HomeMy WebLinkAboutPOLY ROOF CARPORTTI"LBLE OF ROOF BEAMS, COLUMNS, PURLINS AND GIRTS: SPECIFICATION NOTES AND DESIGN PARAMETERS: THIS POLY ROOF CARPORT MEETS THE FLORIDA BUILDING CODE FOR A HEIGHT 13'-6", 150 MPH, EXP. 'C' WIND SPEED. THE TABLES BELOW ARE BASED ON SIMULTANEOUS LOADING AS DEFINED IN THE FLORIDA BUILDING CODE (FBC), CHAPTERS 16 AND 20, AND OTHER REFERENCES SUCH AS ALUMINUM ASSOCIATION OF FLORIDA (AAF) "GUIDELINES TO ALUMINUM CONSTRUCTION IN HIGH WIND AREAS". STRUCTURAL VALUES FOR EXTRUDED ALLOY 6005T5 ARE TAKEN FROM THE ALUMINUM DESIGN MANUAL, 2015 EDITION. TABLE 1 MAIN ROOF MEMBER SCHEDULE MEMBER I MARK I MANF. I WEIGHT ATERIA THICKNESS I LENGTH DESIGN BASIS # I SKIN I 'P70—LY-1 SKIN I FT. IFL. PROD. APPR. POLY ROOF PANEL # 1 PRP1 I ELITE 1 2 1 ALUM 1 1 26'-0" FL7561-R3, DWG. OR = �_030 FL-1001, 3-20-15 TABLE 2 MAIN MEMBER SCHEDULE MEMBER I MARK SIZE I MATERIALI TYPE I THICKNESS ILENGTH DESIGN BASIS b x t ALLOY W F FT. COLUMN # 1 COLUMN # 2 COLUMN # 3 CARRIER BEAM # 1 CARRIER BEAM # 2 ROOF BEAM # 1 BRACE # 1 Cl 4x4-12 ALUM TUBE 0.125 0.125 16'-0" CALCULATION C2 2x3-9 ALUM HOLLOW 0.090 0.090 8'-11" CALCULATION C3 4x4-12 ALUM TUBE 0.125 0.125 16'-6" CALCULATION CBI 2x8 ALUM SMB 0.072 0.224 12'-0" CALCULATION CB2 2x3-9 ALUM HOLLOW 0.090 0.090 6%0" CALCULATION RBI 2x3 ALUM HOLLOW 0.050 0.050 24'-0" CALCULATION B1 2x4H ALUM HOLLOW 0.050 0.050 4'-6" CALCULATION ADDITIONAL SITE SPECIFIC INFORMATION THIS POLY ROOF CARPORT IS LOCATED IN A RESIDENTIAL COMMUNITY SOUTH OF INDIAN RIVER ESTATES AND A LITTLE MORE THAN A MILE' WEST OF S. INDIAN RIVER DRIVE IN PORT ST. LUCIE. THE POLY ROOF CARPORT HAS MANY OPEN AREAS AROUND IT. IN ACCORDANCE WITH THE EXPOSURE CATEGORIES LISTED IN SECTION 1609.4.3 OF THE FLORIDA BUILDING CODE THIS ENCLOSURE SHALL BE CALLED AN EXPOSURE 'C'. ACCORDING TO THE COMPUTER PROGRAM "WINDSPEED BY LOCATION-, A PRODUCT OF 'APPLIED TECHNOLOGY COUNCIL' THE DESIGN WIND LOAD REQUIREMENTS FOR A RISK CATEGORY I ENCLOSURE IN THIS LOCATION IS DICTATED BY A WIND SPEED OF 148 MPH. HENCE, THE DESIGN PARAMETERS BEING USED HERE ARE 150 MPH WIND LOAD, EXPOSURE 'C', RISK CATEGORY I. THE POLY ROOF HAS A RISE OF 6 INCHES AND A RUN OF 24 FEET, WHICH GIVES A SLOPE OF ABOUT 0.25 INCHES PER FOOT. THE POLY ROOF CARPORT IS BEING BUILT ON NEW ISOLATED FOOTER THAT ARE 24" x 24" x 32" DEEP. THE THESE ISOLATED FOOTERS ARE AN ACCEPTABLE FOUNDATION FOR THE CARPORT. THE DESIGN DRAWING IS SHOWN ON SHEET 2. THE BACK WALL OF THE POLY ROOF AND OPTIONAL CARRIER BEAM TO COLUMN CONNECTIONS ARE SHOWN ON SHEET 3. POLY ROOF CONNECTIONS ARE SHOWN ON SHEET 4. ADDITIONAL CONNECTION DRAWINGS ARE SHOWN ON SHEET 5. SEE ISOLATED FOOTER DETAIL BELOW. <-COLUMN 12" 32" 12" 1 8" -16" 24" 24" ELEVATION VIEW PLAN VIEW 24�. SKETCH OF ISOLATED FOOTER THIS DESIGN COMPLIES WITH THE GUIDELINES DEFINED IN CHAPTERS 16 & 20 OF THE FLORIDA BUILDING CODE (FBC), 5TH EDITION (2014) BUILDING, USING THE ALLOWABLE STRESS DESIGN PRESSURES LISTED IN TABLE 2002.4 AND TABLE 2002.4A. THE AAF STANDARDS OF THE "GUIDELINES TO ALUMINUM CONSTRUCTION IN HIGH WIND AREAS" FOR TABLE 1 ARE APPLIED. A DESIGN BASICS: THIS POLY ROOF ROOM IS RISK CATEGORY I STRUCTURE. HEIGHT 13'-6", 150 MPH, EXP. 