HomeMy WebLinkAboutENGINEERING PROJECT SPECSGENERAL NOTES 1. DESIGN CRITERIA: ALUMINUM SPECIFICATIONS: APPLICABLE CODES, REGULATIONS & STANDARDS: 1. THE 2014 FLORIDA BUILDING CODE, 5TH EDITION SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CHAPTER 23 WOOD. 2: ASCE 7-10. & SEI7 3. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 4. ACI318 CONCRETE REFRENCE MANUAL. 5. PCI PRECAST & PRESTRESSED CONCRETE. 6. AA ASM 35 & AA ADM 1 WIND LOADS: 1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3- B 3. SCREENED ROOF ENCLOSURE FBC 2014 CH. 20 TABLE 2002.4 CONCRETE & FOUNDATION DESIGN: 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE APPLICABLE: A. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING COMPONENTS: I. PORTLAND CEMENT TYPE 1 - ASTM C 150 II. AGGREGATES - LARGE AGGREGATE 3/4" MAX. - ASTM C 33 III. AIR ENTRAINING +/- 1 % - ASTM C 260 IV. WATER REDUCING AGENT - ASTM C 494 V. CLEAN POTABLE WATER VI. OTHER ADMIXTURES NOT PERMITTED B. METAL ACCESSORIES SHALL CONFORM TO: I. REINFORCING BARS - ASTM A615, GRADE 60 II. WELDED WIRE FABRIC - ASTM A185 C. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT PERMITTED. D. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3 INCLUDING HOT WHEATHER RECOMMENDATIONS. E. MOIST CURE OR POLYETHYLENE CURING PERMITTED. F. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE FOR TERMITES IN COMPLIANCE WITH THE FBC. EXCEPTION: AN INSPECTION IS NOT REQUIRED FOR DRIVEWAY SLABS,PATIO SLABS, WALKS, ETC.' WHICH ARE CONSIDERED NON -HABITABLE SPACES G. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR BARRIER. 2. IF A MINIMUM 4" CONCRETE SLAB IS PROVIDED IN SOUND CONDITION, FREE FROM STRUCTURAL CRACKING, SPALLING & OTHER DETERIORATION. NO ADDITIONAL FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE PROPOSED CONSTRUCTION. 3. WHEN APPLICABLE FOR ATTACHING NEW FOOTER TO EXISTING, DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN. HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE (OR EQUAL) TYP. ALL LOCATIONS. 4. WHEN INSTALLING 4" CONCRETE SLAB -ADD ADJACENT TO EXISTING-DOWELL INTO EXISTING CONCRETE 48" O/C W/8" #5 REBARS- DRILL 3/4" HOLE 4" EMBEDMENT- EPDXY W/ NON -SHRINKING "SIMPSON EPDXY TIE" (OR EQUAL). 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHER WISE NOTED. 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS OTHERWISE SPECIFIED. 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH #12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050". 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH BE PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC.. FASTNER SPECIFICATIONS: 1. FASTENERS ARE REQUIRED TO BE SAE GIR.ADE 2 OR BETTER ZINC PLATED. 