HomeMy WebLinkAboutLOCATION MAPUMMARY OF WORK: 1. Project Description: New Bathhouse as per Section 8.00.03 (E) - Particular Permitted Accessory Structures and Uses in Residential, Agricultural, and Planned Unit Development Districts. 2. Work Involved: a. Interior walls: i. New interior walls of 3-5/8" MTL studs, 5/8" drywall, batt insulation (R-11) around all mechanical areas and bathrooms. b. Exterior Walls: i. New 8" CMU with PT furring strip and 5/8" drywall. ii. Provide MIN R-5 rigid board insulation. iii. Provide new hurricane impact resistant windows and doors per plans. c. Interior ceilings: i. New 5/8" Drywall ceilings, painted. ii. Provide crown molding as shown, style to be selected by owner d. Mechanical: i. Provide new AHU & CDU units as shown. e. Electrical: i. Provide lighting and power, per plans. ii. Provide new appliances as shown. f. Plumbing: i. Provide new plumbing service as shown. ii. Plumbing fixtures as selected by owner. g. Roofing: i. Provide new concrete "S" tiles as shown. New tile shall match existing main residence 3. Work completed shall meet all local and state building code requirements COORDINATION: 1. Contractor shall verify existing site conditions of project location prior to commencement of work. 2. Contractor shall coordinate and verify all utility requirements, compatibility and location of projected utilities of project, as shown on the drawings. 3. Contractor responsible for coordinating all trades to complete work. Contractor shall issue full sets of drawings to sub- contractors commissioned to complete the work. 4. Contractor shall verify space requirements and location of project utilities. 5. Contractor shall field verify all dimensions of project. Do not scale drawings. 6. Contractor shall notify Architect of any discrepancies in drawings and/or specifications of project, Commencement of the work without proper notification to the Architect, the contractor will assume responsibility of work preformed. 7. Contractor shall notify the Architect, when the full intent of the drawings and/or specifications is not clear. Commencement of the work without proper notification to the Architect, the contractor will assume responsibility of work preformed. 8. Owner and Contractor shall coordinate Schedule of Values, Applir:ation of Payment, Construction Cost and any other fees related to this project. 9. Owner and Contractor shall coordinate Schedule of Construction ;ind notify Architect of schedule. 1. Architect will submit Supplemental Instructions for minor changes. 2. Contractor may propose changes by submitting a request for change to Architect. Architect and Owner shall give written approval for all changes made by the Contractor. Commencement of the work without written approval from Architect and Owner, the contractor will assume responsibility of work preformed. SUBMITTAL: 1. Prior to construction Architect and Owner shall submit a list, to the Contractor of required shop drawings submittals for this project. 2. Prior to construction Architect and Owner shall submit a list, to the Contractor of all required testing for this project. Contractor shall be responsible for the cost of any testing requested by the Owner. TEMPORARY FACILITIES: 1. Contractor shall provide and maintain access to the site of the project. 2. Contractor shall coordinate with Owner for temporary facilities requirements, if required for this project. 3. Contractor shall be responsible for maintaining a clean and safe construction site. 4. Contractor is responsible for the removal of all construction debris. MATERIALS: 1. Store and protect all project products and materials in accordan(:e with manufacturer instrucftons. Products and materials of this project shall be installed free of damage. 2. Architect shall approve all product or material substitutions. CLOSEOUT: 1. Contractor shall notify the Owner 30 days prior to the date of suf:)stantial completion. At the time of substantially complete, Contractor shall submit a list of items (punch list) to be completed or corrected within the final days of construction. Owner and Contractor will set the project completion date. 2. Owner and/or Architect will make an inspection with seven (7) days of receipt of substantially complete punch list. Owner and/or Architect may add items to complete or correct prior to final completion. 3. Contractor shall leave site clean and free of any construction dei-ris or equipment at the end of the project. 4. Contractor shall give Owner operating instructions for the mech,i,,ical, electrical, and other operating equipment installed for this project. 5. Contractor shall submit to the Owner all warranties, operating avid mainterance manuals for the following products and equipment: a. Termite Soil Poisoning b. Roof System c. Impact Resistant Doors and Windows d. HVAC unit(s) e. Finish Hardware, Keying system f. All installed Flooring g. Toilet Accessories 6. Owner may request additional warranties for other products. Contractor will be given notice prior to work, PROJECT INFORMATION DESIGN PARAMETERS: 2007 Florida Building Code, With 2009 Amendments 2007 Florida Residential Code 2007 Florida Existing Building Code 2007 Florida Plumbing Code 2007 Florida Mechanical Code 2007 Florida Fuel Gas Code 2008 National Electric Code 2007 Florida Accessibility Code (Chapter #11 2004 Florida Building Code) 2007 Florida Energy Code (Chapter #13 2004 Florida Building Code) 2004 Florida Fire Prevention Code (Based on NFPA-1 & NFPA 101 - 2003 Edition) 2002 National Fire Alarm Code - (NFPA-72) 2002 Fire Sprinkler Code - (NFPA-13/13R/13D) 2002 Standard for Automatic Fire Suppression Systems (NFPA-17/17A) 2000 Standard for Safeguarding Const., Alterations, & Demo Operations (NFPA-241) 2001 Commercial Hoods & Ventilation - (NFPA-96) Building Design: Basic Wind Speed: Building Category: Wind Importance/Use Factor: Internal Pressure Coefficient: Building Mean Height: Roof Overhang: Roof Pitch: Garage Design Pressure: 120 sqft. Door Design Pressure: 50 sqft. Window Design Pressure: 20 sqft. Exposure: Design Loads: Impact Protection: OCCUPANCY: R3 One -Family Residence CONSTRUCTION: Enclosed 140 mph 3 second gust II 1.0 +/-0.18 20'-0" 1' - 611 6:12 Int. Zone (+26.3/-29.3) Ext. Zone (+30.0/-36.7) Int. Zone (+31.6/-34.6) Ext. Zone (+31.6/-39.8) Int. Zone (+33.7/-36.7) Ext. Zone (+33.7/-44.0) C Roof Dead Load/Live Load: 15/40 psf Floor Dead Load/Live Load: 15/30 psf New Doors and Windows - Hurricane Impact Resistant Type VB Unsprinklered Ext. brg walls- CMU Eng. wood trusses Int walls-MTL stds & drywall Roofing Material - Concrete S-tile to match existing residence AREA TABULATIONS: Ground Floor A/C: 420 sqft. Second Floor A/C: 420 sqft. TOTAL A/C: 840 sqft. Loggia: 115.5 sqft. Balcony: 115.5 sqft. Total Bldg. Area: INDEX OF DRAWINGS Revised 0e-Deo-11 Sheet Sheet Title A0.1 Cover Sheet, General Information & Notes Al.l Site Plan & Notes A2.1 Floor Plans & Notes A2.2 Roof Plan, Reflected Ceiling Plans & Notes A2.3 Schedules, Details & Notes A3.1 Exterior Elevations & Notes A3.2 uilding Sections & Notes S1.1 F:)undation Plan, Details & Notes 52.1 Second Floor & Roof Framing Plans, Details & Notes S3.1 Structural Details S3.2 Structural Notes Al M2.1 Mechanical Plan, Schedules Details & Notes P2.1 Plumbing Plan, Schedules, Details & Notes E2.1 L ghting Plan, Details & Notes E3.1 Power Plan, Details & Notes SYMBOLS Window Q Detail Door F# Keyed Note Revision 06- Dec-11 06- Dec-11 06-Dec-11 06-Dec-11 xx-xx-xx 06-Dec-11 xx-xx-xx 06-Dec-11 06-Dec-11 06- Dec-11 06-Dec-11 06-Dec-11 xx-xx-xx 06-Dec-11 06-Dec-11 I:?,00rn Name x�.x `�' Interior Elevation <x,, > Wall Type Exterior Elevation x.x �----- Ak � Wa'l Section Building Section PROJECT ONTACTS OWNERS: Dr. John A char 511 NW Winters Creek Road Palm City, Florida 34990 (772) 334- a660 ARCHITECT: Crossroads Architecture Inc. Niki L. Norton, R.A. 1235 SE Indian St., Ste. 103 Stuart, Florida 34997 (772) 287-7330 LOCATION MAP CONTRACTOR: Watlee Construction, Inc. Ryan N. Watley P.O. Box 1537 Port Salerno, Florida 34992 (772) 223-0604 IECESSARY IN ORDER M t `itrw tM I ^ "PI ICABLE CODES, aao�L cu m�E �3aa NL +'C 41 N U = N L = EC'p�EUOC LLUo= a3 'L �Q1�v OL LU c� Uov+-(5 =LE==DO� E C L8 Q= =L ® L.