HomeMy WebLinkAboutLETTER- COMMENT RESPONSES1`'V11.1s, Short 8 Associate
CIVIL I STRUCTURAL I SURVEYING I ENVIRONMENTAL
CERTIFICATION OF AUTHORIZATION 30698
January 18, 2018
St. Lucie County Building and Inspections
2300 Virginia Ave.
Fort Pierce, FL 34982
Re: Comment Responses
Peterson Residence
2583 Dyer Rd.
Port St. Lucie, FL 34952
Permit #: 1712-0008
To Whom It May Concern:
This letter is written to provide certification that I, as a Professional Engineer, have been retained to establish
compliance with the 2014 Florida Building Code (5t' Edition) & the St. Lucie County codes and regulations
pertaining to the modifications at the residence listed above. Please see the responses to the comments below:
Comment Responses
Comment:
PLEASE PUT ON THE PLANS THE SOIL DENSITY OR SUBMIT GEOTECHNICAL REPORT IN
COMPLIANCE WITH R401 OF THE 2014 RESIDENTIAL BUILDING CODE.
Response:
Compaction requirement added to structural notes on sheet 6.0
Comment:
PLEASE ADD THE CUBIC VOLUME OF THE CONDITIONED SPACE TO INFORMATION
BLOCK CONTAINING THE SQUARE FOOT INFORMATION OR A LETTER FROM THE DESIGN
PROFESSIONAL SPECIFYING THE CUBIC VOLUME OF THE CONDITIONED SPACE. SEE
CHAPTER 1 SECTION 107 OF THE 2014 FLORIDA BUILDING CODE.
Response:
Cubic footage added to the area tabulation schedule on site plan, sheet 2.0
Comment:
PLEASE FURNISH ENERGY CALULATIONS AND MANUAL J IN ACCORDANCE WITH
SECTIONS 402 AND 403 OF THE 2014 FLORIDA ENERGY CODE. NOTE ONLY; ENERGIES
MUST HAVE ORIGINAL SIGNATURE OF PREPARER.
Response:
Owner to provide
Comment:
CONCRETE GENERAL NOTES DO NOT MATCH THE FOUNDATION GENERAL NOTES ON
PAGE 6.0. PLEASE SEE THE CONCRETE PSI. SEE CHAPTER 1 SECTION 107 OF THE 2014
FLORIDA BUILDING CODE. .
Response: File C®
PSI discrepancy has been addressed on sheet 6.0 ��
Comment:
800 Eighth Street I Vero Beach FL 32962 1772.226.7282
ONLY ONE DOCUMENT WAS SUBMITTED FOR THE SEPTIC SYSTEM. ALL DOCUMENTS
SUBMITTED FOR REVIEW MUST BE IN DUPLICATE. AS PER CHAPTER 1, SECTION 107
SUBSECTION 107.1 OF THE 2014 FLORIDA BUILDING CODE.
Response:
Owner to provide
Comment:
ONLY ONE DOCUMENT WAS SUBMITTED WELL WATER PERMIT. ALL DOCUMENTS
SUBMITTED FOR REVIEW MUST BE IN DUPLICATE. AS PER CHAPTER 1, SECTION 107
SUBSECTION 107.1 OF THE 2014 FLORIDA BUILDING CODE.
Response:
Owner to provide
Comment:
NO PRODUCT REVIEW AFFIDAVIT OR PRODUCT APPROVALS WERE SUBMITTED FOR
REVIEW. SUBMIT THE PRODUCT APPROVALS, IN DUPLICATE OR PRODUCT REVIEW
AFFIDAVIT COMPLETE WITH FLORIDA PRODUCT APPROVAL OR N.O.A. NUMBER WITH
INSTULATION INSTRUCTIONS AND SIGNED SEALED AND DATED BY THE DESIGN PERSON
OF RECORD FOR ALL COMPONETS AND CLADING IN ACCORDANCE WITH 553.842 OF THE
FLORIDA STATUTES. PRODUCT APPROVAL'S MUST BE HIGHLIGHTED OR MARKED
IDENTIFYING THE OPENING OR CLADDING COMPONENTS, WITH FASTENERS AND
DESIGN PRESSURES.
