HomeMy WebLinkAboutGPP FABRIC SHUTTERS SPECIFICATIONSGENERAL NOTES: 1. GPP FABRIC SHUTTER — SERIES 2000 SHOWN ON THIS PRODUCT EVALUATION DOCUMENT (P.E.D.) HAS BEEN VERIFIED FOR COMPLIANCE IN ACCORDANCE WITH THE 2014 (5th EDITION) OF THE FLORIDA BUILDING CODE. THIS PRODUCT SHALL NOT BE INSTALLED AT HIGH VELOCITY HURRICANE ZONES (MIAMI�DADE % BROWARD COUNTIES). DESIGN WIND LOADS SHALL BE DETERMINED AS PER SECTION 1609 OF THE ABOVE MENTIONED CODE, FOR A WIND SPEED AS REQUIRED BY THE JURISDICTION WHERE THESE SHUTTERS WILL BE INSTALLED AND FOR A DIRECTIONALITY FACTOR Kd=0.85. USING ASCE 7-10 FOR INSTALLATIONS UNDER 2014 FBC AND SHALL NOT EXCEED THE MAXIMUM (A.S.D.) DESIGN PRESSURE RATINGS INDICATED ON NOTES 1 & 4. IN ORDER TO VERIFY THE ABOVE CONDITION, ULTIMATE DESIGN WIND LOADS DETERMINED PER ASCE 7-10 SHALL BE FIRST REDUCED TO A.S.D. DESIGN WIND LOADS BY MULTIPLYING THEM BY 0.6 IN ORDER TO COMPARE THESE W/ MAX. (A.S.D) DESIGN PRESSURE RATINGS INDICATED ON NOTES 1 & 4, IN ORDER TO VERIFY THAT COMPONENTS AND ANCHORS ON THIS P.E.D. AS TESTED WERE NOT OVER STRESSED, A 33% INCREASE IN ALLOWABLE STRESS FOR WIND LOADS WAS NOT USED IN THEIR ANALYSIS. MAXIMUM A.S.D. DESIGN PRESSURE RATING, MAXIMUM PANEL SPAN & MINIMUM SEPARATION TO GLASS SHALL BE AS INDICATED ON SCHEDULES #1 & #2 ON SHEET 13. PRODUCT'S ADEQUACY FOR IMPACT AND WIND RESISTANCE HAS BEEN VERIFIED IN ACCORDANCE WITH SECTION 1609.1.2 OF THE ABOVE MENTIONED CODE AS PER AMERICAN TESTING LAB OF SOUTH FLORIDA. REPORT # 0904.01--09, AS PER ASTM E 1886, E 1996 AND E 330 STANDARDS, QUALIFYING INSTALLATIONS FOR WIND ZONES 1, 2, 3 & 4, MISSILE TYPE D, APPLICABLE TO BASIC PROTECTION FOR INSTALLATIONS AT NON ESSENTIAL FACILITIES AS DEFINED BY SECTIONS 6.2.1.1. 6.2.1.2 AND 8.3 OF ASTM E 1996. 2. ALL COMPONENTS TO BE AS PER DETAILS AND BILL OF MATERIALS ON SHEETS 2 & 3. 3. FABRIC MADE FROM HIGH DENSITY POLYETHYLENE TAPES, COATED ON (2) SIDES WITH LOW DENSITY POLYETHYLENE AND LAMINATED TOGETHER WITH (3) LOW DENSITY POLYETHYLENE, MODEL X719NiN1, MANUFACTURED BY FABRENE INC., 240 DUPONT RD. P.O. BOX 4040 NORTH BAY, ON, CANADA P1 B 8Z4. SHALL HAVE THE FOLLOWING PROPERTIES: PROPERTIES (1) UNIT WEIGHT: (2) WARP CONSTRUCTION: (3) TENSILE MAXIMUM STRENGTH: (4) COATING: (5) SELF IGNITION TEMPERATURE: FLASH IGNITION TEMPERATURE: (6) RATE OF BURN: (7) AVERAGE SMOKE DENSITY RATING: RESULT TEST METHOD 30.4 oz/yd2 ASTM D3776 16 TAPES/in WARP ASTM D3775 27.9 TAPES/in WEFT 14.8 psi (VERTICAL) ASTM D751 11.4 psi (HORIZONTAL) 0.9 mil NATURAL ASTM D1777 MOD 380'C ASTM D1929 390'C 5. PRODUCT MAY ALSO BE INSTALLED HORIZONTALLY FOLLOWING INSTALLATION DETAILS SHOWN ON SECTIONS A, B. C. D. E, F & F' ON SHEETS 5 THRU 8. 6. THIS PRODUCT SHALL BE ONLY INSTALLED WHEN A HURRICANE WARNING IS ISSUED AND SHALL BE IMMEDIATELY REMOVED AFTER THOSE CONDITIONS ARE OVER. FABRIC SHALL BE STORED IN A PLACE NOT EXPOSED TO THE WEATHER AND SHALL BE PROPERLY MAINTAINED, PER MANUFACTURER'S RECOMMENDATIONS. 7. IT SHALL BE THE RESPONSIBILITY OF* THE CONTRACTOR TO VERIFY THE SOUNDNESS OF THE STRUCTURE WHERE PRODUCT IS TO BE ATTACHED TO INSURE PROPER ANCHORAGE. THIS PRODUCT SHALL ONLY BE ATTACHED TO POURED CONCRETE, GROUT FILLED BLOCK, HOLLOW BLOCK, WOOD AND STEEL FRAME BUILDINGS WITH LIMITATIONS INDICATED ON THIS DRAWING. 8. THE INSTALLATION CONTRACTOR IS TO SEAL/CAULK ALL PRODUCT COMPONENT EDGES WHICH REMAIN IN CONTINUOUS CONTACT WITH THE BUILDING TO PREVENT WEND/RAIN INTRUSION. INSTALLATION AND DRIVING OF FASTENERS AND SLEEVES (AS APPLICABLE) INTO EXISTING STRUCTURE'S FINISH SHALL BE CAREFULLY PERFORMED IN SUCH A WAY THAT FINISH AROUND FASTENERS IS NOT DAMAGED. SIDEWALK BOLTS (SCREWS OR RODS) SHALL BE LEFT AT ALL CORRESPONDING ANCHOR'S LOCATION. 9. PRODUCT'S INSTALLATION SHALL COMPLY WITH SPECS INDICATED IN THIS DRAWING PLUS ANY BUILDING AND ZONING REGULATIONS PROVIDED BY THE JURISDICTION WHERE PERMIT IS APPLIED TO. 10. (a) THIS PRODUCT EVALUATION DOCUMENT (P.E.D.) PREPARED BY THIS ENGINEER GENERIC AND DOES NOT PROVIDE INFORMATION FOR A SITE SPECIFIC PROJECT; i.e. WHERE THE SITE CONDITIONS DEVIATE FROM THE P.E.D. (b) CONTRACTOR TO BE RESPONSIBLE FOR THE SELECTION, PURCHASE AND INSTALLATION INCLUDING LIFE SAFETY OF THIS PRODUCT BASED ON THIS P.E.D. PROVIDED HE/SHE DOES NOT DEVIATE FROM THE- CONDITIONS DETAILED ON THIS DOCUMENT. CONSTRUCTION SAFETY AT SITE IS THE CONTRACTOR'S RESPONSIBILITY. (c) THIS P.E.D. WILL BE CONSIDERED INVALID IF ALTERED BY ANY MEANS. (d). SITE SPECIFIC PROJECTS SHALL BE PREPARED BY A FLORIDA REGISTERED ENGINEER OR ARCHITECT WHICH WILL BECOME THE ENGINEER OF RECORD (E.O.R.) FOR THE PROJECT AND WHO WILL BE RESPONSIBLE FOR THE PROPER USE OF THE P.E.D.ENGINEER OF RECORD, ACTING AS A DELEGATED ENGINEER TO THE P.E.D.ENGINEER, SHALL SUBMIT TO THIS LATTER THE SITE SPECIFIC DRAWINGS FOR REVIEW. (e) THIS P.E.D. SHALL BEAR THE DATE AND ORIGINAL SEAL AND SIGNATURE OF THE PROFESSIONAL ENGINEER OF RECORD THAT PREPARED IT. 11. PRODUCT MANUFACTURER'S LABEL SHALL BE LOCATED ON A READILY VISIBLE LOCATION AT PRODUCT IN ACCORDANCE WITH SECTION 1710.8.3 OF FLORIDA BUILDING CODE. ONE LABEL SHALL BE PLACED FOR EVERY OPENING. LA13EUNG TO COMPLY WITH SECTION 1710.8.2 OF THE FLORIDA BUILDING CODE. .N'��.