Loading...
The URL can be used to link to this page
Your browser does not support the video tag.
Home
My WebLink
About
PROJECT INFORMATION
Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-29 10:40:08 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Load Short Form 9/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Key Largo Spec, NisAir Air ConditioningFor: 5604 Hickory Dr, Fort Pierce, FL 34982 Design Information InfiltrationClgHtg SimplifiedMethod9041Outside db (°F) AverageConstruction quality7570Inside db (°F) 0Fireplaces1529Design TD (°F) L-Daily range 5030Inside humidity (%) 572Moisture difference (gr/lb) HEATING EQUIPMENT COOLING EQUIPMENT Make Make Lennox Trade Trade LENNOX Model Cond ML14XC1S036-230C** AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 204289057 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.9 Sensible cooling Btuh24220 Heating output Btuh27037 Latent cooling Btuh10380 Temperature rise °F21 Total cooling Btuh34600 Actual air flow cfm1153 Actual air flow cfm1153 Air flow factor cfm/Btuh0.046 Air flow factor cfm/Btuh0.049 Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.77 ROOM NAME Area Htg load Clg load Htg AVF Clg AVF (ft²)(Btuh)(Btuh)(cfm)(cfm) Laundry 36 425 843 19 42 Bed 2 136 2379 1764 109 87 Bath 42 58 89 3 4 Bath 2 51 759 559 35 27 Hall 30 0 0 0 0 Bed 3 153 3169 2568 145 126 Bed 4 157 2464 1852 113 91 Foyer GR 426 5170 5695 237 280 Pantry 14 0 0 0 0 Kitchen DR 411 4592 6432 210 317 Master Bath 117 2076 966 95 48 Hers 20 402 155 18 8 Master Bed 209 3699 2510 169 124 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-29 10:40:08 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW House 1801 25194 23431 1153 1153 Other equip loads 1769 939 Equip. @ 0.95 RSM 23250 Latent cooling 7223 TOTALS 1801 26963 30473 1153 1153 2021-Sep-29 10:40:08 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Building Analysis 9/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Key Largo Spec, NisAir Air ConditioningFor: 5604 Hickory Dr, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor:7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Heating Walls Glazing Ceilings Floors Infiltration Ducts Ventilation % of loadBtuhBtuh/ft²Component 17.246503.1Walls 14.0377717.4Glazing 000Doors 6.617851.0Ceilings 21.357363.23.2Floors 11.831822.2Infiltration 22.56063Ducts 00Piping 00Humidification 6.61769Ventilation0Adjustments 100.026963Total Cooling Walls Glazing Ceilings Infiltration Ducts Internal Gains Ventilation % of loadBtuhBtuh/ft²Component 11.828671.9Walls 19.5475822.0Glazing 000Doors 10.826341.5Ceilings 000Floors 3.68890.6Infiltration 27.86783Ducts 3.9939Ventilation 22.65500Internal gains 00Blower 0Adjustments 100.024371Total Latent Cooling Load = 7223 Btuh Overall U-value = 0.104 Btuh/ft²-°F Data entries checked. 2021-Sep-29 10:40:08 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Component Constructions 9/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Key Largo Spec, NisAir Air ConditioningFor: 5604 Hickory Dr, Fort Pierce, FL 34982 Design Conditions Location: CoolingHeatingIndoor: 7570Indoor temperature (°F)St Lucie Co Intl, FL, US 1529Design TD (°F)ft26Elevation: 5030Relative humidity (%)°N28Latitude: Outdoor:56.92.4Moisture difference (gr/lb)CoolingHeating Infiltration:9041Dry bulb (°F) SimplifiedMethod)L(15-Daily range (°F) AverageConstruction quality77-Wet bulb (°F) 0Fireplaces7.515.0Wind speed (mph) Construction descriptions GainLoss Clg HTMHtg HTMInsul RU-valueAreaOr BtuhBtuh/ft²BtuhBtuh/ft²ft²-°F/BtuhBtuh/ft²-°Fft² Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inI, 8" Thk, 1/2" Gyp Bd Int Fnsh 7913.155.10.109251ne 5062.02 7482.0211693.155.10.109371se 7802.0212203.155.10.109387sw 4592.027173.155.10.109228nw 24932.0238973.155.10.1091237all Partitions Frm Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"x4", 16" OC Stud 3741.467542.9411.00.101257 Windows Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 103722.184118.000.62047ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 4.7 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht 66116.567616.800.58040ne Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.17 ft window ht, 1 ft sep.); 6.8 ft head ht 9520.27916.800.5805sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 68121.852516.800.58031sw 