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, AND FASTENERS TO MANUFACTURING SPECIFICATIONS. 3. WHERE WOOD DECK IS PRESENT USE 1/4"X3-1/2" GALV. LAG SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE SPECIFIED. 4. 1"X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED 1/4"X2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS B. FOR WOOD APPLICATION USE #14X2-3/4;' WOOD SCREW AT 24" O.C. AND 6" FROM ENDS. C. FOR ALUMINUM APPLICATION USE #10X'i-1/2" SMS OR TEK SCREW AT 24" O.C. AND 6" FROM ENDS D. WHERE 1'X2" INSTALLED THROUGHOUT AN "OPEN VIEW" SPACING SHALL BE REDUCED TO 18" O.G. AND 6" FROM ENDS MASONRY SPECIFICATIONS: 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR. 2. ALL MORTAR SHALL BE TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4. PROVIDE CLEAN -OUTS FOR REIN FORCED.CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS V-0" IN HEIGHT. MISCELLANEOUS: 1. SCREENED ENCLOSURES CONTAINING S1A/IMMING POOLS SHALL COMPLY WITH THE APPLICABLE REQUIRLIJIENTS OF FBC R4101.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN THE FIELD. 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR SHALL EPDXY TO DECK OR GROUT TO DECK w/3000 PSI GROUT WITH BONDING AGENT. 5. INTEGRITY OF EXISTING/ HOST STRUCTU-RE SHALL NOT BE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED STRUCTURE. RESPONSIBILITIES: 1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. I;T LUCIS COUNTY 8VI40ING DIVISION REVIEWED FOR COMPLIA REVIEWED BY DATE LQ-N-il MUST BE KETT ON JOB OR INSPECTION WILL BE MADE `��'�41 o O _:z =C7:ul 0 co 0 can o 2. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND INSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. 3. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOU i LEGEND: (ALL MAY NOT APPLY) � o � SCR = SCREEN cQ.s KID = KICK PLATE o PW = PICTURE WINDOW as X = HORIZ. SLIDING WINDOW z 0 = HORIZ. STATIONARY WINDOW DH = DOUBLE HUNG WINDOW SH= SINGLE HUNG WINDOW n SIP = SOLID INSULATED PANEL CT = CABLE TIE L °'u SG = SUPER GUTTER z CS = CLEAR SPAN C> KB = KNEE BRACE ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS LE cKr 2 x 2: 2"x2"x0.044"' 2 x 3: 2"x3"x0.044" 2 x 4: 2"x4"4.044" L c c �� n n On w 2 x 5: 2 x5 x0.050 C0 - U_ OPEN BACK SECTIONS r; 0 e 1 x 2: 1 "x2"x0.044" CL 3 co - 1 x 3: 1 "x3"0.044" ` � cr, SNAP SECTIONS=_¢F) 2 x 2 SNAP: 2"x2"4.050" 2 x 3 SNAP: 2"x3"x0.050" a.- � =R= s no �~. 