HomeMy WebLinkAboutPROJECT INFORMATIONProject Summary rY Job:Date: Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FT..PIERCE, FL 34946 Phone: 772466-6799 Fax 772-466-6796 Email: QUICKCALCS @\OL.COM Project• • For: WYNNE DEV: THE MAJESTIC, FT. PIERCE, FL Notes: 9 9 Design Information Weather. Winter Design Conditions Outside db 42 OF Inside db 70 OF Design TD 28 OF Heating Summary Structure 17339 Btuh Ducts 5899 Btuh Central vent (0 cfm) 0 Btuh (none) Humidification 0 Btuh Piping 0 Btuh Equipment load 23239 Btuh Infiltration . Method Construction quality Fireplaces Fort Pierce, FL, US Simplified Average 0 Area (ft2) Heating, 1608 Coolingg 16 1 Volume (fN) 13924 13924 Air changes/hour 0.38 0.20 Equiv. AVF (cfm) 88 46 Heating Equipment Summary Make Carrier Trade CARRIER AIR CONDITIONING Model 25HBC536A*030 AHRI ref 7914585 Efficiency Heating input Heating output Temperature rise Actual air flow Airflow factor Static pressure Space thermostat Capacity balance point = 32 OF 8.5 HSPF 34600 Btuh @ 470F 27 0 1160 cfm 0.050 cfm/Btuh 0.50 in H2O Summer Design Conditions Outside db 90 Inside db 75 °F Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 gr/lb Sensible Cooling Equipment Load Sizing Structure 17020 Btuh Ducts 8920 Btuh Central vent (0 cfm) 0 Btuh (none) Blower 0 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Equipment sensible load 24643 Btuh Latent Cooling Equipment Load Sizing Structure 3339 Btuh Ducts . 2433 Btuh Central vent (0 cfm) 0 Btuh (none) Equipment latent load 5772 Btuh Equipment total load 30415 Btuh Req. total capacity at 0.70 SHR 2.9 ton Cooling Equipment Summary Make Carrier Trade CARRIER AIR CONDITIONING Cond 25HBC536A*030 Coil FX4DN(B,F)037 AHRI ref 7914585 Efficiency 12.0 EER, 15 SEER Sensible cooling 24360 Btuh Latent cooling 10440 Btuh Total cooling 34800 Btuh Actual air flow 1160 cfm Air flow factor 0.045 cfm/Btuh Static pressure 0.50 in H2O Load sensible heat ratio 0.82 Backup: �j �e y Input = 7 kW, Output = 23009 Btuh, 100 AFUE Copy Calculations approved byACCA to meet all requirements of Manual J 8th Ed. .4CC + wrightsoft` Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-11 09:Page age I ...k CaIcslDocuments\WYNNE-MAJESTIC MODEL-1606.rup Calc = MJB Front Door faces: N - - wrightsofir Right-JO Worksheet Job: Entire House Date: ' QUICK CALCS, INC. By: 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772466.6799 Fax 772-466-6796 Email; QUICKCALCS@AOL.COM 1 2 Room name F;posed wall Entire House MASTER BEDROOM 3 Room height 141.0 ft 8.7 ft d 46.0 ft 8.0 ft heat/cool 4 5 Room scans Room area 1608.0 ft2 21.0 x 294.0 ft 294.0 ft2 1.0 Ty IConstruction number U-value (Btuh/ft2-°F) Or HTM (Btuh/ft2) Area (M or perimeter (ft) Load (Btuh) Area (ft2) or Load perimeter (ft) (Btuh) - --- - --- ..•. -- 1 •.w vwaa I 1111r10 meal 1 l;ool 6 13A-4ocs 4A5.2om 0.143 ne 4.00. 2.55 454 408 1634 1039 56 56 224 143 4A52om . 0.770 0.770 ne ne 21.56 21.56 36.90 36.90 21 25 0 446 0 764 0 0. 0. 0 V►/ �-D 13A-4ocs 0.143 se 4.00 2.55 64 41 543 165 930 105 0 0 0 0 0 0 11 11DO 0.390 se 10.92 11.31 23 23 248 257 0 0 0 0 0 13AAocs" 1A c1om. 0143 1 270 : sw. 4;00 :35:56 255 . 