70622.652516.800.58031nw 138722.2105016.800.58062all Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 8 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht 21013.526216.800.58016sw 2021-Sep-29 10:40:08 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.21); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 8 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht 56314.075818.800.65040sw Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.2 ft window ht, 1 ft sep.); 6.8 ft head ht 14922.611116.800.5807nw Doors (none) Ceilings Attic, Shngl Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh 0.0341801 26341.4617850.9930.0 Floors On Grade Depth, Tile Flr Fnsh 00573628.700.989200 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-29 10:40:08 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Project Summary 9/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Key Largo Spec, NisAir Air ConditioningFor:5604 Hickory Dr, Fort Pierce, FL 34982 Notes: Design Information St Lucie Co Intl, FL, USWeather: Winter Design Conditions Summer Design Conditions Outside db °F41 Outside db °F90Inside db °F70 Inside db °F75 Design TD °F29 Design TD °F15Daily range L Relative humidity %50Moisture difference gr/lb57 Heating Summary Sensible Cooling Equipment Load Sizing Structure Btuh19131 Structure Btuh16649 Ducts Btuh6063 Ducts Btuh6783Central vent (56 cfm) 1769 Btuh Central vent (56 cfm) Btuh939 Outside air Outside airHumidification Btuh0 Blower Btuh0 Piping Btuh0Equipment load Btuh26963 Use manufacturer's data n Rate/swing multiplier 0.95InfiltrationEquipment sensible load Btuh23250 Method Latent Cooling Equipment Load SizingSimplified Construction quality Average0Fireplaces Structure Btuh3031 Ducts Btuh2047Central vent (56 cfm) Btuh2145 CoolingHeating Outside air18011801Area (ft²) Equipment latent load Btuh7223 1576615766Volume (ft³)Air changes/hour 0.200.38 Equipment Total Load (Sen+Lat)Btuh30473 Equiv. AVF (cfm) 53100 Req. total capacity at 0.70 SHR ton2.8 Heating Equipment Summary Cooling Equipment Summary Make Make LennoxTrade Trade LENNOX Model Cond ML14XC1S036-230C**AHRI ref Coil CBA27UHE-036-230*++TDR AHRI ref 204289057Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input kW7.9 Sensible cooling Btuh24220Heating output Btuh27037 Latent cooling Btuh10380 Temperature rise °F21 Total cooling Btuh34600Actual air flow cfm1153 Actual air flow cfm1153 Air flow factor cfm/Btuh0.046 Air flow factor cfm/Btuh0.049Static pressure in H2O0.70 Static pressure in H2O0.70 Space thermostat Load sensible heat ratio 0.77 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-29 10:40:08Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Right-J® Worksheet 9/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name House Laundry 2 Exposed wall 200.0 ft 5.5 ft 3 Room height 8.8 ft 8.0 heat/coolft 4 Room dimensions ft6.5x5.5 5 Room area 1800.8 ft²35.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 338 251 791 506 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 47 0 841 1037 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 16.4516.45 40 0 676 661 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 371 371 1169 748 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 479 387 1220 780 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2120.21 5 1 79 95 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 31 4 525 681 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 16 16 262 210 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 40 40 758 563 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 266 228 717 459 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 7 0 111 149 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 31 0 525 706 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 257 257 754 374 44 44 129 64 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 1801 1801 1785 2634 36 36 35 52 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 1801 200 5736 0 36 6 158 0 6 c) AED excursion 655 -17 Envelope loss/gain 15949 10260 322 99 12 a) Infiltration 3182 889 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 5 1150 0 0 Appliances/other 4350 500 Subtotal (lines 6 to 13)19131 16649 322 599 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 19131 16649 322 599 15 Duct loads 32%41%6063 6783 32%41%102 244 Total room load 25194 23431 425 843 Air required (cfm)Air required (cfm)1153 1153 19 42 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-29 10:40:08Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Right-J® Worksheet 9/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 2 Bath 2 Exposed wall 24.