'C' B THE BUILDING CLASSIFICATION RISK CATEGORIES ARE FROM FBC, TABLE 1604.5 AND AREA LOCATION WIND SPEED PER FBC, FIGURE 1609C. BUILDING CLASSIFICATION PER TABLE 27.2-1, ASCE 7-10. C DESIGN PRESSURE: FOR SOLID ROOF @ 30.96 PSF PER TABLE 2002.4. D MAXIMUM HEIGHT: HEIGHTS HIGHER THAN LISTED ABOVE REQUIRE SITE -SPECIFIC DESIGN BY THE ENGINEER OF RECORD. E ALLOWABLE DEFLECTION: L / 60 MINIMUM, AS SPECIFIED IN TABLE #1604.3 OF FBC. F CONTINUOUS LOAD PATH IS PROVIDED WITHIN THE CALCULATIONS USING ALLOWABLE STRESS DESIGN PRESSURES. 2 MATERIALS (UNLESS OTHERWISE SPECIFIED BY THE ENGINEER OF RECORD): A ALL EXTRUSION MATERIALS SHALL BE ALUMINUM ALLOY # 6005T5 OR # 606lT6; ALLOY # 6063T6 IS NOT ACCEPTABLE. B FASTENERS: ALUMINUM ALLOYS #2024-T4 & #7075-T6, DOUBLE CAD -PLATED STEEL, HOT -DIPPED GALVANIZED STEEL OR 300-SERIES STAINLESS STEEL. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE FOR SEPARATION OF DISSIMILAR MATERIALS AS DEFINED IN THE FBC. HE/SHE MAY IMPLEMENT ANY OF THE MEANS LISTED IN THESE SECTIONS. ALTERNATIVES MUST BE REVIEWED AND APPROVED IN WRITING BY THE ENGINEER OF RECORD PRIOR TO ANY INSTALLATIONS UTILIZING THE SUBJECT METHODS. C SCREEN CLOTH: SHALL BE VINYL -COATED, WOVEN FIBERGLASS, MAXIMUM DENSITY OF 18 X 14, 58% OPEN MINIMUM. OTHER SCREEN DENSITY REQUIRE ADDITIONAL ENGINEERING CONSIDERATION. D ANY CONNECTION USED, THAT IS NOT SHOWN ON THESE SHEETS, MUST MEET ALL FBC AND AAF GUIDELINES. q F E MATERIAL UPGRADES (STRONGER AND/OR HIGHER GRADE MATERIALS) CAN BE SUBSTITUTED AT ANY TIME. F A 2x2 OR A 2x3 SNAP MEMBER CAN ALWAYS REPLACE A 2x2 OR A 2x3 HOLLOW MEMBER, RESPECTIVELY. G WHEREVER SCREENING OR KICKPLATES ABUTS THE HOUSE OR CONCRETE THE MEMBER USED TO SUPPORT THAT /O 1 SCREENING OR KICKPLATE WILL BE A 1" x 2" x 0.046" O.B. OR STRONGER ALUMINUM MEMBER. H ALL DOOR JAMS (DJ) SHALL BE 2" x 2" x 0.046" ALUMINUM MEMBERS OR STRONGER. I IT IS ALWAYS ACCEPTABLE TO ADD OR RELOCATE A SCREEN DOOR AS LONG AS THE COLUMNS ARE NOT DISTURBED J ALL FASTENERS AT FLOORS, WALLS AND CEILINGS MUST BE NO MORE THAN 24" 0. C. WITH 2" ENGAGEMENT (MIN.).40 (� y 4 �- 3 ALL HOUSE FASCIA DETAILS, BOLTING OR SCREW SELECTIONS, BEAM SPLICE DETAILS, DIAGONAL "K" BRACING DET/�(k W: COLUMN TO BEAM DETAILS, STRUCTURAL GUTTER DETAILS, WALL AND FASCIA DETAILS, CORNER ANCHOR DETAILS, E ROOF BRACING DETAILS, EAVE BRACING DETAILS, ETC., IF NOT EXPLICITLY OUTLINED ON THIS SPECIFICATION, SHALLBEQ IN ACCORDANCE WITH THE LATEST FBC EDITION, INCLUDING THE AAF. ALL INTERNAL CONNEjTHW&lSF&%LANDFALL yYAOPOSED WC FBC (AAF) AND THERE INSTALLATION ARE THE RESPONSIBILITY OF THE CONTRACTOR. ARE SUBJECT TO ANY CORRECTIONS REQUIRED BY FIELD INSPECTORS THA 4 THE LOCATION OF ALL "K" BRACING, WIND BRACING, EAVE RAILS AND CHAIR RAILS, ALONG VRW J31SY489MNRY IN ORDER TO