2 x 4 SNAP: 2"x4"4.045" - t 0.1 rn SELF MATING (SMB) 2 x 4 SMB: 2"x4"x0.044"x0.100" 2 x 5 SMB: 2"x5"x0.050"x0.100" 2 x 6 SMB: 2"x6"x0.050"x0.120" - 2 x 7 SMB: 2"x7"x0.057"x0.120" 2 x 8 SMB: 2"x8"x0.072"x0.124" 2 x 9 SMB: 2"x9"x0.082"x0.124" 2 x 10 SMB: 2"x10"0.092"0.398" NOTE: AS INDICATED ABOVE ALL MEMBER PROFILES ARE INDICATED IN INCHES. FILE COPY ..j x 8" FOOTER HOUSE Gratip 3000 PSI 8 FIBERMESH 8" X 8" FOOTI p W(1) #5 REBAR CONT. FOOTING PIN NOTE: CONCRETE FOOTING INTERSECTING EXISTING FOOTING NEW 4" CONCRETE SLAB DOWELL INTO EXISTING CONCRETE45 REBAR, (2) 6" 3/4" HOLE 6" D EXISTING SLAB 3000 PSI W/FIBERMESH NMSIMPSON EPDXY -TIE" OR EQUAL PROVIDE 8BEDDMENT-DRILL o DOOR AVAILABLE FOR LAP ONTO NEW REBARS L PAD SLAB PIN NOTE: 4' CONCRETE SLAB -ADD ADJACENT TO EXISTING- DOWELL INTO EXISTING CONCRETE 48" O/C W/8" #5 REBARS- DRILL 3/4" HOLE 4" EMBEDMENT - EPDXY W/ NON -SHRINKING "SIMPSON EPDXY ::............:::::::::::::::::::::::::::: TIE" OR EQUAL L 16'-0" I CONC. PLAN NTS 8'-3 1X2 co J 2X2 o X X co N X N 2X4 S M B 1X2 --R'�IO-0-0���O(MAX) 4'-0- Y) % ' i a I I a I O I W I J I I 3 I T CHAIR RAIL ROOF RISE PROFILE HOST 36" O/H STRUC. GUTTER ARE S1:BJ.'E','C e Oa ANY Cffsr)-�-0 611ON'J FIEZ0U!RE'si BY r''iELst) IN, P.E0T0,'iS!1 T11.'si1 1M."kY BE l' Eir� 'ESSAY IN t"NDEER TO C^ r tla Y V lTH A.LL A.a�'LVC/ P,BLE G0DE3,. 2X3X.050 DIAG. BRACE TYP. -- 2X4X.044 I I I I I I 1X2 (TYP.) o cM CD G7 07 (/) f/) � � c7 9 N Lo N Lo N —1 Lo N Lo N Lo 2X2 (TYP.) N �n N `n50 N X N - o N Ll 1 1 X2 (TYP.) 1 44 7'-6" T T-6" 1 7'-6"� �__8'-O`T8'-0" TT-6" I T-6" 61T'-0"T-6" 1X2 2X2 DJ 2X2 DJ 0 2X5 SMB N O X N X a) 2X5 SMB. 0 /1X2 .� . CNI co ul :W o H 0: _ Z :C �. (o U' ui K-BRACE=2X3X.050 TYP J J m 00 UI M (M Z Z p O U U W —1 0 0 w Lo c z_ ~ r N co 1--co- c W Q 0 Q Q � 2 U 0Lo� Lo � � d N o n o co tr w U U N O ti cM O Z H U W O w a_ z w � 0 Y J Q Z LLL. O U ~U Q W Z m U) Ogl- W O o O CD W L �rnO Z O O a DESIGN DATE: 11/17/2017 REVISION 1: DATE PAGE: REVISION 2: DATE SCALE: NTS 3 ( NOTE: 2x4 SMB BEAM ONLY REQUIRES 4" WIDTH GUTTER BRACKET W/ (2) 3/8" LAGS 5" OR T'x6" WIDTHx0.250" EXTRUDED GUTTER BRACKET @ EA. BEAM W/ (4) #;2x3/4" S.M.S. INTO GUTTER LIP 4) 3/8" LAG SCREWS @ 1-1/2- SPACING @ EA GUTTER BRACKET Vx2"4.045" OPEN & (1) @ 12 O.C. MAX -MIN EMBEDMENT BACK W/ (2) #12x2" SHALL BE 2" INTO GUTTER & (1) #12x 2" @ 24" O.C. O BEAM 1 O 0 O O 2"x2"x1/8" X ALUMINUM ANGLE W/ (2) #14x3/4" THE HOST STRUCTURE SHALL S.M.S. INTO BEAM ON EA SIDE HAVE AT LEAST A 2"x4" (4) INTO GUTTER FASCIA AND ROOF TRUSS SYSTEM. CONTRACTOR SHALL OPTIONAL: 2"x2"x0.062" 4) #14x3/4" S.M.S. VERIFY THIS AND IF RECEIVING CHANNEL W/ (2) INTO GUTTER EA SIDE SMALLER CONTRACTOR #10x3/4" EA SIDE TO SHALL BRING STRUCTURE UP COVER EXPOSED BEAM TO A 2"x4" FASCIAAND ENSURE LESS THAN A 2'-0" OVERHANG GUTTER BRACKET & BEAM ATTACHMENT DETAIL SCALE:NTS NOTES: 1. HINGES SHALL BE ATTACHED TO STRUCTURE W/ (4) #10x5/8" S.M.S. MINIMUM. 