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft135.8x1.0 ft6.0x7.0 5 Room area 135.8 ft²42.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 16.4516.45 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2120.21 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 84 68 216 138 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 108 108 317 158 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 136 136 135 199 42 42 42 61 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 136 24 688 0 42 0 0 0 6 c) AED excursion 98 -2 Envelope loss/gain 1618 945 42 60 12 a) Infiltration 184 51 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13)1802 1247 42 60 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 4 6 2 4 14 Subtotal 1806 1253 44 63 15 Duct loads 32%41%572 510 32%41%14 26 Total room load 2379 1764 58 89 Air required (cfm)Air required (cfm)109 87 3 4 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-29 10:40:08Right-Suite® Universal 2021 21.0.08 RSU29066 Page 3...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Right-J® Worksheet 9/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bath 2 Hall 2 Exposed wall 6.0 ft 0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft6.0x8.5 ft8.5x3.5 5 Room area 51.0 ft²29.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 16.4516.45 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2120.21 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 48 41 130 83 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 7 0 111 149 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 51 51 51 75 30 30 29 44 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 51 6 172 0 30 0 0 0 6 c) AED excursion 50 -1 Envelope loss/gain 464 357 29 42 12 a) Infiltration 105 29 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13)569 386 29 42 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 7 11 -29 -42 14 Subtotal 577 397 0 0 15 Duct loads 32%41%183 162 32%41%0 0 Total room load 759 559 0 0 Air required (cfm)Air required (cfm)35 27 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-29 10:40:08Right-Suite® Universal 2021 21.0.08 RSU29066 Page 4...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Right-J® Worksheet 9/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Bed 3 Bed 4 2 Exposed wall 25.5 ft 21.0 ft 3 Room height 8.0 heat/coolft 8.0 heat/coolft 4 Room dimensions ft153.3x1.0 ft157.0x1.0 5 Room area 153.3 ft²157.0 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 16.4516.45 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 64 64 202 129 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 96 80 253 162 104 88 279 178 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2120.21 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 16 2 262 340 16 2 262 340 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 108 92 291 186 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 16 0 262 353 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 153 153 152 224 157 157 156 230 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 153 26 731 0 157 21 602 0 6 c) AED excursion 173 82 Envelope loss/gain 1953 1439 1501 959 12 a) Infiltration 447 125 368 103 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 250 250 Subtotal (lines 6 to 13)2399 1814 1868 1312 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 7 11 2 4 14 Subtotal 2407 1825 1871 1316 15 Duct loads 32%41%763 743 32%41%593 536 Total room load 3169 2568 2464 1852 Air required (cfm)Air required (cfm)145 126 113 91 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-29 10:40:08Right-Suite® Universal 2021 21.0.08 RSU29066 Page 5...