Loading...
HomeMy WebLinkAboutRHVAC LOADSR. F.0 E.IVE-D NOV 3 0 201? PERN71171, IG Cooper St. Lucie Counh;, FL HVAC Load Calculations for Ken Cooper 6740 N. Hwy. A1A Fort Pierce, FL. 34949 Prepared By: Mike Thornton Smith Services, Inc. 1306 29th Street Vero Beach, FL. 32960 (772)770-3300 Tuesday, November 28, 2017 Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. �ecciaLHVAG Loads �, _ d , tuzea: 1 vero,beacn�rru �3Z5bu Project Report Project Title: Designed By: Project Date: Client Name: Client Address: Client City: Company Name: Company Representative Company Address: Company City: Company Phone: Cooper Smith Services, Inc. Friday, September 01, 2017 Ken Cooper 6740 N. Hwy. A1A Fort Pierce, FL. 34949 Smith Services, Inc. Mike Thornton 1306 29th Street Vero Beach, FL. 32960 (772) 770-3300 Design'. Data-,,,," Reference City: Fort Pierce, Florida Building Orientation: Front door faces West Daily Temperature Range: Medium Latitude: 27 Degrees Elevation: 25 ft. Altitude Factor: 0.999 Outdoor Outdoor Outdoor Indoor Indoor Grains Dry Bulb Wet Bulb Rel.Hum Rel.Hum Dry Bulb Difference Winter: 42 39.4 n/a n/a 70 n/a Summer: 90 78 59% 50% 75 61 Check Fi ores, �.x Total Building Supply CFM: 2,358 CFM Per Square ft.: 0.708 Square ft. of Room Area: 3,333 Square ft. Per Ton: 574 Volume (ft'): 36,510 Total Heating Required Including Ventilation Air: 43,120 Btuh 43.120 MBH Total Sensible Gain: 52,283 Btuh 92 % Total Latent Gain: 4,449 Btuh 8 % Total Cooling Required Including Ventilation Air: 56,732 Btuh 4.73 Tons (Based On Sensible + Latent) 5.81 Tons (Based On 75% Sensible Capacity) Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residmm ential & Light Coercial HVAC Loads Smith Heating & A/C Elite Software Development, Inc. Cooper, VeroBeacki; FL 329fi0 a� -:-. ' Fa e 3; Miscellaneous Report System 1 System 1 OutdoorOutdoor :Outdoor Indoor 9, N Indoor Grams" Iri ut ,,,,,Data,-,,' Bulb z. s °ReI:Hu'm , ° Rel,Hunp- D r :Bulb Difference, . . Winter: 42 39.4 80% n/a 70 n/a Summer: 90 78 59% 50% 75 61.09 System 2 System 2 Qutdoor; ;Outdoor' Outdoor Iridoorj,' 9 Indoor Grains" In' ut Data; �ti.,..;� ,� , �° �D r,Bulb-_�. .. UUet Bulb a..:, .ReLHurn„ - :° ReLHum ` �. OrF,Bulb, :- .Difference Winter: 42 39.4 80% n/a 70 n/a Summer: 90 78 59% 50% 75 61.09 Main Trunk Runouts Calculate: Yes Yes Use Schedule: Yes Yes Roughness Factor: 0.00300 0.01000 Pressure Drop: 0.0800 in.wg./100 ft. 0.0800 in.wg./100 ft. Minimum Velocity: 650 ft./min 450 ft./min Maximum Velocity: 900 ft./min 750 ft./min Minimum Height: 0 in. 0 in. Maximum Height: 0 in. 0 in. 0utsidewAi"Data : let" Winter Summer Infiltration Specified: 0.100 AC/hr 0.100 AC/hr 61 CFM 61 CFM Infiltration Actual: 0.100 AC/hr 0.100 AC/hr Above Grade Volume: X 36,510 Cu.ft. X 36,510 Cu.ft. 3,651 Cu.ft./hr 3,651 Cu.ft./hr X 0.0167 X 0.0167 Total Building Infiltration: 61 CFM 61 CFM Total Building Ventilation: 0 CFM 0 CFM ---System 1--- Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 28.00 Winter Temp. Difference) Winter Infiltration Specified: 0.100 AC/hr (32 CFM) Summer Infiltration Specified: 0.100 AC/hr (32 CFM) ---System 2--- Infiltration & Ventilation Sensible Gain Multiplier: 16.49 = (1.10 X 0.999 X 15.00 Summer Temp. Difference) Infiltration & Ventilation Latent Gain Multiplier: 41.50 = (0.68 X 0.999 X 61.09 Grains Difference) Infiltration & Ventilation Sensible Loss Multiplier: 30.77 = (1.10 X 0.999 X 28.00 Winter Temp. Difference) Winter Infiltration Specified: 0.100 AC/hr (29 CFM) Summer Infiltration Specified: 0.100 AC/hr (29 CFM) C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM RhvBc Residential & Light Commercial HVAC Loads*Elite Smith Heatirig & AIC ' Software Development, Inc Vero Beach,: FL 32960i Page 4N Load Preview Report Net Rec ft.' Sen Lat Net Sen Sys Htg ysi Sys Act Duct Scope Ton Ton /Ton Area Gain Gain Gain Loss CFM CFM CFM Size Building 4.73 5.81 574 3,333 52,283 4,449 56,732 43,120 561 2,358, 2,358 System 1 2.53 3.10 510 1,581 27,899 2,437 30,336 21,100 274 C^T1,249i 1,249 18 Return Duct 451 0 451 0 Zone 1 1,581 27,448 2,437 29,885 21,100 274'j, 1249 1,249 1-Foyer 315 4,357 279 4,636 4,398 57 ` 198:. 198 7.7 2-Family Room 480 6,428 291 6,719 7,060 92 ! °292 j 292 8,8 3-Dining Room 240 8,011 277 8,288 5,673 74' 364 364 9,9 4-Ktchen 252 6,356 1,008 7,364 2,400, 31.3 . •289, 289 8,8 5-Guest Bedroom 196 1,955 521 2,476 1,191 15� 86!i 89 7 6-Guest Closet 35 262 61 323 286 ' 4 ;, 121 12 3 7-Guest Bath 63 80 0. 80 92 1 4;i 4 2 System 2 220, 2.71 647 1,752 24,384 2,012 26,396 22,020 286'?. 1,109 1,109 17 Zone 1 - Clg.: 50%, Htg : 48% 596 12,473 1,104 13,577 10,643 ' 138 P' w 567 567 8-Master Bedroom 400 10,620 • 814 11,434, 7,930, 103 i 4831 483 10,10 9-Master Bath 196 1,853 290; 2,143, 2,713 35, 84 84, 6 Zone 2 - CIg.: 50%, Htg.: 52% 1,156 12,656 908 13,564 11,377 148 576 576 10-Master Hall/Closet 140 386 0 386 638 8 j „ 1 W 18 4 11-West Bedroom 196 1,447 145 1,592' 2,198 29 66j' 66 6 12-West Bath 64 553 83 636 816 11 i ° ° 25;i 25 4 13-West Closet 48 52 0 52 70 1 ' ` .. 