HomeMy WebLinkAboutFIELD EVALUATION REPORTNemko North America, Inc.
I Nem ko 2210 Faraday Ave., Sdite 150, Carlsbad, CA 92008, USA
Phone (760) 444-3500 Fax (760) 444-3005
Contender Boats
FIELD EVALUATION
REPO
RT
EQUIPMENT
DMS Glacier 5 Axis CNC Machine.,
REPORT NUMBER
NEX # 467317
DATE ISSUED
,June 2, 2022
3
Rev 2021-06-30
CNcemko
Nemko North America, Inc.
2210 Farad Iy Ave., Suite 150; Carlsbad, CA 92008, USA
Phone (760) 444-3500 Fax (760) 444-3005
Equipment covered: DMS Glacier 5 Axis CNC Machine
Standard(s) NFPA 79, & N PA 70
Applicant: Contender Boats
5701 Environment Dr.
34981 Ft. Pierce FLUSA
Applicant Contact:
Robert Desan.E
305-242-7401I
Phone:
Email:
robertcontehderboats.com
Date of Inspection:
June 6, 2022
Evaluation Site:
5701 Environment
Dr.
Ft. Pierce, FLU
34981
USA
On -Site Contact: Chris Becker
Office: 5701 Environment Dr. Ft. Pierce, FL 34981
Mobile: 516-426-6030
Email: chriscontenderboats.com
Authority Having:
Jurisdiction (AHJ)
Reference #
Issued by:
No Inforrnationl provided at this time
Christopher Caserta! -
Chris.casertAo-nemko:com
(904) 753-3420 (Remote Office: Jacksonville FL)
Nemko North America, Inc.
2210 Faraday Ave., Suite 150
Carlsbad, CA 92008
USA
Report:.(NEX # 467317) Pdge 2 of 10
Nemko North America, Inc.
CN,emko 2210 Faraday Ave., Suite 150; Carlsbad, CA 92008, USA
Phone (760) 444-3500 Fax (760) 444-3005
SUMMARY
June 2, 2022
The DMS Glacier 5 Axis CNC Machine model: 506-10-5-8E(x is located at Contender.
Boats, and will be used for the parts fabrication of boats.
Key inspection points or other special circumstances to be noted.
Grounding
Incoming phase conductor segregation
Wire sizing
Wire Insulation
Circuit protection
Conclusion (Installation Field Evaluation must be completed for a final comclusion)
Report: (NEX # 467317) Page 3 of 10
CNIeE-mko
PURPOSE OF EVALUATION:
Nemko North America, Inc.
2210 Faraday Ave., Suite 150, Carlsbad, CA 92008, USA
Phone (760) 444-3500 Fax (760) 444-3005
The Authority Having Jurisdiction over aij electrical equipment installation may rely on
independent testing laboratories that are qualified and equipped to perform safety
evaluations. Typically, equipment installed in the U:S. or Canada has been investigated,
Listed, and Labeled by a Nationally Recdgnized Testing Laboratory (NRTL) in the U.S and
by a. Standards Council of Canada (SCC� accredited Certification. Body in Canada. In the
absence of such approval(s), judgment as to the suitability and compliance of equipment
can be a burden to the Authority Having �burisdiction (AHJ). As such, a qualified laboratory
may be utilized to evaluate such equipment for purposes of assessing compliance with
applicable standards and requirements.
CONDITIONS OF ACCEPTABILITY:
Procedures used to approve the gquipment described in this report comply with
International Accreditation Service (IAS) accreditation criteria AC354 and are based
on the National Fire Protection Association (NFPA) Standards 790 and 791:
"Standard for Competency of Third -Party Field Evaluation Bodies" and
"Recommended Practice and Procedures for Unlabeled Electrical Equipment
Evaluation". Additionally, requirements per the Standards Council of Canada (SCC)
are followed for Canada.
2. -For equipment that has not been) evaluated at the final installation site, there may be
additional site installation requirements mandated by local authorities having
jurisdiction (AHJs) and are the responsibility of the customer.
3. The equipment has been evaluated for electrical safety only, for installation and use
in ordinary (non -hazardous) loc tions in accordance with national and local
electrical codes; requirements other than electrical safety may be mandated by local
authorities having jurisdiction (AJs) and are the responsibility of the customer.
4. The equipment or system shall be used in a manner consistent with the
manufacturers design and instrt Ictions. Instructions shall be available in an
accessible location for maintenance and reference by the end user.
5. The area surrounding the equipment or system shall be kept free and clear from,
combustible material. Adequate clearances shall be maintained for proper safety,
operation and servicing.
6. A maintenance and servicing schedule shall be followed to keep the equipment or
system operating as designed.
he final responsibility for establishing a
maintenance program will rest the end user.
7. As parts deteriorate or cease to' function properly, they shall be replaced or repaired
with the same part, or the equipment shall be removed from service. No changes to
the design, construction or use Ishall be made without the written acknowledgment
and approval of Nemko. Additional evaluation and testing may be required to
determine acceptability of any changes made.