����%°�� FLORIDA BUILDING CODE (Non High Velocity Hurricane Zone) 25mm/min, CLASS CC2 ASTM D635 �c� GPP FABRIC SHUTTER -- SERIES 2000 ®20i5 7{LiECO INC. F.R.LOWN By 2.2 ASTM D2843 ,.�—� i 4. MAXIMUM ANCHORS SPACING & ANCHOR SPECS SHALL BE AS PER SCHEDULES #3 & #3A ON SHEETS 2,. 14 & 15. . - 0.075" TOTAL FABRIC THICKNESS W/O COATING LOW �� �D O* DENSITY �Q V(EW X POL�IYEiHn E (2) SIDES COATED �-� NATE 0.9 mi1/SIDE .078' m �& COO - ISOMETRIC ±0.025" TAPE t0.025" .320" TAPE t0.025" RIM TAPE (SIDE VIEW) OA COATED POLYETHYLENE FABRIC: (SEE SHEEr 2 FOR END DETAILS WITH HEMMED EDGES) N.T.S. 1.500" � o N n 1/4"0-20 THREADS n1/4"0-20x1112" SIDEWALK BOLT (AIS1304 SERIES STAINLESS STEEL) SCALE: 1/2" - 1" .750' 1/4"0^-20 AISI 304 125" SERIES S-S. STUD )- RIVETED TO ANGLE w ®e' O.C. o '? DETAAIIL 1 L1.500"- to O ANGLE WITH STUD (6063-T6 ALLOY) SCALE: 1/0 = 1" _094" .063" In 00 /4 -20 THREADS m � I .1875" O 7/8" 0 WASHERED WINGNUT W11/4"0-20 THREADS (ZAMAC NICKEL. PLATED) SCALE: 1/2' = 1" j TtLK .078" 96S. O D• (Typ-) °lSr4. VIEW Y 070" 2 1 r-- 1 0 g 1. ISOMETRIC Sri � .150' SPUR WASHER (SIDE VIEVV) O ROLLED.GROMMET SCALE: 1/2' = 1" .055" N00i.5240" FENDER WASHER AIS1304 SERIES STAINLESS STEEL) SCALE: 1/2" = 1" .094' DETAIL 1: STUD W/ WINGNUT H1 N.T.S. 0 9 pepnppp��j (D114'0 ELCO CONSTRUCTION PRODUCTS ULTRACON a 5/16- 0 ITW BUILDEX TAPCON XL ANCHOR -SCAM- 1/2" = 1" SCALE: 1/2" = 1" I Goo" IZ 511670 ELCO CONSTRUCTION PRODUCTS ULTRACON SCALE: 1/2- = 1" 1/4"0-20 THREADS O L to t (+N-0.270" .200" O SAFETY NUT (AISI304 SERIES STAINLESS STEEL) SCALE: 1/2" = 1 " 2.000" Q 0 MAX. 19 - o--------- ALUMINUM SLEEVE (6063-T6 ALLOY) SCALE: 1/2' = 1" .094" .063' to IT s }' C11 I I;I;;, /4'0-20 THREADS � LL i- 1875" H1 1 1 /8"0 WASHERED WINGNUT W/ IWO-20 THREADS 9AMAC NICKEL PLATED) SCALE: 1/2' = 1" COMPONENTS 2.000" O 5116"0 ELCO CONSTRUCTION PRODUCTS HANGERMATEO N W11/4"0-20 THREADS (EZG365 ANCHOR) CARBON STEEL(AISI CIOB21) CASE HARDENED AND TEMPERED 13 5/16.0 ELCO CONSTRUCTION PRODUCTS ULTRACON SCALE: 1/2' = 1' SCALE: 1/2" = 1" .996" .736" 0 N I , 1/4.0-20 THREADS O 1/4"0 ELCO CONSTRUCTION PRODUCTS PANELMATE® PRO W/1I4"0-20 THREADS SCALE: 1/2" = 1" SELF -DRILLING POINT 1/4'0-20 THREADS s o �n 'cc N � .750" M1 1/470-10 ELCO CONSTRUCTION PRODUCTS HANGERMATEO W/ 11400-20 THREADS (EZG910 ANCHOR) CARBON STEEL (AISI CI0821) CASE HARDENED AND TEMPERED iw " SCALE: 1/2" = 1" s N 445- -373" 1/4"�-20 THREADS 01/4"0 ELCO CONSTRUCTION PRODUCTS PANELMAT09 FEMALE ID 11Wl 11470-20 THREADSSCALE: 1/2" _ ]"1/4"0-20 THREADS 750" O IWO ELCO CONSTRUCTION PRODUCTS FAB-LOK HD o W/ 1/4'0-20 THREADS "' -- 1/4'0-20 THREADS SCALE: 1/2" = 1" O 1/4"M3/4" ALL•POINT SOLID -SET ANCHOR W/ 1/4"0-20 THREADS M . ' I F 1/4"0-20 THREADS SCALE: 1/2" = 1" .800" 0 1 250" o OO 300 ELCO CONSTRUCTION PRODUCTS MODIFIED CONFLEX d `W/ 1/470-20 THREADS p in SCALE 1/2" = i' "I /4"- /4"0 0 THREADS It 1.500" K1 1/2"0 ELCO CONSTRUCTION PRODUCTS PANELMATE® L INSERT Il l t t I I I I I€ I I W11/4"0-20 THREADS 0° 3/8"0-20 THREADS SCALE: 1/2' = 1.500" P 1/2"0xl 9/115" POWER ANCHOR W/ 3/8'0-20 THREADS N SCALE: 1/2- = 1 " /4"0-20 THREADS OL 1/4"0-20xl 1/, AISf 304 SERIES S.S. ROD SCALE: 1/2" = 1" 0 3.000' N 1 /4.0-20 THREADS RJ 20x3" AISI 304 SERIES S.S. ROD 4 �j SCALE: 1/2" = I" 7a. n: Llcr .� 1.500" in in r� 3/8'0-20 THREADS"-3 O 3/8"MOM 1/2' SIDEWALK BOLT (AIS1304 SERIES STAINLESS STEEL) SCALE: 1/2' = 1" FLORIDA BUILDING CODE (Non High Velocity Hurricane Zone 02015 nLTEC0 INC. i1LUT TESTING A: ENGINEERING ODMPANY 16= N.W. 3M St.. Ste. 305 - ViR M CMDEM ET. "166 Ft m".: (MOB) Wl-1530 . F= : (305) 671-1531 e-mail: tilEeco0col.com E6-0006719 WAL TER A. TILUr Jr.. P.E. GPP FABRIC SHUTTER - SERIES 2000 1 DRAWNWN ABY GLOBAL PROTECTION PRODUCTS, LLC.I osDAIE DATE 4800 S.W. 51 STREET DAVIE, FL 33314 I15-020PHONE (954)689-7545. FAX: (954)689--8797 av NI RM ME RE7 M 0mw DRAMNG it SHEET 2 OF 15 BILL OF MATERIALS ITEM No. DESCRIPTION 3-PLY FABRIC. MADE FROM HIGH DENSITY POLYETHYLENE TAPES, COATED ON (2) SIDES WITH LOW DENSITY POLYETHYLENE AND LAMINATED TOGETHER WITH (3) LOW DENSITY OPOLYETHYLENE, PER FA13RENE INC. MODEL X719N1 N1 W/ 3.00"-3.25" HEMMED EDGES AT TOP & BOTTOM ENDS, PER DETAIL X ON THIS SHEET. O IS ALWAYS ONE ENTIRE PIECE, EXCEPT WHERE OVERLAPS ARE ALLOWED. OROLLED RIM GROMMET (RRG#2/45-00992) WITH' SPUR WASHER (RRG#2/45-00882) HEAVY-DUTY BRASS W/ 1" E.D. IN RESPECT TO FABRIC OC 1IN'0-20xl 1/2" SIDE WALK BOLT (AISI 304 SERIES STAINLESS STEEL) Da FENDER WASHER (AISI 304 SERIES STAINLESS STEEL) OSAFETY NUT W11/4"0-20 THREADS (AISI 304 SERIES STAINLESS STEEL) O1 1/2"xl 1/2"x1/8" EXTRUDED 6063-T6 ALUMINUM ALLOY ANGLE W1 STUDS @ 8" o:C. OALUMINUM SLEEVE (6063-T5 ALUMINUM A" OY) OH 718" 0x3 31132" WASHERED WINGNUT W11/4" 0-20 THREADS (ZAMAC NICKEL PLATED) H 1 1 11870x3 31132" WASHERED WINGNUT W/ 1/4"0-20 THREADS (ZAMAC NICKEL PLATED) O1/4" 0 ELCO CONSTRUCTION PRODUCTS ULTRACON ANCHOR 0 5/16"0 ELCO CONSTRUCTION PRODUCTS ULTRACON ANCHOR 12 5/16" 0 ELCO CONSTRUCTION PRODUCTS ULTRACON ANCHOR W/ 1" THREADED PENETRATION i3 5116"0 ELCO CONSTRUCTION PRODUCTS ULTRACON ANCHOR WIZ'THREADED PENETRATION O1/4" 0 ELCO CONSTRUCTION PRODUCTS PANELMATE® PRO W/ 1/4"0-20 THREADS J1 1/4"0 ELCO CONSTRUCTION PRODUCTS PANELMATE® FEMALE ID W/ 114"0-20 THREADS OK 1/4"0x314" ALL POINT SOLID -SET ANCHOR W/ 1/4'0-20 THREADS K1 1/2" 0 ELCO CONSTRUCTION PRODUCTS PANELMATE® L INSERT W/ 1/4"0-20 THREADS OL 1/4" 0.