2;i 2 2 14-East Bedroom 2 325 5,014 335 5,349 3,678 48 1- 228' 228 7,7 15-Hall 60 166 0 166 273 4 `^ , ` �`8' 8 Not TMDD: 1-4 16-East Bedroom 3 224 4,765 345 5,110 3,253 42 ; n 217` 217 9 17-Bedroom 3 Closet 36 99 0 99 164 21 5' 5 2 18-Bedroom 3 Bath 63 174 0 174 287 4 i 81i 8 3 Sum of room airflows may be greater than system airflow because system has multiple zones. C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential& Light Commercial HVAC Loads Elite Software Development, Inc. Smith Heafing & A/C Cooper, M Veach;�,FL�32960 Duct Size Preview Room or Source Minimum Maximum Rough. Design SP Duct Duct I Htg Clg Act. Duct Duct Name Velocity Velocity Factor L/100 Loss Velocity Length Flow Flow Flow Size System 1 Supply Runouts Zone 1 0 0 0.01 0.08 0.02303 ' 387.5 10 7 1-Foyer (SR-140, SR-150) TMDD 0 0 0.01 0.08 0.00802 : 387.5 10 57 198• - :., 198 i 7 2-Family Room (SR-160, TMDD 0 0 0.01 0.08 0.00641 428.2 8 92 292 8 SR-170) 0 0 0.01 0.08 0.00641 428.2 8 .i 292 . �w�`r 8 3-Dining Room (SR-100, TMDD 0 0 0.01 0.08 0.02609 452.9 8 j 74 3fi4'� 3.9 9 SR-1 10) 0 0 0.01 . 0.08 0.02609 452.9 g = 0 0 0.01 0.08 0.02466 427. 3 ` 8 8 4-Kitchen (SR-120, SR-130) TMDD 0 0.08. 0.02466 427.3, 8 31 289' �; 289 8 0 0.01 5-Guest Bedroom (SR-180) TMDD 0 0 0.01 0.08 0.008 378.6, 10 15a 89 7 6-Guest Closet (SR-190) TMDD 0 0 0.01 0.08 0.00641 221.8 8 4 12• 3 7-Guest Bath (SR-200) TMDD 0 0 0.01 0.08 0.00639 163.9 8 1 ,a _A 4 2 Other Ducts In System 1 Supply Main Trunk (ST-100) TMDD 0 0 0.01 0.08 0.32161 737.5 16 276-1;249,� 1,249 18 STA 10 TMDD 0 0 0.01 0.08 0.03578 627.3 1 106 ",654 j 654 14 ST-120 TMDD 0 0 0,01 0.08 0.04052 462.6 25 58 '1,98�� 198 9 ST-130 TMDD 0 0 0.01 0.08 0.03915 552.7 15 112 397 11 ST-140 TMDD 0 0 0.01 0.08 0.03301 510.4 10 32 ,:°;29t); 290 10 ST-150 TMDD 0 0 0.01 0.08 0.02507 393.2 12 20 c `"105 105 7 RT-100 TMDD 0 0 0.003 0.08 0.04751 831.4 10 `1 1,249 1249f 1,249 17 RRA00 TMDD 0 0 0.003 0.08 0.01773 831.4 1 1249 '° 249I 1,249 17 System 2 Supply Runouts Zone 1 8-Master Bedroom (SR-230, TMDD 0 0 0.01 0.08 0.0064 487. 3 8 103 �° 4$3'� 483 10 SR-240) 0 0 0.01 0.08 0.0064 487.3 8 „w , 10 9-Master Bath (SR-220) TMDD 0 0 0.01 0.08 0.00641 371.1 8 35 84 6 Zone 2 10-Master Hall/Closet (SR-2 10) TMDD 0 0 0.01 0.08 0.00801 247.3 10 8 ' 18' 18 4 11-West Bedroom (SR-300) TMDD 0 0 0.01 0.08 0.0048 348.5 6 29 6Ei 66 6 12-West Bath (SR-320) TMDD 0 0 0.01 0.08 0.00799 269.7 10 11 .,s:25 25 4 13-West Closet (SR-310) TMDD 0 0 0.01 0.08 0.00479 , 134.9 6 1 2 2 14-East Bedroom 2 (SR-280, TMDD 0 0 0.01 0.08 0.00639 401.3 8 ��` 48 228 228 7 SR-290) 0 0 0.01 0.08 0.00639 401.3 8 7 15-Hall Built -In 450 750 0.01 0.08 86.5 4 '._ .- 8, 8 1-4 16-East Bedroom 3 (SR-250) TMDD 0 0 0.01 0.08 0,0064 473.8 8 42 217) 217 9 17-Bedroom 3 Closet (SR-260) TMDD 0 0 0.01 0.08 0.0048 174.5 6 2 , "•.r' S 5 2 18-Bedroom 3 Bath (SR-270) TMDD 0 0 0.01 0.08 0.00479 198.3 6 4 I 8 3 Other Ducts In System 2 Supply Main Trunk (ST-160) TMDD 0 0 0.01 0.08 0.0032 714.5 4 284 1;1,02 1,102 17 ST-170 TMDD 0 0 0.01 0.08 0.04 602.4 50 147 ?w+558 558 13 STA80 TMDD 0 0 0.01 0.08 0.00799 580.8 10 104 484 12 ST-190 TMDD 0 0 0.01 0.08 0.02046 600.4 10 137 m 551: 551 13 ST-200 TM DD 0 0 0.01 0.08 0.0343 523.5 10 89 321 11 ST-210 TMDD 0 0 0.01 0.08 0.0301 479.8 , 10 48 - ._ 228 ( 228 9 ST-220 TMDD 0 0 0.01 0.08 0.03447 380.8 ' 25 41 93 7 ST-230 TMDD 0 0 0.01 0.08 0.01713 226.5' 15 6,°.1'3) 13 3 RT-110 TMDD 0 0 0.01 0.08 0.0032 715.3 4 1,108 5'; 1',1.08 ( 1,108 17 RR-1 10 TMDD 0 0 0.01 0.08 0.01199 504.2 15 277 271<< 277 10 RT-120 TMDD 0 0 0.0003 0.08 0.02253 901.6 25 831 831 13 RR-120 TMDD 0 0 0.01 0.08 0.00478 507.9 6 277 5277 277 10 RR-130 TMDD 0 0 0.01 0.08 0.00957 507.9 12 277,277 277 10 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM RhVac Residential & Light Commercial HVAC Loads ¢ Smith Heating & A/G_ Elite Software Development, Inc. Cooper6 _► Duct Size Preview cont'd) Room or Source Minimum Maximum Rough. Design SP Duct Duct Htg Clg Act. Duct Duct Name Velocity Velocity Factor L/100 Lass Velocity Length Flow Flow Flow Size RR-140 TMDD 0 0 0.01 0.08 0.00957 507.9 12 277 ;; 277, 1 277 10 Summary System 1 Heating Flow: 274 Design Friction Rate: 0.08 TEL Return: 81.5 Cooling Flow: 1249 Total Cumulative SP Loss: 0.48 TEL Supply: 156.2 Fan ESP: 0.48 Device SP Loss: 0.29 TEL Total: 237.7 Fan SP Available: 0.19 Return Loss Added to Supply: 0.065 System 2 Heating Flow: 286 Design Friction Rate: 0.081 TEL Return: 41 Cooling Flow: 1109 Total Cumulative SP Loss: 0.136 TEL Supply: 125.6 Fan ESP: 0.136 Device SP Loss: 0 TEL Total: 166.6 Fan SP Available: 0.136 Return Loss Added to Supply: 0.035 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential-& Light Commercial HVAC Loads Ehte Software Development, Inc. Smith Heating & A/C ,. Cooper Vero Beach, -FL 32960 Page 7 Tabular Manual D Ductsize Grid - System 1 -'Ducts Room Zones Flow Diam Wid Hei Vel System 1 -System 1 _ 0 Ej>Suppiy 8 F& ST-100 0 Q� ST-110 1 1 1249 ....... 654 17.6 13.8 13.6 10.7 19.3 - - 15.1 738 ---- 627 �jSR-100 Dining Room 1 182 8.6 6.7 9.4 453 ,SR-110 Dining Room 1 182 8.6 6.7 9.4 453 El Q� ST-140 1 290 10.2 7.9 11.2 510 --*SR-120 Kitchen 1 145 7.9 6.1 8.6 427 SR-130 0 � ST-120 Kitchen 1 1 145 198 7.9 8.9 6.1 6.9 8.6 9.7 427 463 - -- S SR-140 Foyer - 1 99 - 6.8 5.3 7.5 388 S SR-150 Foyer 1 99 6.8 5.3 7.5 388 El � ST-130 1� 397 11.5 8.9 12.5 553 SR-160 Family Room 1 146 7.9 6.1 8.6428 _ Y '*SR-170 Family Room 1 146� 7.9wW 6.1 8.6 428 El � ST-150 - --- SR-180 --.._._........................................................................................ Guest Bedroom 1 1 105 89 7 _........ .............. 6.6 5.4 17.6 ........__.............._._. 5.1 7.2 393 377 -_-- SR-190 Guest Closet 1 12 3.2 2.4 3.4 1222 SSR-200 Guest Bath 1 4 2.1 1.7 2.3 164 �_ i'� Return_ El RT-100 1249 16.6 12.9 18.1 831 RR-100 1249 116.6 112.9 18.1 831 C-] System3 -System 3 tem --------.