Response:
Owner to provide
Comment:
FOOT NOTES ON THE PLANS SPECIFY SEE ENERGY CALC'S FOR THE INSULATION R-
VALUES. NO ENERGY CALC'S WERE SUBMITTED. PLEASE FURNISH ENEGRY
CALULATIONS AND MANUAL J IN ACCORDANCE WITH SECTIONS 402.AND 403 OF THE
2014 FLORIDA ENEGRY CODE FIFTH EDITION. NOTE ONLY; ENERGIES MUST HAVE
ORIGINAL SIGNATURE OF PREPARER
Response:
Owner to provide
Comment:
PLEASE ADD TO THE PLANS THE CLIMATIC AND GEOGRAPHIC DESIGN CRIERIA
WEATHERING AND TERMITE AREA IN ACCORDANCE WITH TABLE 301.2.(1).
Response:
Requirement added to structural notes on sheet 6.0
Comment:
PLEASE SHOW FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX FOR WALL AND
CEILING FINISHES IN ACCORDANCE WITH SECTION 302.9 OF THE 2014 FLORIDA
RESIDENTIAL CODE.
Response:
Notes for flame spread and smoke developed index for finishes added with interior wall framing detail on
sheet 3.0
Comment:
PLEASE SHOW THE FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR THE
INSULATION AS REQUIRED IN SECTION 3 02. 10 OF THE 2014 FLORIDA RESIDENTIAL CODE.
Response:
Notes for flame spread and smoke developed index for finishes added with interior wall framing detail on
sheet 3.0
Comment:
PLEASE SHOW GYPSUM BOARD MATERIALS ARE IN ACCORDANCE WITH 702.3.1 OF THE
2014 FLORIDA RESIDENTIAL CODE.
Response:
Notes for finishes added with interior wall framing detail on sheet 3.0
Comment:
PLEASE SEE PAGE 11.0 SANITARY WASTE PLAN. THE SANITARY WASTE LINE IS EXITING
THE FRONT OF THE HOUSE. THE APPROVED DRAWING FROM FDOH SHOW THE WASTE
LINE EXITING THE STRUCTURE FROM THE REAR. PLEASE CORRECT AND RESUBMIT. SEE
SECTION 107 OF THE 2014 FLORIDA BUILDING CODE.
Response:
Sanitary waste plan and isometric has been revised to reflect drainage to rear of building.
The engineering services addressed therein have been performed and based upon my professional engineering
kn jled ep technical documentation, information and belief, and in accordance with commonly accepted procedures
�ie t�i h6pplicable standards of practice, and is not a guaranty or warranty, either expressed or implied. Should
C, v'�40ns, please feel free to call me at the number listed below.
*. S 19018 '*
on W. Short, P; SCE
P l &gingergo—
FLORID P'�R
�''�� 4NAL
dills, Short 8 AssociatCJ
CIVIL I STRUCTURAL I SURVEYING I ENVIRONMENTAL
CERTIFICATION OF AUTHORIZATION 30698
January 18, 2018
St. Lucie County Building and Inspections
2300 Virginia Ave.
Fort Pierce, FL 34982
Re: Comment Responses
Peterson Residence
2583 Dyer Rd.
Port St. Lucie, FL 34952
Permit #: 1712-0008
To Whom It May Concern:
This letter is written to provide certification that I, as a Professional Engineer, have been retained to establish
compliance with the 2014 Florida Building Code (5t' Edition) & the St. Lucie County codes and regulations
pertaining to the modifications at the residence listed above. Please see the responses to the comments below:
Comment Responses
Comment:
PLEASE PUT ON THE PLANS THE SOIL DENSITY OR SUBMIT GEOTECHNICAL REPORT IN
COMPLIANCE WITH R401 OF THE 2014 RESIDENTIAL BUILDING CODE.
Response:
Compaction requirement added to structural notes on sheet 6.0
Comment:
PLEASE ADD THE CUBIC VOLUME OF THE CONDITIONED SPACE TO INFORMATION
BLOCK CONTAINING THE SQUARE FOOT INFORMATION OR A LETTER FROM THE DESIGN
PROFESSIONAL SPECIFYING THE CUBIC VOLUME OF THE CONDITIONED SPACE. SEE
CHAPTER 1 SECTION 107 OF THE 2014 FLORIDA BUILDING CODE.