- a ONTO U��o� - N O a._ Qc3a�3ro3 s Vr. O C IH O N (y)M N Mrn r� 00 (y) 00 ®N 0 0 4-J O N N N V l0 N N Q� r\� Q Q i V 4 a c � Q 4 O un�ru � CYCf e,. -c3 O -p 1e ru c L O (n c.J O ~' M ZwOLL- O N ,-i E S_ _j Ln a) E1M' O U v Z cn cn a,l L 71 � u V C: O� ^ W L (y) •- V) Ufa -0 O W J i 1,0 V tL ,� (� C: 4-J � C_�UM O z tJ'l r n E N Q ® L-n a �✓ Rev. # Date 1 06-Dec-11 Bldg Dept Comments Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet A0s1 Cover Sheet LOT COVERAGE CALCULATIONS AIR CONDITIONED AREA 1ST FLOOR A/C AREA 3,230 SQFT ENTRY 82 SQFT GARAGE 824 SQFT LOGGIA 150 SQFT COVERED LANAI 259 SQFT * NEW BATHHOUSE - A/C AREA 420 SQFT * NEW BATHHOUSE - LOGGIA 115.5 SQFT SQFT TOTAL STRUCTURE COVERAGE 5,080.5 EQUIPMENT AREAS 207 SQFT DRIVEWAY 2,676 SQFT * POOL DECK - MODIFIED 2,843 SQFT TOTAL COVERAGE 10,806.5 SQFT LOT AREA 27,584 SQFT ALLOWABLE COVERAGE (27,584 x .40) = 11,033.6 SQFT GENERAL CONTRACTOR TO VERIFY ALL SQUARE FOOTAGES LANDSCAPE LEGEND EXISTING SILVER BISMARK - 13'-0" O.A. NEW FOXTAIL PALM - 18'-0" O.A. NEW VIBURNUM AWABUKI HEDGE - 6`0" O.A. / / / / / / / / �CP \ SITE PLAN SQUARE FOOTAGE CALCULATIONS AIR. CONDITIONED AREA 1ST FLOOR A/C AREA 3,230 SECOND FLOOR/BONUS ROOM 2,218 * NEW BATHHOUSE (2 STORY) 840 SUB TOTAL A/C AREA 6,288 GARAGE (FOR DEHUMIDIFICATION) 824 SQFT SQFT SQFT SQFT SQFT TOTAL A/C AREA 7,112 SQFT NOIN-AIR CONDITIONED AREA ENTRY 82 SQFT LOGGIA 150 SQFT BALCONIES 269 SQFT COVERED LANAI 259 SQFT * NEW BATHHOUSE LOGGIA 115.5 SQFT TOTAL NON A/C AREA 875.5 SQFT TOTAL AREA 7,987.5 SQFT GENERAL CONTRACTOR TO VERIFY ALL SQUARE FOOTAGES I— GENERAL NOTES 1. Soils shall be termite treated. 2. Landscape design and drawings by others. 3. Contractor to verify all utility connections as required. 4. Bathhouse has been designed to meet all of the requirements of the Harbour Ridge Architectural Review Board. LEGAL DESCRIPTION / \ / / Oq /'0000l� PO / / MOTOR COURT C; Lot G. RIVER POINT VILLAGE, HARBOUR RIDGE PLAT NO. 20, according to the Plat thereof, as recorded in Plat Book 31, Page 12 to 12B, Public Records of St. Lucie County, Florida. / _ 10'-0" SETBACK LINE ___ P.L. = 225.04' POOL. DECK. / / / / EXISTING TWO-STORY RESIDENCE / /o) 4,)441 i ko THESE PLANS AND ALL PROPOSED WORT" ARF SUBJECT TO ANY CORRECTIONS '!11RED BY FIELD INSPECTORS THA" BE NECESSARY IN ORDER TO COMPLY PLY WITH ALL APPLICABLE COLka. NOTE: / SEE CERTIFIED SURVEY FOR RESIDENCE LOCATION ON SITE SCALE: 1" = 10'-0" v r .�3 OOiV: Q-- CL N�v.U��iC O o �� aro+�c ° En ��uw 4 yy Lac J-i Q .- C ,,=�L t C) C::5 C E O V7 y� Ln L �=� n m� 41 0 0 C C L COa=-+i� QOQ u.c O � �c O(V3o o > o -OQO N•i Q++ Qc3no�o3 O li C: H o N M 0) ^ ) N M M r\ 00 L M 00 N N O I, 00 00 4-J 00(NU NN � QCY) �h L_ _ Q r, C °' 0) cn 4-5 M V) U-J 0 M W o ® E--o i. i) (1) E M �' O O ._+ U U z r+ to V) J L J Q� n 1� L V) U fu V 0 O ON ^C W � � L (� .� U ru -0 � f0 '0 C_� 0 �.D V),0) Q (� C: 0 Rev. # Date 1 06-Dec-11 Bldg Dept Comments Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet A i 1 Site Plan 111V11 VV 1111 r-F-IJ TO REJECT A 4" SPHERE ENLARGED STAIR PLAN (1:12 SCALE: 1/2" = V-0" N SCALE: 1/4" = V-0" 1-1/2" 0 HANDRAIL 3'-0" HIGH HANDRAIL TO REJECT A 4" SPHERE HANDRAIL ELEVATION SCALE: 1" = V-0" WALL LEGEND lew 8" CMU Walls - Walls shall receive P.T. furring strips W,' 5/8" GYP. BD. & min. R-5 rigid board i isulation. Exterior finish shall be stucco to match existing residence. 1 New Interior Framed Partitions. GENERAL NOTES 1. Field verify all existinc dimensions and utilities prior to construction. Notify Architect of any discrepancies. 2. Dimensions are to frar iing. 3. Cabinetry shall be Kra tmaid, Omega or approved equal. NO particle board cabinetry. 4. Cabinetry hardware sl all be selected by Owner. 5. Countertops shall be granite or solid surfacing. Color to be selected by Owner. 6. New plumbing fixtures to be selected by owner. 7. Bathhouse has been d signed to meet all of the requirements of the Harbour Ridge Architectural Review Board. M O \ / O \ / d O - — — — — — — — — — — I En I I I I I - z - 0 I I I I 611 J STORAGE a? I ALCONY ;p w o O 105 1 °i' N z I I J I 105 D m 18'-8" I I � I I o En \ 1 o M e r. 4'-5" 5'-7" -7" 4'-5" 4'-511 10" 3" 20'-0" 5'-6" 5'-6" (BUILDIrIG OVERALL) SECOND FLOOR PLAN 3 A3.1 w {-, - •I If i Al" 1 ' 1► BUILDING CODE. MAY NECESSARY IN 001EW I-L COMPLY WITH ALL APPLICP h/A I I ST. LUCIE CO:JNN BUILDING DIVISION REVIEWED FORcc IANCE REVIED DATE 0 ; 1 PLANS APftxPCRMI - MUST BE KEPT ON JOB OR NO INSPECTION !MILL t3E MADE SCALE: 1/4" = V-0" 1 >- .L @n�T0N3 fl°O�,L-�, la��-o3aa"i,.� 0" �n10 1UC�LC OM�. c E.S E-uu4-J If 0 @� U y li >y:E B C u.- O U 0 J-+ L c � E E :3 = c � � nodIn cc °1: C ct .0 Lu 3 0+-+�tj -a Q-r-d `--,° 00 0 U Q) C, tCL-0 ¢ � M U O Ii C: �—...o o•--� o N m N � � O0 m N o NN 00 co 4-J� o N U l0*-+ NN Q j N G) QQ 11-001-0 L— _ T ru V)� Ic c ru 70 O U0~M�° z Lu o ® .-H E J L- Ln N E m lu ® •-N �� U U T-+ U) cn n O i . Ln O r_ - (J fu V 0o � �rn L M •— V / U � L W fa .� J O l0 4-J U M E N Q 0 U-) 0 Rev. # Date 1 06-Dec-11 Bldg Dept Comments Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet A2ml Floor Plans A3.1 CLOSET . CLG HEIGHT - &-W.- ' iX4 T&G CEILING FINISH TO BE SELECTED BY. OWNER :. `CLOSET :...,.. CLG HEIGHT 8' O. --- - BATHHOUSE t0>`,E,IF� GROUND FLOOR REFLECTED CEILING PLAN 'N SCALE: 1/4" = 1'-0" ON SCALE: 1/4" = V-0" ROOF GENERAL NOTES 1. New roof til s to match existing roof tiles of main residence. 2. Install new roof tiles as per Miami Dade County N.O.A. 3. Provide roof truss shop drawings for Architect and Engineer approval prior to fabrication. RCP GENERAL NOTES 1. Provide 1X I &G ceiling at new loggia as shown. Finish shall be selected by Owner. 2. Refer to E2.. and E2.2 for all light fixture, ceiling fan, and junction box locations. 3. Provide and install crown molding as shown. Size, profile and finish color to be selected by owner. SECOND FLOOR REFLECTED CEILING PLAN THESE PLAN SUP�JEC110 ANY CrWREC"(j� :S ARE REQUIRED BY FIELD 1N ORDER TO MAY BEY ECESSARWITH ALL A?p1 ICAE�.E COCC Com - N SCALE: 1/4" = 1'-0" rou:3 2, c� c E rao -,Cu' � uL N� v� V.V C-iC o fu(Uro,1¢o �Q ES�aEvyc O -0 v's= ro O uocE a3 c��ou L O� >`N O L V OaC C ! u E ` Q co�� oa�Q ® -(..Y +Y' 0 a)>,O U L 0 fo V J-r s a— 3 Q 0 U ■ U OLL = u �—o H O N m Ql N 00 L m 00 h O N ap 00 -�-J N N O NCD U �O T N N Q Q Q U L- _ a-' O O V Q s- ®1 Ln ry O �� � C O 'p (n u o ~ m Z uW O O N E S- yr 'J LC) N E m 4- U U cncn sir r LV o t) r � —\ s W (a V 0® i M V/ U ru V) -0 O .L ro l0 -F- 4--, O �.D L.` U') L Q �M ru 0ZU.-. cn r, E N Q ® U) CL Rev. # Date 1 06-Dec-11 Bldg Dept Comments Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet A2n2 Roof & Ceiling Plans O DOOR SCH E[ DOOR SIZE DOOR NO. WIDTH HEIGHT THICK MAT. FINISH HDW. TYPE ELEV. MDL# N 101 15'-0" 6'-8" 1.75 AL FAC - SLIDER 102A 2'-8" 6'-8" 1.375 WD PTD - POCKET V 102B 2'-8" 6'-8" 1.375 WD PTD - POCKET V 104A 2'-8" 6'-8" 1.375 WD PTD POCKET V 104B T-0" 6'-8" 1.375 AL FAC - FRENCH 105A 3'-0" 6'-8" 1.75 AL FAC - FRENCH 105B 5'-0" 6-8" 1.75 AL FAC - FRENCH DOOR LEGEND SCW SOLID CORE WOOD HCM SCM SOLID CORE METAL MTL GL TEMPERED GLASS DOOR WD HCW HOLLOW CORE WOOD AL HOLLOW CORE METAL BRN BRON; METAL DOOR FRAME/DOOR AND CLEAR WOOD DOOR FRAME FAC FACTO ALUMINUM DOOR FRAME MFR MANUF NOTES: 1. DOOR HARDWARE TO BE SELECTED BY OWNER. 2. INTERIOR DOORS AND FRAMES, STYLE AND FINISH TO BE SELECTED BY OWNER. 3. DOOR CASINGS TO BE SELECTED BY OWNER. 4. ALL EXTERIOR DOORS SHALL BE HURRICANE IMPACT RESISTANT BY PEACH TREE OR APPRO` 5. INTERIOR DOOR STYLE AND PROFILE TO BE SELECTED BY OWNER. 5/8" MIN. STUCCO FINISH CONCRETE BEAM OR PRE -CAST LINTEL - REFER TO STRUCT. DWGS & BUILDING SECTIONS FLASHING 2x P.T. WD. BUCK FASTEN TO CMU 3/16" TAPCON w/ 1-1/4" EMBEDMENT INTO CONC.-PER HOLE DOOR -SEE PLN EXTERIOR DOOR -SEE PLN #10 SCREW -'STAGGERED 1-112" EMBEDMENT INTO WD.