__.._._. (- - --;Return --.....--._._.._.__...._.._ ................................__..._...................._._.._._._..--... C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhv'ac Residential & Light Commercial HVAC Loads t Elite Software Development, Inc. Smith Heating & A/C - Cooper_ � -Pa e 8 Tabular Manual D Ductsize Grid - System 2 Ducts Room FeedsFlow Zones Diam Wid Hei Vel System 2 - System 2 El Supply El � ST-160 _...,-._.-.-.. _ ------------- S Q� ST-170 --...... _...... .......__............ ........--- 1,2 ..... _......... 1,2 1102 ......... ............. . 1558 16.8 --- -- 13 . 13 110.1 18.4 114.2 714 602 SR-210 Master Hall/Closet 2 18 3.7 2.9 4 247 SR-220 _ .._..... _...-_.._...... --....._._..-...__... - --- - B Z� ST-180 Master Bath --- ....... ...... 1 .... _._.....- 1 84 484 6.4 12.4 5 9.6 7 13.5 371 581 SR-230 Master Bedroom 1 242 9.5 7.4 10.4 487 SSR-240 Master Bedroom 1 242 9.5 7.4 10.4 487 l] � ST-190 2 551 13- 10.1 14.2 600 SR-250 _ East Bedroom 3m 2 .__-- 217 9.2 7.2 10 14741 B ST-200 2 321 10.6 8.2 11.6 524 B ST-210 SR-280 SR-290 R ST-220 jEast Bedroom 2 !East Bedroom 2 2 2 2 2 228 114 114 93 9.3 7.2 7.2 6.7 7.2 5.6 5.6 5.2 10.2 7.9 7.9 7.3 480 401 401 381 SSR-300 West Bedroom 2 66 5.9 4.6 6.4 348 SR-310 West Closet 2 2 1.6 -1.3 1.8 135 _ SR-320 West Bath 2 25 4.1 3.2 4.5 270 l] Qj ST-230 2 13 3.2- 2.5 3.5 226 _ SR-260 Bedroom 3 Closet 2 5 2.3 1.8 2.5 174 SR-270 Bed room 3 Bath 2 8 2.7 2.1 3 198 - El !Return E3 FART-11C 1108 16.9 13.1 18.4 715 RR-1 10 �- 277 10 7.8 11 504 RT-120 831 13 10.1 14.2 902 RR-120 j 277 .10 7.8 10.9 508 y S RR-130 277 10 7.8 10.9 508 S RR-140 277 10 7.8 10.9 508 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Smith Heating & A/C _ Cooper W_Pa e 9 Tabular Manual D Ductsize Data - Duct System. I - Supply ---Duct,Name, etc. .. ., Type _ Roughness �1 i Diameter �aVelocity•• SPL.Duct ;Upstream" ,Temperature Width i. Loss/100 SPL.Fit Shape Length Height Fit. Eq. Len SPL.Tot Sizing `CFM, Area SP.Avail SPL.Cumul ---Duct Name: ST-100, Fitting: 1-A, Effective Length: 39.5 Trunk 0.01 17.6 738 0.013 Up: Fan 60 13.6 0.080 0.019 Rnd 16.0 19.3 23.5 0.322 Exact 1,249 73.8 0.093 0.387 ---Duct Name: ST-110, Fitting: 11-A, Effective Length: 44.7 Trunk 0.01 13.8 627 0.001 Up: ST-100 60 10.7 0.080 0.035 Rnd 1.0 15.1 43.7 0.036 Exact 654 3.6 0.058 0.423 ---Duct Name: ST-120, Fitting: 11-A, Effective Length: 50.7 Trunk 0.01 8.9 463 0.020 Up: ST-100 60 6.9 0.080 0.021 Rnd 25.0 9.7 25.7 0.041 Exact 198 58 0.053 0.427 ---Duct Name: ST-130, Fitting: 11-A, Effective Length: 48.9 Trunk 0.01 11.5 553 .0.012 Up: ST-100 60 8.9 0.080 0.027 Rnd 15.0 12.5 33.9 0.039 Exact 397 45.1 0.054 0.426 ---Duct Name: SR-100, Supplies: Dining Room, Fitting: 11-A, Effective Length: 32.6 Runout 0.01 8.6 453 0.006 Up: ST-110 60 6.7 0.080 0.020 Rnd 8.0 9.4 24.6 0.026 Exact 182 18 0.032 0.449 ---Duct Name: SR-110, Supplies: Dining Room, Fitting: 11-A, Effective Length: 32.6 Runout 0.01 8.6 453 0.006 Up: ST-110 60 6.7 0.080 0.020 Rnd 8.0 9.4 24.6 0.026 Exact 182 18 0.032 0.449 ---Duct Name: ST-140, Fitting: 11-A, Effective Length: 41.2 Trunk 0.01 10.2 510 0.008 Up: ST-110 60 7.9 0.080 0.025 Rnd 10.0 11.2 31.2 0.033 Exact 290 .26.7 0.025 0.456 ---Duct Name: SR-120, Supplies: Kitchen, Fitting: 11-A, Effective Length: 30.8 Runout 0.01 7.9 427 0.006 Up: ST-140 60 6.1 0.080 0.018 Rnd 8.0 8.6 22.8 0.025 Exact 145 16.5 0.000 0.480 ---Duct Name: SR-130, Supplies: Kitchen, Fitting: 11-A, Effective Length: 30.8 Runout 0.01 7.9 427 0.006 Up: ST-140 60 6.1 0.080 0.018 Rnd 8.0 8.6 22.8 0.025 Exact 145 16.5 0.000 0.480 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac - Residential & Light Commercial HVAC Loads Smith Heating & A/C Elite Software Development, Inc. cooper. _ _ Vero i-each, FL 32960 _ _. , _.-..,. _. _. W_ ._._ Tabular Manual D Ductsize Data - Duct System 1 - Supply cont`d) Duct Name, etc I` SPL.Ducf 9 Diameter; Velocity p Width Uystream .,' F - Temuerature� p d Loss/100 SPL.Fit Shape 'Length Height ; io" �Fit.Eq.Len SPL.Tot Sizih CFM ., Area €. SP.Avail SPL'Cumul ---Duct Name: SR-140, Supplies: Foyer, Fitting: 11-A, Effective Length: 28.7 Runout 0.01 6.8 388 0.008 Up: ST-120 60 5.3 0.080 0.015 Rnd 10.0 7.5 18.7 0.023 Exact 99 17.9 0.030 0.450 ---Duct Name: SR-150, Supplies: Foyer, Effective Length: 10.0 Runout 0.01 6.8 388 0.008 Up: ST-120 60 5.3 0.080 0.000 Rnd 10.0 7.5 0.0 0.008 Exact 99 17.9 0.045 0.435 ---Duct Name: SR-160, Supplies: Family Room, Effective Length: 8.0 Runout 0.01 7.9 428 0.006 Up: ST-130 60 6.1 0.080 0.000 Rnd 8.0 8.6 0.0 0.006 Exact 146 16.6 0.048 0,432 ---Duct Name: SR-170, Supplies: Family Room, Effective Length: 8.0 Runout 0.01 7.9 428 0.006 Up: ST-130 60 6.1 0.080 0.000 Rnd 8.0 8.6 0.0 0.006 Exact 146 16.6 0.048 0.432 ---Duct Name: ST-150, Fitting: 11-A, Effective Length: 31.3 Trunk 0.01 7 393 0.010 Up: ST-130 60 5.4 0.080 0.015 Rnd 12.0 7.6 19.3 0.025 Exact 105 22 0.029 0.451 ---Duct Name: SR-180, Supplies: Guest Bedroom, Effective Length: 10.0 Runout 0.01 6.6 377 0.008 Up: ST-150 60 5.1 0.080 0.000 Rnd 10.0 7.2 0.0 0.008 Exact 89 17.2 0.021 0.459 ---Duct Name: SR-190, Supplies: Guest Closet, Effective Length: 8.0 Runout 0.01 3.2 222 0.006 Up: ST-150 60 2.4 0.080 0.000 Rnd 8.0 3.4 0.0 0.006 Exact 12 6.6 0.023 0.457 ---Duct Name: SR-200, Supplies: Guest Bath, Effective Length: 8.0 Runout 0.01 2.1 164 0.006 Up: ST-150 60 1.7 0.080 0.000 Rnd 8.0 2.3 0.0 0.006 Exact 4 4.4 0.023 0.457 Report Units: Pressure: in.wg, Duct lengths: feet, Duct sizes: inch, Airflow: CFM, Velocity: ft./min, Temperature: F C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhv'ac Residential & Light Commercial HVAC Loads Elite Software Development, Inc. _Smith Heating & A/C_. Tabular Manual D Ductsize Data - Duct System 1 - Supply (cont'd) ---Duct Name; etc •' °� . Type Roughness Diameter `' Velocity SPL.Duct Upstream. Temperature Width la Loss/100 SPL.Fit. Shape Length Heightµ Fit.Eq:Len 'SPL.Tot Sizin CFM.