Loading...
HomeMy WebLinkAboutCERIFICATE OF PRODUCT RATINGSV This combination qualifies for a Federal Energy Efficiency Tax Credit when placed in service between Feb 17, 2009 and Dec 31, 2016. WW, �, ��F. E - AHRI Certified Reference Number: 8864544 Date: 8/3/2017 Product: Split System: Air -Cooled Condensing Unit, Coil with Blower Outdoor Unit Model Number: YCG421321 Indoor Unit Model Number: AE60CX21+TXV Manufacturer: YORK BY JOHNSON CONTROLS Trade/Brand name: YORK f;ILE COP Region: All (AK, AL, AR, AZ, CA, CO, CT, DC, DE, FL, GA, HI, ID, IL, IA, IN, KS, KY, LA, MA, MD, ME, MI, MN, MO, MS, MT, NC, ND, NE, NH, NJ, NM, NV, NY, OH, OK, OR, PA, RI, SC, SD, TN, TX, UT, VA, VT, WA, WV, WI, WY, U.S. Territories) Region Note: Central air conditioners manufactured prior to January 1, 2015, are eligible to be installed in all regions until June 30, 2016. Beginning July 1, 2016, central air conditioners can only be installed in region(s) for which they meet the regional efficiency requirement. Series name: LX SERIES Manufacturer responsible for` the, ratilhg'of�this<sysi6ih combination is;YORK-BY JOHNSON CONTROLS Rated;as follows in accordance • with AHRI Standard`2101240-2008'•for Unitary Air -Conditioning and Air -Source Heat Pump Equipment and subject to verification of rating accuracy by AHRI-sponsored, independent, third party testing: Cooling .Capacity (Btuh): EER:Raiing•(.Gooling)' SEER`Rating jCooling): .. 42000 17.00 THESEPL PLANS Rating AND ALL PROPOSED WORC ARE SUBJECT TO ANY CORRECTIONS "REQUIRED BY FIELD iNSPECTORS THAT MAY BE NECESSARY IN ORDER TO COMPLY WITH ALL A,` pUCABILE COM& ' Ratings followed by an asterisk (') indicate a voluntary rerate of previously published data, unless accompanied with a WAS, which indicates an involunlary rararc �. l�annnrt AHRI does not endorse the product(s) listed on this Certificate and makes no representations, warranties or guarantees as to, and assumes no responsibility for, the product(s) listed on this Certificate. AHRI expressly disclaims all liability for damages of any kind arising out of the use or performance of the product(s), or the unauthorized alteration of data listed on this Certificate. Certified ratings are valid only for models and configurations listed In the directory at www.ahrldirectory.org. TERMS AND CONDITIONS confidential reference purposes. The contents of this Certificate This Certificate and its contents are proprietary p p ry products AHRI. This Certificate shall only be used for individual, personal and te ,. ficate may not, in whole or in part, be reproduced; copied; disseminad; v F entered into a computer database; or otherwise utilized, in any form or manner or by any means, except for the user's Individual, personal and confidential reference. AIR-CONDITIONING, HEATING. CERTIFICATE VERIFICATION &REFRIGERATION INSTITUTE The information for the model cited on this certificate can be verified at www.ahridirectory.org, click on "Verify Certificate" link and enter the AHRI Certified Reference Number and the date on which the certificate was issued, e make lite beaer^ which is listed above, and the Certificate No., which Is listed at bottom right. i _------------------------- ©2014 Air -Conditioning, Heating, and Refrigeration Institute ' CERTIFICATE NO.: 131462599457551918 SUBMITTAL a/►TA SHEET LX SERIES SPLIT SYSTEM AIR CONDITIONERS 17 SEER — R-410A —1 PHASE —1.5 THRU 5 NOMINAL TONS MODELS: YCG18 THRU 60 JOB NAME: LOCATION: PURCHASER: ORDER NO: ENGINEER: SUBMITTED TO: FOR: REF: APPROVAL: SUBMITTED BY: DATE: UNIT DESIGNATION: SCHEDULE NO. PRODUCT DATA Cooling Performance Total Capacity MBH Outdoor Design Temp °F Electrical Data Power Supply / / Compressor Ampacity AMPS Total Unit Ampacity AMPS Power Input Req KW Minimum Wire Size AWG Maximum Overcurrent Device ❑ Fuses ❑ Circuit Breaker Unit Weight Unit Weight LBS �I III C US �r\i10.wIR0.AMiT0 COM}'pyfRt Good Housekeeping Promises m� �+47GRAE VND1 50 AMERICAN QUALITY DESIGNED. ENGINEERED & ISO 9001 ASSEMBLED IN THE USA Certified Quality �® Management System r VOR Heating and Air Conditioning CONSTRUCTION: MODEL NO. DIMENSIONS - INCHES A0339-001 Unit Model Dimensions (Inches) Refrigerant Connection Service Valve Size A B C Liquid Vapor YCG18B21S 30 29-1/4 29-1/4 3/8 3/4 YCG24B21S 30 29-1/4 29-1/4 YCG30B21S 36-1/4 35-1/4 31-3/4 YCG36B21S 36-1/4 35-1/4 31-3/4 YCG42B21S a = 39-1/2 38 34-1/4 7/8 YGG4PB21S 39-1/2 38 34�1//4 YCG60B21S 42-3/4 38 34-1/4 7/8$ $ Adapter fitting must be field installed for the required 1-1/8" line set. All dimensions are in inches and are subject to change without notice. Overall height is from bottom of base pan to top of fan guard. Overall length and width include screw heads. 5186820-YSD-A-0216 a i� FEATURES • High System Efficiency - Optimized system designs p vide ENERGY STAR coil -only ratings in all tonnages. 1 geted furnace and air handler matches meeting Federal - Credit efficiencies are available for almost all tonnages e markets. • Easier Installation - Independent panels provide qu access for unit setup. Installation time is reduced by e� power and control wiring access. The factory installed flit drier and factory charge for a 15-Ft lineset means less tii spent brazing and charging the system. • Accessible Information - QR code on unit provides qu access to technical documents and warranty information. • Durable Finish - The coated steel wire fan guard, coal external fasteners, and pre-treated G90-equivalent gal, nized steel chassis components resist corrosion and r creep. Champagne colored powdercoat paint further proti external panels. • Quality Coils - The high efficiency microchannel alum) 1 coil is manufactured using an improved material system p viding reliable performance and smaller unit size. • Rugged Coil Protection - Coils are protected from me h� ical damage by a proven stamped steel coil guard design. • Protected Compressor - Compressors are protected lint nally by a high pressure relief valve and a temperature s sor, and .externally by the system high and low presst switches. The liquid line filter -drier is factory installed 10 p tect the compressor against moisture and debris. • Reliable Operation - ECM ball bearing fan motors rov superior performance in extreme temperatures. • Environmentally Friendly - CFC-free R-410A refliger delivers environmentally friendly performance with z ozone depletion. • Top Discharge - Warm air is blown up, away from tIJe str ture and any landscaping and allows compact location multi -unit applications. • Low Operating Sound Levels - Specific sound a d vib tion development tests provide a design sound pe Iorma of 74 dBA or lower. Swept -wing fan blades are featured units 2.5-Tons and higher. Compatible accessories for ther sound reduction are also available. WARRANTY SUMMARY* Standard 5-Years limited parts warranty. Standard 10-Years limited compressor warranty. Extended 10-Years limited parts warranty when product is registered online within 90 days of purchase for replacemel or closing for new home construction. 