-20 x1 1/2" AISI 304 SERIES S-S. ROD W/ 1/4"0-20 THREADS Ll 1/4"0 20 x3" AISI 304 SERIES S.S. ROD W/ 1/4"0-20 THREADS 5116"0 ELCO CONSTRUCTION PRODUCTS HANGERMATE® W/ 1/4'0-20 THREADS (EZG365ANCHOR, GIMLET POINT) CARBON STEEL (AISI CI01321) CASE HARDENED AND TEMPERED 1/4"0-10 ELCO CONSTRUCTION PRODUCTS HANGERMATE® M1 W11/4"0-20THREADS (EZG910ANCHOR. SELL`DRILLING POINT) CARBON STEEL (AISI CIOB21) CASE HARDENED AND TEMPERED �N 1/4"0 ELCO CONSTRUCTION PRODUCTS FAB-LOK HD W/ 114"0-20 THREADS O318"0 ELCO CONSTRUCTION PRODUCTS MODIFIED CONFLEX W/ 1/4"0-20 THREADS 1/2" Ox1 9/16" POWER ANCHOR W/ 3/8"0 20 THREADS { Q j 3/8"0-20xl 1/2" SIDE WALK BOLT (AISI 304 SERIES STAINLESS STEEL) 1.000" 3.000" .3.250" 2.000" E.D. - HEMMED EDGES ONE ROW STITCHED AT .750"-1.000" B (FROM END OF HEM) .250" .750' 1.000" 11 EXTERIOR TYPICAL HEMMED EDGE FABRIC DETAIL X SCALE 3/4" =1" TWO ROWS STITCHING SHALL CONSIST OF SIX LOCK STITCHES PER INCH WITH 12/4 POLYESTER THREADS, TWISTED TOGETHER WITH 7% LUBRICATION & SILICONE PER ASTM D-6193. a�c�"v9 3??4a3i Dul FLORIDA BUILDING CODE (Non High Velocity Hurricane Zone)l A/5 ® j ® B/6 I jl�C/6 ® p/7 I 2") A /5 ANCHORS (SEE SCHEDULE 3 2 P ANCHORS (SEE SCHEDULE 3 2 " ANCHORS (SEE SCHEDULE #3 2 P. ANCHORS (SEE SCHEDULE J3 2 " ITYP) J�E/7 ANCHORS (SEE SCHEDULE #3 ON SHEET 14) F ON SHEET 14) F ON SHEET 14) F ON SHEET 14) F ON SHEET 14) i' _ E D. 1" E-D. 1" -- _- ___ 1" '--- - ---- E.D. 1" E D. --- -- O O As O mix PANEL A oMAX PANEL PP MAX PANEL PANEL SPAN (SEE SCHEDULE 11 (SEE SUIEDULE 11 ON SHlkf t3) (SEE SCFEDUIE 01 ON SHEET 13) {SEE SCHEDULE1 ON SHEET 13) �J SPAN (SEE SCHEDULE #1 ON 91EET 13) I f I ON SHEET 13) (TYP•) PANEL WIDTH niv�HUxs SEE SCHEDULE $ (SEE SCHEDULE #3 ON SHEET t3) Q ON SHEET 14) A/5 A'/5 ELEVATION FOR DIRECT WALL MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK, HOLLOW BLOCK, WOOD OR STEEL SUBSTRATE AT TOP & BOTTOM 2" L F ANCHORS (Typ,) (SEE SCHEDULE PANEL WIDTH ON SHEET 14) (SEE SCHEDULE ON SHEET 13) Q B/6 ELEVATION FOR STUDDED ANGLE WALL MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK, HOLLOW BLOCK OR WOOD SUBSTRATE AT TOP & BOTTOM 1' 2"- ANCHORS 3 Qyp,) F (SEE SCCNEDULE #3 PANEL WIDTH ON SHEET 14) SEE SCHEDULE fl ON SHEET 13) A jj� C/6 ELEVATION FOR STUDDED ANGLE FLOOR TO CEILING MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK, HOLLOW BLOCK OR WOOD SUBSTRATE AT TOP & BOTTOM SINGLE PANEL ELEVATIONS SCALE 1/2"= 1'=O" Q FABRIC SHALL ENTIRELY COVER THE OPEMP WITH NO NEED OF OVERLAPPING,-.11w t l DTH 2" F ANCHORS (Typ.) (SEE SCHEDULE #3 PANEL WIDTH ON SHEET 14) SEE SCHEDULE (N1 SHEET 13) 4 J�D/7 ELEVATION FOR STUDDED ANGLE WALL MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK, HOLLOW BLOCK OR WOOD SUBSTRATE AT TOP & STUDDED ANGLE FLOOR MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK, OR WOOD SUBSTRATE AT BOTTOM r 2 F ANCHORS �') (SEE SCHEDULE§ PANEL WIDTH ON SHEET 14) (SEE SCHEDULE ON SHEET 13) A 11K/7 ELEVATION FOR STUDDED ANGLE WALL MOUNT TO STEEL SUBSTRATE AT TOP & BOTTOM FLORIDA BUILDING CODE (Non Hiah Velocity Hurricane Zone)I EXISTING 2 X4- WOOD HEADER REQ D OJ OR J� (SEE SCHEDULE g3 ON SHExT 14) PLATE REQ'D OJ OR J1 (SEE SCHEDULE #3 ON SHEET 14) u11u If It 11 GIASs�II Win. SEPARATION AR TION TO (SEE SCHEDULE JP ON SHEET 13) rn1Lir�-n FOR DIRECT WALL MOUNT TO WOOD SUBSTRATE AT TOP & BOTTOM NOTE FOR COMBINATION OF SECTIONS - TOP AND BOTTOM MOUNTINGS CAN BE COMBINED IN ANY WAY TO SUITANY INSTALLATION. EXISTING POURED CONCRETE, GROUT FILED BLOCK HOLIAW BLOCK REQ'D ANCHORS (SEE SCHEDULE #3 EXISTING STUCCO (Typ.) ON SHEET 14)—\ PANEL SPAN (SEE SCHEDULE 11 ON Sim 13) EXISTING STUCCO (FYP•) �I I I EXISTING !I GLASSr) I II - 1 - II Min. SEPARATION TO GLASS fI(s O1�i) 12 L ANCHORS (SEE SCHEDULE #3 ON SHEET 14 IXISITNG POURED CONCRETE, GROUT FILLED BLOCK. HOLLOW BLOCK REQ'D SECTIONS A - A SCALE 3/8"=1" FOR DIRECT WALL MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK OR HOLLOW BLOCK SUBSTRATE AT TOP & BOTTOM EXISTING CONT. 1/a- THK. GALVANIZED STEEL METAL FRAME REQUIRED-7 (SEE SCHEDULE #3 ON SHEET 14) f 1 I MAA PANEL II spats SCHmUIE 11 Min. SEPARATION ON SNLfT 13) GLASS _�� TO GLASS I (SEE 13) SE I ON SEfEEf 13) I� I I �I I P EL SPAN (SEE SCHBAU #1 ON SHEET 13) DUSTING CONE. 1/87 THK. GALVANIZED STIM METAL FRAME REQUIRED (SEE SCHEDULE #3 ON SHEET 14) l I rEXISDNG METAL SHEATHING (TY0.) I /1( it �J II EXISIIN II Min. S PARATION GLASS TD GLASS !V — {SEEC�H�U 13) IS !I !i I I �1 u II11. (SEE S041DULE if ON SHM 13) - - ----- _ Uri------ E- L I I EXISTING METAL SHEATHING (Typ.) EXISTING CON1. 