� Areai�a�' SP,Avail , ; SPL.Cumul Notes: Static pressure available values for return ducts are at the entrance of the duct. For supply, they are at the exit. The cumulative static pressure loss value for a return trunk is with respect to the entry point of the return runout upstream with the highest static pressure available. Total and cumulative static pressure loss values for the supply main trunk include any device pressure losses entered, and the cumulative may also include the total static pressure loss of the return side. Surnrhary.,.. . Number of active trunks: 6 Number of active runouts: 11 Total runout outlet airflow: 1,249 Main trunk airflow: 1,249 Largest trunk diameter: 17.6 ST-100 Largest runout diameter: 8.6 SR-100 Smallest trunk diameter: 7 ST-150 Smallest runout diameter: 2.1 SR-200 Supply fan external static pressure: 0.480 Supply fan device pressure losses: 0.290 Supply fan static pressure available: 0.190 Runout maximum cumulative static pressure loss: 0.480 SR-120 Return loss added to supply: 0.065 Total effective length of return ( ft.): 81.5 RR-100 Total effective length of supply ( ft.): 156.2 SR-120 Overall total effective length ( ft.): 237.7 RR-100 to SR-120 Design overall friction rate per 100 ft.: 0.080 (Available SP x 100 / TEL) System duct surface area (Scenario 1): 395.4 (Linked to duct load) Total system duct surface area: 395.4 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential & Light Commercial HVAC Loads Smith Heating &A/C Elite Software Development, Inc. Vero Beach, FL 32960 - Pa a 12 Tabular Manual D Ductsize Data - Duct System 2 - Supply -Duct Name; etc. Type Roughness Diameter, Velocity SPL.Duct :Upstream Temperature = ° Width a "' Loss/100 SPL.Fit' o° Shape >;„ �E Length ;Height �' Fit.Eq,Len SPL.Tot Sizin .� CFM�:, .,- Area:,-`.SP.Avail, $PL:Cumul ---Duct Name: ST-160, Supplies Zones: 1, 2 (3% Diversity), Effective Length: 4.0 Trunk 0.01 16.8 715 0.003 Up: Fan 60 13 0.080 0.000 Rnd 4.0 18.4 0.0 0.003 Exact 1,102 17.6 0.097 0.038 ---Duct Name: ST-170, Supplies Zones: 1, 2 (5% Diversity), Effective Length: 50.0 Trunk 0.01 13 602 0.040 Up: ST-160 60 10.1 0.080 0.000 Rnd 50.0 14.2 0.0 0.040 Exact 558 170.6 0.057 0.078 ---Duct Name: STA80, Supplies Zone: 1, Effective Length: 10.0 Trunk 0.01 12.4 581 0.008 Up: ST-170 60 9.6 0.080 0.000 Rnd 10.0 13.5 0.0 0.008 Exact 484 32.4 0.049 0.086 ---Duct Name: SR-210, Supplies: Master Hall/Closet (in Zone 2), Effective Length: 10.0 Runout 0.01 3.7 247 0.008 Up: ST-170 60 2.9 0.080 0.000 Rnd 10.0 4 0.0 0.008 Exact 18 9.6 0.049 0.087 ---Duct Name: SR-220, Supplies: Master Bath (in Zone 1), Effective Length: 8.0 Runout 0.01 6.4 371 0.006 Up: ST-170 60 5 0.080 0.000 Rnd 8.0 7 0.0 0.006 Exact 84 13.5 0.051 0.085 ---Duct Name: SR-230, Supplies: Master Bedroom (in Zone 1), Effective Length: 8.0 Runout 0.01 9.5 487 0.006 Up: ST-180 60 7.4 0.080 0.000 Rnd 8.0 10.4 0.0 0.006 Exact 242 20 0.043 0.093 ---Duct Name: SR-240, Supplies: Master Bedroom (in Zone 1), Effective Length: 8.0 Runout 0.01 9.5 487 0.006 Up: ST-180 60 7.4 0.080 0.000 Rnd 8.0 10.4 0.0 0.006 Exact 242 20 0.043 0.093 ---Duct Name: ST-190, Supplies Zone: 2, Fitting: 1-A, Effective Length: 25.6 Trunk 0.01 13 600 0.008 Up: ST-160 60 10.1 0.080 0.012 Rnd 10.0 14.2 15.6 0.020 Exact 551 34 0.077 0.059 ---Duct Name: ST-200, Supplies Zone: 2, Fitting: 11-A, Effective Length: 42.9 Trunk 0.01 10.6 524 0.008 Up: ST-190 60 8.2 0.080 0.026 Rnd 10.0 11.6 32.9 0.034 Exact 321 27.8 0.042 0.093 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Smith Heating & A/C__, Page 13 Tabular Manual D Ductsize Data - Duct System 2 - Supply cont'd) . .- Duct,Name, etc.':, Type Roughness,,,, - . Diameter, , Velocity - SPL.Duct Upstream " Temperature ,. ,Width ii Loss/100 SPL.Fit , Shape ---'. Length' _ Height;3 Fit.Eq.Len SPL.Tot Sizing ,• CFM ,~,,�` ,. ' _ ,, mArea �� SP.Avail ° SPL.Cumul, ---Duct Name: ST-210, Supplies Zone: 2, Fitting: 11-A, Effective Length: 37.6 Trunk 0.01 9.3 480 0.008 Up: ST-200 60 7.2 0.080 0.022 Rnd 10.0 10.2 27.6 0.030 Exact 228 24.4 0.012 0.123 ---Duct Name: ST-220, Supplies Zone: 2, Fitting: 11-A, Effective Length: 43.1 Trunk 0.01 6.7 381 0.020 Up: ST-200 60 5.2 0.080 0.015 Rnd 25.0 7.3 18.1 0.034 Exact 93 43.8 0.008 0.128 ---Duct Name: SR-250, Supplies: East Bedroom 3 (in Zone 2), Effective Length: 8.0 Runout 0.01 9.2 474 0.006 Up: ST-190 60 7.2 0.080 0.000 Rnd 8.0 10 0.0 0.006 Exact 217 19.2 0.070 0.065 ---Duct Name: ST-230, Supplies Zone: 2, Fitting: 11-A, Effective Length: 21.4 Trunk 0.01 3.2 227 0.012 Up: ST-190 60 2.5 0.080 0.005 Rnd 15.0 3.5 6.4 0.017 Exact 13 12.7 0.060 0.076 ---Duct Name: SR-260, Supplies: Bedroom 3 Closet (in Zone 2), Effective Length: 6.0 Runout 0.01 2.3 175 0.005 Up: ST-230 60 1.8 0.080 0.000 Rnd 6.0 2.5 0.0 0.005 Exact 5 3.6 0.055 0.081 ---Duct Name: SR-270, Supplies: Bedroom 3 Bath (in Zone.2), Effective Length: 6.0 Runout 0.01 2.7 198 0.005 Up: ST-230 60 2.1 0.080 0.000 Rnd 6.0 3 0.0 0.005 Exact 8 4.3 0.055 0.081 ---Duct Name: SR-280, Supplies: East Bedroom 2 (in Zone 2), Effective Length: 8.0 Runout 0.01 7.2 401 0.006 Up: ST-210 60 5.6 0.080 0.000 Rnd 8.0 7.9 0.0 0.006 Exact 114 15.1 0.006 0.130 ---Duct Name: SR-290, Supplies: East Bedroom 2 (in Zone 2), Effective Length: 8.0 Runout 0.01 7.2 401 0.006 Up: ST-210 60 5.6 0.080 0.000 Rnd 8.0 7.9 0.0 0.006 Exact 114 15.1 0.006 0.130 ---Duct Name: SR-300, Supplies: West Bedroom (in Zone 2), Effective Length: 6.0 Runout 0.01 5.9 349 0.005 Up: ST-220 60 4.6 0.080 0.000 Rnd 6.0 6.4 0.0 0.005 Exact 66 9.3 0.003 0.133 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Smith Heating & A/C Cooper. _ _ _ _. _. _ ._w,. Vero Beach, FL 32960 _- m. _. ._ ... _.- _ _ _ -, Pa e:14 Tabular Manual D Ductsize Data - Duct System 2 - Supply cont'd) Type Roughness Diamueter j `°, Velocity SPL.Duct Upstream,- , Temperature Width �j Loss/100 SPL.Fit, Shape Lengfh.`. ` Height, ' °. F.it.Eq.Len SPL.Tot` Sizing CFM ' �.�Area i, SP.Avail SPL.Curnul ---Duct Name: SR-310, Supplies: West Closet (in Zone 2), Effective Length: 6.0 Runout 0.01 1.6 135 0.005 Up: ST-220 60 1.3 0.080 0.000 Rnd 6.0 1.8 0.0 0.005 Exact 2 2.6 0.003 0.133 ---Duct Name: SR-320, Supplies: West Bath (in Zone 2), Effective Length: 10.0 Runout 0.01 4.1 270 0.008 Up: ST-220 60 3.2 0.080 0.000 Rnd 10.0 4.5 0.0 0.008 Exact 25 10.8 0.000 0.136 Report Units: Pressure: in.wg, Duct lengths: feet, Duct sizes: inch, Airflow: CFM, Velocity: ft./min, Temperature: F Notes: Static pressure available values for return ducts are at the entrance of the duct. For supply, they are at the exit. The cumulative static pressure loss value for a return trunk is with respect to the entry point of the return runout upstream with the highest static pressure available. Total and cumulative static pressure loss values for the supply main trunk include any device pressure losses entered, and the cumulative may also include the total static pressure loss of the return side. Summary Number of active trunks: 8 Number of active runouts: 12 Total runout outlet airflow: 1,137 Main trunk airflow: 1,102 Largest trunk diameter: 16.8 ST-160 Largest runout diameter: 9.5 SR-230 Smallest trunk diameter: 3.2 ST-230 Smallest runout diameter: 1.6 SR-310 Supply fan external static pressure: 0.136 Supply fan device pressure losses: 0.000 Supply fan static pressure available: 0.136 Runout maximum cumulative static pressure loss: 0,136 SR-320 Return loss added to supply: 0.035 Total effective length of return ( ft.): 41.0 RR-130 Total effective length of supply ( ft.): 125.6 SR-320 Overall total effective length ( ft.): 166.6 RR-130 to SR-320 Design overall friction rate per 100 ft.: 0.081 (Available SP x 100 / TEL) System duct surface area (Scenario 1): 506.2 (Not linked to duct load) Total system duct surface area: 506.2 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential. & Light Commercial HVAC Loads Heating & A/C Elite Software. Development, Inc. !Smith Vero Beacb,.FL 32960 °� Pa a 15 Tabular Manual D Ductsize Data - Duct System 9 - Return - Duct Name, etc.'';_ _ Type, Roughness_ Dla'meter" Velocity,,,SPL:Duct 'Upstream.-.,. - Terperature--. : 'Width,V Loss/100 SPL.Fit Shape �- Length ;,i > ' , Height 11 `Fit.Eq.Len SPL.Tot Sizin CFM Area li SP.Avail SPL.Cumul ---Duct Name: RT-100, Fittings: 6-F, 5-K, Effective Length: 59.3 Trunk 0.003 16.6 831 0.008 Up: Fan 60 12.9 0.080 0.040 Rnd 10.0 18.1 49.3 0.048 Exact 1,249 43.4 -0.018 0.065 ---Duct Name: RR-100, Fitting: 6-H, Effective Length: 22.1 Runout 0.003 16.6 831 0.001 Up: RT-100 60 12.9 0.080 0.017 Rnd 1.0 18.1 21.1 0.018 Exact 1,249 4.3 0.000 0.018 Report Units: Pressure: in.wg, Duct lengths: feet, Duct sizes: inch, Airflow: CFM, Velocity: ft./min, Temperature: F Notes: Static pressure available values for return ducts are at the entrance of the duct. For supply, they are at the exit. The cumulative static pressure loss value for a return trunk is with respect to the entry point of the return runout upstream with the highest static pressure available. Total and cumulative static pressure loss values for the supply main trunk include any device pressure losses entered, and the cumulative may also include the total static pressure loss of the return side. Summa Number of active trunks: 1 Number of active runouts: 1 Total runout outlet airflow: 1,249 Main trunk airflow: 1,249 Largest trunk diameter: 16.6 RT-100 Largest runout diameter: 16.6 RRA 00 Smallest trunk diameter: 16.6 RT-100 Smallest runout diameter: 16.6 RRA 00 Runout maximum cumulative static pressure loss: 0.018 RR-1 00 Return loss added to supply: 0.065 Total effective length of return ( ft.): 81.5 RR-1 00 System duct surface area (Scenario 1): 47.8 (Linked to duct load) Total system duct surface area: 47.8 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Smith Heating & A/C_ . __. _M _- = Cooper. Vero Beach, nFL .32960 - -.. _ o.