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Right-J® Worksheet 9/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Foyer GR Pantry 2 Exposed wall 34.5 ft 0 ft 3 Room height 9.5 heat/coolft 8.0 heat/coolft 4 Room dimensions ft426.3x1.0 ft5.5x2.5 5 Room area 426.3 ft²13.8 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 223 152 478 306 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 31 0 561 691 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 16.4516.45 40 0 676 661 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 0 0 0 0 0 0 0 0 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2120.21 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 105 105 307 152 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 426 426 423 624 14 14 14 20 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 426 35 989 0 14 0 0 0 6 c) AED excursion -117 -1 Envelope loss/gain 3435 2317 14 20 12 a) Infiltration 489 137 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 3 690 0 0 Appliances/other 900 0 Subtotal (lines 6 to 13)3923 4044 14 20 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 2 3 -14 -20 14 Subtotal 3926 4047 0 0 15 Duct loads 32%41%1244 1649 32%41%0 0 Total room load 5170 5695 0 0 Air required (cfm)Air required (cfm)237 280 0 0 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-29 10:40:08Right-Suite® Universal 2021 21.0.08 RSU29066 Page 6...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Right-J® Worksheet 9/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Kitchen DR Master Bath 2 Exposed wall 28.0 ft 19.5 ft 3 Room height 9.5 heat/coolft 8.0 heat/coolft 4 Room dimensions ft410.5x1.0 ft116.5x1.0 5 Room area 410.5 ft²116.5 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 0 0 0 0 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 16.4516.45 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 71 71 224 144 72 72 227 145 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 195 139 438 280 84 79 250 160 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2120.21 0 0 0 0 5 1 79 95 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 16 16 262 210 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 40 40 758 563 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 411 411 407 601 117 117 115 170 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 411 28 803 0 117 20 559 0 6 c) AED excursion 432 14 Envelope loss/gain 2892 2230 1230 584 12 a) Infiltration 582 163 342 95 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 2 460 0 0 Appliances/other 1700 0 Subtotal (lines 6 to 13)3475 4552 1572 680 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 12 18 5 7 14 Subtotal 3487 4570 1577 686 15 Duct loads 32%41%1105 1862 32%41%500 280 Total room load 4592 6432 2076 966 Air required (cfm)Air required (cfm)210 317 95 48 Calculations approved by ACCA to meet all requirements of Manual J 8th Ed. 2021-Sep-29 10:40:08Right-Suite® Universal 2021 21.0.08 RSU29066 Page 7...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Right-J® Worksheet 9/29/2021Date:House Chris BatemanBy:Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com 1 Room name Hers Master Bed 2 Exposed wall 4.0 ft 32.0 ft 3 Room height 8.0 heat/coolft 8.5 heat/coolft 4 Room dimensions ft4.0x5.0 ft15.5x13.5 5 Room area 20.0 ft²209.3 ft² Ty Construction U-value Or HTM Area (ft²)Load Area (ft²)Load number (Btuh/ft²-°F)(Btuh/ft²-°F)(Btuh/ft²)(Btuh/ft²)or perimeter (ft) (Btuh)or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nene 3.153.15 2.022.02 0 0 0 0 115 99 312 200 .GG Impact, Clear Low-e 0.620Impact, Clear Low-e 0.620 nene 17.9817.98 22.1522.15 0 0 0 0 16 0 280 346 .GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nene 16.8216.82 16.4516.45 0 0 0 0 0 0 0 0 .WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 sese 3.153.15 2.022.02 32 32 101 64 132 132 415 266 11 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 swsw 3.153.15 2.022.02 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 20.2120.21 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 21.8221.82 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 swsw 16.8216.82 13.4813.48 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.650Impact, Clear Low-e 0.650 swsw 18.8518.85 14.0214.02 0 0 0 0 0 0 0 0 WW Blk Wall, Stucco Ext 0.109Blk Wall, Stucco Ext 0.109 nwnw 3.153.15 2.022.02 0 0 0 0 26 26 80 51 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 GG Impact, Clear Low-e 0.580Impact, Clear Low-e 0.580 nwnw 16.8216.82 22.6422.64 0 0 0 0 0 0 0 0 PP Frm Wall, 1/2" Gyp B 0.101Frm Wall, 1/2" Gyp B 0.101 --2.942.94 1.461.46 0 0 0 0 0 0 0 0 CC