FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION
Florida Department of Business and Professional Regulation - Residential Performance Method
I
Project Name: ROBERT DOLLAR ADDITION Builder Name:
Street: 6703 ONECO WAY Permit Office:
City,State,Zip: FT. PIERCE, FL, Permit Number:
Owner: Jurisdiction:
_Deisign Location: FL,Fort Pierce County: St.Lucie(Florida Climate Zone 2)
1. New construction or existing Addition 9. Wall Types(242.7 sqft.) Insulation Area
2. Single family or multiple family Single-family a. Frame-Wood, Exterior R=13.0 242.67 ftZ
�umber
b. N/A R= ft2
3. of units,if multiple family 1 c.N/A R= ftZ
4. Number of Bedrooms(Bedrms In Addition) 0(1) d. N/A R= ftz
1 10.CeilingTypes 250.0 s Insulation Area
N0
5. Is this a worst case? yp ( sqft.)
a. Under Attic(Vented) R=19.0 250.00 ftZ
6. Conditioned floor area above grade(ftZ) 250 b.N/A R= ftZ
Conditioned floor area below grade(ftZ) 0 c.N/A R= ftZ
1 11. Ducts R ftZ
7. Windows(12.0 sqft.) Description Area a.Sup:Attic, Ret:Attic,AH:Main 6 25
a! U-Factor: Sgl, U=0.70 12.00 ftZ
SHGC: SHGC=0.35
b'. U-Factor: N/A ftZ 12.Cooling systems kBtu/hr Efficiency
SHGC: a.Central Unit 42.0 SEER:14.00
ci U-Factor: N/A ftZ
SHGC: 13. Heating systems kBtu/hr Efficiency
d. U-Factor: N/A ftZ a.Electric Strip Heat 34.0 COP:1.00
SHGC:
Area Weighted Average Overhang Depth: 2.000 ft.
Area Weighted Average SHGC: 0.350 14.Hot water systems-None required
a. Cap: N/A
8. Floor Types (250.0 sqft.) Insulation Area
bSlab-On-Grade Edge Insulation R=0.0 250.00 ftZ b. Conservation features EF:0.000
.N/A R= ftZ
.N/A R= ftZ 15.Credits CF,Pstat
Glass/Floor Area: 0.048 Total Proposed Modified Loads: 8.96 PASS
Total Baseline Loads: 9.05
i
i
I hereby certify that the plans and specifications covered by Review of the plans and 1TKE STa?,
this calculation are in compliance with the Florida Energy specifications covered by this
;.'
Code. calculation indicates compliance y'��,,, '�� _ .��`vc+
with the Florida Energy Code. � +++Rr ��" �.•,.• . « �
PREPAR BY: !-� Before construction is completed r .�
DATE: this building will be inspected for
compliance with Section 553.908
I hereby certify that this building, as designed, is in compliance Florida Statutes.
wit
h the Florida Energy Code. CpD WE
OWNER/AGE T: A , ,% 0 - BUILDING OFFICIAL:
DATE: oy i® DATE:
I
- Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as
certified factory-sealed in accordance with R403.3.2.1.
-CI ompliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an
envelope leakage test report with envelope leakage no greater than 7.00 ACH50(R402.4.1.2).