392 " 369 1476 . 939, -200 200 - . 801 0 - 509: 1Ac1om :`sw 'sw 42:91 . 7 - 5 .247 298 . p 0 " 0' 0 �1 13AAocs 1.2.70 0.143 nw 35.56 4.00 .' S4:02 2.55 16 308 .8 581 '883 .: 0 p . p , . , 0 I- -G 1A-c1om 1.270 nw 35.56 45.24 33 235 939 0 1162 597 1478 112 33 79 318 0 202 " 4A5-2omd " 0.770 nw 21.56 36.90 41 0 880 1505 0 1162 1478 P. . • .12U6w :- : 0.091 - - 2.55 .. 1:28 .:376 376 958 : 482 0 0 0 0 0. C 0.032 - 0.90 2.32 1608 1608 1441 3731 . 294 294 263 0 682 F .' 22441md 22Atpl - .. U89 •- 27.69 • . abb 1668 14i 3905 ' " 0 294 46 : '. `1274 - --0 6 c)AED emursion 1638 729 Envelope loss/gain 14626 14645 4042 3743 12 a) Infiltration 2714 765 820 231 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 7 1610 1 230 Appliances/other 0 0 Subtotal (lines 6 to 13) 17339 17020 4862 4205 Less e)demal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 17339 17020 4862 4205 15 Duct loads -T 34% 52% 5899 8920 34% 52% 1654 2204 F-1 Total room load 23239 25941 T 6516 6408 Air required (cfm) I 1160 1160i 325 287 Calculations approved bVACCA to meet all requirements of Manual J 8th Ed. A-�- wrightsoft• 2017-Apr-11 09:28:14 C& Right -Suite® Universal 2017 17.0.14 RSU08101 Page 1 k CalcsW.cumentslWYNNE-MAJESTIC MODEL-1608.rup Cato = MJ8 Front Door faces: N - +- wrightsoft° Right-M Worksheet Job: Entire House Date: QUICK CALCS, INC. By: 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466.6799 Fax 772-466-6796 Email: QUICKCALCS(cDAOL.COM 1 Room name WIC M. BATH 2 Exposed wall 0 ft 7.0 ft 3 4 Room height Room dimensions 8.0 ft heat/cool 8.0 ft heat/cool 5 Room area 7.0 x 9.0 ft 63.0 ft2 1.0 x 61.0 ft 61.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2-°F) (Btuhlft2) or perimeter (ft) (Btuh) or perimeter • (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 VIA/--G 13A4gcs ` ' ' 0143 =na 'rie . 4:00 2:55 - 0 0, 0 0 0 0 0' 0 4A5 tom ; `" 0 770 21.56 36. 0 0 0 0 0 0 `, 0 :0 0 I--G 4A5 2oni : 0.770 . ne - . . 21:56 . :.36.90 o 0 0 .0 .. 0 ; 0 0 : 0 V�J 13A-4ocs 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11130 0.390 se 10.92 11.31 0 0 0 0 0 0 0 0 13A6cs. 1Ac1om•` 0143 sw. 4:00 2,55 - 0 0 0 0 56 '49 . " 196 125 1Ac1om 1 270 1270 sw -sw= 35.56 35i56 42 911 54.02 - 0 0 0. 0 : 0 0 `: 7 5 247 298 13A4ocs 0.143 nw 4.00 2.55 .0 0 0 0 0 0 0 0 0 0 0 0 IA-clom 1.270 nw 35.56 45.24 0 0 0 0 0 0 0 0 0 F 4A6-2omd 0.770 nw 21.56 36.90 0 0 0 0 0 0 .0 0 0 12C. Suv ; _.. 0.091 .- . 2.55 1.28 - 0 0 0 0 0 -. '0 ' 0 -" -"0 C F_ .` .:'22Atpl- _16A-3Omd 0.032 0.989 - -" 0.90 27.69 2.32 0.00 63 63 63 56 146 61 61 . 55 142 . 0 0 :.. 0 .: 61 7 194 •. 0 6 c)AED excursion 0 234 Envelope loss/gain 56 146 692 798 12 a) Infiltration 0 0 125 35 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal pines 6 to 13) 56 146 816 833 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 56 146 816 833 15 Duct loads 34% 52% 19 77 34% 52% 278 437 Total room load 76 223 1 1094 1269 "Air required (cfm) 4 10 55 57 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. .i',., wrightsoft' Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-11 09:28:14 .P. ... k Calcs\Documents\WYNNE-MAJESTIC MODEL-1608.rup Calc = MJ8 Front Door faces: N Page 2 wrightsoft° Right-M Worksheet Job: Entire House Date: By: QUICK CALLS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-46M799 Fax 772-466-6796 Email: QUICKCALCS or7AOL.COM 1 Room name LAUDRY DR BEDROOM 2 2 Exposed wall 0 ft ft 3 4 Room height Room dimensions 8.0 ft heat1cool 8.0 ft heat/cool 5 Room area 6.0 x 6.0 ft 36.0 ftz 15.0 x 12.0 R 180.