2. DOOR SHALL BE ATTACHED TO ENCLOSURE W/ (2) HINGES MINIMUM. 3. HINGS SHALL BE ATTACHED TO DOOR WITH (4) #104/8" S.M.S. FASTEN A 1"x2"4.044" TO UPRIGHT W/#12x1" S.M.S. @ 12" O.C. AND WITHIN 3" FROM END OF THE UPRIGHT. TYPICAL SCREEN DOOR CONNECTION DETAIL SCALE:NTS BEAM SCREWS 2"x4" SMB 6 2"x5" SMB 6 2"x6" SMB 8 2"x7" SMB 8 2"x8" SMB 10 2"x9" SMB 10 2"x10" SMB 12 2"x PURLINS (SEE A 1 FOR SIZE) ATTACHED TO BEAM W/ MIN. (4) #10xl 1/2" SMS N 0 O o 0 /-3/16" ALUMINUM GUSSET ELATE /-B #14 SMS cp O 0 �I ��� m o 0 - : 0 1- 'k 00 O O O 0 O O -O O i N �\ \$ Cye 1'O (E e EN C 93lS�ET P -_ BEAM "B" "N" "S1" "S2" "S3" "S4' 2X4 12 4 3/4" 11/2" 16". 3.75" 2X5 12 4 3W' 1112" 16" 4.75" 2X6 16 5 1" 11/2" 19" 5.75" 2X7 20 6 1" 11/2" 22" 6.75" 2X8 24 7 1" 13/8" 2T 7.75" 2X9 24 7 V 13/9' 23" 8.75" 2X10 28 8 1" 11/4" 24" 9.75" NOTES: 1. "N" NUMBER OF SCREWS IN ANY DIRECTION. 2. TOTAL NUMBER OF SCREWS PER JOINT EQUALS 4 TIMES "B". 3. PLATE WIDTH SHALL BE DETERMINED FROM ANGLE OF BEAM AND MIN SPACE REQUIRED. 4. GUSSET PLATES MAY BE INTERNAL OR EXTERNAL. 5. INTERNAL SCREWS FOR PURLIN CONNECTION MAYBE INCLUDED IN TOTAL NUMBER OF SCREWS. 6. GABLE SPLICE WILL HAVE THE SAME PATTERN. BEAM SPLICE GUSSET DETAIL TYPICAL SCALE:NTS MAINTAIN MIN, OF 5/8" SEPERATION FROM EDGE OF BEAM SMS O.C. FOR SLOPED BEAMS MAINTAIN ALL SCREW SPACING FROM EDGE OF BEAM 2"x2" EAVE RAIL SECTION (UNLESS OTHERWISE SHOWN ON S-2) ATTACHED TO BEAM W/ (4)10x2" SMS INTO SCREW BOSS 1"x2" OPEN BACK EAVE RAIL ATTACHED TO UPRIGHT W/ (2) #10xl 1/2" SMS INTO SCREW BOSS #10x1 1/2" SMS 24" C/C #14x3/4" SCREWS (SEE TABLE ABOVE) SELF -MATING BEAM SHALL BE NOTCHED 7 FOR UPRIGHT / . (MIN) UPRIGHT UPRIGHT TO BEAM CONNECTION -ALL WIND ZONES SCALE:NTS ka �y ' , G,03ED}-1/ WITH e 1 =:6- �r!f C10'00. 1 1/2"xl/16" PLATE (TOP OR BOTTOM) 1"x2" FASTENED TO COLUMN WITH (2) #10x1 1/2" SMS INTO SCREW BOSSES FOR SMB OR SNAP COLUMN (12) #12xl' SCREWS @ 1" SPACING = Z ' . :Z D Z= :yam Z F¢- . ' c 2"x2" EDGE BEAM (UNLESS OTHERWISE SHOWN ON SHEET 5-2) (2) #10x3" SMS INTO SCREW BOSSES CONNECTING EDGE BEAM TO PURLIN 69-I1] NOTE: A RECEIVING CHANNEL (1/16" THICKNESS) WITH (4) #10x3/4" SMS AT EACH CONNECTION MAY BE USED IN PLACE OF THE (2) #10x3" SCREW BOSS CONNECTION. SLOPED OR FLAT PURLIN CONNECTION DETAIL SCALE:NTS EDGE MEMBER OR PURLIN (2) #10x4" SMS INTO SCREW BOSSES FOR EDGE MEMBERS J m Jo 00 UI M co Zzo 0 U n/ Ll U W�:s 0c W m .a) z ~ W c aj Z 5 W � O r- c' Qrn-7 0 Q U 0L0Ix LL 04 0 0 LLI r-1 ,0 N Joni � U w rn F- U I ;10 Z W O 1 O 000 O 10 I I .0625" 6063-T6 FLAT PLATE W/ (12) # 10x3/4" SMS J Q z J I I