i
11/20/2018 9:36 AM EnergyGauge®USA Section R405.4.1 Compliant Software Page 1 of 4
FORM R4U0-2017 INPUT SUMMARY CHECKLIST REPORT
PROJECT
FTB'iuilding
le: ROBERT DOLLAR ADDITIO Bedrooms: 0 Address Type: Street Address
Type: User Conditioned Area: 250 Lot#
Owner Name: Total Stories: 1 Block/Subdivision:
#of Units: 1 Worst Case: No PlatBook:
Builder Name: Rotate Angle: 0 Street: 6703 ONECO WAY
Permit Office: Cross Ventilation: County: St. Lucie
` Jurisdiction: Whole House Fan: City,State,Zip: FT.PIERCE,
Family Type: Single-family FL,
New/Existing: Addition
Comment:
CLIMATE
Design Temp Int Design Temp Heating Design Daily Temp
Design Location TMY Site 97.5% 2.5% Winter Summer Degree Days Moisture Range
FL, Fort Pierce FL VERO_BEACH_MUNI 39 90 70 75 299 62 Low
I
BLOCKS
Number Name Area Volume
1 Block1 250 2000
SPACES
Number Name Area Volume Kitchen Occupants Bedrooms Infil ID Finished Cooled Heated
1 Main 250 2000 No 1 1 Yes Yes Yes
FLOORS
# Floor Type Space Perimeter R-Value Area Tile Wood Carpet
1 Slab-On-Grade Edge Insulatio Main 60 ft 0 250 ft2 _--- 0 0 1
I
ROOF
/ Roof Gable Roof Solar SA Emitt Emitt Deck Pitch
# Type Materials Area Area Color Absor. Tested Tested Insul. (deg)
1 Hip Composition shingles 271 ft2 0 ft2 Light 0.5 No 0.9 No 0 22.6
I
ATTIC
I # Type Ventilation Vent Ratio(1 in) Area RBS IRCC
1 Full attic Vented 150 250 ft2 N N
I
CEILING
# Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type
1 Under Attic(Vented) Main 19 Blown 250 ft2 0.11 Wood
I
11/20/2018 9:36 AM EnergyGauge®USA Section R405.4.1 Compliant Software Page 2 of 4
i
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
WALLS
Adjacent Space Cavity Width Height Sheathing Framing Solar Below
we Et In Ft In Area RA/ahle Eraction AhSor rwe%
1 S Exterior Frame-Wood Main 13 18 4 8 0 146.7 ft2 0 0.25 0.4 0
2 E Exterior Frame-Wood Main 13 12 0 8 0 96.0 ft2 0 0.25 0.4 0
DOORS
Y
# Ornt Door Type Space Storms U-Value Width Height Area
Ft In Ft In
1 S Insulated Main None .28 2 8 6 8 17.8 ft2
I
WINDOWS
Orientation shown is the entered, Proposed orientation.
Wall Overhang
# Ornt ID Frame Panes NFRC U-Factor SHGC Imp Area Depth Separation Int Shade Screening
1 E 2 Metal Single(Tinted) Yes 0.7 0.35 N 12.0 ft2 2 ft 0 in 1 ft 4 in Drapes/blinds None
I
INFILTRATION
I
# j Scope Method SLA CFM 50 ELA EgLA ACH ACH 50
1 Wholehouse Proposed ACH(50) .000356 233.3 12.81 24.09 .2578 7
i
HEATING SYSTEM
# System Type Subtype Efficiency Capacity Block Ducts
1 Electric Strip Heat/Supplemen None COP:1 34 kBtu/hr 1 sys#1
i
COOLING SYSTEM
# System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts
1 Central Unit/Supplemental for None SEER:14 42 kBtu/hr 1260 cfm 0.85 1 sys#1
I
SOLAR HOT WATER SYSTEM
FSEC Collector Storage
Cert # Company Name System Model# Collector Model# Area Volume FEF
ft2
I
DUCTS
---Supply--- ----Return— Air CFM 25 CFM25 HVAC#
Location R-Value Area Location Area Leakage Type Handler TOT OUT QN RLF Heat Cool
1 Attic 6 25 ft2 Attic 10 ft2 Default Leakage Main (Default) (Default) 1 1
i
11/20/2018 9:36 AM EnergyGauge®USA Section R405.4.1 Compliant Software Page 3 of 4
FORM R405-2017 INPUT SUMMARY CHECKLIST REPORT
TEMPERATURES
Pi ogramable Thermostat:Y Ceiling Fans:
Cool in an Feb Mar A r Ma ri
Jun rl
Jul ri
Aug
Se [ ]Oct Nov Dec
Heating lX�Jan Feb x Mar f Apr f May Jun Jul Au Sep [ ]Oct XNov Dec
'Ventin [ Jan Feb X Mar [X A r [ Ma Jun Jul Aug Se [X]Oct X Nov Dec
Thermostat Schedule: HERS 2006 Reference Hours
,,Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12
Cooling(WD) AM 78 78 78 78 78 78 78 78 80 80 80 80
PM 80 80 78 78 78 78 78 78 78 78 78 78
Cooling(WEH) AM 78 78 78 78 78 78 78 78 78 78 78 78
PM 78 78 78 78 78 78 78 78 78 78 78 78
Heating(WD) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
Heating(WEH) AM 66 66 66 66 66 68 68 68 68 68 68 68
PM 68 68 68 68 68 68 68 68 68 68 66 66
MASS
Mass Type Area Thickness Furniture Fraction Space
Default 8 Ibs/s .ft. 0 ftz Oft 0.3 Main