� _�__ _ ___._ . ".._. _. _. _ _. _ .. _��-__ . . _ _._. _ t:. - - - Pa a 16 Tabular Manual D Ductsize Data - Duct System 2 - Return --Duct.Name, etc. .Type° Roughness Diameter? Velocity SPL.Duct Upstream,,- Temperature', "1Nidth;' Loss/100 SPL.Fit Shape . _ , Length`.: "�'Height 1i.. Fit. Eq. Len. ; : SPL:Tot' Sizin `a r°. °,:= CFM `",,: ° �� °;Area!! S P.Avail SPL.Cumul ---Duct Name: RT-110, Effective Length: 4.0 Trunk 0.01 16.9 715 0.003 Up: Fan 60 13.1 0.080 0.000 Rnd 4.0 18.4 0.0 0.003 Exact 1,108 17.6 -0.032 0.035 ---Duct Name: RR-110, Effective Length: 16.0 Runout 0.01 10 504 0.012 Up: RT-110 60 7.8 0.080 0.000 Rnd 15.0 11 0.0 0.012 Exact 277 39.4 -0.020 0.012 ---Duct Name: RT-120, Effective Length: 25.0 Trunk 0.0003 13 902 0.023 Up: RT-110 72 10.1 0.090 0.000 Rnd 25.0 14.2 0.0 0.023 Nearest Inch 831 85.1 -0.010 0.013 ---Duct Name: RR-120, Effective Length: 6.0 Runout 0.01 10 508 0.005 Up: RT-120 72 7.8 0.080 0.000 Rnd 6.0 10.9 0.0 0.005 Nearest Inch 277 15.7 -0.005 0.005 ---Duct Name: RR-130, Effective Length: 12.0 Runout 0.01 10 508 0.010 Up: RT-120 72 7.8 0.080 0.000 Rnd 12.0 10.9 0.0 0.010 Nearest Inch 277 31.4 0.000 0.010 ---Duct Name: RR-140, Effective Length: 12.0 Runout 0.01 10 508 0.010 Up: RT-120 72 7.8 0.080 0.000 Rnd 12.0 10.9 0.0 0.010 Nearest Inch 277 31.4 0.000 0.010 Report Units: Pressure: in.wg, Duct lengths: feet, Duct sizes: inch, Airflow: CFM, Velocity: ft./min, Temperature: F Notes: Static pressure available values for return ducts are at the entrance of the duct. For supply, they are at the exit. The cumulative static pressure loss value for a return trunk is with respect to the entry point of the return runout upstream with the highest static pressure available. Total and cumulative static pressure loss values for the supply main trunk include any device pressure losses entered, and the cumulative may also include the total static pressure loss of the return side. Sumrna Number of active trunks: 2 Number of active runouts: 4 Total runout outlet airflow: 1,108 Main trunk airflow: 1,108 Largest trunk diameter: 16.9 RT-110 Largest runout diameter: 10 RR-1 10 Smallest trunk diameter: 13 RT-120 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM ii;ro hvac Residential &Light Commercial HVAC Loads Elite Software Development, Inc. rCoopBeach, FL �32960 ��.__ --_- "Pae17 Tabular Manual D Ductsize Data - Duct System 2 - Return (cont'd Summary., Smallest runout diameter: 10y RRA20 Runout maximum cumulative static pressure loss: 0.010 RRA30 Return loss added to supply: 0.035 Total effective length of return ( ft.): 41.0 RRA30 System duct surface area (Scenario 1): 220.7 (Not linked to duct load) Total system duct surface area: 220.7 Notes��, Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Smith Heating & A/C_ _ Cooper Beach,`FL 3296 ------ _ _ _ .._ ._ .... .... _ ,.: _._.... - Pa a 18 Tabular Manual D Ductsize - Pressure Changes Graph - S stem 1 Pressure Changes Through Route with Highest Static Pressure Loss 0.16 0.14 D 0.12 0.10 E 0.08 3 0.06 F C •- w G 0.02 a A 0.00 H -0.02 B -0.04 -0.06 -0.08 —+— Static Pressure Available — ♦— Velocity Pressure —o— Total Pressure Available Notes: Return side point values are at entrance of duct, while supply side points are at exit. When a return system is present, an additional return side point named [Fan Entrance] is drawn in the graph to show the static pressure available at the entrance of the fan. When a supply system is present, and an additional supply side point named [Fan Exit] is drawn to show the static pressure available at the exit of the fan. Any device pressure losses entered for the supply main trunk are accounted for between the fan entry and exit points. PointName °? "•Static,,PressureAvailable •"" TotaloPressureAvailable A RR-100 0.000 0.044 B RT-100-0.018. 0.026 C [Fan Entrance] -0.065 -0.021 D [Fan Exit] 0.125 0.160 E ST-100 0.093 0.128 F ST-110 0.058 0.083 G ST-140 0.025 0.041 H SR-120 0.000 0.012 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential & Light Commercial HVAC Loads Elite Software Development, Inc. Smith Heating & A/C . _ Cooperil ,Vero Beach, FL,' 32960 _ Tabular Manual D Ductsize - Pressure Changes Graph - System 2 Pressure Changes Through Route with Highest Static Pressure Loss 0.16 0.14 0.12 0.10 E m 0.08 G 3 c 0.06 0 m H a` 0.04 / 0.02 0.00 J -0.02 -0.04 A B D —•— Static Pressure Available —O— Velocity Pressure —�— Total Pressure Available Point. mg.o -E Notes: Return side point values are at entrance of duct, while supply side points are at exit. When a return system is present, an additional return side point named [Fan Entrance] is drawn in the graph to show the static pressure available at the entrance of the fan. When a supply system is present, and an additional supply side point named [Fan Exit] is drawn to show the static pressure available at the exit of the fan. Any device pressure losses entered for the supply main trunk are accounted for between the fan entry and exit points. Pointe, h,Name' {. Static :Pressure Available Total Pressure'Available A RR-130 0.000 0.016 B RT-120 -0.010 0.041 C RT-110 -0.032 0.000 D [Fan Entrance] -0.035 -0.003 E [Fan Exit] 0.100 0.133 F ST-160 0.097 0.130 G ST-190 0.077 0.100 H ST-200 0.042 0.060 1 ST-220 0.008 0.017 J SR-320 0.000 0.005 C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential &Light Commercial HVAC Loads Elite Software Development, Inc. Smith Heating & A/G -_ Cooper: -_ _ _.: . _ _ _ , _ .. w ¢ Vero Beach,VFL 32960 _ _.