'Does not apply to R-22 models, 3-Phase models, or Internet sales. See Limited Warranty certificate in User's Information Manual for details. TYPICAL CLEARANCES The minimum clearances for a typical installation are shown below. See the Technical Guide for alternate installations. • 10" Clearance Coil Area • 48" Overhead Clearance • 18" Minimum Service Panel Access • 24" Minimum Unit to Unit Distance MATCHING AIR SIDE EQUIPMENT Model No. ❑ Submittal Form No. ❑ er- enQ FIELD INSTALLED ACCESSORIES ro- de ant ero uc- on ra- ce on fur- • Better Service Access - Diagonal base valves with open access for low -loss fittings, single panel access to the electri- cal controls, swing out control box for full corner a cess, and removable fan guard allow easy access for ul it mainte- nance. OD Unit Anti Short Cycle Kit (10 pk) (S1-2TD08700124BK) Standard Low Ambient Control Kit (S1-2LA06700424) Low Pressure Switch Kit (S1-2PS06700524) Outdoor Communicating Board Kit (S1-33102952310) Compressor Start Assist Kit (S1-2SA067 )* Compressor Crankcase Heater (S1-025 )' Indoor Blower -Off Delay Kit (S1-2FD06700224) Support Feet (S1-HPRKIT- )* Anchor Bracket Kit (S1-1HK0401) Indoor TXV Kit (S1-1TVM )* Wall Mount Kit (S1-ACB- )` Winter Cover Kit IS1-CCVRE )` Cold Weather Charging Tent (S1-CHGTENT01) Touch-up Paint (S1-5130153 )` Compressor Sound Blanket (S1-010076 )* * See price pages for accessory information. Refer to Technical Guide for detailed specifications on the unit and its accessories. • Agency Listed - Safety certified by CSA to UL 1995 / CSA Verify the actual ratings for each specific matchup in the online 22.2. Performance certified to ANSI/AHRI Stand rd 210/240 AHRI directory at www.ahridirectory.ora at the time of bid or in accordance with the Uni ary Small Equipmenticertification ale. It�is•'also.recommended to print the rating certificate, if program. needed, of the time of bid or sale. Subject to change without notice. Published in U.S.A. Copyright 0 2016 by Johnson Controls, Inc. All rights rk International Corp. 5005 York Drive Norman, OK 73069 5186820-YSD-A-0216 Supersedes: Nothing R-410A OUTDOOR SPLIT -SYSTEM AIR CONDITIONING MODELS: 13,14 & 17 SEER AMERICAN4K,xl YCD, YCE, YCG, YCS, YFD, YFE, TC3, TC4, TC7, /� �/ C US Iso 9001 CC7 TW4 TF3 TF4 TCD TCG RAC13L RAC14L o4iUALIT i , Certified Quality > > > e r > > > Management System RAC17L, RAW14L, RAC1317, RAC14F SERIES ASSEMBLED IN THE USA 1.5TO5TONS -1 &3PHASE LIST OF SECTIONS GENERAL..............................................1 SAFETY................................................1 UNIT INSTALLATION.....................................2 COIL METERING DEVICES................................6 EVACUATION...........................................8 SYSTEM CHARGE ...................................... 8 ELECTRICAL CONNECTIONS ............................ 10 INSTRUCTING THE OWNER ............................. 13 WIRING DIAGRAM ..................................... 14 START UP SHEET ...................................... 19 LIST OF FIGURES Typical Installation Clearances ..............................3 Outdoor Unit Control Box (Single Phase - Smaller Base) ........ 10 Alternative Installation Clearances ............................3 Outdoor Unit Control Box (Single Phase - Larger Base) ......... 10 Installation of Vapor Line...................................4 Outdoor Unit Control Box (Three Phase) ..................... 11 Underground Installation...................................5 Typical Field Wiring (Air Handler I Electrical Heat) (Single -Phase) . 11 Heat Protection.....................................:....5 Typical Field Wiring (Air Handler I Electrical Heat) (Three -Phase) .. 12 Recommended Distributor Adjustment ........................6 Thermostat Chart - PSC Air Handler with Piston Installation.........................................6 Single Stage Air Conditioner ............................... 12 TXV Installation..........................................7 Thermostat Chart - Single Stage PSC Furnace TXV Bulb and Equalizer line Installations ......................7 with Single Stage Air Conditioner ........................... 13 Proper Bulb Location......................................7 Wiring Diagram - Single Phase 13 & 14 Seer .................. 14 Vertical Temperature Bulb Orientation .........................8 Wiring Diagram - Single Phase 17 Seer ...................... 15 Outdoor Unit Swing Away Control Box .......................10 Wiring Diagram - Three Phase 13 Seer ...................... 16 Wiring Diagram - Three Phase 17 Seer ...................... 17 LIST OF TABLES Application Limitations.....................................2 R-410A Saturation Properties ............................... 9 SECTION 1: GENERAL These outdoor condensing units are designed to be connected to a matching UPG indoor coil. They are equipped with a filter -drier located in the liquid line. Units with quick -connect coupling connections are factory charged with refrigerant to be matched with the appropriate pre -charged line set, and UPG indoor coil. SECTION 1h SAFETY ��This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury. Understand and pay particular attention to the signal words DANGER, WARNING, or CAUTION. DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury. WARNING indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury. CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate iniury. It is also used to alert against unsafe practices and hazards involving only property dam- age. Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for assis- tance or for additional information, consult a qualified contractor, installer or service agency. This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes. A . R-410A systems operate at higher pressures than R-22 systems. Do not use R-22 service equipment or components on R-410A equip- ment. Service equipment Must Be Rated for R-410A. Johnson Controls Unitary Products 1183509-UIM-L-0317 1183509-UIM-L-0317 INSPECTION As soon as a unit is received, it should be inspected for possible dat age during transit. If damage is evident, the extent of the damal should be noted on the carrier's delivery receipt. A separate request t inspection by the carrier's agent should be made in writing. See Loc Distributor for more information. Requirements For Installing/Servicing R-410A Equipment • Gauge sets, hoses, refrigerant containers, and recovery syste must be designed to handle the POE type oils, and the high pressures of R-410A. • Manifold sets should be high side and low side with low sic retard. • All hoses must have a 700 psig service pressure rating. • Leak detectors should be designed to detect HFC refrigerant. • Recovery equipment (including refrigerant recovery contain It must be specifically designed to handle R-410A. • Do not use an R-22 TXV. LIMITATIONS The unit should be installed in accordance with all National, State Local Safety Codes and the limitations listed below: 1. Limitations for the indoor unit, coil, and appropriate accessc must also be observed. 2. The outdoor unit must not be installed with any duct work in to stream. The outdoor fan is the propeller type and is not desii to operate against any additional external static pressure. 3. The maximum and minimum conditions for operation mu observed to ensure a system that will give maximum perforrt with minimum service. TABLE 1: Application Limitations air SECTION III: UNIT INSTALLATION LOCATION Before starting the installation, select and check the suitability of the location for both the indoor and outdoor unit. Observe all limitations and clearance requirements. The outdoor unit must have sufficient clearance for air entrance to the condenser coil, air discharge, and service access. See Figures 1 & 2. For multiple unit installations, units must be spaced a minimum of 24" (61 cm) apart (coil face to coil face). If the unit is to be installed on a hot sun exposed roof or a paved ground area that is seasonally hot, the unit should be raised sufficiently above the roof or ground to avoid taking the accumulated layer of hot air into the outdoor unit. If the system is being installed during seasonally cold weather of 55°F or below, the preferred method is to weigh in the charge. For charging or checking the system charge at 55°F or below, refer to the "Optional Cold Weather Charging" procedures near the end of SECTION VI: SYSTEM CHARGE. There is an "Optional Cold Weather Charging" accessory kit to prevent the outdoor unit from taking in cold air below 55°F. The kit part number can be found in the list of accessory kits on the LIPGNET web site. be Provide adequate structural support for the unit. Ambient Air Air Temper ture Temperature on on Outdoor Coil Indoor Coil MODEL Min. DB Max. DB Min. WB Max. WB YCDffC3/RAC13L 55°F 115°F 57°F y2°F YCSNFE/YCE/TW4/TF4/TC4/ RAC14URAW14URAC14F/ 55°F 125°F 57°F YCG/TC7/CC7/RAC17L i2°F 4. The unit should not be operated at outdoor temperatures below 55°F without an approved low ambient operation accessory kit installed. 