Response:
Cubic footage added to the area tabulation schedule on site plan, sheet 2.0
Comment:
PLEASE FURNISH ENERGY CALULATIONS AND MANUAL J IN ACCORDANCE WITH
SECTIONS 402 AND 403 OF THE 2014 FLORIDA ENERGY CODE. NOTE ONLY; ENERGIES
MUST HAVE ORIGINAL SIGNATURE OF PREPARER.
Response:
Owner to provide
Comment:
CONCRETE GENERAL NOTES DO NOT MATCH THE FOUNDATION GENERAL NOTES ON
PAGE 6.0. PLEASE SEE THE CONCRETE PSI. SEE CHAPTER 1 SECTION 107 OF THE 2014
FLORIDA BUILDING CODE.
Response:
PSI discrepancy has been addressed on sheet 6.0
Comment:
800 Eighth Street I Vero Beach FL 32962 1772.226.7282
r
ONLY ONE DOCUMENT WAS SUBMITTED FOR THE SEPTIC SYSTEM. ALL DOCUMENTS
SUBMITTED FOR REVIEW MUST BE IN DUPLICATE. AS PER CHAPTER 1, SECTION 107
SUBSECTION 107.1 OF THE 2014 FLORIDA BUILDING CODE.
Response:
Owner to provide
Comment:
ONLY ONE DOCUMENT WAS SUBMITTED WELL WATER PERMIT. ALL DOCUMENTS
SUBMITTED FOR REVIEW MUST BE IN DUPLICATE. AS PER CHAPTER 1, SECTION 107
SUBSECTION 107.1 OF THE 2014 FLORIDA BUILDING CODE.
Response:
Owner to provide
Comment:
NO PRODUCT REVIEW AFFIDAVIT OR PRODUCT APPROVALS WERE SUBMITTED FOR
REVIEW. SUBMIT THE PRODUCT APPROVALS, IN DUPLICATE OR PRODUCT REVIEW
AFFIDAVIT COMPLETE WITH FLORIDA PRODUCT APPROVAL OR N.O.A. NUMBER WITH
INSTULATION INSTRUCTIONS AND SIGNED SEALED AND DATED BY THE DESIGN PERSON
OF RECORD FOR ALL COMPONETS AND CLADING IN ACCORDANCE WITH 553.842 OF THE
FLORIDA STATUTES. PRODUCT APPROVAL'S MUST BE HIGHLIGHTED OR MARKED
IDENTIFYING THE OPENING OR CLADDING COMPONENTS, WITH FASTENERS AND
DESIGN PRESSURES.
Response:
Owner to provide
Comment:
FOOT NOTES ON THE PLANS SPECIFY SEE ENERGY CALC'S FOR THE INSULATION R-
VALUES. NO ENERGY CALC'S WERE SUBMITTED. PLEASE FURNISH ENEGRY
CALULATIONS AND MANUAL J IN ACCORDANCE WITH SECTIONS 402 AND 403 OF THE
2014 FLORIDA ENEGRY CODE FIFTH EDITION. NOTE ONLY; ENERGIES MUST HAVE
ORIGINAL SIGNATURE OF PREPARER
Response:
Owner to provide
Comment:
PLEASE ADD TO THE PLANS THE CLIMATIC AND GEOGRAPHIC DESIGN CRIERIA
WEATHERING AND TERMITE AREA IN ACCORDANCE WITH TABLE 301.2.(1).
Response:
Requirement added to structural notes on sheet 6.0
Comment:
PLEASE SHOW FLAME SPREAD INDEX AND SMOKE DEVELOPED INDEX FOR WALL AND
CEILING FINISHES IN ACCORDANCE WITH SECTION 302.9 OF THE 2014 FLORIDA
RESIDENTIAL CODE.
Response:
Notes for flame spread and smoke developed index for finishes added with interior wall framing detail on
sheet 3.0
Comment:
PLEASE SHOW THE FLAME SPREAD AND SMOKE DEVELOPED INDEX FOR THE
INSULATION AS REQUIRED IN SECTION 3 02. 10 OF THE 2014 FLORIDA RESIDENTIAL CODE.