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ftz) Load' number (Btuh/ftz °F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6.13AAocs 0143 ne 4.00 .2.55 0 0 0 0 0 4A5-tom ; .. 0770 ne.-_ 2156 36;90 ,0 0 0 0 0 0 0 0 0 0 0 4A5 tom - 0 770 . he 21."56 . 36.90 .0 0 0 0 0 : " 0 0 : 0 V�1 I-D 13AAocs 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11 11DO 0.390 se 10.92 11.31 0 0 0 0 0 0 0 0 13A-0ocs,;. ,, 0143 sw. 4.00 2:55 0 0 0 . 0 . , 96 .:• 80 b 319 ,203, C270 sw: 35:56: 42 91 0 0 0 0 0 0: 0 0. 1A.c1om 13AAocs 1 270 sw; 35.56 54`02 0. 0' 0 ,' 0 .: 16 '- ; 8 581. 863 1Ac1om 0.143 1.270 my nw 4.00 35.56 2.55 45.24 0 0 0 0 0 0 0 0 0 0 0 0 4A5-2omd 0.770 nw 21.56 36.90 0 0 0 0 0 0 0 0 0 0 0 0 P C '12C-0'sw: 0.091 ..-.: 2:55 128 0 0 0 D f04 104 : 265 133 F :, • ,: 16A 30md 22A tpl : 0.032 0:989 - 0.90 : 27.69 2.32 0:0Q 36 36 36 0 32 84 180 _.: 180 161 . 418 :;: ." . . 0 :.. 0 .. 180 12 : :332 ` 0 6 c)AED excursion 0 507 Envelope loss/gain 32 84 1659 2143 12 a) Infiltration 0 0 214' 60 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 32 84 1873 2204 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 6 151 6 15 14 Subtotal 38 98 1878 2218 15 Duct loads 34% 52% 13 51 U0 52% 639 1162 Total room load 51 149 1 2517 3381 Air required (cfm) 3 7 1 126 151 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. .A +k wrightsoft' 2017-Apr-11 09:28:14 Right -Suite® Universal 2017 17.0.14 RSU08101 Page 3 ...k Calcs\Documents\WYNNE-MAJESTIC MODEL-1608.rup Cale = MJB Front Door faces: N - wrightsoft° Right-M Worksheet Job: Entire House Date: QUICK CALCS, INC. By: 317 ST. LUCIE LN., FT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCWOL.COM 1 2 Room name DINING/GREAT ROOM KrrCHEN 3 E)posed wall Room height 50.0 ft 12.0 ft 4 Room sions 9.8 ft heat/cool x 589.0 ft 8.0 ft heat/cool 5 Room area 589.0 ft21.0 19.0 x 12.0 ft 228.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft-) Load number I (Btutvft2-°F) (Btuh/ft2) or perimeter (ft) (Btuh) I or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool I Gross N/P/S Heat Cool 6 w 13A-4ocs °9A5 tom 0143 ne .4.00 2:55 294 248 993 . 632 .96 96 384 ' 244 -0 770 _ne 21'56 36 90 : 21 ; - 0 446 , 764 .: 0' 0 U U 4A5.2om; '0.770 . nd 2156 36.90 . 25 0 543 930 ' . 0 0 0 : 0 Y--D 13A-4ocs 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11 11130 0.390 se 10.92 11.31 0 0 0 0 0 0 0 0 13A4ocs 0143 sW-- `sw, 4,06 2.55 0 : 0 0 0 0. 0 ~0 0 1270 35.56 42'91 ' ' p 0 0 : 0 t) : : '0 p .. ', p 1A.-c1om - : 1.270 SW' 35.56 . 54:02 , 0 0 -' .. - 0 - 0 - 0 0 a p .0 13A4ocs 0.143 nw 4.00 2.55 196 155 621 395 0 0 0 ,' 0 1Aclom 1.270 nw 35.56 45.24 0 0 0 0 0 0 0 0 P- 4A5-2omd `12c-0sw 0.770 nw ' 21.56 36.90, " 41 0 880 1505 , 0 0 0 0 C 16A 30md 0.091 0.03.2 ._ - -' 2:55. 