5. The maximum allowable line length for this product is 80 1feet. To install more than the maximum allowable line length, co suit the Piping Application Guide (P/N 24077). I ADD -ON REPLACEMENT/RETROFIT When this unit is being used as a replacement for an R-410A unit, it is required that the outdoor unit, indoor coil, and metering device all be replaced. The following steps should be performed in order to insure proper system operation and performance. Line -set change out is also recommended. 1. Change -out of the indoor coil to an approved R-410A coil/ con- densing unit combination with the appropriate metering device. 2. Change -out of the line -set when replacing an R-22 unit with an R410-A unit is highly recommended to reduce cross -contamina- tion of oils and refrigerants. 3. If change -out of the line set is not practical, then the following pre- cautions should be taken. • Inspect the line set for kinks, sharp bends, or other restrictions, and for corrosion. • Determine if there are any low spots which might be serving as oil traps. • Flush the line set with a commercially available flush kit to remove as much of the existing oil and contaminants as possible. • Install a suction line filter -drier to trap any remaining contami- nants, and remove after 50 hours of operation. 4. If the outdoor unit is being replaced due to a compressor burnout, then installation of a 100% activated alumina suction -line filter drier in the suction -line is required, in addition to the factory installed liquid -line drier. Operate the system for 10 hours. Monitor the suction drier pressure drop. If the pressure drop exceeds 3 psig, replace both the suction -line and liquid -line driers. After a total of 10 hours run time where the suction -line pressure drop has not exceeded 3 psig, replace the liquid line drier, and remove the suction -line drier. Never leave a suction -line drier in the system longer than 50 hours of run time. 1183509-U IM-L-0317 A CAUTION: Special care must be taken to avoid recirculation of discharge air through condenser coil. 48" OVERHEAD CLEARANCE y NEC CLASS 1 WIRING WEATHERPROOF Q °o THERMOSTAT DISCONNECT SWITCH NEC CLASS 2 WIRING NOTE: Ensure a minimum of TO FURNACE OR 24" clearance between AIR HANDLER any two units. TERMINAL BLOCK NEC CLASS 2 WIRING 10" CLEARANCE AROUND PERIMETER (6" clearance permissible on one side only, see Alternative Installation Clearances.) y, CONTROL ACCESS SEAL OPENINGS PANEL Use permagum or equivalent. NOTE: All outdoor wiring MINIMUM 18" SERVICE ACCESS CLEARANCE must be weatherproof. Maintain minimum clearance on one.side of access panel. FIGURE 1: Typical Installation Clearances MINIMUM CLEARANCE BETWEEN UNITS WALL S❑[:I E:IEI❑❑ I:1❑ 1:11:1 ITWn�[:I F-Ia ❑EI NOTE: Ensure adequate wall support. 3 BRACES —' Use for wall mount with center brace under center of compressor. Use in deep snow areas with fifth pump -up under center of compressor. AMW.0o2 FENCE 0 24 24" 24" NOTE: SERVICE SERVICE SERVICE Clearance between two units may be reduced to 18" minimum provided t the service access clearance is increased to 24" minimum, and the 18" 18^ clearance on each remaining side UNIT- ( UNIT- is maintained at 18" minimum. TO -UNIT TO -UNIT 18 18" 0 4 00, -1 18" 18" 18" NOTE: MINIMUM CLEARANCE FROM WALL Clearance to one side of the � unit may be reduced to 6" provided ❑� ❑� �❑ ❑❑ ❑❑ ❑❑ ❑❑ ❑D EI] the clearance to each remaining side is increased to 12" minimum, the 6" s" service access is increased to 24" minimum, and the clearances between WAL 24" any two units is maintained at 24" SERVICE 12^ minimum. 24 AND UNIT - SERVICE TO -UNIT 1110 4 100 12" 12" CAUTION: Special care must be taken to avoid recirculation of discharge air through condenser coil. FENC FIGURE 2: Alternative Installation Clearances a Johnson Controls Unitary Products 3 1183509-UIM-L-0317 GROUND INSTALLATION The unit should be installed on a solid base that is 2" (5.1 cm) above grade and will not shift or settle, causing strain on the refrigerant lines and possible leaks. Maintain the clearances shown in Figures 1 & 2 and install the unit in a level position. The base pad should not come in con- tact with the foundation or side of the structure because sound may f�e transmitted to the residence. The length of the refrigerant tubing between the outdoor unit and indoor coil should be as short as possible to avoid capacity and efficienlcy losses. Excessive spacing of the outdoor unit from the home can result in the refrigerant lines being restricted by trampling or being punctu�ed by lawn mowers. Locate the outdoor unit away from bedroom windows or other rooms where sound might be objectionable. Adverse effects of snow or sleet accumulating on the outdoor coil an be eliminated by placing the outdoor unit where -the prevailing wind does not blow across the unit. Trees, shrubs, corners of buildings, and fences standing off from the coil can reduce capacity loss due to i ind chill effect. Provide ample clearance from shrubs to allow adequate air to Lass across the outdoor coil without leaves or branches being pulled into the coil. ROOF INSTALLATION When installing units on a roof, the structure must be capable of sup- porting the total weight of the unit, including a pad, lintels, rails or any components used to minimize the transmission of sound or vibIration into the conditioned space. WALL MOUNT INSTALLATION Care must be taken to mount the outdoor unit on a solid base Ithat is sloped to shed water, secure from settlement, and is isolated frm the structural foundation or walls to prevent sound and vibration transmis- sion into the living space. On occasion, site conditions may require direct wall mounted brackets to be used to locate and support the outdoor unit. In these applications, care must be taken to address unit base pan support, structural integ- rity, safe access and serviceability, as well as the possible sond and vibration transmission into the structure. These applications are best served by a properly engineered solution. LIQUID LINE FILTER -DRIER The air conditioning unit's filter/dryer is located inside the unit on the liq- uid line between the outdoor coil and the liquid valve inside thg unit. _ A� Failure to do so or using a substitute drier or a granular type may result in damage to the equipment. Filter -Drier Source 1 Part No. I Apply with Models S1-401021 All PIPING CONNECTIONS The outdoor condensing unit must be connected to the indoor evapora- tor coil using field supplied refrigerant grade (ACR) copper t✓Jbing that is internally clean and dry. Units should be installed only wit the tubing sizes for approved system combinations as specified in i abular data sheet. The charge given is applicable for total tubing lengths up to 15 feet (4.6 m). See Piping Application Guide (P/N 24077)Ifor installing tubing of longer lengths and elevation differences. using a larger tnan spectnec tine size coutc result to oil return prop- lems. Using too small a line will result in loss of capacity and other problems caused by insufficient refrigerant flow. Slope horizontal vapor lines at least 1" (2.5 cm) every 20 feet (6.1 m) toward the out- door unit to facilitate proper oil return. If more than the 80 foot line length is necessary, facilitate proper refrigerant velocity with adjusted line diameter in accordance with the Piping Application Guide (P/N 24077). . .su This system uses R-410A refrigerant which operates at higher pres- sures than R-22. No other refrigerant may be used in this system. Gauge sets, hoses, refrigerant containers, and recovery system must be designed to handle R-410A. If you are unsure, consult the equip- ment manufacturer Never install a suction -line filter drier in the liquid line of an R-410A system. Failure to follow this warning can cause a fire, injury or death. PRECAUTIONS DURING LINE INSTALLATION 1. Install the lines with as few bends as possible. Care must be taken not to damage the couplings or kink the tubing. Use clean hard drawn copper tubing where no appreciable amount of bending around obstruction is necessary. If soft copper must be used, care must be taken to avoid sharp bends which may cause a restriction. 