Response:
Notes for flame spread and smoke developed index for finishes added with interior wall framing detail on
sheet 3.0
Comment:
PLEASE SHOW GYPSUM BOARD MATERIALS ARE IN ACCORDANCE WITH 702.3.1 OF THE
2014 FLORIDA RESIDENTIAL CODE.
Response:
Notes for finishes added with interior wall framing detail on sheet 3.0
Comment:
PLEASE SEE PAGE 11.0 SANITARY WASTE PLAN. THE SANITARY WASTE LINE IS EXITING
THE FRONT OF THE HOUSE. THE APPROVED DRAWING FROM FDOH SHOW THE WASTE
LINE EXITING THE STRUCTURE FROM THE REAR. PLEASE CORRECT AND RESUBMIT. SEE
SECTION 107 OF THE 2014 FLORIDA BUILDING CODE.
Response:
Sanitary waste plan and isometric has been revised to reflect drainage to rear of building.
The engineering services addressed therein have been performed and based upon my professional engineering
knowledge, technical documentation, information and belief, and in accordance with commonly accepted procedures
\�X-MIYAt kt* applicable standards of practice, and is not a guaranty or warranty, either expressed or implied. Should
q*S
�tva'Rbf 4tions, please feel free to call me at the number listed below.
ly,
018
. Short,IWFd.ASCEal ilgineg4/
to,
rrrriii��
[. 'Jlls, Short 8 Associates
CIVIL I STRUCTURAL I SURVEYING I ENVIRONMENTAL
CERTIFICATION OF AUTHORIZATION 30698
June 29, 2018
St. Lucie County Building and Inspections
2300 Virginia Ave.
Fort Pierce, FL 34982
Re: Roof Underlayment
Peterson Residence
2583 Dyer Rd.
Port St. Lucie, FL 34952
Permit #: 1712-0008
To Whom It May Concern:
RECEIV
JUL 13 L'",")
6��so�ire
ST. Lucie
This letter is written to provide certification that I, as a Professional Engineer, have been retained to establish
compliance with the 2014 Florida Building Code (5ffi Edition) & the St. Lucie County codes and regulations
pertaining to the residence listed above. It must be noted that the builder is installing a peel-n-stick underlayment, FL
#11602-R3 (Interwrap Inc. Titanium Roof Underlayments).
The engineering services addressed therein have been performed and based upon my professional engineering
knowledge, technical documentation, information and belief, and in accordance with commonly accepted procedures
consistent with applicable standards of practice, and is not a guaranty or warranty, either expressed or implied. Should
` ou hivi p� questions, please feel free to call me at the number listed below.
ON
* ' No 9018
•_Jasoa pert. Pi.,WaSCE
•A
JUL 1.3 201
BY:
700 22°d Place I Suite 2C/2D I Vero Beach, FL 32962 1772.226.7282
100 Federal Hiahwav I Suite B I Lake Park, FL 33403
ii ll
'Aills, Short 8 Associate
CIVIL I STRUCTURAL I SURVEYING I ENVIRONMENTAL
CERTIFICATION OF AUTHORIZATION 30698
June 29, 2018
St. Lucie County Building and Inspections
2300 Virginia Ave.
Fort Pierce, FL 34982
Re: Roof Underlayment
Peterson Residence
2583 Dyer Rd.
Port St. Lucie, FL 34952
Permit #: 1712-0008
To Whom It May Concern:
This letter is written to provide certification that I, as a Professional Engineer, have been retained to establish
compliance with the 2014 Florida Building Code (5111 Edition) & the St. Lucie County codes and regulations
pertaining to the residence listed above. It must be noted that the builder is installing a peel-n-stick underlayment, FL
#11602-R3 (Interwrap Inc. Titanium Roof Underlayments).
The engineering services addressed therein have been performed and based upon my professional engineering
knowledge, technical documentation, information and belief, and in accordance with commonly accepted procedures
consistent with applicable standards of practice, and is not a guaranty or warranty, either expressed or implied. Should
you hiviel p� questions, please feel free to call me at the number listed below.
o
= * No 018
o .Jason E§b prt, P [�— SCE
kVWfee '
Al-
1110 f
700 22nd Place I Suite 2C/2D I Vero Beach, FL 32962 1772.226..7282
100 Federal Highwav I Suite B I i.ake Park. Ff. 13401