Report: (NEX # 467317) Page 4 of 10
Cernko
EVALUATION PROCEDURE:
Nemko North America, Inc.
2210 Faraday Ave., Suite 150, Carlsbad, CA 92008, USA
Phone (760) 444-3500 Fax (760) 444-3005
Objective. The objective of Nemko's third -party Field Evaluation program is to verify that
the design, construction, and installation of the identified equipment or system was in
essential compliance with applicable portions of the referenced Standards.
The Field Evaluation service is,intended for one-of-a=kind, limited -production, used or
modified products and unlisted electrical equipment, where the final installation location is
known and the requirements of the local Authority Having Jurisdiction (AHJ) have been
addressed. The process is completed at the point of manufacturing, interim points of
distribution, in the evaluating company's facilities, at the final installation site, or a
combination of the above, as requested by the customer.
Procedure for Evaluation. The equipment or system is evaluated for the following
elements:
Visual Inspection: A visual inspection of the equipment was conducted, comparing product
construction to requirements of the applicable standard. The evaluation included directly
connected loads to the equipment identified in the report. Complete inspection records are
on file at Nemko.
Suitability for Use and Location: The equipment was found to be suitable for the indoor
location. There were no adverse environmental conditions found that would impair the
proper operation and use of the equipment. The equipment was suitably protected from
physical damage.
Condition of the equipment: The equipment was in good condition. No components were
found to be damaged in a manner that impacted performance and operation. Metallic
parts of the equipment had suitable corrosion protection. Nonmetallic parts were not likely
to suffer deterioration or create a fire hazard.
Access and Workspace clearances: Access was provided about all electrical equipment to
permit ready and safe operation and maintenance of the equipment. The workspace
clearances for electrical enclosures likely to require examination, adjustment, servicing, or
maintenance while energized were provided in compliance with applicable standard.
Exposed Parts: Adequate spacings, creepages, and clearances were provided between
live parts of opposite polarity and noncurrent -carrying metallic parts, or suitable barriers
were provided. Where live parts were exposed, suitable guards or barriers were provided.
Separation: Electrical conductor insulation of different voltage systems were found to be
either rated for the highest voltage or were separated by suitable barriers. Electrical wiring
was separated from other utilities such as oil and water by suitable barriers.
Grounding and Bonding: All required non -current -carrying metallic parts of the equipment
have been determined to be suitably bonded to the supply equipment grounding
conductor. The equipment grounding conductors and bonding jumpers were terminated
properly. Equipment grounding conductors and bonding jumpers served no other function.
Report: (NEX # 467317) Page 5 of 10
Nemko North America, Inc.
C'Nleimko 2210 Faraday Ave., Suite 150, Carlsbad, CA 92008, USA
Phone (76I) 444-3500 Fax (760) 444-3005
Overcurrent.Protection: The type and ra�ings of the overcurrent protection provided within
the equipment were suitable for the conductors and loads served.
Motor Overload Protection: All Motor (
with NEC Article 430 Part III or CEC 2
Conductors: All equipment wiring was fo
verified as acceptable. Conductors were
temperature ratings. Conductor sizes we
given in the standards identified in this n
rload protection was verified to be in compliance
!00 for Canadian Special Inspection.
and to be certified for use, accepted by testing, or
used within the applicable voltage and.
re in accordance with the allowable ampacities
port.
Wiring Methods: The equipment wiring ethods were properly secured, supported, and
routed away from physical damage. The wiring methods utilized in and one the equipment
provided the required separation and protection from live parts as required by the
standards noted in this report.
Field Wirinq Terminations: All field wiring terminals were identified and were suitable for
the conductor.type, stranding, and ampacity of conductors being terminated. Terminals
suitable for more than one conductor were marked.
Guarding of Equipment: The evaluated i
provided.with suitable covers, enclosure
for the evaluation. Fastenings used for (
Hinged doors are able to open at least f
least 110°. Labels were applied on the E
apprising the users of the physical haza
juipment identified in this report has been.
, and guards as required by the.standards used
vers were in accordance with the standard.
°. Swing -out panels if used were able to open at
uipment where required by the standard
Is associated with the equipment. .
Markings: Where applicable the require Caution, Warning, and Danger markings were
provided on the equipment. Complete nameplates were provided as required by the
standard.
General Engineering Practices: The equipment was constructed to meet the requirements
of the standards identified in this report. The equipment was constructed in a workmanlike
fashion.
Cleanability: All surfaces and parts were inspected and determined that areas that are
likely to become dirty can be cleaned as needed. (Sanitation Evaluation Only)
Materials: All materials used were of SS or of NSF approved types. Surfaces are smooth
and cleanable. (Sanitation Evaluation Only)
Conclusion. Once the equipment or system has been evaluated'for the above elements,
any discrepancies are noted in the Non-compliance issues section for correction by the
customer. Once discrepancies (if any) are addressed, Testing is then performed. '
Report: (NEX # 467317) Pade 6 of 10
Nemko North America, Inc.
