesive -set tile (Elastoflex S6 G or Polyflex G only), in which case the maximum exposure is 180 days. 5.8 Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth In Section 5.3, Note 1 of ASTM D1970.09, should be established as to slip resistance. 6. INSTALLAnoN: 6.1 Polyglass Roof Underlayments shall be installed in accordance with Polyglass published installation requirements subject to the Limitations set forth in Section 5 herein and the specifics noted below. 6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly to remove any dust andL debris prior to application, and prime the substrate (if applicable).. 6.3.1 Shall be installed in compliance with the codified requirements for ASTM D226, Type II underiayment in FBC Sections 1507 for the type of prepared roof covering to be installed. 6.3.2 Non -Tile Applications: Reference is made to the current edition of the NRCA Steep -slope Roofing Manual and ARMA recommendations for Installing shingle underlayments and flashings Elastobase, Elastobase P or Mule -Hide Nail Base may be covered with a layer of Polystick, Polyflex SAP or SAP FR, Mule -Hide SA-APP Cap Sheet or SA-APP Cap Sheet (FR), Dual Pro or Tile Pro, self -adhered, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR in hot asphalt or Polyflex G or Polyflex G FR, torch applied. 6.3.3 Tile Applications: Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. Exterior Research and Design, U.C. Evaluation Report P12060.02.09-R22 cerocare afAwhorkorkn 09501 FOC NON-HVHZ EVALUATION FL5259-R26 Polyglass USA, Inc. Revision 22: 03/13/2bi7 Page 11 of 14 F)O V I RINITYIERD 6c4::.•: •:.:;:P iC.k•:MTS.N'ITS;PLUS`•IRXe TUP';N�lii's;:TU;Me ';t)ualfirb`T(t"';Pro, .M o A .P.o ex de .0 e r•Mu a -Wine 5 .R . .3h'e to :'APP a P. >?,;".:'',�;. ::Mul t A 6.4.1 Shall be installed in compliance with the codified requirements for ASTM D1970 underlayment In FBC Sections 1507 for the type of prepared roof covering to be installed. Note: Polystick MU-X has been found through comparative testing to have a lesser coefficient of friction than ASTM D226 roofing felt in a dry condition, tested at standard laboratory conditions. Agreement between purchaser and seller, as set forth In Section 5.3, Note 1 of ASTM D1970-09; should be established as to slip resistance. 6.4.2 Direct -to -Deck with Mechanically Fastened Roof Covers: All self -adhering materials, with the exception of Polystick TU Plus, Polyflex SAP or SAP FR and Mule -Hide SA-APP Cap Sheet or SA APP Cap Sheet (FR) should be back -nailed in selvage edge seam In accordance with Polyglass / Mule - Hide Back Nailing Guide. Nails shall be corrosion resistant,11 gauge ring -shank type with a minimum 1-inch diameter metal disk or Simplex -type metal cap nail, at a minimum rate of 12" o.c, Polystick TU Plus should be back -nailed using the above noted fasteners and spacing, in area marked "nail area, area para ciavar" on the face of membrane. The head lap membrane is to cover the area being back -nailed. All seal4ap seams (selvage laps) must be firmly rolled with a minimum 28 lb. hand i roller to ensure full contact and adhesion. For Dual Pro and Tile Pro, align the edge of 'the top sheet to the end of the glue pattern (the sheet will overlap the fabric). View of Ovelap Seam of Dual Pro and Tile Pro All over -fabric and over -granule end -laps shall have a 6-inch wide, uniform layer of Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PGS00 Modified Cement applied In between the application of the lap. Polystick TU Plus, Dual Pro and Tile Pro may not be used in any exposed application such as crickets, exposed valleys, or exposed roof to wall details Repair of Polystick membranes is to be accomplished by applying Polyplus 50 Premium Modified Wet/Dry Cement or Polyglass PG500 Modified Cement to the area in need of repair, followed by a minimum 6 x 6 Inch patch of the Polystick material of like kind, set and hand rolled to place over the 'repair area. Patch laps, if needed, shall be installed in a water shedding manner. All Polystick membranes shall be installed to ensure full contact with approved substrates. Polyglass requires a minimum of 40-lb weighted -roller or, on steep slopes, use of a stiff broom'with approximately 40-lbs of toad applied for the field membrane. Hand rollers are acceptable for rolling of patches, laps (min. 28 lb roller) or small areas of the roof that are not accessible to a large roller o� broom. 