2. The lines should be installed so that they will not obstruct service access to the coil, air handling system, or filter. 3. Care must also be taken to isolate the refrigerant lines to minimize noise transmission from the equipment to the structure. 4. The vapor line must be insulated with a minimum of 1/2" foam rub- ber insulation (Armaflex or equivalent). Liquid lines that will be exposed to direct sunlight, high temperatures, or excessive humid- ity must also be insulated. 5. Tape and suspend the refrigerant lines as shown. DO NOT allow tube metal -to -metal contact. See Figure 3. 6. Use PVC piping as a conduit for all underground installations as shown in Figure 4. Buried lines should be kept as short as possible to minimize the build up of liquid refrigerant in the vapor line during long periods of shutdown. Fit;uKt 3: instaiiation or vapor Line 7. Pack fiberglass insulation and a sealing material such as perma- gum around refrigerant lines where they penetrate a wall to reduce vibration and to retain some flexibility. 8. For systems with total line length exceeding 75 feet (22.86 m), see Piping Application Guide (P/N 24077) for vapor and liquid line siz- ing, calibration of liquid line pressure loss or gain, determination of vapor line velocity, elevation limitations, TXV connections, system charging or traps. I 1183509-UIM-L-0317 TO INDOOR COIL TO OUTDOOR UNIT LIQUID LINE INSULATED *----VAPOR LINE CAP PVC CONDUIT FIGURE 4: Underground Installation PRECAUTIONS DURING BRAZING OF LINES All outdoor unit and evaporator coil connections are copper -to -copper and should be brazed with a phosphorous -copper alloy material such as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units have reusable service valves on both the liquid and vapor connections. The total system refrigerant charge is retained within the outdoor unit during shipping and installation. The reusable service valves are pro- vided to evacuate and charge per this instruction. Serious service problems can be avoided by taking adequate precau- tions to assure an internally clean and dry system. being brazed, because the temperature required is high enough to cause oxidation of the copper unless an inert atmosphere is provided. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing. Only a small flow is necessary to displace air and prevent oxidation. PRECAUTIONS DURING BRAZING SERVICE VALVE Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Figure 5. Also, protect all painted surfaces, insulation, and plastic base during brazing. After braz- ing, cool joint with wet rag. i ms is nor a nacKseaung vanre. me service access port nas a varoe core. Opening or closing valve does not close service access port. If the valve stem is backed out past the chamfered retaining wall, the O-ring can be damaged causing leakage or system pressure could force the valve stem out of the valve body possibly causing personal injury. Valve can be opened by removing the service valve cap and fully insert- ing a hex wrench into the stem and backing out counter -clockwise until valve stem just touches the chamfered retaining wall. Connect the refrigerant lines using the following procedure: 1. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit. Connect low pres- sure nitrogen to the liquid line service port. 2. Braze the liquid line to the liquid valve at the outdoor unit. Be sure to wrap the valve body with a wet rag. Allow the nitrogen to con- tinue flowing. 3. Carefully remove the plugs from the indoor coil liquid and vapor connections at the indoor coil. j WET RAGS (Wrap wet rags around service valve or refrigerant lines prior to brazing). M23"o1 FIGURE 5: Heat Protection Do not install any coil in a furnace which is to be operated during the heating season without attaching the refrigerant lines to the coil. The coil is under pressure which must be. released to prevent excessive pressure build-up and possible coil damage. 4. Braze the liquid line to the indoor coil liquid connection. Nitrogen should be flowing through the indoor coil. 5. Slide the grommet away from the vapor connection at the indoor coil. Braze the vapor line to the evaporator vapor connection. After the connection has cooled, slide the grommet back into original position. 6. Protect the vapor valve with a wet rag and braze the vapor line connection to the outdoor unit. The nitrogen flow should be exiting the system from the vapor service port connection. After this con- nection has cooled, remove the nitrogen source from the liquid fit- ting service port. 7. Replace the Schrader core in the liquid and vapor valves. 8. Go to SECTION IV for TXV installation. 9. Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight. DO NOT OVER - TIGHTEN (between 40 and 60 inch - lbs. maximum). Line set and indoor coil can be pressurized to 250 psig with dry nitro- gen and leak tested with a bubble type leak detector. Then release the nitrogen charge. Do not use the system refrigerant in the outdoor unit to purge or leak test. 10. Evacuate the vapor line, indoor coil, and liquid line to 500 microns or less. 11. Replace cap on service ports. Do not remove the flare caps from the service ports except when necessary for servicing the system. Do not connect manifold gauges unless trouble is suspected. Approx- imately 314 ounce of refrigerant will be lost each time a standard man- ifold gauge is connected. Johnson Controls Unitary Products 5 1183509-UIM-L-0317 12. Release the refrigerant charge into the system. Open both the liq- uid and vapor valves by removing the plunger cap and with an allen wrench back out counter -clockwise until valve stem just touches the chamfered retaining wall. If the service valve is a ball valve, use a Crescent wrench to turn valve stem one -quarter turn counterclockwise to open. Do not overturn or the valve stem may break or become damaged. See "PRECAUTIONS DURING BRAZING SERVICE VALVE". 13. Replace plunger cap finger tight, then tighten an additional 1r12 turn (1/2 hex flat). Cap must be replaced to prevent leaks. ivever attempt to repair any orazea connections wnue me system Is under pressure. Personal injury could result. See "System Charge" section for checking and recording system charge. SECTION IV: COIL METERING DEVICES A piston or a TXV is to be installed in the field. There is an instal ation manual that comes with the TXV kit. It is recommended to install the piston or TXV kit prior to installation of coil and brazing of line sett Until brazing is completed and cooled, the TXV sensing bulb must not be installed. The outdoor technical guide for outdoor units should be consul ed for required piston or TXV on the indoor coil. The piston and the Sc rader core are supplied with the outdoor unit. When the piston is used i�stead of the TXV, the Schrader core is installed in the suction line equalizer connection port and is capped with the supplied plastic cap. The Schrader core must not be installed if the TXV is installed, bec i se the TXV equalizer line attaches to the equalizer connection port. A COIL UNDER PRESSURE. Verify that pressure has been released by depressing Schrader valve core. The coil requires a metering device to be added. See outdoor unit documentation for correct TXV or piston to t1, used. To prevent moisture and contaminates from entering the system, the coil should not be open to atmosphere for extended periodsof time. If the coil cannot be brazed into the refrigeration system dunpg a rou- tine installation period, the ends should be temporarily closed or plugged. For a short term delay, use masking tape over the ends of the copper tubing to close the tube from the air. For a lo�tger term delay, use plugs or caps. There is no need to purge the coil if this pro- cedure is followed. PISTON INSTALLATION Failure to install Schrader Valve Core in the vapor line eq(Jalizer con- nection port for piston applications could result in total refrigerant loss of the system! Install Schrader Valve Core and as follows: 1. After holding charge is completely discharged, remove black plas- tic cap from equalizer connection port on the vertical part of the vapor line. 2. Distributor position must be adjusted to allow the preformed liquid line assembly to properly line up with the hole in the tubing access panel. Raise the distributor body approximately 2" toward the top of the coil or what would be the top of the coil if coil was in the upflow position. See Figure 6. Adjust as necessary. 