- _.._ r y,, - Pa a 20 Total Building Summary Loads Component Area "Sen ii ,,,, :Lat tiu. S e n .Total Descri tion.L . Quan,i Lo s �, Gain „ Gain Gain, A3A-Loebr: Glazing -Single -hung, vinyl, Impact, no break, 138 4,132 0 4,788 4,788 outdoor insect screen with 50% coverage, u-value 1.07, SHGC 0.37 A1A-cm-x: Glazing -Fixed Window, 2P, Argon, Vinyl, 87 2,605 0 2,669 2,669 Impact, no break, u-value 1.07, SHGC 0.37 A4-cm-o: Glazing -Sliding glass door, 2P, aluminum, no 544 16,302 0 21,946 21,946 break, u-value 1.07, SHGC 0.37 A1A-SGD: Glazing -Sliding Glass Window, vinyl, Impact, 60 1,798 0 1,430 1,430 no break, u-value 1.07, SHGC 0.37 11 D: Door -Wood - Solid Core 30 328 0 304 304 B12B-1311stucco: Wall -Frame, Custom, 2x4 framed 1829 4,967 0 4,276 4,276 wall/R11 batts with Stucco exterior 1861-8-19o: Roof/Ceiling-Roof Joists Between Roof 3333 4,851 0 3,640 3,640 Deck and Ceiling or Foam Encapsulated Roof Joists, Spray Foam Insulation, White or Light Color Asphalt Shingle, Any Wood Shake, Dark or Medium Color Tile, Slate or Concrete, Light or Unpainted Metal, Light or Silver Membrane, Light Tar and Gravel, R-19 open cell 1/2 lb. spray foam, 5 inches in 2 x 8 joist cavity 19A-Ocp: Floor -Over enclosed crawl space, No insulation 2019 6,263 0 3,357 3,357 on exposed walls, sealed or vented space, passive, no floor insulation, carpet or hardwood Subtotals for structure: 41,246 0 42,410 42,410 People: 6 1,200 1,380 2,580 Equipment: 722 3,305 4,027 Lighting: 0 0 0 Ductwork: 0 0 4,185 4,185 Infiltration: Winter CFM: 61, Summer CFM: 61 1,874 2,527 1,003 3,530 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0 - - - ---- ..... ..... - ..... -- -- ----- Total Building Load Totals: -- -- --- - 43,120 -- -_ 4,449 - 52,283 - -- -- 56,732 Check Figures . Total Building Supply CFM: 2,358 CFM Per Square ft.: 0.708 Square ft. of Room Area: 3,333 Square ft. Per Ton: 574 Volume (ft'): 36,510 BuildingLoads' " Total Heating Required Including Ventilation Air: 43,120 Btuh 43.120 MBH Total Sensible Gain: 52,283 Btuh 92 % Total Latent Gain: 4,449 Btuh 8 % Total Cooling Required Including Ventilation Air: 56,732 Btuh 4.73 Tons (Based On Sensible + Latent) 5.81 Tons (Based On 75% Sensible Capacity) Notes, Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvec Residential& Light' Commercial HVAC Loads Smith Heating & A/C Elite Software Development, Inc Cooper Vero:Beach, FL 329fi0 w 4'' '" li '' r aT Pa` a°21, System 9 S stem 1 Summary Loads <'} Area Sen j} Lat Seri`;i Totah. IComponent ,Deicription' u "Quan °, Loss fl Gain;. Gain ] Gain A3A-Loebr: Glazing -Single -hung, vinyl, Impact, no break, 68 2,036 0 2,126 2,126 outdoor insect screen with 50% coverage, u-value 1.07, SHGC 0.37 A1A-cm-x: Glazing -Fixed Window, 2P, Argon, Vinyl, 42 1,258 0 1,595 1,595 Impact, no break, u-value 1.07, SHGC 0.37 A4-cm-o: Glazing -Sliding glass door, 2P, aluminum, no 288 8,630 0 9,314 9,314 break, u-value 1.07, SHGC 0.37 A1A-SGD: Glazing -Sliding Glass Window, vinyl, Impact, 60 1,798 0 1,430 1,430 no break, u-value 1.07, SHGC 0.37 11 D: Door -Wood - Solid Core 30 328 0 304 304 B1 2B-R1 1 stucco: Wali-Frame, Custom, 2x4 framed 1030 2,796 0 2,409 2,409 wall/R11 batts with Stucco exterior 18B1-8-19o: Roof/Ceiling-Roof Joists Between Roof 1581 2,302 0 1,726 1,726 Deck and Ceiling or Foam Encapsulated Roof Joists, Spray Foam Insulation, White or Light Color Asphalt Shingle, Any Wood Shake, Dark or Medium Color Tile, Slate or Concrete, Light or Unpainted Metal, Light or Silver Membrane, Light Tar and Gravel, R-19 open cell 1/2 lb. spray foam, 5 inches in 2 x 8 joist cavity 19A-Ocp: Floor -Over enclosed crawl space, No insulation 315 977 0 524 524 on exposed walls, sealed or vented space, passive, no floor insulation, carpet or hardwood Subtotals for structure: 20,125 0 19,428 19,428 People: 2 400 460 860 Equipment: 722 3,305 4,027 Lighting: 0 0 0 Ductwork: 0 0 4,185 4,185 Infiltration: Winter CFM: 32, Summer CFM: 32 975 1,315 521 1,836 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0 System 1 System 1 Load Totals: 21,100 2,437 27,899 30,336 "Check F ig ures Supply CFM: 1,249 CFM Per Square ft.: 0.790 Square ft. of Room Area: 1,581 Square ft. Per Ton: 510 Volume (ft'): 18,990 System, Loads Total Heating Required Including Ventilation Air: 21,100 Btuh 21.100 MBH Total Sensible Gain: 27,899 Btuh 92 % Total Latent Gain: 2,437 Btuh 8 % Total Cooling Required Including Ventilation Air: 30,336 Btuh 2.53 Tons (Based On Sensible + Latent) 3.10 Tons (Based On 75% Sensible Capacity) 1. Notes" Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential & Light,Commercial, HVAC Loads Smith Heating & A/C Elite Software Development, Inc. Cooper_ _ 'Pa a 22 System 2 System 2 Summaq Loads Component Areal ' 'Zen, Lat Sen ii Total Descri tion . ' �I , ` Quan Loss Gain ' Gain ii. Gain, A1A-cm-x: Glazing -Fixed Window, 2P, Argon, Vinyl, 45 1,347 0 1,074 1,074 Impact, no break, u-value 1.07, SHGC 0.37 A4-cm-o: Glazing -Sliding glass door, 2P, aluminum, no 256 7,672 0 12,632 12,632 break, u-value 1.07, SHGC 0.37 A3A-Loebr: Glazing -Single -hung, vinyl, Impact, no break, 70 2,096 0 2,662 2,662 outdoor insect screen with 50% coverage, u-value 1.07, SHGC 0.37 B12B-R11stucco: Wall -Frame, Custom, 2x4 framed 799 2,171 0 1,867 1,867 wall/R11 batts with Stucco exterior 18B1-8-190: Roof/Ceiling-Roof Joists Between Roof 1752 2,549 0 1,914 1,914 Deck and Ceiling or Foam Encapsulated Roof Joists, Spray Foam Insulation, White or Light Color Asphalt Shingle, Any Wood Shake, Dark or Medium Color Tile, Slate or Concrete, Light or Unpainted Metal, Light or Silver Membrane, Light Tar and Gravel, R-19 open cell 1/2 lb. spray foam, 5 inches in 2 x 8 joist