1/8" THK. GALVANIZED STEEL DUSTING CONT. METAL FRAME REQUIREDW! SEE SCHEDULE 3 1/8' THK GALVAlQRFT) STEEL ON SHEET 14)� FRAME REQUIRED (SEE SCHEDULE f3 ON SHEET 14) FOR DIRECT WALL MOUNT TO FOR DIRECT WALL MOUNT TO STEEL SUBSTRATE STEEL SUBSTRATE AT TOP & BOTTOM AT TOP & BOTTOM SECTIONS A'- Al SCALE 3/8"=1 " FLORIDA BUILDING CODE (Non High Velocity Hurricane Zone)l BASTING 2"x4" WOOD HEADER REC ANCHORS (SEE SCHEDULE-j ON SHEET 14) ANCHORS (SEE SCHEDULE ON SHEET 14) STUCCO (Typ.) PANEL SPAN (SEE SCHEDULE J1 ON SHEET 13) EXISTING STUCCO (Typ.) FOR STUDDED ANGLE WALL MOUNT TO WOOD'SUBSTRATE AT TOP & BOTTOM NOTE FOR COMBINATION OF SECTIONS: TOP AND BOTTOM MOUNTINGS CAN BE COMBINED IN ANY WAY TO SUITANY INSTALLATION. EXISTING POURED CONCRETE, GROUT FILLED BLOCK HOLLOW BLOCK RETE ANCHORS (SEE SCHEDULE ON SHEET 14) 1— GLASS—J I — II _ I I I I I f I MIN. SEPARATION 11 TO GLASS (SEE SCHEDULE 12 h'1 ON SHEET 13) V� ANCHORS (SEE SCHEDULE ON SHEET 14) EX=NG POURED CONCF GROUT FILLED HOLLOW BLACK PANEL. SPAN (SEE SCHEDULE §1 ON SHEET 13) FOR STUDDED ANGLE WALL MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK OR HOLLOW BLOCK SUBSTRATE AT TOP & BOTTOM SECTIONS B - B SCALE 3/8"=1" 4" x 8" OI OR 12 OR 13 (SEE SCHEDULE #3 OOSnm ON SHEET 14) POURED CONCRETE, GROUT FILLED BLOCK OR ^"., HOLLOW BLOCK REC'D ANCHORS )—DDSTING 1 (SEE SCHEDULE �k3 ON SHEET 14) _ OF EXISTING WOOD BEAM TO BE CERTIFIED BY PROFESSIONAL ENGINEER OR ARCHITECT PRIOR TO PANEL INSTALLATION. I tl II II 11 II I I EXISTING II II cEAss II II II A PANEL II 11 i MINTSEPARATION SPAN GLASS SCHEDULE �2 �( (SEE 1 I I I I I pN SHEET 13) il Dm SHEET 3) I [ — I II — I{ MINT GLASS ON O (SEE SCHEDULE $2 f EXISTING I I N SHEET 13) II 1 6 II I It DOsTIN(i Hi MIN. 2"x4" WOOD SUCK REO'D. 1 NO FINISH F ALLOWED GE OF DECK APPUCABLE (EYP.) PANEL SPAN (SEE SCHEDULE 81 ON SHEET 13) t.U. U. �// / EXISTING ANCHORS POURE'DONCETEGROUTDFILLED RBLOCK O O �I OR f2 (SEEMTt4t4)SCHEDULE: �3 HOLLOW BLOCK REO'D N SHEET (SEE SCHEDULE g3 ON SHEET 14) FOR STUDDED ANGLE FLOOR TO CEILING MOUNT FOR STUDDED ANGLE FLOOR TO CEILING MOUNT TO WOOD SUBSTRATE AT TOP & BOTTOM TO POURED CONCRETE, GROUT FILLED BLOCK OR HOLLOW BLOCK SUBSTRATE AT TOP & BOTTOM SECTIONS C ' C SCALE 3/8"=1" FLORIDA BUILDING CODE (Non High Velocity Hurricane Zone 4 EXISTING 2'x4' NA HEADER REQ'D I1Jn�u• I I II MIN. SEPARATION CLASS (SEE TO#2 11 I I tl I I I I ON SHOT i3) It 11 III J � EXISTING MIN. 2SUCK } WOOD BUCK 11 REQ'D. t�l OR .f (SEE SCHEDULE #3 ON SHEET 14) DOSDNG CONE: _ STUCCO 15 EEL METAL GALVANIZED FRAME M� ON SHEET 14LE $3 REQUIRED - ) ANCHORS (SEE SCHEDULE #3 ON SHEET 14) I PANEL SPAN (SEE SCHEDULE 11 ON SHEET 13) NO FINISH ALLOWED FOR STUDDED ANGLE WALL MOUNT TO WOOD SUBSTRATE AT TOP & STUDDED ANGLE FLOOR MOUNT TO WOOD SUBSTRATE AT BOTTOM NOTE FOR COMBINATION OF SECTIONS: TOP AND BOTTOM MOUNTINGS CAN BE COMBINED IN ANY WAY TO SUIT ANY INSTALLATION. EDGE OF DECK IF APPLICABLE (M.) SECTIONS D - D SCALE 3/8"=1" EXISTING POURED CONCRETE, GROUT FILLED BLOCK_ HOLLOW BLOCK REQ'D E)aSpNGG GLASS II _ fl MIN SEPARATION TO GLASS I I (SEE CH #2 )) I I tl 1 I Il ANCHORS {SEE SCHEDUU ON SHEET 14) FOR STUDDED ANGLE WALL MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK OR HOLLOW BLOCK SUBSTRATE AT TOP & STUDDED ANGLE FLOOR MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK OR HOLLOW BLOCK SUBSTRATE AT BOTTOM MErAL SHEATHING (Typ.) ETEQ H1 B EXLSDNO FLASHING n I I A Elam II MEN. SEPARATION GLAss TO GLASS -(� SCHEDULE Il- PANEL SPAN (SEE SCHEDULE #1 It II ON SHEET j jl 13) U n b NO CONT. V / EXISTING - - STING METAL. SHEATHING (Typ.) THK. GALVANIZED . METAL FRAME RED M1 (SEE SCHEDULE J3 ON SHEET 14) FOR STUDDED ANGLE WALL MOUNT TO STEEL SUBSTRATE AT TOP & BOTTOM SECTIONS E - E SCALE 3/8"=1" FLORIDA BUILDING CODE (Non High Velocity Hurricane Zo J�F ANCHORS " (SEE SCHDUIE #3 ON SHEET 14) 2" 2 (Typ.) F (Typ.) o---=--Q --- E. D. 2p PANEL WIDTH (SEE SCHEDULE #1 ON SHEET 13) A 6 PANEL SPAN (SEE SCHEDULE 11 ON SHEET 13) 2"rA (Typ .) 1vj PANE WIDTH ANCHORS (SEE SCHEDULE (SEE SCHDULE #3 ON SHEET 13) A ON SHEET 14) 1 ' F ELEVATION FOR REVERSED STUDDED ANGLE WALL MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK, HOLLOW BLOCK OR WOOD SUBSTRATE - AT TOP & BOTTOM rI ANCHORS (SEE SCHDULE #3 UN SHEET 14) EXISTING 2"x4" WOOD HEADER REQ tH 8 PANEL SPAN (sEE SCHEDULE #1 ON SHEET 13) EX{STING II GPI MIN SEPARATION PANEL TO GLASS SPAN I (SEE SCHEDULE #2 (SEE SCHEDULE 11 I ON SHEET 13) ON SHEET 13) I I I I 8 N. lH ANCHORS (SEE SCHDULE #3 ON SHEET 14) ELEVATION FOR REVERSED STUDDED ANGLE FLOOR TO CEILING MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK, HOLLOW BLOCK OR WOOD SUBSTRATE AT TOP & BOTTOM SINGLE PANEL (REVERSED) ELEVATIONS SCALE 1/2"= 1" A FABRIC SHALL ENTIRELY COVER EXISTING 2"x4' WOOD PLATE REQ! EXISTING POURED CONCRETE OR GROUT FILLED OR HOLLOW EXISTING BLOCK READ STUCCO (Typ.) ` iv I ,wn r. _ r EXISTING GLASSI MIN ANCHORS II SEPARATION (SEE SCHDULE #3 I TO GLASS j�(SEE SCHEDULE #2 ON SHEET 14) MAX• II ON SHEET 13) PANEL SPAN Ei = (SEE SCHEDULE /1 EXTERIOR ON SHEET 13) I (SEE SCHDULE #3 ON SHEET 14) ANCHORS (SEE SCHDULE #3 ON SHEET 14) EXTERIOR 0 OR @oR (13 (SEE SCHEDULE #3 ON SHEET 14) 4" x 8" (Min.) EXISTING WOOD BEAM REQUIRED. STRUCTURAL ADEQUACY_ OF EXISTING - WOOD BEAM TO BE CERTIFIED BY PROFESSIONAL ENGINEER OR ARCHITECT PRIOR TO PANEL INSTALLATION. EXISTING POURED CONCRETE OR GROUT FILLED OR HOLLOW BLOCK REQ'D ANCHORS (SEE SCHDULE #3 ON SHEET 14) V I I EXISTING CLASS TI \ J II II ; II NW. SEPARATION TO GLASS (SEE SCHEDULE #2 ON SHEET 13) I II 1 EXISTING TH MIN_ 2"x4" WOOD BUCK REQ'D. UI OR 12 (SEE SCHEDULE #3 ON