-PER HOLE CHAULK @ FRAME -- CONT. 2x P.T. WD. BUCK FASTEN TO CMU FLASHING GROUT FILL CELL # 5 BAR @ ALL OPENINGS DOOR -SEE PLN 3/16" TAPCON w/ 1-1/4" EMBEDMENT INTO CONC.-PER HOLE a H EAD JAM SI SLOPE WALK AWAY FROM OPENING 4 e e P. �— e e 1/2" FIBEROUS EXP.JOINT EXT FRENCH DOOR 112" GYP. BD. FURRING STRIPS 16" o.c. HORZ. 1 /4" TAPCON w/ 1 1/2" EMBEDMENT INTO CONC.-8" o.c, FIN. WOOD CASING INTERIOR 1/4" TAPCON w/ 1-1/2" EMBEDMENT INTO CONC.-8" o.c. FIN. WOOD CASING FURRING STRIPS VERTICAL @ END 1/2" GYP. BD. THRESHOLD PER MANUFACTURER GROUT FILL FLOORING- SEE FIN. SCHEDULE CONC. SLAB - SEE FDN PLN EXT. DOOR H-S-J DETAILS }" MIN. STUCCO `.' RIGID INSUL. FINISH M. (R5.4) ' CMU LINTEL -SEE . \" GYP. BD. LINTEL SCHEDULE FLASHING r. FURRING STRIPS @ 16" o.c. HORZ. 2x P.T. WD. BUCK 1/2" TAPCON w/ FASTEN TO CMU _ 1-1/2" EMBEDMENT #10 SCREWS 1 1/2" INTO CONC.-8" O.C. EMBEDMENT INTO71 WOOD -PER HOLE WOOD _FIN. CASING FRENCH SLIDER -SEE 4. H EAD DOOR SCHEDULE EXTERIOR INTERIOR (2) 2x6 WD. HDR FRENCH SLIDER -SEE 1/2" TAPCON w/ ADJUST HEIGHT - DOOR SCHEDULE _ 1-1/2" EMBEDMENT FOR TRACK #10 SCREWS- 1-1/2" JAMB INTO CONC.-B" O.C. 2x4 WD. BUCK — EMBEDMENT INTO TRACK PER MFR. WOOD -PER HOLE FIN. WOOD WD. DOOR -SEE - CASING CHAULK @ FRAME DR. SCHEDULE CONS. 2x P.T. WD. BUCK FURRING STRIPS FASTEN TO CMU VERTICAL @ END FLASHING CAULK FULL FRAME \" GYP. BD. PERIMETER, TYP. GROUT FILL CELL #5 BAR @ ALL a' RIGID INSUL. OPENINGS (R5.4) WD. DOOR FRAME SIZED TO WIDTH OF WALL FRENCH SLIDER -SEE THRESHOLD PER DOOR SCHEDULE SIL MANUFACTURER WD. DOOR -SEE - DR. SCHEDULE 3/16" TAPCON w/ GROUT FILL 1-1/4" EMBEDMENT INTO CONC-PER HOLE FLOORING- SEE FIN. SCHEDULE SLOPE WALK AWAY WD. DOOR -SEE - DR. SCHEDULE FROM OPENING o ' a D e e' a ° CONC. SLAB THRESHOLD -SEE • FIN. SCHEDULE SEE FDN PLN EXP.JOINT J1LL FRENCH DOOR SLIDER POCKET DOOR SCALE: 1-1/2" = V-0" 5/8" GYP. BD. BOTH SIDES, TYP, 1/2" WD. SHIM FINISHED WD CASING SIZE WD. BLKG. FOR TRACK PTD. GRADE WD. FRAME 5/8" GYP. BD. BOTH SIDES, TYP. FINISHED WD CASING PTD. GRADE WD, FRAME FLOORING -SEE FIN. SCHEDULE CONC. SLAB - SEE FDN PLN INT. DOOR H-S-1 DETAILS SCALE: 1-1/2" = V-0" WINDOW SCHEDULE WIN SIZE ROUGH OPENING MUTTINS FINISH MANUFACTURER MODEL #/SERIES TYPE NOTES: TYPE (STYLE) (SEE NOTES BELOW) HEIGHT WIDTH HEIGHT COLOR ELEV. WINDOW HARDWARE OWIDTH A 2'-6" 5'-2" VERIFY VERIFY TBD A TBD TBD PEACH TREE CASEMENT 1,2,3,4,5,6 B 2'-0" T-6" VERIFY VERIFY TBD B TBD TBD PEACH TREE CASEMENT 1,2,3,4,5,6 C 2'-6" 4'-6" VERIFY VERIFY TBD C TBD TBD PEACH TREE CASEMENT 1,2,3,4,5,6 D 4'-8" 4'-6" VERIFY VERIFY TBD D TBD TBD PEACH TREE CASEMENT 1,2,3,4,5,E NOTES: 1. NEW WIND GWS SHALL BE PEACH TREE WINDOWS AND DOORS OR APPROVED EQUAL AND HURRICANE IMPACT RESISTANT. 2. 5.7 SQFT FC R EGRESS FOR ALL BEDROOMS AND LIVING AREAS. 3. VERIFY WINDOW ROUGH OPENINGS WITH WINDOW MANUFACTURER. 4. ALL DIMENSIONS ARE NOMINAL (MASONRY OR ROUGH) DIMENSIONS, SHOP DRAWINGS TO BE PROVIDED FOR ALL UNITS ALONG WITH FIELD DIMENSIONS. 5. REFER TO B JILDING ELEVATIONS AND WINDOW TYPES FOR WINDOW CONFIGURATION. 6. ALL WINDO'V FINISHES SHALL BE SELECTED BY OWNER. 2'-6" I 22'-0" \ M \ O WINDOW TYPES 5/8" MIN. STUCCO FINISH CMU LINTEL - SEE BEAM SCHED. FLASHING 2x P.T. WD. BUCK FASTEN TO CMU CHAULK @ FRAME CONT. WINDOW -SEE PLAN WINDOW -SEE PLAN SLOPE STUCCO SILL AWAY FROM WIN. EDGE FLASHING CMU LINTEL -SEE BEAM/ LINTEL SCHEDULE STUCCO FINISH WINDOW -SEE PLAN CHAULK @ FRAME CONT. 2x P.T. WD. BUCK FASTEN TO CMU FLASHING GROUT FILL CELL # 5 BAR @ ALL OPENINGS 2'-6" 4'-8" 2'-4" 2'-4" O SCALE: 1/4" = V-0" THESE PLANS AND ALL PROPU ARE SUBJECT TO ANY CORREG H EAD REQUIRED BY FIELD INSPECTOR MAY BE NECESSARY IN ORDER COMpj.V \AIITI.A j. APPLICf' - a �. . 1/2" GYP. BD. �' FURRING STRIPS @ 16" o.c. HORZ. FIN. WOOD CASING 1/2" GYP. BD. w/ CORNER BEAD -- 1/4" TAPCON w/ 1-1/2" EMBEDMENT INTO CONC - 8" o.c. SPACING FOR ALL FOUR SIDES SILL #10 SCREW -STAGGERED 1-1/2" EMBEDMENT INTO WD.-PER HOLE 2x P.T. WD. BUCK FASTEN TO CMU VERIFY w/ OWNER FIN. WOOD SILL <— FIN. WOOD TRIM ' FURRING STRIPS \ @ 16" ox. f 1/2" GYP. BD. ALUMINUM WINDOW WINDOW H-S-J DETAILS SCALE: 1-1/2" = 1'-0" a 0) v� J=I fs .L •� C� i-+ O O voo•-��m —a oL c ctum N N U L C O Emu E-&a-0 U.E 4 ccr m 20� V L L� U + vca�an ao!E>'v0Lu c"U oin, �N L C LL L (n =1- vnvooccU LJ.. c0_� ooQ U cat O= O`L° C o >-o a�oLa U Qr3ao3°o3 ■ O L_ u M 01 0) N 00 L M 00 N N O N 00 00 4•J 0� NN �0 r, nU —J IN ,,J Q Q �✓ a i V Q 4-1 c v rn (n -0 Q 4-J ON i C M 0-0 L c L O cn U OEM zwoU_ O E J S- L L(1 N E1M' O •—N O4_5 U U z cn cn U L N.� ILI � lI' To rn O L U THAT IDES. W � V 0o • — U ra ((n i - O •L W flu `Q 4-J �� )•�LLO e V 4-J �(Dm 0 z cn E N fE3 r 0 U) 0- O Rev. # Date Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet A2m3 Schedules, Notes & Details A" ROOFING TO MATCH EXISTING RESIDENCE OVERHANG DETAIL TO MATCH EXISTING RESIDENCE IN MATERIAL AND PROFILE T.O. BEAM 16'-2" — — — B.O. WIN. DOOR HEAD STUCCO FINISH TO — MATCH EXISTING RESIDENCE RAILING AND RAILING POSTS TO MATCH EXISTING RESIDENCE \ �� �j- 9'-6" _ FLOOR _ — 9'-0" BALCONY 6 -8" _ B.O. WIN. DOOR HEAD STUCCO FINISH TO MATCH EXISTING RESIDENCE 0'-01, - — --� — 1 - NORTH ELEVATIOj`" 3 - SOUTH ELEVATION 12 6 +45.4 PSF +45.4 PSF - 49.2 PSF - 49.2 PSF +45.4 PSF - 49.2 PSF +45.4 PSF - 4 9. 2 PSF +45.4 PSF - 49.2 PSF +45.4 PSF - 49.2 PSF SCALE: 1/4" = V-0" aTC H DENCE -AIL TO MATCH DENCE IN MATERIAL I TO IG RESIDENCE AILING POSTS ;TING RESIDENCE TO G RESIDENCE SCALE: 1/4" = 11-0" "A GENERAL NOTES 1. New windows to match existing existing residence. 2. New roof overhang & soffits shall match existing residence in profile and construction. 3. New column capitals and bases to be selected by owner. 4. New roof tiles sl,iall match existing residence in profile and color. 5. Bathhouse has been designed to meet all of the requirements of the Harbour Ridge Architectural Review Board. 4 - WEST ELEVATION 4TCH DENCE -AIL TO MATCH DENCE IN MATERIAL I TO IG RESIDENCE AILING POSTS ;TING RESIDENCE ITO IG RESIDENCE = 11-011 TYFSE PLANS AN , . _:_ ... - , ARE SUBJECT TO ANY CO!, REQUIRED BY FIELD INSPECTOR MAY BE NECESSARY IN ORDEP r GOMPly WIT 14 A!!, APP►„!r 12 r 6 yi r r r i r r i ROOFING TO MATCH EXISTING RESIDENCE ——17'-2" Ilk T.O. BEAM OVERHANG DETAIL TO MATCH EXISTING RESIDENCE IN MATERIAL AND PROFILE STUCCO FINISH TO MATCH EXISTING RESIDENCE 2ND FLOOR 'r 9'-0" BALCONY B.O. WIN. HEAD I STUCCO FINISH TO MATCH EXISTING RESIDENCE SCALE: 1/4" = 11-011 rUcE_30-G)'; -� @ 2 L !- c cc, 'LC V7@Ca...V o (, , 1 � ova@¢ EQ,00Euc T .20 fuV i 3°�c�wcpw -o p_E>-w0 t @z,¢ p I'll 11O p ISC U G_ OL.+�� Off¢ ® �VwVdJ pTO UL L� Q�3a�3�3 ■ U ,-o ® u- iH V/%.e O N M Ol N 00 L M 00 N N O N N � N 0 � U Na+ NN J Q h Q < a✓ es U L_ _ (1) -0 Q 4 o, 0 ` v M a/ � (� f0 O 0 (n O~'M0 Z W O O E JLn L (Ut E M :�' O .-N =3 4-J U U zU)Ln U C ul � c9 v'1 U 0 t-A U Q) M U �o C: V CJ1 -0 i ty-) •— U ro -0 L (j) CT dim- Q M V 4-% U M ° z (� � c�i 4— — ra r, 0 Rev. # Date 1 06-Dec-11 Bldg Dept Comments Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet All Building Elevations GENERAL NOTES 1. New windows t match existing existing residence. 2. New roof overh ng & soffits shall match existing residence in profile and construction. 3. New colurn ca itals and bases to be selected by owner. 4. New roof s s all match existing residence in profile and color. 5. Bathhouse has een designed to meet all of the requirements of the Harbour Ridge Architectural Review Board. 12 6 T.O. BEAM 16'-2" B.O. WIN. DOOR HEAD .."• co STORAGE BALCONY . 105 12 106 ..� 6 i 91-611 77 .. .. .., ..:. ..�2ND FL •kK 9' 0" BALCONY 6'-8" — — — — — — — — — B.O. WIN. DOOR HEAD O O r y BATH w BATHHOUSE LOGGIA c0 L 104 101 101 .' a - x T.O. S �Sa �r ✓ i/��,� � � �� �'�':�'?.-,,•V• �.. ��i`i� /����� %� r�li?r�.� is%��ia r INTERIOR 1 - BUILDING SECN SCALE: 1/4" = 1'-0" a. 2 - BUILDING SECTION '. F I SCALL: 1/4" = l'-U" a. INTERIOR 3 - TYPICAL WALL SECTION KA ° a. • e . � T L C T C-nYY tv 0 ��;�3 ra � fu LA UJ�tu OJV COi'C Q O O E�-0-:EVNC Y O M U L L�UpC,-,a3 • -O OL TN O L V � C Y U � � Y � � UIY�Y-_ L (n i a`^ L --+vo�Ci OO C O+� tJ U tQ lly_r-v 3Y o O , Zo 1D Qs3a=03r3 V '-' u O ROOFING TO MATCH EXISTING RESIDENCE O N M O N 00 PREFAB ROOF TRUSSES - SUBMIT M rn SHOP DRAWINGS FOR ARCHITECT'S O N 00 00 APPROVAL -J O N N N l0� NN MIN R-30 ICYNENE ^U W rN Q Ul SPRAY INSULATION 4J Q Q s V 2 j-J C 17'-2" 16 O T.O. BEAM -0 M fu O S.