Name: Signature:�hftbr_
Rating Compant: Date:
I
I
1;1/20/2018 9:36 AM EnergyGauge®USA Section R405.4.1 Compliant Software Page 4 of 4
2017 -AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
TABLE 402.4.1.1
AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA
Project Name: ROBERT DOLLAR ADDITION Builder Name:
Street: 6703 ONECO WAY Permit Office:
City,State,Zip: FT. PIERCE, FL, Permit Number: Y
U
Owner: Jurisdiction: 2
Design Location: FL,Fort Pierce U
(COMPONENT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA
eneral A continuous air barrier shall be installed in the building envelope. Air-permeable insulation shall
The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material.
requirements Breaks or joints in the air barrier shall be sealed.
The air barrier in any dropped ceiling/soffit shall be aligned with The insulation in any dropped ceiling/soffit
Ceiling/attic the insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier.
Access openings,drop down stairs or knee wall doors to
unconditioned attic spaces shall be sealed.
Walls The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls
The junction of the top plate and the top of exterior walls shall be shall be insulated by completely filling the cavity
sealed. with a material having a thermal resistance of R-3
Knee walls shall be sealed. per inch minimum.
Exterior thermal envelope insulation for framed
walls shall be installed in substantial contact and
continuous alignment with the air barrier.
Windows,skylights The space between window/doorjambs and framing,and
and doors skylights and framing shall be sealed.
Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated.
Floors The air barrier shall be installed at any exposed edge of Floor framing cavity insulation shall be installed to
(including insulation. maintain permanent contact with the underside of
above-garage subfloor decking,or floor framing cavity insulation
and cantilevered shall be permitted to be in contact with the top side
floors) of sheathing,or continuous insulation installed on
the underside of floor framing and extends from the
bottom to the top of all perimeter floor framing
members.
Crawl space walls Exposed earth in unvented crawl spaces shall be covered with Where provided instead of floor insulation,insulation
a Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace
Shafts,penetrations Duct shafts, utility penetrations,and flue shafts opening to
exterior or unconditioned space shall be sealed.
Batts in narrow cavities shall be cut to fit,or narrow
Narrow cavities cavities shall be filled by insulation that on
installation readily conforms to the available cavity
spaces.
Garage separation Air sealing shall be provided between the garage and conditioned spat as.
Recessed lighting Recessed light fixtures installed in the building thermal envelope Recessed light fixtures installed in the building
shall be sealed to the drywall. thermal envelope shall be airtight and IC rated.
Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring
and plumbing in exterior walls,or insulation that on
installation readily conforms to available space shall
extend behind pjp4na and wiring,
Shower/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall
on exterior wall tubs shall separate them from the showers and tubs. be insulated.
Electrical/phone box or The air barrier shall be installed behind electrical or communication
I
xterior walls boxes or air-sealed boxes shall be installed.
VAC register boots HVAC register boots that penetrate building thermal envelope shall
be sealed to the sub-floor or drywall.
Concealed When required to be sealed,concealed fire sprinklers shall only be
sprinklers sealed in a manner that is recommended by the manufacturer.
Caulking or other adhesive sealants shall not be used to fill voids
between fire spr plil
a! In addition, inspection of log walls shall be in accordance with the provisions of ICC-400.