Ne m k� 2210 Faraday Ave., Suite 150, Carlsbad, CA 9200.8, USA
Phone (760) 444-3500 Fax (760) 444-3005
LIST OF CRITICIAL COMPONENTS:
Critical. components list, schematics, and other supporting documents on file in Nemko
project folder.
See schematic: Multiple drawing in file: Supporting Documents
NON -COMPLIANCES:
Non -Compliance Approved Resolution
No Issues
TEST RESULTS:
The equipment was subjected to the following tests with acceptable results.
Insulation'Resistance Test —A test potential of 500 V do is applied between each phase
power circuit conductor to ground at the machine supply terminals and the contactor load
terminals of the motor and heater loads. The measured insulation resistance_ is at least 1
megohm at any point tested.
Grounding Continuity Test— Ground continuity verified between ground terminal and to
all accessible dead metal surfaces of equipment assembly. All metal parts found to .be
continuous to ground connection.
Torque (Customer Equipment) — Main terminals were torque down to manufacturer
specification guide. N/A
Refer to SPE 1000-13 for following test: N/A
r Leakage r Hi -Pot r Strain Relief r flame r temperature r input rating
other (refer to following data)
TEST RESULTS:
The equipment was subjected to the following tests with acceptable results.
All Models:
Insulation test- Pass > 1 meg Ohm
Ground continuity — Passed, < .1 Ohm
Dielectric test — Passed, 1500 Vac
Report: (NEX # 467317) Page 7 of 10
CmkoNer
2210 F
Phone
North America, Inc.
y Ave., Suite 150, Carlsbad, CA 92008, USA
444-3500 Fax (760) 444-3006
Model
913.89
Multi
Fluke
116
18320052
7-16-2021
7-16-2022
meter
ncrmal
SI390
RMS Multi
Fluke
87111
78946137
7-16-2.021
7-16-2022-
meter
S1391
Multi
Fluke..
77111
77470272
7-16-2021
7-1672022.
meter
S1392
RMS Multi.
Fluke
189
80260372
7-16-2021
7-16-2022 .
meter
S1393
Power
Fluke
39
D17900090
.7-16-2021
.7-16.2022
Analyzer
S1394
Insulation
Biddle
BM.122
6311-
7-16-2021
7-16.2022
Tester
055/0201021367
6
S1395
100 Mhz
Fluke.
FLK-196
9444 001 96003
7-14-2021:
7-14-2022.-
Sca meter
S1396 '
Caliper
Electronic
Di ital
00400835
7-14-2021
.7-14-2022
S1397
Infrared
Raytek
MT41)
1.2072
7-15-2.021
7-15-2022
Thermomet
er
S1398
AC/DCAR/
V.irtek
V74
026163.
7=1&2021
7-16-2022'
GB Tester
S1399
AC Current
Fluke
801-500S
63913404
746-2021
7=16-2022
Clamp
S1431
I
Torque
Nemko own
6PAF7
19020,01725
7.27-2021
7-27-2022:
Wrench.
Westward
8. of 10
Nemko North America, Inc.
N Ee m k o 2210 Faraday Ave., Suite 150, Carlsbad, CA 92008, USA
Phone (760) 444-3500 Fax (760) 444-3005
IF —
Owl.
-
-
At
IM
- p y ouoppn e
parooc
� q � pn duo■
A G7 Ip 4 A n ni LaaomtC _ ;
�: � ''O.4 COP r.� � tl•! /�.M
l 0 ,, Y
' {tf •�� - "`f Nip
Report: (NEX # 467317) Page 9 of 10
Nemko
CONCLUSION:
Nern !o North America, Inc.. .
2210 Fara ay Ave., Suite 150, Carlsbad, CA 92008, USA
Phone (76;0) 444-3500 Fax (760) 444-3005
The equipment covered by this: field eva uation report was evaluated to comply with NFPA
70 and essential compliance to nationall recognized standards. This evaluation is not
equivalent to product certification. Folio ing the evaluation and testing, and any corrective
action(s) that were deemed necessary, tie unit(s) were labeled with the serialized Nemko
field evaluation label(s),' as specified below:
Manufacturers �Motlel Ratings ' Label
DMS 506-10-5- 460 V� c, 40 A, 3 Ph, 60 Hz, 3003 110042
8E/x rSCCR1OkA
The Nemko field evaluation label appliel to this device indicates that the evaluation was
performed with.the intent of meeting app opriate nationally recognized standards and is
intended to assist code., enforcing authorities and others (AHJ) involved in judging
acceptance of the device for use in their urea of jurisdiction. This report shall apply only to
the products tested and generally only toy; one location or installation.
If there are any questions regarding the �1esults contained in this report, please do not
hesitate to contact the undersigned or your dedicated Project Manager.
Issued by:
Chris Caserta
Sr.Machinery Engineer
Chris.casertaCcD-nemko.com
Nemko USA, Inc.
Reviewed by:
/4L
Michael Anthony
Sr FE Engineer
Michael.Anthony(&-nemko.com
Nemko USA, Inc.
Report: (NEX # 467317) Pago 10 of 1.0