I I (MIN.1/2" EDGE DISTANCE) = Z LL LLI Q �? I DGE MEMBER L1J coZ J N O F- OR PURLIN W Q Q a (n fn U Z Q F 0 C) 1 -3 w >1` d ROOF BRACING CONNECTION DETAIL SCALE:NTS DESIGN DATE: 11/17/2017 REVISION 1: DATE PAGE: REVISION 2: DATE SCALE: NTS (4) #10x3/4" SMS FASTENING SECONDARY ANGLE TO COLUMN (TYP EACH SIDE) (B) 3/8" 0 CONCRETE SCREW ANCHOR INTO SECONDARY ANGLE (TYP EACH SIDE) (SEE TABLE) ANCHOR SPA (MIN) (TYP) (SEE TABLE) COLUMN SIZE 3/8" 0 CONCRETE SCREW ANCHOR B MIN SPA 2X3 0 0 2X4 1 3 2X5 1 3 2X6 1 4 2X7 1 5 2X8 2 3 2X9 2 4 2X10 2 4.5 SECONDARY ANGLE MIN 0.125" THICK (NOT REQUIRED FOR 20 MEMBER) —PRIMARY 2"x2" x0.125" ANGLE 2) #10x3/4" SMS FASTENING COLUMN TO PRIMARY ANGLE OPTION #1 O cr (TYP EACH SIDE) O I O "x2" BASE MEMBER (TYP EACH SIDE) (4) #10x1 1/2" SMS I I INTO SCREW BOSSES j OPTION #2 1) 3/8" 0 CONCRETE SCREW I I ANCHOR INTO PRIMARY I ANGLE AND @ 1/4" 0 CONCRETE I �3" MIN. SCREW ANCHOR @ I 24" O.C. BETWEEN COLUMNS NOTES: (TYP EACH SIDE) -------------- CIF ( 1. NUMBER OF ANCHORS "B" IS EACH SIDE INTO THE SECONDARY ANGLE AND DOES NOT INCLUDE THE ANCHOR INTO THE 1X2. 2. MINIMUM EMBEDMENT OF ANCHORS INTO CONCRETE FOOTING SHALL BE 2 3/4" AT ALL UPRIGHT LOCATIONS. ALL SCREW LENGTH AT UPRIGHT CONNECTIONS SHALL BE OF SUFFICIENT LENGTH FOR REQUIRED EMBEDMENT INTO CONCRETE FOOTING WHEN A PAVER DECK IS PRESENT. 3. CONCRETE SCREW ANCHOR DESIGNS ARE BASED ON THOSE LISTED ON S-1, D. FASTENERS, OTHER BRAND & TYPE SHALL BE APPROVED BY ENGINEER. 4.2X3 W/ 1X2 CORNER POST SHALL REQUIRE SAME BASE CONNECTIONS AS 2X4 SHOWN IN TABLE. 5. IF FOR AN IN -FILL, TOP OF COLUMN CONNECTIONS SIMILAR IF CONCRETE LINTEL IF WOOD LINTEL SUBSTITUTE 1/4" OX3" LAG SCREW FOR 3/8" 0 LDT FOR BOTH PRIMARY & SECONDARY ANGLES. 6. 2X2X.045 DOOR JAMB MEMBER SHALL CONNECT SIMILAR TO 2X3 MEMBER. 2"xY OR LARGER UPRIGHT TO CONCRETE W/WO PAVER DETAILS SCALE:NTS 91 - A-36 STEEL LIP M CLIP MAY BY PLACED ON .� TOP OR SIDE OF DECK W/ TOP OF A CHO3/8"R"SLEEVE ANCHOR CONCRETE DOUBLE COMPRESSION ° SLEEVES a O O a 4" NOMINAL SLAB v ° d c° MINIMUM 3/8" OX3" MASONRY OPTION #1 ANCHOR (MIN 3 3/4" 2500 PSI CONCRETE W/ EMBEDMENT 4" SLAB ONLY WELDED WIRE OR FIBERMESH 125" STAINLESS STEEL CABLE 2500 PSI CONCRETE W/ WELDED WIRE OR TOP OF FIBERMESH CONCRETE 4" NOMINAL SLAB MINIMUM 1 1/2"X5 1/2" ALUMINUM J OPTION #2 STRAP W/ (2) 3/8" OX3" USE WITH FOOTING MASONRY ANCHOR (MIN 3 3/4" EMBEDMENT) CABLE TO FOUNDATION CONNECTION DETAIL SCALE:NTS CORNER POST EAVE RAIL \��\\\IL�O • • • • �/�•/`�'`i /- N off• LL �- 1"x2"O.B. _ :Z O Lu Lu PATIO SECTION = --- - (D: W � I- z - 3" x 3" x 0.050" MIN., 6063-T6 ALLOY PLATE DR STRONGER (ONE SIDE) WITH IC SHOWN (3/8"MIN. PLATE EDGE DISTANCE /01111 1 1 11 111\1\\\\ & C-C FASTENER SPSPACING)NG) PLANS AND AI°Iw mCpoSm 111ioi.;ARE SUB- `. K-BRACE C-QUIRED-BY FIELD INSPECTORI THAT AY ICE INECESSA€ Y IN ORDER TO 2"x2" OR 2"x3"J I ' I C"0/ 1 I:f Ir/ITW ALL A rpu'VABLE CODES. MEMBER 1 .062"ALUMINUM INTERNAL OR LATERAL"K"-BRACING I I EXTERNAL RECEIVING CHANNEL CONNECTION DETAILS I W/ (4) #10x3W INTO BEAM OR I 1 UPRIGHT (2) #14x3/4" EA LEG INTO GIRT OR PURLIN (0.062" ANGLE CLIPS W/ (2) #14x3/4" SMS EA LEG) 6" x 5" x 0.050" PR BEAM -SNAP 6063-T6 ALLOY PLATE (ONE SIDE) OR STRONGER 2 x 2 x 0.050 OR SEELFLF MATING OR HOLLOW \ BRACE (TYP.) I COLUMN K-BRACE \ \ I PURLIN OR GIRT TO BEAM OR POST DETAIL ``� SCALE:NTS 2 x 2 x 0.050 CHAIR RAIL O\ I O I O`er O O O O GIRT (CHAIR RAIL) K-BRACE--------- ----------a O O O� /----- O I 2x2x0.050 I I BRACE (TYP.L% (11 TOTAL) - 912 x 3/4" S.M.S. AS SHOWN (1/2" MIN. PLATE EDGE DISTANCE & I I LATERAL "K"-BRACING C-C FASTENER SPACING) I I "x2"xl/8"ANGLE CONNECTION DETAILS 4) SMS / O P TOP TYP TOP AND SIDE) O Wit? NOTE: WHEN USING OPTION #2 DIA STAINLESS CONNECTION CABLE MUST BE FWELDED CORNER POST EEL CABLE WITHIN 6" OF CORNER OR PRIMARY MEMBER. 3" x 2" x 0.050" MIN., 6063 T6 ALLOY PLATE DR STRONGER (ONE SIDE) INLESS STEEL EYE BOLT SIDE VIEW "0 (MIN) WASHER OfOHENEATH NUT O --- O I TOP VIEW o O OPTION #2 ! o (3) - #12 x 3/4" S.M.S., (8) #14x3/4 SMS EACH SIDE AS SHOWN I (1/2" MIN. PLATE EDGE j j K-BRACE DISTANCE & C-C FASTENER SPACING) x2x0.050 ------ - ---- � ----- I i �% BRACE(TyP O O -- O O I O / O 3/8" 0 ADJUSTABLE EYE O I BOLT FOR CABLE TENSION ;--------------- = d _ I I --------------- /8" 0 STAINLESS i / STEEL CABLE ° e a ° a �--2"xZx1/8" EXTRUDED ANGLE SIDE VIEW ON45°ANGLE OPTION #1 CABLE CONNECTION AT CORNER SCALE:NTS a d 3/8" 0 CONCRETE ANCHOR (2 PLATES FOUNDATION IN LIEU OF TYP. 1/4" 0 CONCRETE SCREWS FOR CORNER COLUMN LATERAL "K"-BRACING CONNECTION DETAILS CONCRETE OR FI MASONRY .024 FLASHING SEALED TO YP.) 2x3/4" SMS @ 12" O.C. TOP BOTTOM -3" RECEIVING CHANNEL TEN TO MASONRY WALL /4" X 3" TAPCONS 18" O/C (INTERNAL) ROOF PANEL ATTACHMENT - MASONRY SCALE:NTS 0 EXISTING RAFTER OR TRUSSER C - � COPY cc),C #12x3/4" SMS @ 12" O.C. TOP & BOTTOM + 040X3"LYHEADER (1'�l, t.�'. ��i E j1dS3 ALL PROOF, SM WORK 2" NOMINAL STRUCTURAL p _ y S _ FASCIAMIN. OR COMPOSITEPANELS: A1,-i a '+I f tEC"( T!d A(t1Y (2) #12 X 2"SMS L� r^ r io p- Y p Y� 9 i a C THROUGH RECEIVING FOR ALUMINUM PANS: Rr;:t < I 0 B 7 t 1 1.D 1%Sf E0T 01: S ) HAT G CHANNEL @ 12" O.C. #12 X 2" SMS THROUGH �,i r . , i• a a a r "BOXED END": INTO WD FASCIH'd1A BE (�i•'ECtE�?�NRY IN E.t�i{�'E!ri TO ALTERNATELY: (3) PER PAN (1) 114W LAG BOLT c:f� j7""!.y 4 i I .