— ra -J C L 1, z w 011- E O —' rn a� i- ru E M : OVERHANG DETAIL TO MATCH (Ll � � 0 EXISTING RESIDENCE IN MATERIAL V z U) (� AND PROFILE CONCRETE BEAM - SEE STRUCTURAL DWGS STUCCO FINISH TO MATCH EXISTING RESIDENCE 8" CMU WALLS 5/8" 1 )RYWALL OVER 3/4"� P.T. I URRING STRIPS OVER U MIN R 5 RIGID BOARD INSULATION CONCRETE BEAM & 6-1/2" EPICORE CONCRETE DECK - SUBMIT SHOP DWGS FOR ARCHITECT'S APPROVAL 9'-6" 2NDtLOOR Y V �O EXTERIOR C: -,.,e (� (]) Q M • — U ra V)-0 STUCCO FINISH TO L- ' MATCH EXISTING RESIDENCE fu L. 0 � C-_ LL Cn 8" CMU WALLS < :3: d- 4-J M 5/8" DRYWALL OVER 3/4" ; j M P.T. FURRING STRIPS OVER ® z v MIN R-5 RIGID BOARD n N INSULATION r.{ _ L *� f CONCRETE SLAB AND FOUNDATION < Ln a- - SEE STRUCTURAL DRAWINGS OVER MIN 6 MIL VAPOR BARRIER Rev. Date CLEAN COMPACTED TERMITE TREATED FILL 00 OIL T.O. SLAB VESE PLANS A�3V ALL UI � ARE SUBJECT 10 ` N �CTORS%`� "' Proj 11-0470 //\//\//, i\\j\\j� RE6�UiREN EY FIE N o . NECESSARY 1N ORDER i0-� •., Comm V'411H ALL APPLICAP +� ��' ' Status Final Issue 14-Sep-11 -- Date SCALE: 3/4" = 1'-0" Sheet A302 Building Sections J J 00 N z 0 J_ m 2 51.1 o 2 L A FOOTING SCHEDULE MARK WIDTH x LENGTH T REINFORCING (BOTTOM) WF1 GE 2'-0" x CONT. 18" (3)-#5 LONG WAY BOTT. #5 @ 48" O.C. SHORT WAY BOTT. O3'-0" x 3'-0" 12" (4)-#5 EA. WAY BOTTOM T.E. V-0" x CONT. 12" (2)-#5 CONT. 25'-6" (BUILDING OVERALL) 20' -0" 5'-6" 0'-0" SLAB ELEV 4" CONCRETE SLAB 1N/ 6X6 W1.4XW1,4 1NWF OVER 10 MIL VAPOR BARRIER ON TERMITE TREATED (J Fx COMPACTED FILL 5 S1.1 FOUNDATION PLAN LL-L 0 1 S1.1 WF1 I MITE TREATMENT REQUI ED — _ C.J. — — F- - �) O T.E. S1.1 ' —� SLOPE w 6" 7777/ AO t n L C.J. ' 5 V., 6_' .. -0'-6" SLABI EL V. 4" CONCRETE LAB W/ 6X6 W114X%Vl.4 WWF OVER 10 1IL VAPOR BARRIE ON TERMIT�Tv�A E4 j & COM AC ED =Ift T.E. A I) II 2 7 S1.1 2'-0" 20'-0" 5'-6" 25'-6" (BUILDING OVERALL) COLUMN SCHEDULE MARK SIZE REINF. TIES TYPE CAP PLATE MATERIAL 0 12" DIA (4) #5 #3 @ 12" O.C. - - CONC RETE 016X16 (4) #5 #3 @ 12" O.C. - - C U COLUMN BLOCK 0 NOT USED - - - - 4O NOT USED - - - - TERMITE TREATMENT REQUIRED N SCALE: 1/4" = 1'-0" GENERAL NOTES: FOUNDATION PLAN 1. CONCRETE a. shall be Class 1. b. shall meet 5" Slump Test. c. shall meet 3000 psi compressive strength after 28-day cure. d. Grade floor slab for drainage. e. Finish concrete with single trowel. f. footing design based on soil bearing capacity of 2500 psf 2. REINFORCING a. shall meet ASTM standards for 60 Grade. b. vertical reinforcing shall be 3/4" from masonry. c. vertical reinforcing shall extend from footing through pre -cast lintels. d. horizontal reinforcing shall be Cont. for pre -cast lintels over openings. d. horizontal reinforcing lapping shall a min. 22". e. protect for reinforcing: floor slab: 3/4" min. cover from top 1-1/2" min. cover from bottom footing: 3" min. cover walls: 1-1/2" min. cover beams: 1-1/2" min. cover #5 REBAR i @ EVERY 4'-0" o.c. a @ BOTH SIDES OF ALL 1 i � MASONRY OPENINGS w SEE PLANS O I CONC SLAB FIN FLR FIN GR x xCD (3) #5 CONT j\/ I 3" MIN. COV. & �, \�M%N.>\\/\\//\\/ #5 @ 48" O.C. \\A 2'-0" TRANSVERSE SEARING FOOTER (1) #5 EXTEND 24" BEYOND W&B (TYP.) I #5 REBAR E a I EVERY O @ BOTH SIDES OF ALL I I MASONRY OPENINGS w SEE PLANS rn 0 0 I RECESS FTG 4" 12" I FIN FLR CONC SLAB I FIN GR d14 X X—X I (1) #5 CONT— (3) #5 CONT \/ 3" \\/\\/ 3" MIN. COV. 3" MIN. COV. & .'MIN. #5 @ 48" O.C. 2'-0" TRANSVERSE 2 BEARING FOOTER @ SHOWER SCALE: 1/2" = 1'-0" 1/2" FIBER EXP JOINT #5 REBAR @ EVERY 4'-0" o.c. E a @ BOTH SIDES OF ALL MASONRY OPENINGS E LU I SEE PLANS O "' i o � CONC SLAB FIN F EXT STP Co ° x e 4 , X (3) #5 CONT 3" MIN. COV. & #5 @ 48 O.C. 2 _/ TRANSVERSE BEARING FOOTER @ EXT STEP 3 SCALE: 1/2 = 1 -0 12" DIA OR 16" SQUARE COLUMN BLOCK 1/4" PMJ IIII ALL SIDES ,'+'. .x X II '.X X' '1 SLAB ON GRADE •. SEE PLAN d. N T-0" SQUARE 8 COLUMN DETAIL SCALE: 1/2" = 1'-0" 2a. Alternate for wire mesh: Fiber mesh made of synthetic fiber manufacturer per ACI 544.IR-82. Fibers shall be a certified suitable replacement for welded wire fabric per SSTD 10-93. 3. CONCRETE MASONRY UNIT a. shall be meet ASTM C 90. b. shall load bearing concrete masonry units. c. shall meet 3000 psi compressive strength after 28-day cure. d. Grade floor slab for drainage. e. Finish concrete with single trowel. See Finish Schedule for floor finishes. 4. MORTAR a. shall meet ASTM C 270 standards. b. shall be type M. c. joint type shall be concave. 5. GROUT a. shall meet ASTM C 476 standards. b. shall have a min. 2000 psi compressive strength. c. shall meet 8" -10" slump test. 6. SOIL BEARING CAPACITY a. shall meet 2500 psf. LU CONC SLAB FIN FLR FIN GR 0 x--��x x (2) #5 CONT 3" MIN. COV. MIN. 1'-0" 4 THICKENED EDGE T.E. 1/2" FIBER EXP JOINT FIN FLE— X" �— EXT STP (3) #5 CONT \\ j 3 3" MIN. COV. & j ; MIN. #5 @ 48 O.C. / /\\/� 2'- TRANSVERSE 5 FRONT ENTRY SCALE: 1/2" = 1'-0" 1/4" SAW -CUT 1" MIN. DEPTH r— CONC. SLAB (TYP. ) x x x—x—x—x—x—x 6 SAW -CUT JOINT DETAIL SCALE: 1/2" = 1'-0" 1' Cb #5@12"O.C. (T&BOT. SHORT WAY) #4 NOSING (TYP. ) (2) #5 T&B & (7) #7 CONT #3 STIRRUP @ TOP & 16" O.C. BOTTOM GRADE 1 4 N REINF. CONC. SLAB (4) #5 VERT DOWELS 1/2" EXP. IT. MAT. W/ HOOK EA. END EA. SIDE (3) #5 CONT. & 2'-0" (4) #5 TRANSVERSE BOTTOM STAIR DETAIL aQo- a�v m�E•. THE ANS AN D ALL .APP JECT TC ANY C 'D BY F11 LD INSI NECE ' 1Y IN 1 ,!WIT[ . APPL W V C C W ' VI L C ��W LL V Q e 01 r^� V 1 � 4— ® L o Rev. # I Da' 1 06-[ Bldq Proj 11. No. Status Fin Issue 14 Date Sheet Foe Pla l� ENCORE 'CHE UL. REINFORCINGa�e T & S TOP SLAB THK. MESH (SEE PLAN) 6 1/2" 6x6-W2,1xW2.1 -p #5@8"O.C. EPICORE MSR (2") 22GA GALV. DECK (SINGLE SPAN) 25'-6" (BUILDING OVERALL) FLOORSECOND SLAB PLAN -�NN SCALE: 1/4" = V-0" I� M Ln Ln lM r-1 U U U C7 f- (� U U U CJ1 — �— � B-4 �I CJ3 CJ3 I C35 CJ5 .J ko �ti0 I O I 07 vI 07 CJ7 m 07 w II SLOPE 6:12 07 CJ7 SLOPE 6:12 I 07 07 1 o 2 07 3: Cj 07 Uj W N CJ5 �, z � _ a ��� CJ 5 U O w (n LOCh F �? I CJ 3 ���� a D J CJ 3 CJ1U /5u U C7 ~ ~ U U U U ROOF FRAMING PLAN 6 S11 TYP. 4 SIDES TF?ESE PLANS AND All PROPOSED W",-As AIDE 'SUBJECT TO ANY CORRECTIONS RMWIRED BY FIELD INSPECTORS THA' MAC E �.irCESSARY IN ORDER TO Tw •.! aV il'`s. Y % I i i� xi i~"4s s N SCALE: 1/4" = V-0" m-cW �L O -c En i i 0 v > _,U, 0— c-�U,, ro:3=-a3aa"i� a o, c °cV)rro ray �F�uc�L0 ra c- ¢ o .- E•�a-0EUa)c Q)0 6L@VU 3� r- w-oU) 'O WL%'Q10i V Ln L (n C) O1n NOOCOU L C O.N Q2-6 VL¢ o U roco�°n' - :3 >'O U Yy0 -0 L L U QJ-+ — � O 03 IQL3"A ■ Ou ~, ON N 00 L M 1 00 N N O / � N N V ® ENO ;~ Q R N Q Q �.vs V L _ Q a N c Q) ON M ® o --0 Q ~ M LL Z L1J 0 n VJ O O E t Ln a) O .— N O Ir U U Z ,-q V) cn U c L rryl z; 0j O�C II A U V 0o W L ry) ■� Vl � (, L- L- ._ VJ M (3) L- 1�0 I-- 4-J O l0 o z E N � — 0 Rev. # Date 1 06-Dec-11 Bldg Dept Comment! Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet S2ml Framing Plans (1) #5 CONT. @ SILL HOOK INTO JAMBS 1 - SECTION DETAIL THROUGH BALCONY t, t T.O- BECK 9'-6" BEAM B-2 SEE PLAN FOR VERT. J REINF. HOOK INTO LINTEL WHERE ABOVE t• OPENING 0 1 2 - WALL SECTION DETAIL 8F8-1B TYP. FOR OPENINGS UP TO 48" WIDE (1) #5 CONT. HOOK INTO, JAMB (TYP.) SEE PLAN FOR VERT. REIPIr. . HOOK INTO SILL WHO FILE REINF. IS BELOW WINi)OW 5/8" CDX EXTERIOR PLYWOOD ATTACHED W/8d NAILS @ 6" O.C. FIELD & EDGES ZONE (1) 4" O.C. 12 FIELD & EDGES ZONE (2) & (3) (7) #7'S T&B CONT. FROM STAIRS 6 HOOK TOP BARS INTO B-5 BEAM ATTACH PLYWOOD TO BLOCKING m \ W/8d NAILS @ 4" O.C. (TYP.) g T.O. DECK 9'-6" w 2X BLOCKING TIGHT BETWEEN w ; EACH TRUSS & TOE NAIL IN PLACE w ` Ln e . r t—1— —gyp '• PRE-ENGINEERED T.O. BEAM « ' WD TRUSS @ 24" BEAM B-3 10 O.C. MAX I �. J,. (2) #6 TOP EXTEND TO BEAM B-5 - CANTILEVERED END OF CANT. BEAM & °� BEAM MAN BACK B-2 BEAM SIMPSON HETAL-16 BEAM B-4 16X16 MASONRY . (TYP.) UNO ' COL. @ CORNERS t•. �_ (2) #5 EXTEND TO END 8" CMU -SEE PLAN FOR OF CANT BEAM REINFORCING (HOOK INTO TOP OF TIE BEAM 12" 0 COLUMN BEAM B-2 SCALE : 3/4" = V-0" SCALE:: 3/4" = V-0" T.O. DECK 9'-6" •x' ,�• t BEAM B-2 1 i �a SEE PLAN FOR Lie REINFORCING 1. . 