1I/20/2018 9:36 AM EnergyGaugeO USA FBC 6th Edition(2017)Compliant Software Page 1 of 1
2017 EPL DISPLAY CARD
ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD
ESTIMATED ENERGY PERFORMANCE INDEX* = 99
The lower the Energy Performance Index, the more efficient the home.
i
r
1. New home or, addition 1. Addition 12. Ducts, location&insulation level
a) Supply ducts R 6.0
2. Single-family or multiple-family 2. Single-family b) Return ducts R 6.0
c)AHU location Attic/Attic
3. No. of units(if multiple-family) 3. 1
4. Number of bedrooms 4. 0 13. Cooling system: Capacity 42.0
a) Split system SEER
5. Is this a worst case? (yes/no) 5. No b) Single package SEER
c) Ground/water source SEER/COP
6. Conditioned floor area (sq.ft.) 6. 250 d) Room unit/PTAC EER
e) Other 14.0
7.Windows,type and area
a) U-factor:(weighted average) 7a. 0.700
b) Solar Heat Gain Coefficient(SHGC) 7b. 0.350 14. Heating system: Capacity 34.0
c)Area 7c. 12.0 a) Split system heat pump HSPF
b) Single package heat pump HSPF
8. Skylights c) Electric resistance COP 1.0
a) U-factor:(weighted average) 8a. NA d) Gas furnace, natural gas AFUE
b)Solar Heat Gain Coefficient(SHGC) 8b. NA e) Gas furnace, LPG AFUE
f) Other
9. Floor type, insulation level:
a) Slab-on-grade(R-value) 9a. 0.0
b)Wood, raised (R-value) 9b. 15.Water heating system
c) Concrete, raised (R-value) 9c. a) Electric resistance EF
b)Gas fired, natural gas EF
10.Wall type and insulation: c) Gas fired, LPG EF
A. Exterior: d)Solar system with tank EF
1.Wood frame(Insulation R-value) 10A1. 13.0 e) Dedicated heat pump with tank EF
2. Masonry(Insulation R-value) 10A2. f) Heat recovery unit HeatRec%
B.Adjacent: g) Other
1. Wood frame (Insulation R-value) 10B1.
2. Masonry(Insulation R-value) 10132.
16. HVAC credits claimed (Performance Method)
11. Ceiling type and insulation level a) Ceiling fans Yes
a) Under attic 11a. 19.0 b) Cross ventilation No
b) Single assembly 11 b. c)Whole house fan No
c) Knee walls/skylight walls 11 c. d) Multizone cooling credit
d) Radiant barrier installed 11 d. No e) Multizone heating credit
f) Programmable thermostat Yes
I
*Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT.
I certify that this home has complied with the Florida Building Code, Energy Conservation,through the above energy
saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL
display card will be completed based on installed code compliant features.
Builder Signature: Date:
Address of New Home: 6703 ONECO WAY City/FL Zip: FT. PIERCE, FL
1 i1/20/2018 9:36:47 AM EnergyGauge®USA 6.0.02-FlaRes2017 FBC 6th Edition(2017)Compliant Software Page 1 of 1
I
Job:
-F - wrightsoft, Project Summary By:
Entire House y:
QUICK CALCS, INC.