6.4.3 Tile ADolications (not allowed for Poi wit IR-Xe or Po/vsttck MU X): Reference is made to FRSA/TRI April 2012 (04-12) Installation Manual and Table 1 herein, using the instructions noted above as a guideline. For mechanically fastened the roofing over 2-ply system, consisting of Base Sheet and self -adhering top sheet(s), Base Sheet fastening shall be not less than FRSA/TRI April 2012 (04-12), Table.i. For adhesive -set tile applications, refer to Section 5.6.4 herein, For nail -on the systems over Polystick MTS, battens are required for loading / staging of the tile. For nail -on the systems over Polystick MTS PLUS: D Battens are required for loading/staging of lugged the regardless of slope. ➢ Battens are required for loading/staging of flat tile at slopes in excess of 5:12. Exterior Research and Design, I.I.C. Evaluation Report P12060.02.09•R22 CertllmteofAuthorl=ian#9509 FBC NON-HVHZEVALUATiON FLS259-R26 Polyglass USA, Inc Revision 22, 03/13/2017 Page 12 of 14 '-,ITwwNIrrlERD 6.4.4 Two (21 Ply Underlayment Systems: Potystick MTS or MTS ,PLUS followed by Potystick MTS, MTS PLUS, TU P, TU Plus, TU Max, Tile Pro, MU-X or Polyflex SAP is allowable for use under mechanically attached prepared roof systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. Potystick MTS PLUS followed by Potystick TU P, TU Plus, TU Max, Tile Pro or Polyflex SAP is allowable for use under foam -on the systems. Limits of use are those associated with the top -layer material. This is not a requirement, but is allowable if a 2-ply underlayment system is desired. 6.5.1 Elastoflex G TU, Elestoflex S6 G or Elastoflex S6 G FR shall be installed in compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Elastoflex G TU is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012.(04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems. ✓ Elastoflex S6 G is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply. System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the `Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered the roof systems. ✓ Elastoflex S6 G FR is for use as an alternate to "Mineral Surface Roll Roofing" (ASTM D6380, Class M) in the "Single Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems or the Hot Asphalt applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened the roof systems. 6.5.2 For hot -asphalt -applications, Elastoflex G TU, Elastoflex S6 G or Elastoflex S6 G FR shall be fully asphalt -applied to the substrates noted in Section 5.6. Side laps shall be minimum 3-inch and erid-laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully adhered in a complete mopping of hot asphalt with asphalt extending approximately 3/8-Inch beyond the lap edge. 6.6.1 Polyflex G or Polyflex G FR shall be installed In compliance with current Polyglass published installation requirements. For use in tile applications: ✓ Polyflex G is for use as an alternate to the Heat Applied "Cap Sheet" in the "Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened or adhered tile roof systems (Base Sheet limited per 5.6.3). ✓ Polyflex G FR is for use as an alternate to the Heat Applied applied "Cap Sheet' in the 'Two Ply System" from FRSA/TRI April 2012 (04-12) beneath mechanically fastened tile roof systems (Base Sheet Limited per 5.6.3). 6.6.2 Polyflex G or Potyflex G FR shall be fully torch -applied to the substrates noted in Section 5.6. Side laps shall be minimum 34nch and end -laps minimum 6-inch wide, off -set minimum 3 feet from course to course. Side and end laps shall be fully heat -welded and Inspected to ensure minimum 3/8-inch flow of modified compound beyond the lap edge. C Exterior Research and Design, LLC. Evaluation Report P12060.02.09-R22 [ertUkatcofAuthoritation89503 FBC NON-HVHZ EVALUATION FLSZS9-R26 Polyglass USA, Inc. Revision 22: 03/13/2017 Page 13 of 14 TRINITY ERD 6_7 Tile Stasinlr. 6.7.1 Tile shall be loaded and staged in a manner that prevents tile slippage and/or damage to the underlayment. Refer to Polyglass published requirements for tile staging. 6.7.2 Battens and/or Counter -battens, as required by the tile manufacturer and FRSA/TRI April 2012 (04-12) must be used on all roof slopes greater than 7:12. Precautions should be taken as needed, such as the use of battens or sail- boards, to prevent tile 'sliding and/or damage to the underlayment during the loading process. 6.7.3 For nail -on the systems over Polystick MTS, battens are required for loading / staging of the tile. 6.7.4 For nail -on tile systems over Polystick MTS PLUS; ➢ Battens are required for loading/staging of lugged tile regardless of slope. ➢ Battens are required for loading/staging of flat tile at slopes'in excess of 5:12. 6.7.5 The minimum cure time after installation of self -adhering membranes and before loading of roofing tiles is forty-eight (48) hours. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. S. MANUFACTURING PLANTS: Contact the noted QA agency for information on product locations covered for F.A.C. Rule 61620-3 QA requirements. 9. QUAuTY ASSURANCE ENTITY: UL, LLC—QUA9625; (314) 578-3406; k.chancellor@us.ul.com - END OF EVALUATION REPORT- . Exterfor Research and Design, LLC. Evaluation Report P12060.02.09-1122 Cerrftote ofAuthodrotion 09S03 FBC NON-HVHZ EVALUATION FLS259•R26 Polyglass USA, Inc. Revision 22: 03/13/2017 Page 14 of 14