3 - WALL SECTION DETAIL SCALE 3/4" = V-0" 4 - STAIR LANDING DETAIL 6' - 7" SEE FLOOR PLAN 5 - STAIR LANDING DETAIL SCALE: 3/4" = V-0" SCALE: 3/4" = V-0" 6 - OVERHANG SECTION DETAIL SCALE: 3/4" = 1'-0" THESE PLAvS Ai�D ALL rlWri... ,. ARE SUBJECT TO ANY CORRECTIG REQUIRED BY FIELD INSPECTORS IH MAY BE NECESSARY IN ORDER TO COMPLY WITH ALL APPIJC`A"•" m� �� �� c� ,moo CLOL0 � �_ Q) a :3C-0 0(1), t U (U/l O�_ U U C L Co t u Q) C 070-0 CEMOCmm— Lutt. a3 3 z w - w--8, � _�, vL>'v 0Lu +' M vi+� �.0 �E7CV, aU-i 01 w v O U C C U -0 Ut 3��vv �o (s0 LL UL Q� dt 3:OLa 3 n C u F•--1 O N M Q't r_ 00 M Of" 00 0 0 4—J rN U ® 00 k .q N N a-, h Q Q �✓ 6 a-' (1) C N C) O <ro T-t O C r2° C — "a O 'p V aim 1 nV) Wzwo L- �/ L Ln w E Mom' 10 O — N :3 4-J U U z 0 ci 6� m 0 L. v) 0 U W V 0o 70 i M •— U n, L U) -0 O �L W f0 Q) l0 - 4 -+ 0 �O � T70) L . Q ru Zj U M o z to E N Q o u7 0-...� Rev. # Date 1 06-Dec-11 Bldg Dept Comments Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet S11 1 �( Structural Details STRUCTURAL NOTES CONTRACTOR NOTE: THE CONTRACTOR IS SOLELY RESPONSIBLE FOR INITIATING, MAINTAINING AND SUPERVISING ALL SAFETY PRECAUTIONS AND PROGRAMS IN CONNECTION WITH THE WORK. WIEDER ENGINEERING, INC. IS NOT RESPONSIBLE FOR THE MEANS AND METHODS OF CONSTRUCTION OR FOR RELATED SAFETY PRECAUTIONS AND PROGRAMS. CODES AND STANDARDS 1. WIND LOADS ARE PER ASCE 7-05 MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES, FOR A 140 MPH WIND SPEED (3 SECOND GUST), EXPOSURE C, +/-0.18 INTERNAL PRESSURE COEFFICIENT (ENCLOSED BUILDING), 1.0 IMPORTANCE FACTOR, AND BUILDING CATEGORY II. 2. THE PROJECT WAS DESIGNED IN ACCORDANCE WITH THE: A. FLORIDA BUILDING CODE 2007 EDITION w/ 2009 AMENDMENTS B. BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE (ACI 318-02) C. SPECIFICATION FOR STRUCTURAL CONCRETE FOR BUILDINGS (ACI 301-05) D. MANUAL OF STANDARD PRACTICE FOR DETAILING REINFORCED CONCRETE STRUCTURES (ACI 315-99). E. NATIONAL DESIGN SPECIFICATION, WOOD CONSTRUCTION NDS/1997 EDITION. F. BUILDING CODE REQUIREMENTS AND SPECIFICATIONS FOR MASONRY STRUCTURES (ACI 530, 530.1/ASCE 5, 6/TMS 402, 602/ 2002 EDITIONS). 3. ARCHITECTURAL AND MECHANICAL DRAWINGS: A. THE STRUCTURAL DRAWINGS ARE PART OF THE CONTRACT DOCUMENTS AND DO NOT BY THEMSELVES PROVIDE ALL THE INFORMATION REQUIRED TO PROPERLY COMPLETE THE PROJECT STRUCTURE. THE GENERAL CONTRACTOR SHALL CONSULT THE ARCHITECTURAL, MECHANICAL AND ELECTRICAL DRAWINGS AND COORDINATE THE INFORMATION CONTAINED IN THESE DRAWINGS WITH THE STRUCTURAL DRAWINGS TO PROPERLY CONSTRUCT THE PROJECT. B. REFER TO ARCHITECTURAL, MECHANICAL OR ELECTRICAL DRAWINGS FOR ADDITIONAL OPENINGS, DEPRESSIONS, FINISHES, INSERTS, BOLTS SETTINGS, DRAINS, REGLETS, ETC. C. BEFORE ORDERING ANY MATERIALS OR DOING ANY WORK, THE CONTRACTOR SHALL VERIFY ALL MEASUREMENTS TO PROPERLY SIZE OR FIT THE WORK. NO EXTRA CHARGE OR COMPENSATION WILL BE ALLOWED BY THE OWNER RESULTING FROM THE CONTRACTOR'S FAILURE TO COMPLY WITH THIS REQUIREMENT. D. DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT AND ENGINEER BEFORE PROCEEDING WITH ANY WORK. 4. ALL DETAILcl, SECTIONS AND NOTES SHOWN ON THE DRAWINGS ARE INTENDED TO BE TYPICAL AND SHALL APPLY TO SIMILAR SITUATIONS ELSEWHERE UNLESS OTHERWISE SHOWN. 5, MATERIALS AND ASSEMBLY TEST AS FOLLOWS: A. EXTERIOR WINDOWS, SLIDING AND PATIO GLASS DOORS SHALL BE TESTED BY AN APPROVED INDEPENDENT TESTING LABORATORY, AND SHALL BE LABELED WITH AN APPROVED LABEL IDENTIFYING THE MANUFACTURER, PERFORMANCE CHARACTERISTICS AND APPROVED PRODUCT CERTIFICATION AGENCY, TESTING LABORATORY, EVALUATION ENTITY OR MIAMI-DADE NOTICE OF ACCEPTANCE TO INDICATE COMPLIANCE WITH THE REQUIREMENTS OF ANSI/AAMA/NWWDA 101/I.S. 2-97 OR TAS 202 B. EXTERIOR DOOR ASSEMBLIES SHALL BE TESTED FOR STRUCTURAL INTEGRITY IN ACCORDANCE WITH ASTM E330 AT A LOAD OF 1.5 TIMES THE REQUIRED DESIGN PRESSURE LOAD. THE LOAD SHALL BE SUSTAINED FOR 10 SECONDS WITH NO PERMANENT DEFORMATION OF ANY MAIN FRAME OR PANEL MEMBER IN EXCESS OF 0.4 PERCENT OF ITS SPAN AFTER THE LOAD IS REMOVED. AFTER EACH SPECIFIED LOADING, THERE SHALL BE NO GLASS BREAKAGE, PERMANENT DAMAGE TO FASTENERS, HARDWARE PARTS, OR ANY OTHER DAMAGE, WHICH CAUSES THE DOOR TO BE INOPERABLE. C. WINDOW AND DOOR ASSEMBLIES SHALL BE ANCHORED IN ACCORDANCE WITH THE PUBLISHED MANUFACTURER'S RECOMMENDATIONS TO ACHIEVE THE DESIGN PRESSURE SPECIFIED. SUBSTITUTE ANCHORING SYSTEM USED FOR SUBSTRATES NOT SPECIFIED BY THE FENSTRATION MANUFACTUER SHALL PROVIDE EQUAL OR GREATER fNCHORING PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING PRACTICE. SPECIALTY ENGINEERED PRODUCTS 1. THE GENET, 1L CONTRACTOR IS RESPONSIBLE TO COORDINATE TrIE PROPER SUBMISSION OF SPECIALTY ENGINEERED SHOP DRAWINGS WHICH SHALL BE SIGNED AND SEALELI BY AN ENGINEER REGISTERED IN THE STATE OF FLORIDA. IT IS THE GENERAL CONTRACTOR'S RESPONSIBILITY TO ASSURE THAT THE SPECS ? T`:' ENGINEERED SHOP DRAWINGS ARE SUBMITTED IN A TIMELY MANNER SO AS 03 ALLOW REVIEWS AND RESUBMISSIONS AS REQUIRED. ALL SPECIALTY ENGINEERED PRODUCTS SHALL BE DESIGNED FOR THE APPROPRIATE GRAVITY LOADS AND WIND LOADS INCLUDING UPLIFT AND LATERAL LOADS. INTERIOR SPECIALTY PRODUCTS SHALL BE DESIGNED FOR LATERAL LOADS TO ASSURE STABILITY. SPECIALTY ENGINEERED PRODUCTS SHALL BE, BUT ARE NOT LIMITED TO LIGHT GAUGE METAL INCLUDING, HUT NOT LIMITED TO, SOFFITS, CLADDING, CEILINGS, ETC. FOUNDATION 1. ALL SITE PRUPARATION AND EXCAVATION WORK IS TO BE PERFORMED IN STRICT ACCORDANCE WITH THE RECOMMENDATIONS ON SOILS AND FOUNDATIONS INVESTIGATION PREPARED BY AN APPROVED TESTING LABORATORY PRIOR TO FOUNDATION WORK. 2. THE BUILDING; SITE SHOULD BE EXCAVATED TO THE DEPTH AND EXTENT INDICATED IN THE SOIL '; REPORT. ALL SUBGRADES SHALL BE APPROVED IN WRITING BY THE SOILS ENGINEER PRIOR TO BACKFILLING. 3. BOTTOM OF I OOTINGS ASSUMED TO BEAR ON SOIL CAPABLE OF SAFELY SUPPORTING 2500 PSF. 4. SOILS SUPPORTING ALL FOOTINGS MUST BE INSPECTED AND APPROVED BY A REGISTERED SOILS ENGINEER BEFORE COMMENCING WORK. APPROVAL IN WRITING MUST INDICATE THE SOIL IS ADEQUATE TO SAFELY SUSTAIN SPECIFIED SOIL BEARING PRESSURE. 5. TOP OF ALL EXTERIOR FOOTINGS SHALL BE MINIMUM 1'-0" BELOW EXTERIOR FINISH GRADE. 6. ALL EXCAVATION SHALL BE KEPT DRY. EXCAVATE TO DEPTHS AND DIMENSIONS INDICATED. TAKE EVERY PRECAUTION TO GUARD AGAINST ANY MOVEMENT OR SETTLEMENT OF ADJACENT STRUCTURES, UTILITIES, PIPING, ETC. 7. PROVIDE ANY BRACING OR SHORING NECESSARY TO AVOID SETTLEMENT OR DISPLACEMENT OF EXISTING FOUNDATION OR STRUCTURES. 8. CENTERLINE OF FOOTINGS: SHALL COINCIDE WITH CENTERLINE OF COLUMNS UNLESS OTHLRWISE NOTED ON DRAWINGS. 9. ALL DIMENSIONS AND ELEVATIONS SHOWN ON THE STRUCTURAL DRAWINGS MUST BE VERIFIED AND COORDINATED WITH THE ARCHITECTURAL DRAWINGS BY THE CONTRACTOR BEFORE PROCEEDING WITH THE CONSTRUCTION. DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT OR ENGINEER IN WRITING BEFORE PROCEEDING WITH ANY WORK. CONCRETE 1. CONCRETE ELEMENTS TO HAVE THE FOLLOWING STRENGTHS: A. FOUNDATIONS 3000 PSI B. SLAB -ON -GRADE 3000 PSI C. COLUMNS 4000 PSI D. BEAMS 4000 PSI E. EPICORE SLABS 4000 PSI F. STAIRS 4000 PSI H, MASONRY GROUT 3000 PSI ALL OTHER CONCRETE: TO BE 4000 PSI UNLESS NOTED OTHERWISE 2. ALL CONCRETE SHALL BE READY MIX AND MEET THE FOLLOWI G REQUIREMENTS: A. A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI @ 28 DAY!;. B. A MINIMUMI COMPRESSIVE STRENGTH OF 4000 PSI @ 2E DAYS C. SLUMPS SHALL BE 4 INCES MINIMUM AND 6 INCHES MAXIMUM. D. CONCRETE SHALL HAVE A MINIMUM OF 3 PERCENT AIR ENTRAINMENT. E. ALL CONCRETE TO HAVE MAXIMUM WATER/CEMENT RATIO OF 0.55. F. JOBSITE WATER SHALL NOT BE ADDED. _ CONCRETE COVER FOR REINFORCING STEEL SHALL BE S REQUIRED BY ACI SPECIFICATIONS. WELDED WIRE FABRIC SHALL COMPLY WITH ASTM A 185 UNLESS OTHERWISE SPECIFIED. PLACE FABRIC 2" CLEAR FROM TOP OF THE SLAB I J SLAB ON GRADE AND SUPPORT ON SLA13 BOLSTERS SPACED AT 3'-0" O.C. 5. ALL REINFORCING STEEL SHALL BE MANUFACTURED FROM H GH STRENGTH BILLET STEEL CONFORMING TO ASTM DESIGNATION A 615 GRADE 60. 