0.90 1128 2.32 ` - 0 589 0 589 0 528 -' 0 1366 •- 104'. 228 -:104 265 - . ' '133 F-' :22A tpl' 0.989 - _ 27.69 -0.-00: 589 50 '1385 . 0 .. 228' 228 _ :', : ,12. 204 332 529 ; 0 6 c)AED a)Eursion 168 0 Envelope loss/gain 5396 5760 1186 907 12 a) Infiltration 1092 308 214 60 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 4 920 2 460 Appliances/other 0 0 Subtotal Qines 6 to 13) 6488 6988 1400 1427 Less e#emal load 0 0 0 0 Less transfer 0 0 0 0 Redistributicn 6 15 0 0 14 Subtotal 6494 7002 1400 1427 15 Duct loads 34% 52% 2209 3670 34% 52% 476 748 Total room load 8703 10672 T1876 2175 Air required (cfm) 434 477 94 g7 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. - - wcigiltsoft' Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-11 09:age 4 4 I&k Page ...k CaIcslDocuments\WYNNE-MAJESTIC MODEL-1608.rup Calc = MJ8 Front Door faces: N - - wrightsoft Right-M Worksheet Job: Entire House Date: QUICK CALCs, INC. By: 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1 Room name BATH 2 HALL 2 F)posed wall 5.0 ft 0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions x 5.0 ft 5.0 x 5.0 ft 5 Room area 50.0 ft210.0 25.0 ftZ Ty Construction U-value Or HTM Area. (ft') Load Area (ft� Load number (Btuh/ftz °F) (Btuh/ft') or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross NIP/S Heat Cool Gross I N/P/S Heat Cool 6 13A4ocs 0.143 -ne 4.00 2.55 0 0 0 0 0 0 0 0 4A5-2om 0:770 ne 21:56 36.90 0 0 0 0 0 0 0 0 4A5 tom 0.770 ' ne 21:56 . 36.90 0 0 0 0 0 0 0 0 y! 13A4ocs 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11 a 11DO 0.390 se 10.92 11.31 0 0 0 0 0 0 0 0 13A-4= 0143 .sw. 4.00 255 40 40 ;. 160 102 0 0 0 0 1Ac1om.' 1270 sw, 3556 42:91 0 _ 0 0 .0 - 0" 0 0 1Acloin 1.270 sw 3556 5402 - 0 0. 0. 0 0 .0 % 0 p 13A4ocs 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 IA-clom 1.270 nw 35.56 45.24 0 0 0 0 0 0 0 0 _ 4A5-2omd -12C,0sw: 0.770 nw ` 21.56 36.90 0 0 0 0 0 0 0 0 ,P.-... :° 0 091 ._ 2:55 ' 128 0 0 0 0 .' 0 0 Q. 0 C F ' 16A 30md 0.032 - 0.90 2.32 50 50 45 116 25 25 22 58 , 22A-tpl . 0.980 27.69 ._ 0i00 50 5 138 : ; '0 :25 0 0: 0 6 c)AED excursion 0 0 Envelope loss/gain 343 218 22 58 12 a) Infiltration 89 25 0 0 b) 'Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 p p p Appliances/other 0 0 Subtotal (lines 6 to 13) 433 243 22 58 Less wdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 6 15 -22 -58 14 Subtotal 438 257 0 0 15 Duct loads 34% 52% 149 135 34% 52% 0 0 Total room load 587 392 0 0 Air required (cfm) 29 18 1 0 0 Calculations_ approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoitRight-Suite® Page 5 Universal 2017 17.0.14 RSU08101 2017-Apr-11 09:ge 5 ... k Calcs\DocumentslWYNNE-MAJESTIC MODEL-1608.rup Calc = MJB Front Door faces: N - wrightsot Right-J® Worksheet Job: Entire House Date: QUICK CALCS, INC. By: 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS ,AOL.COM 1 Room name FOYER 2 Fposed wall 9.0 ft 3 Room height 8.0 ft heaticool 4 Room dimensions 1.0 x 82.0 ft 5 Room area 82.0 ftz Ty Construction U-value Or HTM Area (ft-) Load Area Load number (Btuh/ftMF) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AAocs 0.143 ne 4.00. 