�Zi'I �Fry ' !v 1?"i THROUGH RECEIVING c1t WITH s A'"'" y la0i Ev. CHANNEL @ 12" O.C. ROOF PANEL ATTACHMENT - WOOD FRAME SCALE:NTS FOR ALUMINUM PANS OR GALVALUME STEEL PANS WHERE ROOF INTERSECTS CAGE USE #12 X 9/16" W/ 5/8" NEO WASHER (3) PER PAN CAGE BEAM AND OPTIONAL GUTTER FOR COMPOSITE PANELS #12 X 1" LG. THAN PANEL GUTTER BRACE PER DETAIL "H "AT THICKNESS SMS W/ 1-1/2" NEO-WASHER 12" O/C EACH BEAM LOCATION _ / COVER END OF PANEL , ROOF PER PLAN BEAM PER PLAN BEAM (4) 3/8"x4" TAPCON THRU BOTTOM LEG OF ANGLE INTO CONC. 1^ 2^ 33/4" FROM EDGE —L 1" OF SLAB TOP VIEW (3) 1/4" DIA MACHINE COLUMN PER PLAN BOLTS w/ WASHERS I 1/8'SQ"X1"x33/4" (4) 3/8"x7" LTD TAPCON (LENGTH) ANGLE THRU BOTTOM LEG (INTERNAL) OF ANGLE INTO CONC. (2)3/8"THRU-BOUT ma+zsn SEE ALSO COL/EDGE14 BEAM ALTERNATES �" CONC. FOOTING ` NOTE: WHERE SMB USED �" BELOW % FOR COL. AT END OF GUTTER CAGE BEAM ATTACH BEAM ATTACH PER POST PER DETAIL "H" SHEET 4 FRONT VIEW DETAIL "E" SHEET 3 COL. PER PLAN WHERE MIDPOINT ROOF PER PLAN 2"X2" PER PLAN COL. IS INDICATED. ALT. COLUMN BASE ATTACHMEN ATTACH TO ROOF PANELS DETAIL SCALE: NTS W/# 12 X 2-1/2" SMS 12" O/C HOST 6" FROM ENDS ROOF TO CARRIER BEAM CONNECTION SCALE: NTS (4) 3/8"x4" TAPCON THRU BOTTOM LEG OF ANGLE ALTERNATES FOR COL. INTO CONC TO 2"X2"AT HEADER: CARRIER BEAM SEE NOTE #1XTHIISS PAGE BOLTS 1" 1-DETAIL "C" SHT 3 FOR BOLT PLACEMENT 2- (4) # 10 X 3" SMS (2) 1/4" THRU BOLT ____ 2" THROUGH MEMBERABOVE SEE ALSOCOL/EDGE i I INTO COL SCREW BOSS BEAM ALTERNATES ® 2" FROM EDGE 3- NOTCH COL. TO RECEIVE 2" FROM EDGE OF SLAB' BEAM FASTEN W/ COL. PER PLAN OF SLAB • L---- OF SLAB M EDGE (2)'/." THRU-BOLT 1 "X2" FASTEN TO/ 1" X 2" FASTEN TO CHAIR RAIL PER PLAN ADJOINING WALL ADJOINING WALL TOP VIEW TOP MEWW/#12 X 1-1/2" SMS W/#12 X 1-1/2" @ 18" O.C. SMS @ 18" O.C. (2) 1/4" DIA MACHINE (3) 1/4" DIA MACHIN 4"x4"x0.125" POST 1/4"X2-3/4" TAPCONS BOLTS w/ WASHERS 3")6"x0.125" POST BOLTS w/ WASHERS I I OR EQUAL AT 24" O.C. I I AND 6" FROM ENDS ADJOINING BEARING WALL (2) 3/8" DIA EXPANSION BOLTS I (4) 3/8"x7" LTD TAPCON I 2"1Q"x0.125 ANGLE WHERE KICK PLATE IS INDICATED SEE NOTE #1 THIS PAGE 3� I THRU BOTTOM LEG I FOR BOLT PLACEMENT Gi k0.125 ANGLE OF ANGLE INTO CONC. I FASTEN W/#10 X 9/16" SMS I 8" O/C AT PERIMETER CONC FOOTIN CONC FOOTING BELOW BELOW EXISTING CONCRETE TYPICAL SIDE WALL 1/4" TAPCON (RED HEAD MFG. OR EQUAL) 6" FROM ENDS 24" O.C. COLUMN 1-1/2" PENETRATION INTO UNDERLYING FOOTING FRONT VIEW FRONT VIEW SCREEN ROOM END WALL 3"x3" POST CONNECTION DETAIL 4")W' POST CONNECTION DETAIL SCALE:NTS SCALE:NTS SCALE:NTS z W coZ_ v> z CUD rMo 0 '0 011 I I 1110\\\,• .A