Field Density Tests of Compacted Soils Method D-6938
Project: Proposed Residence Lot 109, Creekside Date: November 24, 2017
Address: 3100 Yellowstone"Circle, Fort Pierce, FL 34945 Order #: 17-DR-1152
Area Tested: Building" Pad Permit #:
Material Type: Light Brovvn Sand with Some Rock Tech: SL
Client:
Address:
R. Horton, Inc. '
1430 C 'lver,Drive' NE Compaction Req.: 95%
Palm Bay, FL 32907 Proctor Method: ASTM D-1557
Test
#
TEST LOCATION
Probe
Depth
p
Elev.
Moist
oi
Dry'
Density
PCF
Proctor
Value
PCF
Optimum
Moisture
%
Compaction
Pass
1
NE Corner of Pad
12"
FL
11.3
105.1
110.5
12.5
1 95.1 %
Yes
2
Center of Pad
12"
FL
9.8
106.4
110.5
12.5
96.30/6
Yes
3
SW Corner of Pad
12"
FL
9.4
105.8
110.5
12.5
95.7%
Yes
4
5
6
7
8
9
10
11
12
13
14
FT
I.
I
KemarKS: See Reverse Side (Page 2 of 2) for Additional Information for Disclaimer
This Is a Compaction Test only on the top 12" of the pad and is not a verification of Soil Bearing Capacity.
Legend for Elevation:
PR = Proofroll 1,2,3 =1st, 2nd, 3rd Lift Submitted by:
SL = Springline FL = Final Lift Keith LeE?lanc, P-.E' _ r raj r2
SG =' Subgrade BG = Below Grade Federal Engineering 3Jb ting, Inc.
BC = Basecourse , BOF = Bottom of Footing Florida Reg. No. 69394 c.
TOP = Top of Pipe FG = Finished Grade _Certificate 611"Adthorizati0h #5471
As a mutual protection to clients, the public and ourselves, all reports are submitted as the confidential property of clients; and authorization forrpublication of statements,
conclusions or extracts from or regarding our reports is reserved pending our written approval. A dens ty test detemiliies'iha degree of compaction of the tested layer of
material only. A density does not replace a soil bearing capacity determination. These density tests do not certify the underlying soil materials below the proposed structure.
The results do not preclude or guarantee that future settlement and cracking will not occur. A soil boring.test'is required to certify.that thelund.6dying soils will support the
proposed structure without settlement. If no soil borings have been performed to verify the underlying solls,.ws r?comrlend tn2t soil bc'rciys:be performed to evaluate the
suitability of the underlying soil to support the proposed structure. After laying dormant for a period of 90 days or' fief heavy rain/sto , s, ►etosting must be performed on this
work. '�' I `�
PAGE 1 of 2
Corn
Pursuant to your request, Federal Engineers
project on the reverse side. The purpose of
material only. In no way shall a compaction
performed by the client prior to construction t(
12" of added fill material. FET was not cons
the added fill material does not include an
supporting the proposed structure without se
materials or conditions below the tested top 1
the proposed structure, we recommend perl
verify the underlying soil conditions.
Solis Method ®-6936 Disclaimer
g & Testing, Inc. (FET) has performed a compaction test at the referenced
our test was to determine the degree of compaction of the tested layer of
:st replace a soil bearing capacity determination. A soil boring test must be
verify subsoil conditions. Our scope of services only included testing the top
acted to perform supervision of the building pad preparation. This testing of
nalysis of the underlying soil materials to determine if they are capable of
lement. This density compaction test does not warranty any underlying soil
inches of material. If no soil borings have been performed in the location of
)rming soil boririgs below all foundation areas of the proposed structure to
Environmental analysis of the soil materials is not part of the scope of services. If environmental analysis of the soils is
required, we can provide a proposal for performing an environmental analysis of the soil materials. The scope of services is
for determination of the degree of compaction of the tested layer of material only. No other analysis is implied or warranted.
Job project specifications were not available at'the time the work was performed. Determination of the pass/fail compaction
results are based on current common industry requirements of 95% of the ASTM D-1557 standard for building foundations
and 98% of the AASHTO T-180 standard for paved areas such as roadways and parking lots. If different specifications are
required, Federal Engineering & Testing, Inc. shall be notified.
Our findings are relative to the date and areas of our site work and should not be relied upon to represent conditions on
other areas or dates. Any subsequent site disturbances due to water erosion, rain waters, construction activities,
excavations, overgrown, vegetation, traffic and other disturbances will void this test and the site must be re<compacted and
re -tested prior to construction.
As a mutual protection to clients, the public and 'ourselves, all reports are submitted are the confidential property of clients
and authorization for use, publication of statements, conclusions or extracts from or regarding our reports is reserved
pending written approval.