SHEET 14) EXISTING POURED CONCRETE, GROUT FILLED BLOCK OR ANCHORS HOLLOW BLOCK REQ'D (SEE SCHEDULE #3 11V ON SHEET 14) 1\ \ % \\11 EXTERIOR 11 EXTERIOR OOSnt II GLASS II A MAX. I I MAX. SPANPANEL f f PANEL (SEE SCHEDULE 11 II (SEE SCHEDULE #1 ON SHEET 13) II Uk SEPAHA710N ON SHEET 13) EDGE OF DECK I IF APPLICABLE (TYP.) 10 Om(SEE SCKENULE 2 11 ON SHEET 13) it II I TH ANCHORS (SEE SCHEDULE 3 ON SHEET' 14 j/ EXISTING POURED CONCRETE, GROUT FILLED BLOCK HOLLOW BLOCK REM FOR REVERSED STUDDED ANGLE FOR REVERSED STUDDED ANGLE FOR REVERSED STUDDED ANGLE WALL MOUNT TO WOOD SUBSTRATE - WALL MOUNT TO -POURED CONCRETE, FOR REVERSED STUDDED ANGLE FLOOR TO CEILING MOUNT AT TOP & BOTTOM GROUT FILLED BLOCK OR FLOOR TO CEILING MOUNT TO POURED CONCRETE, HOLLOW BLOCK SUBSTRATE TO WOOD SUBSTRATE GROUT FILLED BLOCK OR AT TOP & BOTTOM AT TOP &BOTTOM HOLLOW BLOCK SUBSTRATE AT TOP & BOTTOM SECTIONS F - F SECTIONS F' - F SCALE 3/8"=1" SCALE 3/8"=1" THE OPENING WIDTH NOTE FOR COMBINATION OF SECTIONS: WITH NO NEED OF TOP AND BOTTOM MOUNTINGS CAN BE COMBINED IN OVERLAPPING BEYOND IT ANYWAY TO SUIT ANY INSTALLATION. FLORIDA BUILDING CODE (Non High Velocity Hurricane Zone @2015 TILTECO INC. GPP FABRIC SHUTTER — SERIES 2000 F.R.L iL EC O INC. DRAWN BY GLOBAL PROTECTION PRODUCTS, LLC. 03/12/15 DATE 4800 S.W_ 51 STREET JT TEMNG & ENGINEERING COMPANY Tiw. 36M St., St.. 30S - YMNA "MENS, Fl. 3316S Phase : (M5) 871-1530 , Fm[ : (305) 871-IS31 DAVIE, EL 33314 PHONE (954)6BD-7545, FAX: (954)689-8797 f 5-020 e-ail: ti{teco®aol.Com m DRAWING IT Fm wl DEGarm WE jw/wI 00oww 1 I WE EB-0006719 1 Din 11-212 oa/tt/u 3 SHEET 8 OF 15 WALTER A TILER Jr., P.E. ` A (•gyp,) ANCHORS ` G (TrPJ % (SEE SCHEDULE #3A OVERL 7 I` ov Rtar'� / ON SHEET 15) o- o— +1 0 0 1 I 1 •I I I 1 I +I 4 1 H H +I I I 1 o o o + r C W/o-,,. I t ® 12" o.c. � t •I t I �I 1 1 i 0 0 +I o 0 ol .9O C,,-� G mrp) / A (Typ-) PANEL WIDTH PANEL WIDTH PANEL WIDTH SEE SCHEDULE # SEE SCHEDULE SEE SCHEDULE # ON SHEET 13) ON SHEET 13) ON SHEET 13) A ELEVATION FOR DIRECT WALL MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK, HOLLOW BLOCK OR WOOD SUBSTRATE AT TOP & BOTTOM 3" 1'{ �'` 3' _RL I CTMp•) I I avlkw WIDTH PANEL WIDTHqj�NELSCHEDULE PANEL WIDTH EE SCHEDULE SHEET 13) V__(SEE SCHEDULE ON SHEET 13) ON SHEET 13) EXTERIOR PLAN OVERLAPPED MULTIPLE PANELS SCALE 1/2"= 1'—O" O OR J1 (SEE SCHEDULE #3A ON SHEET 15) PANEL SPAN (SEE SCHEDULE #1 ON SHEEP' 13) ED. A FABRIC SHALL ENTIRELY COVER THE OPENING WIDTH WITH NO NEED OF OVERLAPPING BEYOND IT EXISTING 2"x4" WOOD HEADER REQ'D ANCHORS (SEE SCHEDULE #3A ON SHEET 15) OOR Jl (SEE SCHEDULE #3A ON SHEET 15) L=a R I = 11 h it I1 I I II I1 It EXISTING 'I GLASS j� Min. SEPARATION ij _(SEETSCHEDULE II ON SHEET 13) I I II it iI I Ij �I EXISTING 2"x4" WOOD - PLATE REQ'D FOR DIRECT WALL MOUNT TO WOOD SUBSTRATE AT TOP & BOTTOM OTE FOR COMBINATION OF SECTIONS: P AND BOTTOM MOUNTINGS CAN BE COMBINED IN WAY TO SUIT ANY INSTALLATION. STUCCO (TYP.) D W/O ® 12" O.C. (rrp-) PANEL SPAN (SEE SCHEDULE #1 ON SHEET 13) EXISTING STUCCO (TYP-) SECTI (AT OVF EXISTING POURED CONCRETE, GROUT FILLED BLOCK OR HOLLOW BLOCK REQ'D ANCHORS (SEE SCHEDULE #3A ON SHEET 15) .a I 1r 11 II EXISTING GLASS �I I I 1� Min. SEPARATION TO GLASS I�_(SEE SCHEDULE 11 ON SHEET 13) tl I I I I I !I I I i1 Ir II I1 I I EXISTING POURED CONCRETE, GROUT FILLED BLOCK OR HOLLOW BLOCK REQ'D -- G ANCHORS (SEE SCHEDULE #3A ON SHEET 15) 12" (TYP-) PANEL SPAN (SEE SCHEDULE #1 ON SHEET 13) FOR DIRECT WALL MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK OR HOLLOW BLOCK SUBSTRATE AT TOP & BOTTOM FLORIDA BUILDING CODE INTERIOR 3" 0 12" o.c. SECTION H - H SCALE 3/8"=1" h Velocity Humcdne Zone 1 (� D im'.) I' A v} Dv � I r OVE;0 I I� 1 J I; J SCHEDULE 13A HEET 15) O ORO (SEE SCHEDULE #3A ON SHEET 15) EXISTING 2"x4" WOOD HEADER REQ,D STUCCO Cw.) O 11 0 11 O I Jx. r---1- MM 9 0 12" a.(. 2^ L.-. PANEL WIDTH PANEL WIDTH PANEL WIDTH SEE SCHEDULE SEE SCHEDULE SEE SCHEDULE ON SHEET' 13) ON SHEEP' 13) ON SHEET 13) ELEVATION FOR DIRECT WALL MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK, .HOLLOW BLOCK OR WOOD SUBSTRATE AT TOP & BOTTOM C W/ H 3" 0 12" o.c. 3" OVE3tLAP 1 roJiLAP PANEL WIDTH EE SCHEDULE ON SHEET 13) PANEL WIDTH EE SCHEDULE ON SHEEP' 15) PANEL WIDTH EE SCHEDULE ON SHEET' 13, PLAN SAFETY PANEL FOR DOORS W/ OVERLAPPED MULTIPLE PANELS SCALE 1/2"= V-0" Q FA13RIC SHALL ENTIRELY COVER THE OPENING WIDTH WITH NO NEED OF OVERLAPPING BEYOND IT SPIN (SEE SCHEDULE #1 ON SHEET 13) E.D. ANCHORS (SEE SCHEDULE 03A ON SHEET 15) lul11I= I I I I I I I tiJ a 12" O.C. I 11 �•) If I it 11 EXISTIN��II class { 1 I If Min. SEPARATION TO GLASS SEE SCHEDULE tl ON SHEET 13) li I I 11� 111 I; I; I I ��II p 1 I ++�� � li 1 I —I 1 OJ OR .f1 (SEE SCHEDULE #3A ON SHEET 15) EXISTING 2"x4" WOOD - PLATE REQ'D (Typ-) FOR DIRECT WALL MOUNT TO WOOD SUBSTRATEAT TOP & BOTTOM NOTE FOR COMBINATION OF SECTIONS: TOP AND BOTTOM MOUNTINGS CAN BE COMBINED IN ANY WAY TO SUIT ANY INSTAUATION. (m'.) 