2.55 8 8 32 20 4P5.2om. 0:770 `ne :21.56 36.90 0 0 0 0 ,4A5 2otn 0.770 : ne. 21.56: 36.90 0 0 0 0 V�/ 13AAocs 0.143 se 4.00 2.55 64 41 165 105 . 11 L—D 11DO 0.390 se 10.92 11.31 23 23 248 257 13A-0acs 0143 sw 4.00 2:55 0 0 0 0 1Ac1om 1 270 sw. 35.56 42 91' 0 0 , ' 0 . 0 ' 1Ac1orit.... 1.270 sw 35.56 54;, .. • 0 0 0 ' 0 13AAocs 0.143 nw 4.00 2.55 0 0 0 0 _ 1Ac1om 1.270 nw 35.56 45.24 0 0 0 0 4A5-2omd 0.770 nw 21.56 36.90 0 0 0 0 P. .i2C-Osw: 0:091 '- = 2:55 ; 1.28 168 ` 168 428 ` 216 C 16A-30md 0.032 - 0.90 2.32 82 82 73 190 22Xtpl . 0:989 .. _ 27:69 .:' • 0.00 . 82 9 249 . 0 .' 6 c)AED excursion 0 Envelope loss/gain 1196 788 12 a) Infiltration 160 45 b) Room ventilation 0 0 13 Internal gains: Occupants @ 230 0 0 Appliances/other 0 Subtotal Qines 6 to 13) 1357 834 Less extemal load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 1357 834 15 Duct loads 34% 52% 462 437 Total room load 1818 1271 Air required (cfm) 91 57 Calculations approved WACCA to meet all requirements of Manual J 8th Ed. 'F[I' wrightsoft' Right Suite® Universal 2017 17.0.14 RSU08101 2017-Apr 11 09:28:14 .A ...k Calcs\Documents\WYNNE-MAJESTIC MODEL-1608.rup Calc = MJB Front Door faces: N Page 6 wrightsoft0 Duct System Summary Job: y Date: Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 _Fax 772466-6796 Email: QUICKCALCS@,AOL.COM ?Ioject Information For: WYNNE DEV. THE MAJESTIC, FT. PIERCE, FL External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.266 in/100ft 1160 cfm Cooling 0.50 in H2O 0 in H2O 0.50 in H2O 0.2504 0.250 in H2O 0.266 in/100ft 1160 cfm 188 ft Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mat[ Actual Ln (ft) Ftg.Egv . Ln (ft) Trunk BATH 2 h 587 29 18 0.359 4.0 Ox 0 VIFx 24.3 115.0 st1 BEDROOM 2 c 3381 126 151 0.372 7.0 Ox 0 VIFx 19.4 115.0 st1 DINING/GREAT ROOM c 3558 145 159 0.351 7.0 Ox0 VIFx 27.5 115.0 st1 DINING/GREAT ROOM -A C 3557 145 159 0.287 7.0 Ox0 VIFx 39.4 135.0 st1 DINING/GREAT ROOM-B C 3557 145 159 0.277 7.0 Ox 0 VIFx 45.2 135.0 st1 FOYER h 1818 91 57 0.515 4.0 OxO VIFx 2.0 95.0 KITCHEN c 2175 94 97 0.377 6.0 Ox0 VIFx 17.6 115.0 st1 LAUDRY c 149 3 7 - 0.359 4.0 Ox 0 VIFx 24.3 115.0 st1 M. BATH c 1269 55 57 0.274 4.0 Ox0 VIFx 47.4 135.0 st1 MASTER BEDROOM h 3258 163 143 0.266 7.0 Ox0 VIFx 52.9 135.0 st1 MASTER BEDROOM -A h 3258 163 143 0.276 7.0 Ox 0 VIFx 46.1 135.0 st1 WIC c 223 4 10 0.287 4.0 Ox 0 VIFx 39.0 135.0 st1 Name Trunk Type Htg (cfm) Clg (cfm) Design FR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk st1 Peak AVF 1069 1103 0.266 1032 14.0 0 x 0 V[nlFlx wrightsofta Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-11 09:28:15 Page 1 ...k CalcslDocuments\WYNNE-MAJESTIC MODEL-1608.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Name Grille Size (in) . Htg (cfm) clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox0 1160 1160 0 0 0 0 Ox 0 VIFx wri htsoftj 2017-Apr-11 09:28:15 AM* 9 Right -Suite® Universal 2017 17.0.14 RSU08101 Page 2 ..k CalcslDocumentslWYNNE-MAJESTIC MODEL-1608.rup Calc = MJ8 Front Door faces: N