317 ST.LUCIE LANE,FORT PIERCE,FL34946 Phone:772-466-6799 Email:QUICKCALCS@AOL.COM
i
Prooect Information
g For. ROBERT DOLLARADDITION
6703 ONECO WAY FT.PIERCE,FL
Notes:
® - •n' '.14ormation
Weather: Fort Pierce,FL,US
Winter Design Conditions Summer Design Conditions
Outside db 42 OF Outside db 90 OF
Inside db 70 OF Inside db 75 OF
Design TD 28 OF Design TD 15 OF
Daily range M
Relative Humidity 50 %
Moisture difference 61 grAb
Heating Summary Sensible Cooling Equipment Load Sizing
Structure 20835 Btuh Structure 21058 Btuh
Ducts 5393 Btuh Ducts 7477 Btuh
Central vent(0 cfm) 0 Btuh Central vent(0 cfm) 0 Btuh
(none) (none)
Humidification 0 Btuh Blower 0 Btuh
Piping 0 Btuh
Equipment load 26228 Btuh Use manufacturer's data n
Rate/swingg multipplier 0.95
Infiltration Equipmentsensibleload 27108 Btuh
Method Simplified Construction quality Avera Latent Cooling Equipment Load Sizing
ge
Fireplaces 0 Structure 2342 Btuh
Ducts 2193 Btuh
Central vent(0 cfm) 0 Btuh
Heatingg Coolingg (none)
Area(ftz) 1550 1550 Equipment latent load 4535 Btuh
Volume(it') 13950 13950
Airchangges/hour 0.38 0.20 Equipment Total Load(Sen+Lat) 31643 Btuh
Equiv AVF(cfrn) 88 47 Req.total capacity at 0.70 SHR 3.2 ton
Heating Equipment Summary Cooling Equipment Summary
Make Make Carrier
Trade Trade 14 SEER AC
Model Cond CA14NA0420000A0
AHRI ref Coil FB4CNP042L
AHRI ref 9194235
Efficiency 100 EFF Efficiency 11.5 EER, 14 SEER
Heating Input 6.4 kW Sensible cooling 27300 Btuh
Heating output 21953 Btuh Latentcooling 11700 Btuh
Temperature rise 50 OF Total cooling 39000 Btuh
Actual airflow 400 cfm Actual airflow 1300 cfm
Airflowfactor 0.015 cfm/Btuh Airflowfactor 0.046 cfm/Btuh
Static pressure 0.50 in H2O Static pressure 0.50 in H2O
Space thermostat Load sensible heat ratio 0.86
Calculations approved byACCAto meet all requirements of Manual J 8th Ed.
-r+— wrroghtsoft` 2018-Nov-2009:47:21
w,,.••o.. ,..., . w, Right-Sdte®Universal 2018 18.0.16 RSU08101 Page 1
CKUoaanentss\WrightsoftHVAC\DOLLAR,ROBERT.rup Calc=MJ8 Frorf Door faces:NE
i
® Duct stem Summary Job:
wrs���soft Date:
Entire douse By:
QUICK CALLS, INC.
317 ST.LUCIE LANE,FORT PIERCE,FL34946 Phone:772-466-6799 Email:QUICKCALCS@,AOL.COM
y • • •
For: ROBERT DOLLARADDITION
6703 ONECO WAY FT.PIERCE,FL
Heating Cooling
External static pressure 0.50 in H2O 0.50 in H2O
Pressure losses 0 in H2O 0 in H2O
Available static pressure 0.50 in H2O 0.50 in H2O
Supply/return available pressure 0.250/0.250 in H2O 0.250/0.250 in H2O
Lowest friction rate 0.080 in/100ft 0.080 in/100ft
Actual airflow 400 cfm 1300 cfiTi
Total effective length(TEL) 77 ft
Design Htg Clg Design Diam H x W Duct Actual Ftg.Egv
Name (Btuh) (Cfm) (cfm) FR (in) (in) Mat Ln(ft) Ln(ft) Trunk
EXISITNG HOUSE-E C 23803 327 1084 0.080 19.0 OX 0 MFx 0 0
NEWBEDROOM2 c 2366 36 108 0.080 8.0 Ox0 VIFx 6.4 70.0
NEWBEDROOM2-A c 2366 36 108 0.080 8.0 OXO VIFX 7.1 70.0
Table
Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct
Name Size(in) (cfm) (cfm) (ft) FR (fpm) (in) (in) Opening(in) Mat Trunk
rb1 Ox 0 400 1300 0 0 0 0 Ox 0 MFx
Boldlrtalic values have been manually overridden
wrightsoft, 2018-Nov-20 09:47:21
Right Suite®Universal2018 18.0.16 RSU08101 Page 1
kca ...CK\Doaments\WrightsoftHVAC\DOLLAR,ROBERT.rup Calc=MJ8 Frord Door toes:NE