cavity 19A-Ocp: Floor -Over enclosed crawl space, No insulation 1704 5,286 0 2,833 2,833 on exposed walls, sealed or vented space, passive, no floor insulation, carpet or hardwood Subtotals for structure: 21,121 0 22,982 22,982 People: 4 800 920 1,720 Equipment: 0 0 0 Lighting: 0 0 0 Ductwork: 0 0 0 0 Infiltration: Winter CFM: 29, Summer CFM: 29 899 1,212 482 1,694 Ventilation: Winter CFM: 0, Summer CFM: 0 0 0 0 0 System 2 System 2 Load Totals: 22,020 2,012 24,384 26,396 Check Figures Supply CFM: 1,109 CFM Per Square ft.: 0.633 Square ft. of Room Area: 1,752 Square ft. Per Ton: 647 Volume (ft'): 17,520 System yLoads . Total Heating Required Including Ventilation Air: 22,020 Btuh 22.020 MBH Total Sensible Gain: 24,384 Btuh 92 % Total Latent Gain: 2,012 Btuh 8 % Total Cooling Required Including Ventilation Air: 26,396 Btuh 2.20 Tons (Based On Sensible + Latent) 2.71 Tons (Based On 75% Sensible Capacity) Notes .. Rhvac is an ACCA approved Manual J and Manual D computer program. Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D. All computed results are estimates as building use and weather may vary. Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at your design conditions. C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rh%Ac Residential & Light Commercial HVAC Loads Elite Software Development, triec: Pa a 23 System 1 Room Load Summary ..,. ���' ° t Htg; :Min°;. t :Run' �a Run' Clg ' , Clg ` Min, Act Room Area Sens Htg., , Duct -Duct Sens Lat Clg Sys "No Name �. SFr =_, Btuh;.. _CFM, Size �„ Vel �: ,,;;. Btuh ;;..Btuh „CFM°.: CFM, ---Zone 1--- 1 Foyer 315 4,398 57 7,7 - 4,357 279 198 198 2 Family Room 480 7,060 92 8,8 - 6,428 291 292 292 3 Dining Room 240 5,673 74 9,9 - 8,011 277 364 364 4 Kitchen 252 2,400 31 8,8 - 6,356 1,008 289 289 5 Guest Bedroom 196 1,191 15 7 - 1,955 521 89 89 6 Guest Closet 35 286 4 3 - 262 61 12 12 7 Guest Bath 63 92 1 2 - 80 0 4 4 Return Duct 0 451 0 System 1 total __ 1,581 21,100 274 27,899 2,437 1,249 1,249 System 1 Main Trunk Size: 18 in. Velocity: 738 ft./min Loss per 100 ft.: 0.080 in.wg Duct size results above are from Manual D Ductsize. Runout duct velocities are not printed with duct size results from Manual D Ductsize since they can vary within the room. See the Manual D Ductsize report for duct velocities and other data. Cooling System Summary, Cooling, , . Sensible/Latent Sensible ' , Latent' . Total Tons, . S if:, _ Btuh �.° Btuh Btuh Net Required: 2.53 92% / 8% 27,899 2,437 30,336 Recommended: 3.10 75% / 25% 27,899 9,300 37,198 Equi merit Data •. e• Heating System Cooling System Type: Natural Gas Furnace Standard Air Conditioner Model: Indoor Model: Brand: Efficiency: 0 AFUE 0 SEER Sound: 0 0 Capacity: 0 Btuh 0 Btuh Sensible Capacity: n/a 0 Btuh Latent Capacity: n/a 0 Btuh C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM Rhvac Residential & Light Commercial HVAC Loads Smith Heating & A%C_a�j Elite Software Development, Inc. Vero Bea6h,.FL-32960 ' 24 System 2 Room Load Summaty 'Htg' Min Run'" Run Clg'` " a Clg 'Min Act ° ,Room. . „ ° 'Area. ;� Sens: : _ '• �Htg,` .' , ` Duct - Duct Sens Lat Clg, , Sys • N Name SF, Btuh'?° CFM,-' ` ° Size ° Vel Btuh Btuh . � `,CFM CFM ---Zone 1--- 8 Master Bedroom 400 7,930 103 10,10 - 10,620 814 483 483 9Master Bath 196 2,713 35 6 - 1,853 290 84 84 Zone 1 subtotal 596 _ 10,643 — 138 12,473 1,104 567 567 ---Zone 2--- 10 Master Hall/Closet 140 638 8 4 - 386 0 18 18 11 West Bedroom 196 2,198 29 6 - 1,447 145 66 66 12 West Bath 64 816 11 4 - 553 83 25 25 13 West Closet 48 70 1 2 - 52 0 2 2 14 East Bedroom 2 325 3,678 48 7,7 - 5,014 335 228 228 15 Hall 60 273 4 11-4 87 166 0 8 8 16 East Bedroom 3 224 3,253 42 9 - 4,765 345 217 217 17 Bedroom 3 Closet 36 164 2 2 - 99 0 5 5 18 Bedroom 3 Bath 63 287 4 3 - 174 0 8 8 Zone 2 subtotal 1,156 11,377 148 12,656 908 576 576 System 2 total 1,752 22,020 286 24,384 2,012 1,109 1,109 System 2 Main Trunk Size: 17 in. Velocity: 715 ft./min Loss per 100 ft.: 0.080 in.wg Duct size results above are from Manual D Ductsize except where indicated otherwise. Runout duct velocities are not printed with duct size results from Manual D Ductsize since they can vary within the room. See the Manual D Ductsize report for duct velocities and other data. Indicates duct sized with Rhvac's built-in duct sizing rather than with Manual D Ductsize. Note: Since the system is multizone, the Peak Fenestration Gain Procedure was used to determine glass sensible gains at the room and zone levels, so the sums of the zone sensible gains and airflows for cooling shown above are not intended to equal the totals at the system level. Room and zone sensible gains and cooling CFM values are for the hour in which the glass sensible gain for the zone is at its peak. Sensible gains at the system level are based on the "Average Load Procedure + Excursion" method. Conlin 'S stem Summary _ . ` " ' �° " ' Cooling, -,`,­,,Sensible/Latent• Sensible °' :Latent°` Total Tons Slit Btuh'.' Btuh `°' Btuh Net Required: 2.20 92% / 8% 24,384 2,012 26,396 Recommended: 2.71 75% / 25% 24,384 8,128 32,512 E ui merit' Data' w Heatinq System Cooling System Type: Natural Gas Furnace Standard Air Conditioner Model: Indoor Model: Brand: Efficiency: 0 AFUE 0 SEER Sound: 0 0 Capacity: 0 Btuh 0 Btuh Sensible Capacity: n/a 0 Btuh Latent Capacity: n/a 0 Btuh C:\Users\User\Documents\Elite Software\Rhvac 9 Projects\Cooper.rh9 Tuesday, November 28, 2017, 10:46 AM