3. Install Schrader valve core supplied with the outdoor unit into the equalizer fitting connection port using a valve core tool. 4. Loosen and remove the liquid line connection nut and the sealing disc from the distributor assembly. Note that the fitting has ri h hand threads. 5. Slide the nut over the liquid line to be installed, and discard the seal disc. 6. Install required size piston into the distributor. Refer to supplied Tabular Data Sheet for specific piston size and indoor coil match up. 7. Verify that the Teflon washer is still in place in the distributor open- ing. See Figure 7. FIGURE 6: Recommended Distributor Adjustment LIQUID LINE SWIVEL COUPLING (This fitting is a right-handed thread. Turn counter -clockwise to remove.) PISTON o� TEFLON WASHER DISTRIBUTOR noaosmi FIGURE 7: Piston Installation 8. After piston is installed, install the liquid line to the top of the pis- ton/distributor assembly. Hand tighten, and turn an additional 1/4 turn to seal. Do not over tightenDo not over tighten fitting 9. Replace black plastic cap on unused equalizer fitting connection port. 10. After line set is installed, leak test the system. 1183509-UIM-L-0317 THERMOSTATIC EXPANSION VALVE (TXV) 6. Install the TXV equalizer line onto the vapor line by hand tightening INSTALLATION the 1/4" SAE coupling nut to the equalizer fitting, and apply an addi- tional 1/3 turn to seal. See Figures 9, 10 & 11. Outdoor unit model numbers ending with an 'H" have a factory In all cases, mount the TXV temperature sensing bulb after vapor line installed hard start kit which is required when a TXV is installed. Out- is brazed and sufficiently cooled. door unit model numbers with no H" ending do not require a hard start kit unless local regulations dictate it. Failure to use suction line split grommet may result in TXV failure. The following are basic steps for installation. For detailed instructions, refer to the Installation Instructions accompanying the TXV kit. Install TXV kit as follows: Refer to the Technical Guide for the unit to determine the proper TXV kit to be used on this product. 1. Relieve the holding charge by depressing Schrader core on the suction manifold stub out. 2. After holding charge is completely discharged, loosen and remove the Schrader core. 3. Place a backup wrench on distributor, loosen and remove brass distributor nut. Retain brass nut for use on liquid line. Keep Teflon washer in place and discard clear disk. 4. Install the thermal expansion valve to the distributor assembly with supplied fittings. Ensure Teflon washer is seated in distributor. Hand tighten and turn an additional 1/4 turn to seal. Do not over- tiahten fittings. See Figure 8. A Do not over -torque. Do not use slip joint pliers. This will distort the aluminum distributor and the brass fitting (potentially causing leaks). 5. Slide the nut removed in step 3 over the supplied liquid line. Place supplied Teflon washer from TXV kit in place on TXV, and install liq- uid line to the top of the thermal expansion valve. Adjust assembly so liquid line aligns with hole in access panel. See Figure 9. Hand tighten the liquid line, and apply an additional 1/4 turn to seal. LIQUID LINE / TXV COUPLING TEFLON WASHER 1.4 TXV TXV / DISTRIBUTOR COUPLING ®f—TEFLON WASHER DISTRIBUTOR AM - FIGURE 8: TXV Installation p P IT Schrader valve core MUST NOT be installed with TXV installation. Poor system performance or system failure could result. 7. Pass the temperature sensing bulb tube for the TXV through the tube opening in the split grommet of the access panel. 8. Install the TXV bulb to the vapor line near the cabinet, using the bulb clamp(s) furnished with the TXV assembly. Ensure the bulb is making maximum contact. See Figures 9, 10 & 11, and accomplish the following: a. If possible, install the temperature bulb on a horizontal run of the vapor line. Ensure that the bulb is installed at a 10 o'clock or 2 o'clock position. See Figure 10. b. If bulb installation is made on a vertical run, ensure that the bulb is a minimum of 8 inches (20.3 cm) away from elbow coming out of the coil. Position the bulb with the tail of the bulb at the top, so that the bulb acts as a reservoir. See Fig- ure 11. c. Insulate the bulb using thermal insulation provided to protect it from the effect of the surrounding ambient temperature. Cover completely to insulate. FIGURE 9: TXV Bulb and Equalizer line Installations 9. After line set is installed, leak test the system. Bulb at TXV SENSING BULB 10 o'clock (Pass through split hole position. in grommet.) TXV BULB SCREW (Cover completely with Insulation.) �/ CLAMP- UT CLAMP VAPOR LINE ~ A Bulb at 2 o'clock NUT position. I VAPOR LINE SCREW__W. L A OF LINE SET A0287-002 FIGURE 10: Proper Bulb Location Johnson Controls Unitary Products 7 1183509-UIM-L-0317 VAPOR LINE OF LINE SEI NOTE: Ensure bulb is on opposite side of tubing bend plane. TAIL END UP TXV TEMPERATURE BULB CLAMP 16" (40.6 cm) (Ensure bulb is at least 16" from any bend. I FIGURE 11: Vertical Temperature Bulb Orientation SECTION V: EVACUATION It will be necessary to evacuate the system to 500 microns or less. If a leak is suspected, leak test with dry nitrogen to locate the leak. I�Repair the leak and test again. To verify that the system has no leaks, simply close the valve to the vacuum pump suction to isolate the pump and hold the syste1in under vacuum. Watch the micron gauge for a few minutes. If themicron gauge indicates a steady and continuous rise, it's an indicatof a leak. If the gauge shows a rise, then levels off after a few minutes and remains fairly constant, it's an indication that the system is leak ree but still contains moisture and may require further evacuation if the reading is above 500 microns. SECTION VI: SYSTEM CHARGE To ensure that your unit performs at the published levels, it is important that the indoor airflow is determined and refrigerant charge added accordingly. MEASURE INDOOR AIR FLOW To determine rated air flow for a specific match, consult the teThnical lit- erature at www.upgnet.com. When attempting to match this air flow, select the lowest possible speed tap, measure the actual flow, and adjust as necessary. To measure actual air flow, it is not an acceptable method to just check the jumper pin setting tables and is to assume 0.5" water column total external static pressure. To determine indoor air flow, first measure the static pres ure with a manometer between the filter and blower. On a single -piece air handler, take a second reading after the coil. On a furnace or modular air han- dler, take the second reading after the heat exchanger butt before the indoor coil. Add the negative return static to the positive supply static to determine the system total static pressure. Treat the negative return static as a positive pressure (even though it is a negative reading). If there is