9 PANEL SPAN (SEE SCHEDULE #1 ON SHEET 13) ANCHORS (SEE SCHEDULE 13A ON SHEET 15) EXISRNG POURED CONCR GROUT FILLED I HOLLOW BLOCK 9 OC W/ H IIo.c. PANEL 11 SPAN it (SEE SCHEDULE #1 II ON SHEET 13) If GLASS GLASS II If If I� I Min SEPARATION 1 " INTERIOR TO GLASS (TYP.) SCHEDULE IF/ - ON SHEET 13) I I I I{ POUREDG CONCRETE GROUT FlUED BLOCK HOLLOW BLOCK REWD ANCHORS (SEE SCHEDULE #3A ON SHEET 15) 01, 9 FOR DIRECT WALL MOUNT TO POURED CONCRETE, GROUT FILLED BLOCK OR HOLLOW BLOCK SUBSTRATE SECTIONS I - I AT TOP & BOTTOM OVERLP D FABRIC) ® 12" o.a SECTION J - J N.T.S. FLORIDA BUILDING CODE (Non High Velocity Hurricane Zone) GPP FABRIC SHUTTER — SERIES 2000 F.R.L ®2015 TILTECO INC. DRAWN BY GLOBAL PROTECTION PRODUCTS, LLC. 03/D^2E 15 TIWT TESTING $ ENGINEERING COMPANY 4800 S.W. 51 STREET UM N.W. 3M Sk. Ste. = — VIRMA GAEMM R. 33166 DAVIT FL 33314 5-020 Pj- : (3M) 871—ISM . 1-m[ : (3os) 921-1531 PHONE (954)689-7W, FAX: (954)689-8797 e—mail: Slteco®aol.com EB—BOD6719 or M CESC aMM I WE INLVWI LESfltpum I WE DRAWING W WALmE TTLLIT Jr.., P.E. 1 OW11-s12 os/12/ts 3 a c-s 1 1 SHEET 10 OF 15 2. (TyP•) ► K ANCHORS r —CMSEE SCHEDULE #3 SHEET 14) - - I- D. O PANEL PANEL $PAN (SEE SCHEDULE #1 ON SHEEP 13) 8" Max. �P-) C 'O 2- L --- —_-- _-- OVERLAP 11� (Typ") L PANEL WIDTH {SEE SCHEDULE ON SHEET 13) 10,K ANCHORS (SEE SCHEDULE f3 ON SHEET 14) SAFETY SINGLE PANEL FOR SINGLE HUNG WINDOWS SCALE 1/2"= V-0" A FABRIC SHALL ENTIRELY COVER THE OPENING WIDTH WITH NO NEED OF OVERLAPPING BEYOND IT. REQUIRED ANCHORS (SEE SCHE ON SHEET EXISTING n4" WOOD PLATE REQ'D Min. b 11 II MIN. SEPARATION f TO GLASS (S O S E 13) ON SHEET 13) ,I E)ds,nNG--f GLASS ll II 15* li I I I I I I I I I I1 11 I I I, I I I I I I I I I EXISTING POURED CONCRETE. STUCCO (TyA-) GROUT FILLED BLOCK HOLLOW BLOCK REQ'D ANCHORS (SEE SCHEDULE $3 ON SHEET 14) I MIN. SEPARATION TO GLASS ADSCHEDULE # I ON SHEET 13) fl I�fIS71NG—�1 I CAASS II I I SLAP I I MrA L II I I !t 1! MAX. 1 I PANEL I I SPAN I I I I (SEE SCHEDULE #1 II ON SHEET 13) II 1 I I 11 I I i! 11 ANCHORS (SEE SCHEDULE #3 ON SHEET 14) — EXISTING POURED CONCRETE. GROUT n rn BLOCK HOLLOW BLOCK REQ'D PANEL SPAN (SEE SCHEDULE $1 ON SHEET 13) (ryp-) FOR DIRECT WALL MOUNT TO V I (SEE SCHEDULE $3 ON SHEET 14) FOR DIRECT WALL MOUNT TO WOOD SUBSTRATE AT TOP & BOTTOM SECTIONS K - K SCALE 3/8"=1" NOTE FOR COMBINATION OF SECTIONS: TOP AND BOTTOM MOUNTINGS CAN BE COMBINED IN . ANY WAY TO SUIT ANY INSTALLATION. FILLED BLOCK OR H T( V3 L k:- ' e6e 4 M t O'O O r ox- OVERLAP DETAIL SCALE 3/8"=1" FLORIDA BUILDING CODE (Non High Velocity Hurricane Zone) 02015 TILTECO INC. GPP FABRIC SHUTTER - SERIES 2000 F.R.L. DRAWN BY 01 GLOBAL PROTECTION PRODUCTS, LLC. 5 03/DATR/1LIEC N TILLIT TESTING & ENGINEERING COMPANY 4800 S.W. 51 STREET sus tiw 36th St. Ste 3IX1 — vtRGpYIA 6IRDt?LS PL 33566 Fho : (xs) sit-15" , Fm : (aas) 67t-ts3e DAME, FL 33314—�2fl PHONE. (954)689-7545, FAX: (954)689-8797 e-mail: 1,lteco@aol.com EB-0006719 K ° QUE I RLV M neSMP N D= DRAWING If WALTER A TILrr Jr.." P.E. t 01O 11-212 03/12/16 3 SHEET 11 OF 15 ANCHORS 2. I'M ��--((SEE SCHEDULE3 / ON SHEET 14) ANCHORS EXISTING STUCCO (TYP•) (SEE SCHEDULE r 4 „ ._, ON SHEET 14) ED. PANEL MAX. PANEL. SPAN E I qO (SEE SCHEDULE 11 Ij ON SHEET 13) E.D.------------ 1 ANCHORS 2" J�m SEE SCHEDULE #3 (Typ•) ON SHIN 14) PANEL WIDTH -(SEE SCHEDULE # ON SHE7 13) A ELEVATION FOR DRECT WALL MOUNT TO POURED CONCREfF, GROUT FILLED BLOCK OR HOLLOW BLOCK & WOOD SUBSTRATE AT TOP $BOTTOM O OR .)1 (SEE SCHEDULE J3 ON SHEET 14) EXISTING M* 2"x4" WOOD HEADER REQ OFFSET TOP VS BOTTOM iM X.) SINGLE PANEL SCALE 1/2"= 1'-0" A FABRIC SHALL ENTIRELY COVER THE OPENING WIDTH WITH NO NEED OF OVERLAPPING BEYOND IT. OTE FOR COMBINATION OF SECTIONS: OP AND BOTTOM MOUNTINGS CAN BE COMBINED IN Y WAY TO SUIT ANY INSTALLATION. SECTIONS M - M n SCALE 3/8"=1- n I I II I I A I I I li t —�/�- Min. SEPARATION TO GLASS ® MID EFFECTIVE PANEL SPAN — EX1STiNG —(SEE SCHEDULE #2 ON SHEET 13) GLASS {I I I fl LI 6" MAX. Of (MAX.) EXISTING LEDGE (ANY MATERIAL) EXISTING 2"x4" WOOR PLATE REQ O OR J1 (SEE SCHEDULE #3 ON SHEET t4) ELEVATION FOR DIRECT WALL MOUNTTO WOOD SUBSTRATE AT TOP & BOTTOM PANEL MAX. PANEL SPAN (SEE SCHEDULE #1 ON SHEET 13) POURED CONCRETE, GROUT FILLED BLOCK OR II HOLLOW BLOCK REQ'D II A if " Min. SEPARATION TO GLASS C@ MID EFFECTIVE PANEL SPAN — GI1SS ; I (SEE SCHEDULE #2 ON SHEET 13) ii �1 I - r- 6" MAX. Of aE Y No. 44167 9 1%8" (MAX-) ('u'A)L) EXISTING LEDGE (ANY MATERIAL) / ANCHORS (SEE SCHEDULE #3 ON SHEET 14) POURED CONCRETE. GROUT FILLED BLOCK OR HOLLOW BLOCK REQ'D PANEL. MAX. PANEL SPAN (SEE SCHEDULE y 1 ON SHEET 13) I3 ELEVATION FOR DIRECT WALL MOUNTTO POURED ggNi:RMGROLYTRWEDBLOCKORHDLLOWBLOCK SUBSTRATE AT TOP & BOTTOM FLORIDA BUILDING CODE (Non High Velocity Hurricane Zone) @2015 TILTECO INC. 1L EC O Inc. TILLJV IMING & ENGINEERING COMPANY 6355 N.W. 31 K SL. Ste. 30 — VIRGINIA GERM% FL 33166 Plw. .: (=) B71-153D RX : (305) 871-1531 e-mail: tilteco®aoLcom EB-0006719 WALTER A. TILLJT Jr., P.E. GPP FABRIC SHUTTER - SERIES 2000 F-R.L DRAWN I3r GLOBAL PROTECTION PRODUCTS, LLC. 03"'22-'5 4800 S.W. 51 STREET DAME, FL 33314 i 5-02� PHONE (954)689-7545. FAX: (954)689-8797 sy o1scR71101 I WE � N mm I DRAWING W t I an 11-212 03fivis 3 SHEET 12 OF 15 SCHEDULE # 1 MAXIMUM A.S.D. DESIGN PRESSURE RATING, CORRESPONDING MAXIMUM PANEL SPAN & MAXIMUM & MINIMUM PANEL WIDTH FOR OVERLAPPED MAXIMUM FOR SINGLE PANELS MULTIPLE PANELS IMPACT A.S.D. DESIGN MAXIMUM RESISTANCE PRESSURE PANEL SPAN MISSILE TYPE MAXIMUM & APPLICABLE TO MAXIMUM & APPLICABLE TO RATING �•} MINIMUM SECTIONS & ANY MINIMUM SECTIONS & ANY & SPEED , �p'S'�� PANEL WIDTH COMBINATION OF PANEL WIDTH COMBINATION (ft.) (ft.