6. LAP ALL BARS PER A(I MINIMUM TENSION LAP SPLICE BUT N DT LESS THAN 48 BAR DIAMETERS UNLESS OTHERWISE NOTED ON DRAWINGS. LAF ALL WWF A MINIMUM OF 12 INCHES (UNLESS OTHERWISE NOTED). 7. AT CORNERS OF CONCRETE BEAMS AND CONTINUOU`� WAL FOOTINGS, PROVIDE MATCHING HORIZONTAL BARS X 5'-0" BENT BAR FOR EACH HORIZONTAL BAR SCHEDULED AT EACH FACE. 8. ALL HOOKS SHOWN IN REINFORCEMENT SHALL BE ACI RECC MMENDED HOOKS (12 BAR DIAMETERS BEYOND BEND) UNLESS OTHERWISE NOTED. 9. 1ONCRETE LINTELS: A. DROP BOTTOM OF BEAM AT WINDOWS, DOORS AND MASONRY OPENINGS AS REQUIRED TO PROVIDE A CONCRETE CLOSURE BETWEEN THE BO OM OF THE BEAM AND WINDOW AND/OR DOOL� HEADER OR PROVIDE A PRECAST CONCRETE LINTEL BY CASTCRETE IF NOT NEXT IO A POURED CONCRETE COLUMN. CASTC RETE LINTEL SHALL BE 8F8 1B FOR OPENINGS LE'.S THAN 48" IN WIDTH. B. `-'AXIMUM DROP SFIALL BE 12" AND SPAN EQUAL TO MAS NRY OPENING WIDTH, PROVIDE 2-#5 AT BOTTOM OF DROP INCLUDING #3 TIES @ 24" 0 C. EXTENDING TO TOP OF BEAM REINFORCING. IF THE LINTEL EXCEEDS THE ABO LIMIT OF DROP, A SEPARATED LINTEL SHALT BE PROVIDED C. LINTELS TO HAVE 8" MINIMUM BEARING AT EACH END. MASONRY 1. MASONRY UNITS SHALL BE ASTM C 90, NORMAL WEIGHT AN SHALL BE LAID IN A FULL BED OF MORTAR IN RUNNING BOND (UNO). 2. THE COMPRESSIVE STRENGTH OF MASONRY (F'M) SHALL BE 1,500 PSI AS CALCULATED IN ACCORDANCE WITH ASTM C1314. 3. ALL MORTAR SHALL BE IN ACCORDANCE WITH ASTM SPECIFIC TION C270 TYPE M OR S ONLY. 4. GROUT SHALL BE A HIGH SLUMP MIX IN ACCORDANCE WITH ASTM SPECIFICATION C476 AND HAVING A MINIMUM COMPRESSIVE STRENGTH OF 3,000 PSI 5. ALL CONCRETE MASONRY WALLS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE "BUILDING CODF REQUIREMENT FOR MASONRY STRUC URES" (ACI 530/ASCE 5/TMS 402) AND "SPICIFICATIONS FOR MASONRY STRUCTU ES" (ACI 530.1/ASCE 6/TMS 602)/ 2002 EDITIONS. 6. PROVIDE 8" X 8" MASONRY BEAM WITH 1 #5 CONTINIOUS AND HOOKED INTO IAMB AT EVERY WINDOW SILL. EXTEND BEAM 8" BEYOND EDGE OF C PENING. 7. PROVIDE HOT DIPPED GALVANIZED LADDER TYPE HORIZONTAL JOINT REINFORCEMENT (9 GA.) AT 16'' ON CENTER VERTICAL IN LL MASONRY WALLS, PROVIDE DOVE TAIL SLOT ANCHORS AT CONCRETE COLUMNS. WOOD 1. ALL STRUCTURAL WOOD MEMBERS ARE DESIGNED AS "DRY -USE". MOISTURE CONTENT MUST BE 19% OR LESS. STORE WOOD FRAMING ABOVE GROUND AND UNDER TARPS WITH PROPER AIR CIRCULATION 2. ALL LUMBER SHALL BE SOUTHERN PINE SPECIES #2 GRADE OR APPROVED EQUAL. ALLOWABLE DESIGN STRESSES SHALL FOLLOW NATIONAL DESIGN SPECIFICATION (NDS) (LATEST EDITION). 3. PROVIDE SP ACQ PRESSURE TREATED LUMBER IN ACCORDANCE WITH AWPA STANDARDS TO A MINIMUM 0.40 PCF RETENTION WHERE LUMBER IS IN CONTACT WITH CONCRETE/MASONRY OR OUTSIDE OF BUILDING. ALL METAL CONNECTORS IN CONTACT WITH PRESSURE TREATED LUMBER SHALL BE GALVANIZED WITH A RATING OF G-185 AND CONFORM TO ASTM A653. ALL NAILS AND SCREWS USED WITH PRESSURE TREATED LUMBER ARE TO BE HOT -DIPPED GALVANIZED AND TO CONFORM TO ASTM A153 CLASS D. ELECTROGALVANIZED FASTENERS SHALL HAVE A CLASS RATING PER ASTM B695 NO LESS THAN 55. ALUMINUM NOT TO BE USED IN DIRECT CONTACT WITH ACQ TREATED LUMBER. 4. PLYWOOD SHEATHING: A. ROOF: USE 19/32" 40/20 APA RATED, EXP. 1, PLYWOOD SHEATHING. B. SEE FRAMING PLANS FOR NAILING AND/OR BLOCKING REQUIREMENTS. USE 8'- 0" LONG X 4'-0" WIDE SHEETS WITH LENGTH ACROSS FRAMING. STAGGER PANEL END JOINTS 4'-0" TYP., ALLOW 1/8" SPACE ALONG PANEL EDGES AND END JOINTS. 5. WOOD CONNECTIONS - ALL NAILS USED FOR STRUCTURAL FRAMING MEMBERS SHALL BE COMMON WIRE, U.N.O. ALL NAILS, TRUSS HANGERS, TRUSS ANCHORS AND STRAPS SHALL BE GALVANIZED FOR CORROSIVE RESISTANCE. ALL METAL STRAPS MUST BE INSTALLED WITH EQUAL LENGTHS ABOUT THE JOINT LINE. USE SIMPSON STRONG -TIE CONNECTOR PRODUCTS OR APPROVED EQUAL. TOE NAILING WILL NOT BE PERMITTED. WOOD TRUSSES 1. WOOD ROOF TRUSSES ARE TO BE DESIGNED FOR THE WOOD FABRICATOR BY A PROFESSIONAL SPECIALTY ENGINEER REGISTERED IN THE STATE OF FLORIDA. SEALED CALCULATIONS AND LAYOUT DRAWINGS ARE TO BE SUBMITTED FOR APPROVAL. TRUSS FABRICA-�'R TO PROVIDE ALL TRUSS -TO -TRUSS HANGERS AS REQUIRED TO RESIST GRAVIT' AND UPLIFT REACTION 2. WOOD TRUSSES SHALL BE BRACED AND ERECTED IN ACCORDANCE WITH THE "TRUSS PLATE INSTITUTE" HANDLING, INSTALLING AND BRACING OF WOOD TRUSSES: COMMENTARY AND RECOMMENDATIONS, HIB (1991EDITION). BRACING IN THE PLANE OF THE WEB MEMBERS: A. THE TRUSS FABRICATOR SHALL PROVIDE AND LOCATE CONTINUOUS LATERAL BRACING FOR EACH TRUSS WEB MEMBER AS REQUIRED. B. LATERAL BRACING SHALL BE RESTRAINED BY DIAGONAL BRACING (MIN. 2" THICK NOMINAL LUMBER), THIS BRACING IS TO BE CONTINUOUS. C. A MINIMUM OF TWO ROWS OF DIAGONAL BRACING IS REQUIRED, ONE AT EACH VERTICAL WEB MEMBER CLOSEST TO BEARING LOCATIONS. 3. THE BOTTOM CHORDS SHALL BE BRACED BY CONTINUOUS LATERAL BRACING SPACED AT &-0" ON CENTER WITH A CEILING ATTACHED TO BOTTOM OF TRUSSES, IF NO CEILING IS ATTACHED TO BOTTOM OFTRUSSES, BRACING SHALL BE MINIMUM 2X4 @ 36" ON CENTER NAILED TO THE TOP OF THE BOTTOM CHORD. DIAGONALS PLACED AT 45 DEGREES TO THE LATERAL BRACES SHALL BE LOCATED AT EACH END. IF BUILDING EXCEEDS 60 FEET IN LENGTH, DIAGONAL BRACING SHOULD BE REPEATED AT 20-FOOT INTERVALS. 4. DO NOT CUT, DRI+_L OR NOTCH TRUSSES WITHOUT WRITTEN APPROVAL FROM TRUSS ENGINEER. COORDINATE MECHANICAL, ELECTRICAL, PLUMBING, ETC, SIZES AND LOCATIONS WITH TRUSS LAYOUT PRIOR TO ERECTION. 5. TRUSSES SHALL BE MANUFACTURED & DESIGNED IN ACCORDANCE WITH NATIONAL DESIGN SPECIFICATION(r) FOR WOOD CONSTRUCTION, AF & PA, AND NATIONAL DESIGN STANDARD FOR METAL PLATE CONNECTED WOOD TRUSS CONSTRUCTION, ANSI/TPI 1-1995, AND THE LOCAL CODE JURISDICTIONS. 6. DO NOT OVERLOAD ROOF TRUSSES WITH BLDG MAT'LS. 7. CONNECTOR PLATES SHALL BE MANUFACTURED BY A WTCA MEMBER PLATE SUPPLIER AND SHALL MEET OR EXCEED .ASTM A653/A653M REQUIREMENTS FOR STRUCTURAL STEEL. 8. WOOD TRUSS MANUFACUTER TO DESIGN BOTTOM CHORDS OF WOOD TRUSSES AT ALL ATTIC AREAS FOR A MINIMUM OF 10-PSF LIVE LOAD. BOTTOM CHORDS OF WOOD ATTIC TRUSSES TO BE DESIGNED FOR 30-PSF MINIMUM LIVE LOAD. SHOP DRAWINGS 1. SHOP DRAWINGS SHALL BE SUBMITTED IN COMPLETE PACKAGES FOR THE FOLLOWING: A. CONCRETE MIX DESIGNS. B. CONCRETE REINFORCING STEEL TO WELDED WIRE FABRIC. C, PRECAST CONCRETE INCLUDING BUT NOT LIMITED TO PRECAST LINTELS AND OTHER PRECAST CONCRETE SYSTEMS. D. CONCRETE MASONRY UNIT SUBMITTALS AND OTHER MASONRY ACESSORIES. E. COMPOSITE FLOOR/ROOF FRAMING (I.E. EPICORE) F. PRE-ENGINEERED WOOD TRUSSES. 2. PRE-ENGINEERED ITEMS SHALL BE SUBMITTED SIGNED AND SEALED BY A SPECIALTY ENGINEER REGISTERED IN THE STATE OF FLORIDA. THESE PLANS AND ALL PROPOSED Vv t- ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO COMPLY WITH ALL APPLICABLE CODES 7 v �C).r_ 01.CT0=Lf)L �� o, c},3 °- u, aaO�� � c U O. U C i C @ti�aF. Qo � U E &-0-0 as c V �'�O C:Tra o 0ru j ErDNO N D Q :D•- o'^wo°cc� c c � p u.1- 0 ov0.1::o >�o U Qj0MU�a.- Qro3 U _1 i O L1 ' 1-.1 u P__q O N M M N M 0) 00 M N 00 rN r�l O N N 4--J O N U l0 r N N < 0� < Q U L _ � N -2 Q M 0�fu C 70 O -p L-zLu0 0 e E to i. E CM O - N U U Z Lr) Ul U a f 0 L V) 0 U W V �o � ^� (� .- U ru -0 nV i i O W L 1,0 4-J 0 tp V) (z � Q 4--J U M Oz V) EN r-L _ Q ® Ln cL a Rev. # Date 1 06-Dec-11 Bldg Dept Comments Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet S30 Zl\ Structural Notes GROUND FLOOR. MECHANICAL PLAN MECHANICAL LEGEND Supply Diffuser-4 Directional L= Damper Supply Diffuser-1 Direction ■❑ Exhaust Fan Supply Diffuser- Wall Register Rigid Duct xxx CFMl Amount of CFM Supplied Flex Duct N SCALE: 1/4" = 1'-0" Z� GENERAL NOTES: MECHANICAL 1. Contractor shal verify all duct sizes and consult Energy Calculations pri )r to installing A/C system. 2. Provide condensation drain for air condition unit from attic. As shown on pl ns. 3. Locate Thermo 'tat per owner's direction. Manufacturer selected by owner. 4. Flex Duct shall The insulated flexible duct. 5. All main duct trunk lines shall be 1-1/2" heavy duty fire retardant w/ gl ass reinforced foil faced scrim. Follow manufa turer's installation for duct. EQUP. # MANUFACTURER/ MODEL NUN BER CDU #1 MITSUBISHI OR APPROVED EQUAL AHU #1 MITSUBISHI OR APPROVED EQUAL AHU #2 MITSUBISHI OR APPROVED EQUAL EXH #1 GREENHECK OR EQUA MECHANICAL SCHED JLE 1. Mini Split HVAC systems sh2 2. Refer to energy calculations I be P 'For se CLG HEIGHT - U-8" SECOND FLOOR MECHANICAL (PLAN 6. Diffusers shall be selected by owner. 