static pressure on the blower (i.e. -.10) return, add i to a supply static (.40) which equals a (.50) total system static pressu ,e. Compare this value to the table for the indoor unit's static pressure v$. CFM or to a curve chart. SYSTEM CHARGING For cold weather charging of the system at temperatures of 55°F or below, refer to the "Optional Cold Weather Charging" procedures near the end of SECTION V1. SYSTEM CHARGE. R-410A refrigerant cylinders are rose colored. Always charge the system slowly with liquid R-410 refrigerant. The factory charge in the outdoor unit includes enough charge for the unit, a 15 ft. (4.6 m) line set, and the smallest indoor coil match -up. Some indoor coil matches may require additional charge. See tabular data sheet provided in unit literature packet for charge requirements. fi t- Do not leave the system open to the atmosphere. The "TOTAL SYSTEM CHARGE" must be permanently stamped on the unit data plate. TOTAL SYSTEM CHARGE is determined as follows: 1. Determine the Base Charge shipped in the outdoor unit from the Tabular Data Sheet included with the outdoor unit. 2. Determine the charge adder for the matched indoor unit from the Tabular Data Sheet included with the outdoor unit. 3. If the lineset length is greater than 15 feet (4.6 m), calculate the charge adder for actual lineset length using the Tabular Data Sheet included with the outdoor unit. 4. Once the charge adders for matched indoor unit and for lineset have been weighed in, verify the system operation against the temperatures and pressures in the Charging Chart for the outdoor unit. Locate Charging Charts on the outdoor unit and also in the Service Application Data on www.upgnet.com. Follow the Subcool or the Superheat charging procedure in the section below accord- ing to the type of indoor metering device in the system, and 'allow ten minutes after each charge adjustment for the system operation to stabilize. Record the charge adjustment made to match the Charging Chart. 5. Verify that TOTAL SYSTEM CHARGE = Base Charge (as shipped) + charge adder for matched indoor unit + charge adder for actual lineset length + charge adjustments to match Charging Chart. 6. Permanently stamp the unit data plate with the TOTAL SYSTEM CHARGE as defined above. This method is to be used whenever additional refrigerant is required for the system charge. k a� o"" j 77 DO NOT attempt to pump Total System Charge" into outdoor unit for maintenance or service. This may cause damage to the compressor and/or other components. Recover and weigh "System Charge" into an appropriate recovery cylinder for any instances requiring evacua- tion. psi--•r>Te °"h .S J O7 TT . It is recommended to not attempt to pump more than the 'Factory Charge" and an additional 15 foot line charge into a tube and fin out- door unit for maintenance or service. This can cause damage to the compressor and/or other components. AL Refrigerant charging should only be carried out by a qualed air con- ditioning contractor. nson 1183509-U I M-L-0317 A Condenser subcooling is obtained by calculating the difference of the saturated refrigerant temperature of the pressure measured at the liquid base valve and the liquid tube temperature as measured at the liquid Compressor damage will occur if system is improperly charged. On base valve. new system installations, charge system per tabular data sheet for the matched coil and follow guidelines in this instruction. Subcooling Temp. (TC) = Saturated Temp. (TS) — Liquid Temp. (T). If a calibrated charging cylinder or accurate weighing device is avail- able, add refrigerant accordingly. Otherwise, model -specific charging charts are provided on the access panel of the unit. IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS- CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR, SUBCOOLING CHARGING METHOD - TXV INDOOR SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS The outdoor unit comes equipped with subcooling charts optimized for UNIT. that particular unit. Please follow the instructions on the unit. If those instructions are not readily available, follow the instructions below. 1. Set the system running in cooling mode by setting the thermostat at least 6°F below the room temperature and operate system for at least 10 —15 minutes. 2. Refer to the technical guide for the recommended indoor airflow and verify it is correct (it should be 350- 400 SCFM per ton). 3. Measure and record the indoor wet bulb (WB) and the outdoor ambient dry bulb (DB) temperature. 4. Using the charging chart located on the unit, find the intersection of the indoor wet bulb and the outdoor dry bulb. This is the recom- mended liquid pressure (and subcooling value). 5. Measure and record the pressure at the liquid valve pressure port and compare to the value obtained in step 4. 6. Add charge if the measured liquid pressure is lower than the rec- ommended value. Remove I recover charge if the measured liquid pressure is above the recommended value. Example: The liquid pressure listed at the intersection of the indoor WB and the outdoor DB 320 psig. Pressure at the liquid valve is 305 psig. It would be necessary to add refrigerant to increase the liquid pressure to 320 psig. TABLE 2: R-410A Saturation Properties SUPERHEAT CHARGING METHOD - PISTON INDOOR 1. Set the system running in cooling mode by setting the thermostat at least 6°F below the room temperature and operate system for at least 10 —15 minutes. 2. Refer to the technical guide for the recommended airflow and ver- ify indoor airflow (it should be about 350-450 SCFM per ton). 3. Measure and record the outdoor ambient (DB) temperature and the suction pressure at the suction service valve. 4. Using the charging chart located on the unit, find the intersection of the outdoor ambient dry bulb and the suction pressure obtained in step 3. This is the recommended suction tube temperature at the service valve. 5. Measure and record the suction tube temperature at the service valve and compare to the recommended temperature obtained in step 4. 6. Add charge if the measured suction temperature in step 5 is above the recommended value. Remove I recover refrigerant if the mea- sured suction temperature is below the recommended value. Example: The suction tube temperature listed on the table at the intersection of the outdoor DB and the suction pressure is 63°F. Temperature of the suction tube at the service valve is 68°F. It would be necessary to add refrigerant to drop the suction tube temperature to 63°F. TEMP. °F PRESSURE PSIG TEMP. °F PRESSURE PSIG TEMP . °F PRESSURE PSIG TEMP. °F PRESSURE PSIG TEMP. ° F PRESSURE PSIG 45 130 60 170 75 217 90 274 105 341 46 132 61 173 76 221 91 278 106 345 47 135 62 176 77 224 92 282 107 350 48 137 63 179 78 228 93 287 108 355 49 140 64 182 79 232 1 94 291 109 360 50 142 65 185 80 235 95 295 110 365 51 145 66 188 81 239 96 299 ill 370 52 147 67 191 82 243 97 304 112 375 53 150 68 194 83 247 98 308 113 380 54 153 69 197 84 250 99 313 114 385 55 156 70 201 85 254 1 100 317 115 391 56 158 71 204 86 258 101 322 116 396 57 161 72 207 87 262 102 326. 117 401 58 164 73 1 211 88 266 103 331 118 407 59 167 1 74 1 214 89 270 104 336 119 412 OPTIONAL COLD WEATHER CHARGING For better airflow, the size of the charging tent must be at least 70"x70"x70° and must have some adjustable flaps or windows to con- trol the temperature inside the charging tent. The charging tent must not have a floor or floor covering. Be sure to follow the "System Charge"procedures from Section VI of this Installation Manual. 1. Assemble the charging tent. 2. Slide charging tent over top of condenser unit. 3. Position the door zipper over the lineset so charging tent sits evenly on ground. 4. Make sure distance around condenser inside of charging tent is even for airflow. 5. Stake down the edges of the charging tent cover to prevent the unit fan from blowing the charging tent away. 6. Start condenser. Johnson Controls Unitary Products 9 1183509-U IM-L-0317 7. 