Attic, Shngl Roof, R 0.034Attic, Shngl Roof, R 0.034 --0.990.99 1.461.46 20 20 20 29 209 209 207 306 FF On Grade Depth, Tile 0.989On Grade Depth, Tile 0.989 --28.6828.68 0.000.00 20 4 115 0 209 32 918 0 6 c) AED excursion -3 -52 Envelope loss/gain 235 91 2214 1117 12 a) Infiltration 70 20 596 166 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230230 0 0 0 0 Appliances/other 0 500 Subtotal (lines 6 to 13)305 110 2809 1783 Less external loadLess external load 0 0 0 0 Less transferLess transfer 0 0 0 0 RedistributionRedistribution 0 0 0 0 14 Subtotal 305 110 2809 1783 15 Duct loads 32%41%97 45 32%41%890 726 Total room load 402 155 3699 2510 Air required (cfm)Air required (cfm)18 8 169 124 2021-Sep-29 10:40:08 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Duct System Summary 9/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Key Largo Spec, NisAir Air ConditioningFor: 5604 Hickory Dr, Fort Pierce, FL 34982 CoolingHeating External static pressure in H2O0.70in H2O0.70 Pressure losses in H2O0in H2O0 Available static pressure in H2O0.70in H2O0.70 Supply / return available pressure 0.529 / 0.171 in H2O in H2O0.529 / 0.171 Lowest friction rate in/100ft0.213in/100ft0.213 Actual air flow cfm1153cfm1153 Total effective length (TEL) ft329 Supply Branch Detail Table Design Htg Clg Design Diam H x W Duct Actual Ftg.Eqv Name (Btuh)(cfm) (cfm)FR (in)(in)Matl Ln (ft)Ln (ft) Trunk 00VlFx0x0005389cBath st3120.025.5VlFx0x04.00.3633342759hBath 2 st195.012.2VlFx0x06.00.4931041312379hBed 2 st3120.029.1VlFx0x07.00.3551521743169hBed 3 st3120.024.4VlFx0x06.00.3661091352464hBed 4 st2100.032.6VlFx0x07.00.3991681422848cFoyer GR st2100.032.9VlFx0x07.00.3981681422848cFoyer GR-A st5200.048.2VlFx0x04.00.213922402hHers st2100.032.6VlFx0x07.00.3991901263216cKitchen DR-A st2100.032.4VlFx0x07.00.3991901263216cKitchen DR-B st195.013.1VlFx0x04.00.4895023843cLaundry st5195.050.2VlFx0x07.00.216571142076hMaster Bath st5195.050.1VlFx0x06.00.216741021850hMaster Bed st5195.045.0VlFx0x06.00.220741021850hMaster Bed-A Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk st5 Peak AVF 339 214 0.213 622 10.0 0x0 VinlFlx st2 st3 Peak AVF 351 294 0.355 795 9.0 0x0 VinlFlx st1 st1 Peak AVF 505 448 0.355 643 12.0 0x0 VinlFlx st2 Peak AVF 876 931 0.213 871 14.0 0x0 VinlFlx Bold/italic values have been manually overridden 2021-Sep-29 10:40:08 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 2 ...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW Return Branch Detail Table Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm)(cfm)(ft)FR (fpm)(in)(in)Opening (in) Matl Trunk rb5 0x 1350 109 78.8 0.217 506 7.0 x0 0 VlFx rt1 rb6 0x 1770 157 80.4 0.213 508 8.0 x0 0 VlFx rt1 rb7 0x 1310 104 66.1 0.259 489 7.0 x0 0 VlFx rt1 rb1 0x 7150 856 66.8 0.256 484 18.0 x0 0 VlFx rt1 rb8 0x 2250 157 0 0 0 0 x0 0 VlFx Return Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm)(cfm)FR (fpm)(in)(in)Material Trunk rt1 Peak AVF 1159 1227 0.213 694 18.0 0x0 VinlFlx 2021-Sep-29 10:40:08 Right-Suite® Universal 2021 21.0.08 RSU29066 Page 1 ...ts\Wrightsoft HVAC\5604 Hickory Dr PSL Prop.rup Calc = MJ8 Front Door faces: SW 1631Job:Manual S Compliance Report 9/29/2021Date:House Chris BatemanBy: Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL 32966 Phone: 772.800.8413 Email: vickilynne@aircalcs.com Project Information Key Largo Spec, NisAir Air ConditioningFor: 5604 Hickory Dr, Fort Pierce, FL 34982 Cooling Equipment Design Conditions °F76.9Entering coil DB:Btuh24371Sensible gain:°F90.4Outdoor design DB: °F64.0Entering coil WB:Btuh7223Latent gain:°F77.4Outdoor design WB: Btuh31594Total gain:°F75.0Indoor design DB: cfm1153Estimated airflow:%50Indoor RH: Manufacturer's Performance Data at Actual Design Conditions Split ACEquipment type: ML14XC1S036-230C**+CBA27UHE-036-230*++TDRModel:LennoxManufacturer: cfm1153Actual airflow: % of load99Btuh24220Sensible capacity: % of load144Btuh10380Latent capacity: %70SHR:% of load110Btuh34600Total capacity: Heating Equipment Design Conditions °F68.1Entering coil DB:Btuh26963Heat loss:°F41.0Outdoor design DB: °F70.0Indoor design DB: Manufacturer's Performance Data at Actual Design Conditions Elec stripEquipment type: Model:Manufacturer: cfm1153Actual airflow: °F50Temp. rise:% of load100kW7.9Output capacity: Meets all requirements of ACCA Manual S.