7. Provide bird & bug screen for exhaust and make-up air grilles @ soffit. 8. Provide safety switch for exhaust fans. 9. Bathroom exhaust and fresh air intake are more than 10' apart. 10. Ducts in the garage and ducts penetrating the wall or ceilings separating the dwelling from the garage shall be constructed of a min No. 26 gage sheet steel, 1" min rigid nonmetallic Class 0 or Class 1 duct board, or other approved material and shall have no openings into the garage. As per FBC 2007 R309.1.1 I HESE PLAiNb ANO ALL t " vt tisu e ARE SUBJECT TO ANY CORRECTIU ,11 REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO COMPLY WITH ALL APPLICABLE CODES, __�NN SCALE: 1/4" = 1'-0" U� o-a��,s.. c� _1Eii3aa"i,� ---2 L �c � N.0 U L K U� O o �p �E��� -0 L� UO Cya3 0—ID in 0)O L V C=L =CLnJ Y Q L = L °vQ 6 VL 3 �pCOL0 7 ® Qc3ao3o3 s� O./ r\ O u- l--; O N mM N m al �, N CO 7-3 00 r, 00 00 4-J U O (N N N 00 lD T__q N N 4—J Q 0� N N Q Q U L _ Q4 of _0 Q C)) p O "a O 0 Ul U ,� ZLU0LL• Qj ® .-a —� un (1)L' 1 m O UO — N 4.J U z cn cn Lj C e q.o U i O / W U C O �rn �(y) �— U (10 r4-J ot�O un,c�-o� Q Oz (,n EN Q L ® Lf7 o a Rev. # Date 1 06-Dec-11 Bldg Dept Comments Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet M 2 . 1 Mechanical Plans NOTE: 1. MOUNT TANK TO CMU WALL WIT MFR BRACKETS ATTACHED TO UNIT. MOUNT PER MFR. INSTRUCTIONS. will 2" VEN 2" VEN p_g 2" VEN " GAS CONNECTION GAS SUPPLY MIN 3/4" COLD WATER SUPPLY LINE - ><.o- SHUT OFF VALVE SCALE: N.T.S. TIE INTO EXISTNG SEWER I C.O. ELEC. M FTF=R GROUND FLOOR PLUMBING PLAN PLUMBING SCHEDULE ITEM MANUFACTURER/ # EQUIPMENT MODEL NUMBER LOCATION FAUCETS P-1 LAVATORY TO BE SELECTED BATH 104 TO BE SELECTED BY OWNER BY OWNER P-2 WATER CLOSET TO BE SELECTED BATH 104 BY OWNER P-3 SHOWER HEAD AND CONTROLS TO BE SELECTED BATH 104 BY OWNER - P-4 BAR SINK TO BE SELECTED CLOSET 102 TO BE SELECTED 3Y OWNER BY OWNER P-5 DISHWASHER TO BE SELECTED CLOSET 102 BY OWNER P-6 REFRIGERATOR W1 FREEZER TO BE SELECTED CLOSET 102 BY OWNER P-7 WASHER/DRYER TO BE SELECTED CLOSET 103 BY OWNER - P-8 GAS WATER HEATER TO BE SELECTED EXTERIOR BY OWNER PLUMBING SCHEDULE GENERAL NOTES: 1. Contractor to provide electric and water per specifications. 2. - __�NN SCALE: 1/4" = 1'-0" _J L3" VTR / / / / / / / DW N ri / W/D N CLOSET 1 ti I 2" SHOWER LAV WC 2" N BATH 2 SANITARY RISER / n HB PLUMBING RISER SINK GENERAL NOTES: PLUMBING 1. Contractor shall fiE Id verify location and size of all existing 14. For drainage line for dishwasher use copper type 'DWV' per utilities & water pr ssure prior to construction. Any ASTM B-306. discrepancies with existing conditions and Permit Documents, 15. All copper pipes shall avoid contact with all other metals & contractor shall notify the Architect prior to modifications. and concrete masonry. If copper water lines run through 2. All labor, materialE, and equipment provide by Contractor metal studs, provide protection with metal stud inserts. shall be in accordance with all local & state applicable codes. 16. Install main water cut-off valve and backflow preventer All work shall be i stalled by a licensed plumbing contractor. where water line enters the building. Install in an accessible 3. Water & Sewer lines shall be capped and sealed to maintain location. Main water valve shall be ball valve and backflow dust free systems. lines shall be free of debris prior to preventer shall be a double check valve. connection of new equipment. 17. For all domestic water shut off valves install ball valves. 4. Piping penetrating any walls and floors shall be sealed. 18. Install pressure balance and antiscald valve (140°F) Any penetration of fire walls shall be sealed with firestopping for tubs/showers. material, where applicable. 19. Install a ball valve at water heater on the cold water line as 5. Piping penetrating the roof shall receive flashing and counter it enters the water heater. flashing. Coordinate with roofing manufacturer. 20. All connections at water meters, backflow preventers, and 6. Provide sleeves for piping penetrating the slab and under- appliances shall be made union joint. ground water pip+ g, with 1" min. clearance between sleeve 21. Install cleanouts every 50' on 4" drain lines and at base of and inside surface and pipe exterior. each vent in accordance with all applicable local and state 7. All insulation and E dhesives shall have a composite fire and codes. smoke hazard rating to meet ASTM E84, NFPA 255, and 22. All piping shall be concealed within the walls, chases, UL 723 not exceed ng a flame spread rating of 25 and a between floors, and under slab. Provide access panels for smoke developed rating of 50. all concealed shut-off valves. 8. Insulate all hot wa er pipes with 3/4" thick flexible foam. 23. Coordinate all piping to avoid conflicts with all trades. 9. Insulate or wrap a I piping to prevent vibration and sound 24. All plumbing fixtures are located on the plans. transmission causE d by water flow. 25. Plumbing layout and plumbing riser diagrams are 10. Insulate all domes tic water piping where exposed in non- diagrammatically drawn. Field conditions may require conditioned spaceE. Provide aluminum jacket and label modifications to layout for proper installation of piping and piping. fixtures. No modifications shall comprise the design intent 11. All pipe hangers a id supports shall be factory fabricated and of the building. comply with all local and state applicable codes. 26. All finished of pluming fixtures shall be coordinate with 12. All domestic water copper pipes and fittings above ground Owner prior to order accessories for plumbing fixtures. shall be type 'L' and underground shall be type 'K' per 27. Owner shall select all plumbing fixtures and accessories. ASTM B-88. 28. Fees for permits and other related items shall be coordinated 13. All drainage & ven pipes and condesate lines shall be between the Owner and Contractor. Schedule 40, Typ DWV in conformance with ASTM D2665. CLOSET 2" C.O. SCAL E: NTS SCALE: NTS n HB PLUMBING LEGEND PLUMBING PLUMBING SYMBOL DESCRIPTION SYMBOL DESCRIPTION COLD WATER PIPI" CW COLD WATER HOT WATER SUPPI, HW HOT WAFER HOT WATER RETURN THW TEMPERED HOT WATER -J>�o- BACKFLOW PREVEN I -ER HWR HOT WATER RETURN --� CHECK VALVE BALL VALVE THERMOMETER DRAIN VALVE BALANCING VALV[ [�I PRESSURE AND TEMPERATURE RELIEF VALVE -�� STRAINER DIRECTION OF FLOW -0 -•.-�� AQUASTAT DIELECTRIC UNION I, SHUT-OFF VALVE WATER HAMMER ARRESTER _I THESE PLANS AND ALL PROPOSED Vv(�� SUBJECT ARE SUBJCT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO CotV,01 ! �JJTW, qI I_ A.PPI.ICABI-F COura. v 0 v� �=.=y� � � ro.r✓ � �, 3 o�E�3a,� M t n@ N L I n �.0 �i C III O taro+,¢ ° !,�,:' F 'n LO Mom_ L U O O .0 a �i C:c -0 In •e LE=f�� °IACJ'80ccu ^> �..1. E_o � C -00 U ¢ 3:U °-ov�o Q tl U- N O tO U Q�3a-os o3 V '1 Oi H O N M Cn 00 LM N 00 r� n ® I� 00 CO 4--J ® N N N V l0 � N N Q Q� R as V L_ _ Q :G a c 0) � rn _0��� M p fu ra O-0 _0 (n U O-MIO zwo O L- E L -3 Ln (1) ru E 1 M :�' � O •-N :34-+ U v 0 U H� U U T Q00 4t) � V 0o C �M -0 . _ (!� U r� -r- 4-J O <D Ln Q -{-J C- ® Z U �. E N (0 Rev. # Date Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet P 2 . 1 Plumbing Plans GROUND FLOOR LIGHTING PLAN LIGHTING SCHEDULE TYPE MANUFACTURER/ DESCRIPTION LAMP VOLTS NOTES, OR EQUAL MANUFACTURER MODEL NUMBER I A AS SELECTED 6" RECESSED COMPACT FLUORESCENT 120 RECESSED IN CEILING BY OWNER LIGHT FIXTURE B AS SELECTED 6" RECESSED COMPACT FLUORESCENT 120 RECESSED IN CEILING BY OWNER LIGHT FIXTURE - DAMP LOCATION - C AS SELECTED WALL MOUNTED DECORATIVE LIGHT 120 MOUNT @ 80" A.F.F. TO BOTTOV OF BY OWNER FIXTURE-FEILD VERIFY D AS SELECTED WALL MOUNTED EXTERIOR DECORATIVE 120 MOUNT @ 80'' A.F.F. TO THE CE^NTERLINE BY OWNER HID - DAMP LOCATION OF LIGHT'S JUNCTION BOX E AS SELECTED UNDER CABINET LIGHTING 120 VERIFY MOUNTING WITH BY OWNER OVERHEAD CABINETS LIGHTING SCHEDULE GENERAL NOTES: 1. All light fixtures shall be selected by Owner and installed by GC. 2. Install light fixtures as per manufacturer specifications. 