8. 9. 10. 11. 12. For better temperature measurement inside the charging tent, a thermocouple to monitor temperature readings. Locate the t mocouple monitor approximately 8-10 inches away from the guard and 2/3 the way above the bottom of the coil on the oppc side from the control box. Based on outdoor ambient temperature, begin adjusting wind in order to achieve a stable temperature above 55°F inside I Note that the colder the outdoor ambient temperature is the fe windows need removal. Use condenser charging chart. Verify that the outdoor amt temperature listed on the charging chart is the temperature in the charging tent. Carefully adjust the charging tent windows until reaching desired temperature, and allow the unit to stabilize for a minin of 15 minutes. Check the thermocouple to make sure the temp ture is still maintained at desired temperature. If the temperatui out of range, adjust the windows by opening or closing them. I Once the condition inside the charging tent is STABILIZED, fd the "System Charge" procedure to adjust charge in the unit. Add or remove charge, and adjust windows to maintairt desired temperature inside the tent. is the SECTION VI1: ELECTRICAL CONNECTIONS GENERAL INFORMATION & GROUNDING The control box cover is held in place with 3 screws (one screw in each lower corner and one screw at the top center post). The control b8x can swing open by removing the screw from the center of each side of the control box and allowing the control box to lower an inch or so into a pivotal position. A flexible electrical whip must be installed in order to use the Iswing away function of the control box. Other type electrical whips require the wiring to be disconnected in order to swing the control box open. The control box can then swing open from the left by rotatinO on .the right side pivots for easy service of refrigeration components. If no wir- ing is in or routed through the control box, it can be removed from the unit by lifting slightly, tilting the top hinge out, and lifting the bottom hinge out. During the installation, it is recommended to route,' the low voltage wiring for the thermostat along the unit whip to help facilitate the swing away feature of the control box. Refer to Figure 12. CONTROLBOX (Swing away) 0 HIGH VOLTA( ELECTRICAL A033n-00, FIGURE 12: Outdoor Unit Swing Away Control Box Check the electrical supply to be sure that it meets the values ues specified on the unit nameplate and wiring label. Power wiring, control (low voltage) wiring, disconnect switches and over current protection must be supplied by the installer. Wire size should be sized per NEC requirements. All field wiring must USE COPPER CONDUCTORS ONLY and be in accordance with Local, National, Fire, Safety & Electrical Codes. This unit must be grounded with a separate ground wire in accordance with the above codes. The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel. FIELD CONNECTIONS POWER WIRING 1. Install the proper size weatherproof disconnect switch outdoors and within sight of the unit. 2. Remove the screws at the top and sides of the comer cover. Slide the control box cover down and remove from unit. 3. Run power wiring from the disconnect switch to the unit. 4. Route wires from disconnect through power wiring exit provided and into the unit control box as shown in Figures 12, 13, 14 & 15. 5. Install the proper size time -delay fuses or circuit breaker, and make the power supply connections. `START RELAY LOW VOLTAGE CONTACTOR BOX 0 0 OI GROUND + LUG 9 •o 'START CAPACITOR LOW VOLTAGE REVERSIBLE HIGH FIELD WIRING VOLTAGE CONDUIT RUN HIGH VOLTAGE PLATE CAPACITOR FIELD WIRING `Optional accessories on some models. A02ac-001 FIGURE 13: Outdoor Unit Control Box (Single Phase - Smaller Base) CONTACTOR 'START RELAY LOW o VOLTAGE + BOX d c o00 LOW VOLTAGE I G FIELD WIRING GROUND LUG RUN CAPACITOR REVERSIBLE 'START HIGH VOLTAGE HIGH VOLTAGE CAPACITOR FIELD WIRING CONDUIT PLATE 'Optional accessories on some models. A0za3n01 FIGURE 14: Outdoor Unit Control Box (Single Phase - Larger Base) 1183509-U IM-L-0317 0, 0 LOW VOLTAGE BOX -, LOW VOLTAGE FIELD WIRING e 'FAN HIGH VOLTAGE CAPACITOR FIELD WIRING 'Optional accessories on some models. CONTACTOR �i GROUND 5 LUG I REVERSIBLE HIGH VOLTAGE CONDUIT PLATE A0538-001 FIGURE 15: Outdoor Unit Control Box (Three Phase) FIELD CONNECTIONS CONTROL WIRING 1. Route low voltage wiring into bottom of control box as shown in Figure 13, 14 or 15. Make low voltage wiring connections inside the low voltage box per Figure 16. 2. The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel. 3. Replace the control box cover removed in Step 2 of the FIELD CONNECTINS POWER WIRING procedures. 4. All field wiring to be in accordance with national electrical codes (NEC) and/or local -city codes. A Start Assist Kit is available and recommended for long line set applications or in areas of known low voltage problems. The kit may be required when a TXV is used (reference the Tabular Data Sheet to determine if applicable). 5. Mount the thermostat about 5 ft. above the floor, where it will be exposed to normal room air circulation. Do not place it on an out- side wall or where it is exposed to the radiant effect from exposed glass or appliances, drafts from outside doors or supply air grilles. 6. Route the 24-volt control wiring (NEC Class 2) from the outdoor unit to the indoor unit and thermostat. To eliminate erratic operation, seal the hole in the wall at the thermo- stat with permagum or equivalent to prevent air drafts affecting the operation of in the thermostat. ALL FIELD WIRING TO BE IN ACCORDANCE WITH — — — POWER WIRING ELECTRIC CODE (NEC) AND/OR LOCAL CODES — — — — — — CONTROL WIRING FACTORY WIRING POWER WIRING 24 VOLT CONTROL WIRING _ MINIMUM 18 GA. WIRE FURNACE OR AIR HANDLER I I (NEC CLASS 2) TERMINAL BLOCK I I 'TERMINAL W IS ONLY I C) Y R G W REQUIRED ON SYSTEMS WITH HEAT.00 I 1 I I I I CONTACTOR I I I I I TERMINALS I I I I I GND. COIL LUG CONDENSING UNIT___4 ROOM THERMOSTAT ALL OUTDOOR WIRING MUST BE WEATHERPROOF. USE COPPER CONDUCTORS ONLY. A0166801 FIGURE 16: Typical Field Wiring (Air Handier/ Electrical Heat) (Single -Phase) Johnson Controls Unitary Products 11 1183509-UIM-L-0317 For additional connection diagrams for all UPG equipment refer to the Product Catalog Section. ALL FIELD WIRING TO BE IN ACCOR POWER WIRING MI •(N I I I `TERMI REOUI 000 WITH CONTACTOR TERMINALS GND. LUG COIL CONDENSING UNIT ALL OUTDOOR WIRING MUST BE WE FIGURE 17: Typical Field Wiring (Air Handler / Electrical Heat) — - ------------------_----.._.. ----._.._....,...- 2 Heat / 1 Cool Thermostat —F 2 Heat/ 1 Cool' Thermostat 24 - Volt Common I Y' Compressor R 24 — Volt Hot I G - Fan w1 ' First Stage Heat wz-7 " Voltage System Wiring" document available online at www.upgnet.com in DANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES — — — POWER WIRING — — — — — — CONTROL WIRING FACTORY WIRING VOLT CONTROL WIRING NIMUM 18 GA. WIRE FURNACE OR AIR HANDLER EC LASSI2) TERMINAL BLOCK NAL IS ONLY RED ON SYSTEMS I I I 1 HEA . I I I I I I I I I I I I I I 1 I I ROOM THERMOSTAT AT ERPROOF. USE COPPER CONDUCTORS ONLY. A015@. 