} . THEM OF THEM MAX. MIN. MAX. MIN. 60.00 ORLESS 12'- 7 " 12'-0"t 2'-4" A'� A'-A',B-B, 12'-0"t 2'-4" G-G D—D,E—E&F—F TYPE D50ftlsec. 75.00 OR LESS 8'— 7 " 12'-0"t 1'—oil A-AA'—A',B—BD—D, 12 —0al t 2 —4 G—G&I—I E-E,F—F&M-M 75.00 OR LESS 61- 711 12'-01"t 2'-4" K-K - - - t USE MAXIMUM PANEL WIDTH OF 6'-6" FOR INSTALLATIONS WITHIN WIND ZONE 4, AS DEFINED BY SECTION 6.2.2.4 OF ASTM E 1996 STANDARD. SCHEDULE # 2 MINIMUM SEPARATION TO GLASS FOR SINGLE & OVERLAPPED MULTIPLE PANEL REQUIRED MIN. MAXIMUM SEPARATION TO A.S.D. DESIGN MAXIMUM GLASS MEASURED TO PRESSURE PANEL BACK OF FABRIC (in) SPAN RATING (P sf ) (ft.) WIND ZONES NE ZONE _ I THRU 3 4 60.0 OR LESS 12 ' — 711 1 " 0 34 1 /2 " 75.0 OR LESS 8 ' — 711 1" A. 28 5/8 " 75.0 OR LESS 6 ' — 7 " 1" A 1531891 A MINIMUM SEPARATION TO GLASS MAY BE REDUCED TO 1/4" ONLY FOR INSTALLATION W18'-0" PANEL SPAN AND FOR INSTALLATION INTO WOOD FRAME BUILDING. * PER ASTM E 1996 STANDARD W/ A BASIC WIND SPEED IN EXCESS OF 175 M.P.H. FLORIDA BUILDING CODE (Non High Velocity Hurricane SCHEDULE # 3 MAXIMUM A.S.D. DESIGN PRESSURE RATING (p s f )AND CORRESPONDING MAXIMUM ANCHOR SPACING FOR SINGLE PANELS DIRECT MOUNT OR WALL MOUNT W1 STUDDED ANGLE I n 12 l3 5116"o ELCO 5115'0 ELCO IWO ELCO ULTRACON ANCHOR 5116"0 ITW BUILDER TAPCON XL ANCHOR ULTRACON ULTRACON MAXIMUM ANCHOR ANCHOR MAXIMUM PANEL APPLICABLETO BA SEBINA1 A.S.D. DESIGN TOCONCREfE TOGROLRRIED TO HOLLOW BLOCK TO WOOD TOCONCRETE TOGROUfFlLLED TO HOLLOW BLOCK TO WOOD TOWOOD SPAN O F COMMBINATION OF PRESSURE BLOCK BLOCK in) THEM (P-SA) WIMRREQD. WIMN.REOD. WI MIN.REOD. WIMt4RE0D. WIMFLREQD. WIMN.REQD. WILMREOD. WIMURE09. WPUKREQ11 fc=2700p.s.L fm=1924p.s.L fm=1924ps.L G=0.55 fc=2899ps.L fm=1872ps.L fm=1872psi G=0.55 G=0.55 1314' embedment 1 114' embedment 1 tlV embedment 1" Thread. Pent 2114" embedment 2 114'embedmed 1 lie embedment 1' Thread. Penes 2' Thread_ Penet 3118' ED. 2117 ED. 212' ED. 2"E.D. 3115' ED. 4 ED. 4' ED. 310 E.D. 310 E.D. 30.00 ORLESS 7" 512" 412' 212" B. - 8' 7" 5' B" B-B,D-D[IOP) 30.00 -45.00 5° 4' N/A 2' 8° 8" 5' 3112' 712° 12' • 7" & F-F 45.00 -60.00 4' WA NIA 112' 712' 712' 4- 3- 6" 37,50 ORLESS 7" 5' 412. 212' S. 7. 412' 8' 37.50 756.25 S. WA NIA 2" B' 8' 5' 312' 7" 8' • 7" B-B& M-M 56.25 - 75.00 4- WA NIA 1 12' 712 " 712' 4. 3- 512 " 37.50 ORLESS 8" 8" 8" 512' 8' 8' 8" 8- 8° B-BD-D(TOP), 37.60 -56.25 S. 8" 6' 4' S. 8' 8" 7' 8" 8'- 7" F-FM-M 56.25-75.00 712" S. 4112" 3' 8° 8" 612" 5i2` 8" & K-K J Jl K. Ki MAXIMUM A.S.D.MAXIMUM iteo ELCO PANELMATEPRO 114 o ELCO FEMALE ID PANELMATE 114°OALLP01NiSOUDSET 12'o ELCO PANELMATE'L" INSERT P Q AppLICABLE TO SECTIONS DESIGN TOHOLLOWELoatOR TOWOOD TOCONCREIE TOHOLLOWROCKOR TOWOOD TOWHOREIE TOHOLLOW TOCONCREE TOGROLRFLLED TOHOLLOWOLOCK SPAN &ANY TbMKREIE GROUTMMELOd( GEmUfFtL1�i�0Ui BLOCK BLOCK (E) COMBINATION PRESSURE t90LriYREQO. LgJMtLREOD W1E@LRE4D. 1YIMHREOD. YllYLV REQD. WlMN REO'D. WIMIL"D WIM&REO'D. WIMURCOTL WIMILREOi1 W/INN LZEQD. OFTH1Dt RATING(ps.E) fa=3350p.s1. fm=2071p.s.L G=0.55 fc=3350psi. fm=2071psi G=0.55 rc=3000p.s.L fm=1800psi fc=207lp.si fm=2676p.s.i. fm=1794p.s.L 7embddment 11W'embeftmd 17I8"Thre2d.Pmxt 1314 embedment lil4 embedment 1718'Threa4Penet 70embedment 7/8"enbedment 1518'embedment 1114embedment 1114"embedment 21re F.D. 3' E0. 314' E.D. 2117 E.D. 7 ED. 31,r E.Q. 31 E.D. 3' E.D. C E.D. 31/2' ED. 310H.D. 30.00 ORLESS 8" 5" 7° 7" NIA 7' 8' 6V2' 8' 8" 8' A -AB-$ 30.00 -45.00 612" WA 5" 5° NIA 5' 612" 4112" 7' 6° 5112` 12' • 7" D-D(1'OP) 4500-60.00 S. NIA 4- NIA NIA 4" 5' 3V2' SV2' 412' 412" &F-F 37.50 ORLESS 8" 4V2° 6112' 61/2.' NIA 612' 8' 6° 8" 8' 8° 8'' 7' A-AB-B, & M-M 3750 -5625 6t2' NIA 5' 412' NIA 5' B" 4112' 7" 5V2' 5V2" 5625-75.00 5' NIA 4- N/A' WA 4" 5' 312' SV2' 4112' 4112' 50 OR LESS 8' 8' 8' 8° 712' B" 8" 8' 6' B" 8' A-A.B-B. L7-0-5825 $' 812' 8' B 512' 8• 8° 8' 8' 8' 8 6•7'25-75.00 8' §' B. 712" 4- 8° 8' 612' 8- 8' p M M1 N P 114°d ELCO 114 D ELCO 12 o POWER CALK -IN 3Wo ELCO MODIFIED CONFLE( 5/1910 ELCO HANGERMATE HANGERMATE FAB-LOCK HD ANCHOR MAXIMUM APPLICABLE TO MAXIMUM PANEL SECTION56ANY A.S.D. DESIGN TOCOWMM TO(LOUTFL[ED TOHDLL(YlYBLOCK TQCON(ItEiE TOHOLLOWHOCK 70A38STEEL T018GAGE TOCONtXtELE TOHbLLOW BLOCK CONBNOF PRESSURE BLOCK STD (ft.)THEN THEM THEM RATING(p.sf.) WMN.REQD W1MN.REQD. gWUKREO'D. W1ARLREQCL WIMNRECD. W/NKFIM0, WI LetRC-LL'0. MMKRMR W/MItREUM re=1819psi rm=2400p.s.i ftm=2400ps.L fc=3650p.s.L fm=1872p.s.L 118'thk.(A36) 30k.s.i. fe=3D00p.s.L fm=1500ps.L 2 !2° embedment 1314' embedment 1 lie embedment 2' embedment 1 114' embedment 118' Threaded 1/8' Threaded 1 11P embedment 1 12' w&-dmeii 3 314- E.D. 211d' E D. 21IX' E.D. 3 Ifir E.[l. 311W E.D. t 3W ED. I Yr E.D. 8' ED. 8' ED. 30.00 OR LESS 8' 6 V2" S. S. 512" 8". 