3. Provide new bulbs for all new installed light fixtures. 4. Fixture finishes shall be selected by Owner. 5. Coordinate final location of fixtures with Owner prior to installation. N SCALE: 1/4" = 11-011 N GENERAL NOTES: LIGHTING 1. Contractor shall compare the electrical drawings 4. All electrical work and materials to be installed and specifi -ations with drawings from other trades. per NEC, NFPA, local, state, and national code. Contractor shall report any discrepancies to the 5. Location of electrical raceways, switches, panels, Architect. Obtain written instructions for any equipment, fixtures, etc. shall be adjusted to necessary changes. accommodate the work to avoid interferences 2. Furnish and install fixtures as called for on the plans anticipated and encountered. or as selected by Owner. 6. Coordinate heights of wall mounted lighting fixtures 3. Contractor shall verify fixture type and locations to clear mirrors, cabinets, builts-ins, trim, etc. with ownei prior to installations. ELECTRICAL LIGHTING LEGEND s witch Single Pole Ceiling Fan - to be selected by Owner witch with Dimmer way Switch xx Wall Mounted Interior Decorative Light Q unction Box- See KEYED NOTES xx 4 Wall Mounted Exterior Decorative Light xx Under Cabinet Lighting Wall Mounted Floor Light Oxx Zecessed Lights xX ® Exhaust Fan Note: Subscribes are used to designate light types. See I iGHTING SCHEDULE for light types. A l 31S A SECOND FLOOR LIGHTING PLAN THI"SE PLANS AND ALL PROPOSED ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO „ )Mpl`�' ,RTLJ Al 1 A001 it`A4! G ('C?[)F( N SCALE: 1/4" = V-0" .L a C'i yr O O N_ Cis Q) (1) U � i-i t �C Ut o 3CtQa3 U C oQ C u U Ewa 'E�mc 1nro1•u C— °'0 L V' Lo-� U Q7N a100 CC U CC=a) 0a)i 0--0 Q 3 w C U 3, U 0 7- 2 Qaa3rr V O u- �....� O N M Q1 N00 I 1 00 0 N 00 00 4..J 0 N N N V Q� nn a F U L _ QM 4-):4-J Q) n O� (y) ry C ru ru o -a M -J L— cri U Q "—" M - 1— Z L1J ®LL- O J E L u7 4J M '., M — N :3 u UO U Z T—I Lr) V) 0 4` o 7 (:I u. u y 1 U Q ro o Y" r C E U W � V O i M •— U fa r(3 I-- 4-J 0 1,0 � ,�LLrn Q R3 C: .S-- �: U M Oz U) EN 4— '-i - Ln Rev. # Date 1 06-Dec-11 Bldg Dept Comments Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet E2m 1 Lighting Plans LOA D CA LC U LATI O N S New 100 amp SUB PANEL Load Calculations: Total Panel Load: 840 sgft. @ 3.0 VA/sqft. = 2,520 VA A/C #1 @ 2.5 kw = 2,500 VA Garbage Disposal = 900 VA 1st 10,000 VA @ 100% = 10,000 VA Refrigerator = 1,200 VA Remaining VA @ 40% = 1,848 VA Microwave = 1,500 VA Dishwasher = 1,500 VA Total: = 14,348 VA Dryer = 5,000 VA Washer = 1,200 VA Water Heater = 800 VA 14,:348 VA = 59.78 amps A/C #1 @ 2.5 kw = 2,500 VA 240 V Sub -Total: = 17,120 VA Total Amps required: = 59.78 VA Summary: - 1. Provide new 100 amp, 30 curcuit sub -panel at bathhouse. RISER DIAGRAM 0 EXISTING METER (3) #TS 1 #8 GRND D/C D/C 200 T 200 SUB PANEL PANEL PANEL (EXIST.) _.___._! (EXIST.) 100 AMP SCALE: N.T.S. GROUND FLOOR POWER PLAN XX" � /XXX XX" :::QG FI xx" XAFI ::::QwP XX'. ::::nXXX XX'1 �DED ELECTRICAL POWER LEGEND Duplex outlet Duplex outlet (Ground Fault Interrupt) Duplex outlet (Arc Fault Interrupt) Duplex outlet (Waterproof) Duplex split wired outlet Dedicated Duplex outlet Telephone outlet Data Port T.V. cable outlet WIRE SIZING TABLE BRK (P N GND c 20 12 12 12 3/4" 30 10 10 10 3/4" 50 8 8 10 1" 70 4 4 8 1 1/4" 90 3 3 8 1 1/2" 11/2" 100 3 3 8 125 1 1 6 2" 150 1/0 1/0 6 2" 175 2/0 2/0 6 2" 200 3/0 3/0 6 2 1/2" 225 4/0 4/0 4 21/2" 250 250 250 4 3" 300 350 350 3 4" 350 500 500 3 4" 2, _�WN SCALE: 1/4" = V-0" Dedicated Duplex outlet (Ground Fault Interrupt) Dedicated Duplex outlet (Waterproc" Floor Duplex outlet Quadraplex outlet Quadraplex outlet (Ground Fault ]Interrupt) Quadraplex outlet (Waterproof) D/ Disconnect SD Smoke Detector (mount on ceiling, unless noted otherwise) Carbon Monoxide Detector (mount to wall, unless noted otherwise) �—Mounting height to the center -e of the receptacle xx _ _Oxxx Type of receptacle i8 18" 18" GENERAL NOTES: POWER 1. Contrac or shall compare the electrical drawings and sp -.ifications with drawings from other trades. Contractor shall report any discrepancies to the Archite t. Obtain written instructions for any necessary changes. 2. Contrac or to verify and coordinate utility service with local utility company. Locate meter and panel as requ red. 3. Install t ,mporary power for construction as require(''. 4. All elect-ical work and materials to be installed per NEC, NFPA, local, stage, and national code. 5. Locatior of electrical raceways, switches, panels, equipm nt, fixtures, etc. shall be adjusted to accommodate the work to avoid interferences anticipated and encountered. 6. Contractor shall verify switch type and locations with owner prior to installation. Color of cover plates, ;witches and receptacles shall be selected by own !r. 7. Contractor shall determine the exact route and location of each electrical raceway prior to make-up and ass=mbly. 8. Outlets and appliances are shown and located on the drawings as accurately as possible. All measurements shall be verified on the project and in all cases the work shall suit the surrounding trim, finishes and/or construction. 9. Heights of all outlets shown on the drawings are approxi nate only. 10. All outl .ts installed outdoors, bathrooms, and garage ;hall have ground -fault interrupter circuit breaker or receptacle. All outlets installed in the bedrooms shall have arc -fault interrupter recepta les. w 18" 1 III 1 24" P/ G FI STORAGE BALCO 11 005 006 SECOND FLOOR POWER KAN 18', 11. Load data and calculations were designed based on information given to Architect at the time of the design. Prior to installation of all equipment verify size of equipment and panel sizes. 12. Electrical system shall be grounded. See Riser Diagram. 13. Outlet boxes shall be pressed steel in dry locations, cast alloy with threaded hubs in wet and damp locations and special enclosures for other classified locations. 14. Disconnect switches shall be H.P. rated, heavy duty, quick -made, quick break enclosure required by exposure. 15. Smoke detectors shall be hard wired (110 volt type) to non-switchable light circuit and shall not be connected into the load side of a ground fault circuit. 16. Smoke detectors shall be located on or near ceiling inside and outside each sleeping area. Verify locations of smoke detectors with the drawings. 17. Smoke detectors shall be 110 volt type, with a test button with battery back-up system and visible "power on" indicator. 18. All 12-volt, single phase, 15 and 20 amp branch circuits supplying outlets installed in dwelling unit family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, rec rooms, closets, hallways, similar rooms or areas shall be protected by a listed arc -fault circuit interrupter combination type, installed to provide protection of the branch circuit (NEC 2008 210.12 (B)). 19. Tamper Resistant Receptacles (NEC 406.11) are ►-(_,quired in dwelling units in all areas as specified in 2008 NEC 210.52, all 125 volt, 15 and 20 amp eceptacles. THESE PLANS AND ALL PROPWL,-) v- -, ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO COMPLY WITH ALL APPLICABLE CCDFc N SCALE: 1/4" = V-0" O'Lc T N L •L •� C� � N O ap 2. W , C o N@O.UC�i —L aro„a o u E E �p-O E VB" C J(3)� O �n fO � U L LOUO Cya 3 °°4 N 0�°� Cc: C U CC,7�O�Q O+ LL 3°_3� =0=W ® U i ._Y+ 0 TO �a`�° Q� Q�3�a�3ro3 U Ou 1-- 1­0 H 0 N M al n , N M Ql N 00 M ® tom 000 00 4J OrN NN U �0 '-' v i Q0� hN Q Q .,.. L _ Q c 0)v �/� s Q �- M V) Q i O � � ra (a , a .Ei U) U 0 ry) /� O (1)Zuio E Jv E1M:L- O — N :3 4-J U U Z V) (n -------------- UrI W L i� IN a 1 C V: Y O vi O ✓ 2 U W ro W L M •— U fa cn`0O -r— 4- J Q a �M Oz�N cn L� L fu Q 0 Ln c- 0 Rev. # Date 1 06-Dec-11 Bldg Dept Comments Proj 11-0470 No. Status Final Issue 14-Sep-11 Date Sheet Ell Power Plans