01 SC Air Handler —Single Stage Air Conditioner RSC SINGLE STAGE AIR HANDLER AIR CONDITIONER c c 24—°VoltCommon 24'- Volt Common Y Compressor r R 24-,Volt Hot G'e Fao.. Flrst Stage Heat ,- �<�. I Ao28P-001 FIGURE 18: Thermostat Chart - PSC Air Handler with Singh Stage Air Conditioner SC Air Handler —Single Stage Air Conditioner RSC SINGLE STAGE AIR HANDLER AIR CONDITIONER c c 24—°VoltCommon 24'- Volt Common Y Compressor r R 24-,Volt Hot G'e Fao.. Flrst Stage Heat ,- �<�. I Ao28P-001 FIGURE 18: Thermostat Chart - PSC Air Handler with Singh Stage Air Conditioner 1183509-UIM-L-0317 1 Heat / 1 Cool Thermostat —Single Stage Furnace (PSC) —Single Stage Air Conditioner 1 Heat / 1 Cool. SINGLE STAGE SINGLE STAGE Thermostat FURNACE (PSC) AIR CONDITIONER c C c„ 24 Volt Common 24 "Volt Common 24-`—'Volt Common Y YN2: Y, Compressor Full Stage Compnessor, Compressor' , R; R 24 — Volt Hot 24 —Volt Hot . G G Fan `;"Fan w , .w , heat ., Heat A0289401 FIGURE 19: Thermostat Chart - Single Stage PSC Furnace with Single Stage Air Conditioner SECTION VIII: INSTRUCTING THE OWNER Assist owner with processing warranty cards and/or online registration. Review Owners Guide and provide a copy to the owner and guidance on proper operation and maintenance. Instruct the owner or the opera- tor how to start, stop and adjust temperature setting. When applicable, instruct the owner that the compressor is equipped with a crankcase heater to prevent the migration of refrigerant to the compressor during the OFF cycle. The heater is energized only when the unit is not running. If the main switch is disconnected for long peri- ods of shut down, do not attempt to start the unit until 8 hours after the switch has been connected. This will allow sufficient time for all liquid refrigerant to be driven out of the compressor. The installer should also instruct the owner on proper operation and maintenance of all other system components. MAINTENANCE 1. Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air circuit. Clean as often as necessary to keep the unit clean. Use a brush, vacuum cleaner attachment, or other suitable means. 2. The outdoor fan motor is permanently lubricated and does not require periodic oiling. 3. If the coil needs to be cleaned, use clean water to wash dust, dirt, and debris from outdoor condensing coil. DO NOT use coil cleaners to clean outdoor condensing coil. Cleaners containing HF —, hydroxides, chlorides, and sulfates can greatly reduce the lifetime of the micro channel coil. 4. Refer to the furnace or air handler instructions for filter and blower motor maintenance. 5. The indoor coil and drain pan should be inspected and cleaned regularly to prevent odors and assure proper drainage. IT IS UNLAWFUL TO KNOWINGLY VENT, RELEASE OR DIS- CHARGE REFRIGERANT INTO THE OPEN AIR DURING REPAIR, SERVICE, MAINTENANCE OR THE FINAL DISPOSAL OF THIS UNIT. Johnson Controls Unitary Products 13 1183509-UIM-L-0317 SECTION IX: WIRING DIAGRAM DANGER - SHOCK HAZARD FAN MOTORA TURN OFF ELECTRICAL POWER BEFORE SERVICING TOPREVENT POSSIBLE DAMAGE TO THE EQUIPMENT AND POSSIBLE BLK PERSONAL INJURY. C CAUTION TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO AIR CONDITIONER IS SHUT OFF. COMPRESSOR - z tO COMPONENTS SHOWN IN DASHED MOTOR m LINES ARE OPTIONAL. RED O DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON 0 ACTUAL UNIT. RR FAN U O3 WIRING MUST CONFORM TO BRNNATIONAL AND LOCAL CODES. HERM o U ® IF ANY OF THE ORIGINAL WIRE C SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105°C. THERMOPLASTIC Z OR ITS EQUIVALENT. IX: c0 ❑ O5 WHERE POWER SUPPLY HAS ONE (1) .......:... 5 : 230 VOLT CONDUCTOR AND ONE (1) NEUTRAL CONDUCTOR, CONNECTL2 2 • • • • • • • • OF CONTACTOR TO NEUTRAL. S ... YEL :........... . ;m .-•SR.-= HPS - HIGH PRESSURE SWITCH =.......... LPS- LOWPRESSURESWITCH ❑ CCH - CRANKCASE HEATER U.]; HS - HEATER SWITCH SR - START RELAY Y Y SC - START CAPACITOR CC - CONTACTOR COIL ❑ HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTORY WIRING ' ...•..••.••••• OPTIONAL WIRING FIELD WIRING, LINE VOLTAGE O CCH CONTACTOR BLK T1 T2 BLU:' LU BLK © L1 L2 0 Z LPS: w0 } GND. ...:..: LUG J ... BLU J: m: USE COPPER m Y J HPS :•'"'- I CONDUCTORS Z U.I I • ONLY a. >- LU a' O' HS O I I I JUNCTION BOX G ID. I I 24 VAC CONTROL CIRCUIT I I (20 VA MIN.) 208-230 VAC 60 Hz 1 P ASE SUPPLY 1183564-UWD-B-0215 220-240 VAC 50 Hz 1 PI ASE SUPPLY FIGURE 20: Wiring Diagram - Single Phase 13 & 14 Seef t I 1183509-UIM-L-0317 FAN MOTOR DANGER - SHOCK HAZARD RED BLK R SLV RED TURN OFF ELECTRICAL POWER BEFORE BLU 0 VS SERVICING TO PREVENT POSSIBLE DAMAGE 3 j CONTROL TO THE EQUIPMENT AND POSSIBLE IL w PERSONAL INJURY. 1 v 2 V 4 v 3 v 5 v s v z CAUTION Y j SLV it 0 m m - - TO PREVENT ELECTRICAL SHOCK OPEN m REMOTE DISCONNECT SO ELECTRICAL BLK 00 SUPPLY TO AIR CONDITIONER IS SHUT OFF. w0 }0 O COMPONENTS SHOWN IN DASHED COMPRESSOR 0 LINES ARE OPTIONAL. MOTOR w R RED O DUAL CAPACITOR SHOWN SEPARATE CAPACITORS MAY BE USED ON C ACTUAL UNIT. (D O WIRING MUST CONFORM TO FAN a NATIONAL AND LOCAL CODES. BRN S HERM n ¢ ® IF ANY OF THE ORIGINAL WIRE C SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105°C. THERMOPLASTIC OR ITS EQUIVALENT. z: CE• co: 0 5O WHERE POWER SUPPLY HAS ONE (1) 5 Uj 230 VOLT CONDUCTOR AND ONE (1) NEUTRAL CONDUCTOR, CONNECTL2 2 .-.:----- OF CONTACTOR TO NEUTRAL. : YEL :......... SC HPS -HIGH PRESSURE SWITCH 1 """... LPS - LOW PRESSURE SWITCH m sR CCH - CRANKCASE HEATER HS HEATER SWITCH o: w SR START RELAY z: SC START CAPACITOR Y CC - CONTACTOR COIL m HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTORY WIRING ...... • • • • • OPTIONAL WIRING Oz — — FIELD WIRING, LINE VOLTAGE OO CCH rp BLK T2m •' LPS: OL1 L2 m: GND,CONTACTOR ..............: • - LUG m O BLU USE HPS COPPER ( HS I CONDUCTORS I ay ONLY I� w I I JUNCTION BOX G ID. I I 24 VAC CONTROL I I CIRCUIT (20 VA MIN.) �J 208-230 VAC 60 Hz 1 PHASE SUPPLY 5160254-UWD-B-0116 220-240 VAC 50 Hz 1 PHASE SUPPLY FIGURE 21: Wiring Diagram - Single Phase 17 Seer Johnson Controls Unitary Products 15 1183509-UIM-L-0317 FAN MOTOR fRED R BRN S C GRN m COMPRESSOR FC T1 T3 T2 CCH o-VV-Q :Y :Y • J J m : m Z 1O •J HS...m `.A : J • m •.Y J :m T33 L3I L2 F 2 I I GND LUG H 2O8-230 VAC 60 Hz 3 L�J 460 VAC 60 Hz 3 PI 575 VAC 60 Hz 3 PI I USE COPPER CONE GND FIGURE 22: Wiring Diagram - Three Phase 13 Seer DANGER - SHOCK HAZARD TURN OFF ELECTRICAL POWER BEFORE SERVICING TO PREVENT POSSIBLE DAMAGE TO THE EQUIPMENT AND POSSIBLE PERSONAL INJURY. CAUTION TO PREVENT ELECTRICAL SHOCK OPEN REMOTE DISCONNECT SO ELECTRICAL SUPPLY TO AIR CONDITIONER IS SHUT OFF. O COMPONENTS SHOWN IN DASHED LINES ARE OPTIONAL. 0 BLACK WIRE WILL BE REMOVED IF LOW AMBIENT KIT IS INSTALLED. O3 WIRING MUST CONFORM TO NATIONAL AND LOCAL CODES. ® IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105°C. THERMOPLASTIC OR ITS EQUIVALENT. HIPS - HIGH PRESSURE SWITCH LIPS - LOW PRESSURE SWITCH CCH -CRANKCASE HEATER HS - HEATER SWITCH CC - CONTACTOR COIL FC - FAN CAPACITOR HIGH VOLTAGE FACTORY WIRING LOW VOLTAGE FACTORY WIRING .. OPTIONAL WIRING — — FIELD WIRING, LINE VOLTAGE All BLU ; ••... •... Uo Y J (ACTOR T1 L1 ..-LPS: ......BLU....... II r0 IJ J m kSE SUPPLY Y J HPS E SUPPLY a r O E SUPPLY w oO FORS ONLY JUNC TION BOX 24 VAC CONTROL CIRCUIT (20 VA MIN.) 5203528-UWD-A-0416 1183509-UIM-L-0317 FAN MOTOR RED BLK R SLV RED C 0 S BLUF1 J a 1V 2V 4V 3v5v 6v Y J SLV m m m w DANGER - SHOCK HAZARD TURN OFF ELECTRICAL POWER BEFORE SERVICING TO PREVENT POSSIBLE DAMAGE TO THE EQUIPMENT AND POSSIBLE PERSONAL INJURY. 0 Vs CAUTION JTROL TO PREVENT ELECTRICAL SHOCK OPEN w REMOTE DISCONNECT SO ELECTRICAL m z SUPPLY TO AIR CONDITIONER IS SHUT OFF F J �W 7=7 COMPONENTS SHOWN IN DASHED CO m o - LINES ARE OPTIONAL. o0 20 WIRING MUST CONFORM TO r� NATIONAL AND LOCAL CODES. 0 30 IF ANY OF THE ORIGINAL WIRE SUPPLIED WITH THIS UNIT MUST BE REPLACED, IT MUST BE REPLACED WITH TYPE 105°C. THERMOPLASTIC OR ITS EQUIVALENT. COMPRESSOR T1 0 0 T3 T2 HPS - HIGH PRESSURE SWITCH CCH LPS - LOW PRESSURE SWITCH ........, CCH - CRANKCASE HEATER H OO : HS - HEATER SWITCH =------------ CC CONTACTOR COIL J J VS - VARIABLE SPEED m :m Y Y Z J J m m m Y (D HIGH VOLTAGE FACTORY WIRING : m LOW VOLTAGE FACTORY WIRING HS -.:.. OPTIONAL WIRING Y — — FIELD WIRING, LINE VOLTAGE J m BLU :o' [t4. :..... CONTACTOR U zw �.. Q •d••LPS: T3 L3 L2 T2 T1 L1 q d Q 0 LUG I I I n 208-230 VAC 60 Hz 3 PHASE SUPPLY 460 VAC 60 Hz 3 PHASE SUPPLY m Y J HP a } OO 575 VAC 60 Hz 3 PHASE SUPPLY I USE COPPER CONDUCTORS ONLY w 0 GND JUNCTION BOX 24 VAC CONTROL CIRCUIT (20 VA MIN.) FIGURE 23: Wiring Diagram - Three Phase 17 Seer 5275753-UWD-B-1216 Johnson Controls Unitary Products 17