8' 8' *1 A-A,A-A, 8' 4In' 3112 B WA 0"8"8'61I2" 12' • 7" B-B,D-D(rOP), 8 4" 2V2" 812" NIA 7- 7' 8' S'B-fi & F-F [30.00 8' 6' S B 58` 8' 8' 412" 312' 8' NIA 8' 8' 8" 812' 8' • 7' g M-M w 58.25 -75.00 8" 312" 3" 812' NIA 7' 7" 8" 5" 37.50 OR LESS 8' B' 8° 8' B" 8'- B" 8° 8" A-A.A-A', a' B-B,D-1)piq; 37.50-56.25 B' 8" 6' 8' 7" 8' 8' 8° B. 6-- 7" B.B,F-FM-M 66.25-75.00 8' 7- 4112"8 512" 8" 8" 8° B. 1 & K-K FLOOR/CEILING MOUNT WI STUDDED ANGLE a � MAXIMUM IWO ELCO ULTRACON ANCHOR 5116°0 ITW SUILDEX TAPGON XLANCHOR APPLICABLETO A.S.D. HIPA14EL ! sEc71oNs 8 PANELANY DESIGN. TOCONCRELE TOGROLITFO.LED TO HOLLOW BLOCK TOWOOD TO CONCRETE TOG BLOCK LEO TO HO110W BLOCK SPAN COMBINATION PRESSURE BLOCK (R) RATING 41K W/hREQD. WMRREQD. VaIVIRREQD. W1MN.R EGE WILAKREOD. WIMKREQD. WIMIKREQD. OFTHEM (p.S.f) fc=2700p.s.L fm=1924p.s.L fm=1924p.s.L G=0.65 fc-28Mp-s.1 fm=1872p.s.L fm-1372p.s.L 13/4° embedment 1 1/4" embedment 1 1I4" embedme 1Thread. Penet 2114- embedment 2 i/4' embedmerk 1114' enbedma 3118" E.D. 212' ED. 212' H.D. 2' E.D. 31/8' E.D. 4' E.D. 4 E.D. 30.00 OR LESS 712' 7" WA 4- 8' 8 ° 5' C-C, 30.00 - 46.00 512 ' 5. NIA 3- 8 ° 8 " NIA 12 ' . 7 " D - D (BOTTOM) 45.00 -60.OQ 4' N/A NIA 212' 712° 8 ° NIA 12 D 5116"0 ELCO 51160 ELCO MAXIMUM ULTRACON ULTRACON APPUCABLETO ANCHOR ANCHOR MAXIM LM SECTIONS 8 DESIGN BI PRESSURE TOWOOD TOWOOD SPAN CCOMBINATIONNATION RATING ) OFTHEM W/MN.RECD. W/M9J.REQ0. G = 0.55 G = 0.55 1' Thread. Penet 2" Thread. Penet 310 ED. 3 !/8" ED. 30.00 ORLESS, 512" 8` 12'- 7" C-C. D-D(BOTRM) & F' -F' 30.00 -45.00 4' 1 8" 45.00 - 60.00 3'1 8112" K Ki p 1120 POWER CALK -IN MAMUM XI 1/4'eALL POINTSOUDSET In"o B-00 PANELMATE "L' INSERT ANCHOR MAXIMUM APPLICABLTO E A.S.D. PANEL SECTIONS& DESIGN PRESSURE TOCONMERE TORO LOWBLOCK TOOONCREfE TOGRDU7FLLED TOIIOLLCWBLOCH TOCONCRETE T BL� SPAN COMBINATION BLOCK (�) RATING W/MN.REID. WIMKIWO. W1MN.REVI). 0MN. REgD. WAANAECM. W/MILR;EOD. WIMM-PEQI, OF THEM (p.sf.) fc=3000p.s.L fm=1800p.si. fc=2071p.s.L fro =2876p.s.i. fm=1794p.s.i rc=3CO13p.sA fm=1500p.s.i. 71W embedment 7/8' embedment 15/8" embedment 1 1/4" embedment 1 114' embedment 1 1/t embedment 1 112' embedment 3" E.D. 3' E.D. 4' E.D. 3 VT E.D. 312' E.D. W E.O. 6' E.D. 30.00 ORLESS 8' 612' 8' 7" 7' 8" 8" C-G 3QD0-45.00 612" 4112 7• 5' 5" 8° 6° 12'. 7" D-D(BOTLCM) 45.00 -6D.00 5° 312" 512' 4- 4" B ° NIA & F'-F' NOTE: EMBEDMENT AND EDGE DISTANCE ARE BEYOND ANY FINISH MATERIAL. FLORIDA BUILDING CODE (Non High Velocity Hurricane Zo SCHEDULE # 3A MAXIMUM. A.S.D. DESIGN PRESSURE RATING AND CORRESPONDING MAXIMUM ANCHOR SPACING FOR OVERLAPPED MULTIPLE PANELS: DIRECT MOUNT J Jl MAXIMUM 1/4"0 ELCO fANELMATE PRO 114_"o ELCO FEMALE ID PANELMATE A.S.D. MAXIMUM APPLICABLE TO DESIGN PANEL SPAN SECTIONS &ANY COMBINATION OF TO CONCRETE TO HOLLOW BLOCK OR TO WOOD TOCONCRE E TO HOLLOW BLOCK OR TO WOOD PRESSURE GROUT FILLED BLOCK GROUT FILLED BLOCK RATING(p.s.f.) (ft.) THEM W/MIN. REUD. W/MRREQD. WI MRREUD. WIMIRRE= W/MN.REUD. WtMRREOD. fc = 335D p.s.i. Pm = 2071 p.s.L G = 0.55 fc = 3350 p.s.f. Pm = 2071 p-sl G = 0.55 2" embedment 1 1/4' embedment 1 7/8' Tluead. PenOL 1 314" embedment 1 1/4" embedment 1 7/8" Thread Pent 2 1/2" E.D. 3" E.D. 314" E.D. 2 1/2" E.D. 3' E.D. 3/4' E.D. 30.00 OR LESS 8. 4112" 7 " 6112 " NIA 7- 12 ' • 7 " 0-0 30.00 - 45.00 61/2 ' N/A 5 " 5" WA 5. 45.00 - 60-00 5112 " NIA 4111 " 4 " NIA 4 112" 37.50 OR LESS 5. NIA 3112' NIA NIA 31/2 " 8 ' . 7 " 1-1 37:50 - 56.25 NIA NIA 2112 " NIA NIA 2112 " 5625 - 75.00 NIA N/A 21/2 " N/A NIA 2112 " K K1 MAXIMUM 114 o ALL POINT SOLID -SET ELCO PANELMATE "L" INSERT A.S.D. .1/2"a MAXIMUM APPLICABLE TO DESIGN PANEL SECTIONS &ANY TOHOLLOW TO GROUT FILLED PRESSURE TO CONCRETE BLOCK TO CONCRETE BLOCKW1MIN.REC?D. TO HOLLOW BLOCK SPAN COMBINATION OF RATING (ft.) THEM W/MIRRREC'D. WI MIN.REfI'D. W/MN.REQ'D- W/MRREUD. (p_s.f) fc = 3000 p.s.i. 1 m = l W0 p.s.i. fc = 2071 p.s.i. fm = 2676 p s.i. fm =1794 p.sl 71T embedment 7/8' embedment 1 5l8" embedment 1 114" embedment 1 1/4' embedment 3' E.D. 3" E.D. 4" E.D. 3112" E.D. 31/2' E.D. 30.00 ORLESS 8' S. 8. 8. 4$ 12'- 7' G-G 30.00 -45.00 6' 4112" 7' 51/2" 51/2" 45.00 - 60.00 5. 3 1/2 ' 5 1/2 " 4 1/2 " 4 112 " ' 37.50 ORLESS 41/2 ' 3112 " 5. 41/2 " 4112" 8 ' • 7 " 1-1 37.50 -56.25 31/2 ' N/A 4- 3112 " 31/2 ' 56.25 - 75.00 3- NIA' 3112 " 3- NIA 0 M P 318"o ELCO MODIFIED CONFLFJC 5116 a ELCO HANGERMATE 112"0 POWER CALK -IN ANCHOR MAXIMUM AS.D. MAXIMUM APPLICABLETO DESIGN TO GROUT TO HOLLOW TOCOIRETE TO HOLLOW TO CONCRETE TO HOLLOW TOCONCREfE P� SECTIONS & PRESSURESPAN FILLED BLOCK BLOCK BLOCK BLOCK ANY RA71NG (p s.f.) (ft.) COMBINATION OF THEM W/ MIR READ. W1 MIN. REQ'D. W1 MN. RECID. WI MIN. READ. W1 MN. READ. WI MIN. REQ'D. WI MIN. RECID. fc=1819p.s.l. ftn=2400p.s.L Fm=2400p.s.i. fo=3650p.s.L fm=1872p.s.L fc=3000p.s-I. fm=1500p.s.i. 21/2' embedment 1314' embedment 1114' embedment 2" embedment 1 1/4' embedment 1 1/2' embedment 1 1 f2' embedment 3 314" ED. 2 IQ' ED. 2 VT ED. 3118' ED. 31/8' ED. 6' ED. 6' ED. 30.00 OR LESS .8. 61/2 ' 4112 ' 8 " 5 1/2 " 8. 8 " 30.00 -45.00 8' 4112' 3112" 8" WA 8" 61/2" 12'. 7" G-G 45.00 - 60.00 8" 4' 2112' 7' WA 8' 51%2' 37.50 OR LESS 8 " 3 1/2 ' 3- 61 /2 " WA 8 " 5. 37.50 -56.25 8' 21/2" 21/2" 5" 1 WA 7" WA 8'- 7' I -I W.25 - 75.00 8. 2112 ' WA WA WA 6 " WA NOTE: EMBEDMENT AND EDGE DISTANCE ARE BEYOND ANY FINISH MATERIAL. ode° ��- low" :..- ' ° • • a_ FLORIDA BUILDING CODE (Non High Ve t ► f+ R .. �is Hurricane Zone