ABNORMALITY, ARE SHOWN AND/OR LISTED ON SHEET 2, THE "SITE SPECIFIC DRAWING". COMPLY WITH ALL APPLICABLE CODEI POLY ROOF CARPOI DWG. # AQC-2017-233, REV. 0 June 8, 2017 SHEET 1 OF 5 GENERIC DESIGN DATA A QUALITY CONSTRUCTION, LLC 3531 S. 25TH STREET FORT PIERCE, FL 34981 OFFICE (772) 343-0805 FAX((77i#61-3038 LOCATION: HAMPSON RESIDENCE U FL 34952 ST. LUCIE PE13;A1,, ili1v ITHIS DRAWING IS ONLY ACCEPTABLE 5 ALL STRUCTURES ERECTED ON CONCRETE SLABS AND / OR FOOTERS SHALL BE CALCULATED TO ASSURE THERE IS FOR BUILDING PERMITS & ONLY WHEN IT SUFFICIENT HOLD DOWN CAPABILITY TO MEET THE REQUIREMENTS OF A THE ENCLOSURE. HAS THE ENGINEER OF RECORD'S RAISED SEAL. COPIES ARE NOT DEEMED VALID. 6 THE AVERAGE SPACING BETWEEN BEAMS IS SHOWN ON THE "SITE SPECIFIC DRAWING". THE ACTUAL SPACING BETWEEN THIS DOCUMENT IS THE PROPERTY OF ANY TWO BEAMS MUST BE THE LISTED SPACING, +/- 2". THE OVERALL AVERAGE SPACING MUST BE EQUAL TO THE R. A. DUNLEA, P.E. AND SHALL NOT BE AVERAGE SPACING SHOWN ON THE "SITE SPECIFIC DRAWING". ALL SPACING MUST NEVER BE GREATER THAN 8.0' O.C. REPRODUCED IN WHOLE OR IN PART WITHOUT THE WRITTEN CONSENT OF 7 IN LIEU OF "SITE SPECIFIC ENGINEERING" AN EXISTING SLAB SHALL MEET THE FOLLOWING REQUIREMENTS: A THE SLAB MUST BE IN GOOD CONDITION, 4" OR GREATER THICKNESS, CONSTRUCTED WITH REBAR, WIRE OR FIBER MESH. B ALL FASTENERS AT BASEPLATES MUST BE NO MORE THAN 24" O. C. WITH 2-1/4" ENGAG99MAL FASTENERS OR ATTACHMENTS ARE THE RESPONSIBILITY OF THE 8 ALL NEW SLABS, WITH OR WITHOUT FOOTERS, SHALL MEET THE FOLLOWING REQUIREMENTS Ae& ff 11pIIIJ11ft OF RECORD A SOIL MUST BE WELL COMPACTED AND TREATED FOR TERMITES PER COUNTY REQUIREMENTS, ll1Y�H�L�U1i B 4" NOMINAL PATIO SLAB REQUIRES A VAPOR BARRIER IF THE SLAB ABUTS LIVING QUARTERS, C 4" NOMINAL PATIO SLAB WITH CONCRETE @ 3000 PSI (MIN.) WITH FIBER MESH OR REBAR AND WIRE, D SHALL BE SECURED TO EXISTING CONCRETE WITH #5 REBAR EVERY 24" O.C. TO AVOID SETTLEMENT, IF APPLICABLE. 9 ALL NEW PERIMETER FOOTERS SHALL MEET THE FOLLOWING REQUIREMENTS AS A MINIMUM: A SOIL MUST BE WELL COMPACTED AND TREATED FOR TERMITES PER COUNTY REQUIREMENTS, B CONCRETE @ 3000 PSI (MIN.) WITH ONE #5 REBAR FOR 8" x 8" AND TWO #5 REBAR FOR LARGER FOOTERS. 110 ALL NEW PERIMETER FOOTER POURED WITH A SLAB SHALL MEET THE FOLLOWING CONDITIONS: A PERIMETER FOOTER AND THE SLAB SHALL BE MONOLITHICALLY POURED, B ALL REQUIREMENTS OF ITEMS 8 AND 9 ABOVE. 11 ALUMINUM IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PROTECTED WITH AN ALKALI RESISTANT COATING. 12 THIS DRAWING COVERS ONLY THE ITEMS LISTED IN THE TITLE BOX. ANY OTHER TASK, SUCH AS ELECTRICAL, PLUMBING, ETC, SHALL BE BY OTHERS AND SHALL BE COVERED BY A SEPARATE DESIGN DOCUMENT. R. A. DUNLEA. R. A DUNLEA, P.E. 1513 CERVANTES PLACE THE VILLAGES, FLORIDA 32159 (772) 285-6444, (352) 750-6207 bobdunleaCab-centurvlink.net FLORIDA P.E. Lic. No. 42835 26'-0" 11 SITE SPECIFIC DRAWING ALL BRACE BRACE <-RB1 RB1-> <-2x3x0.070 RBI-> <-2x3x0.070 RB1-> <-2x3x0.070 2x3x0.070-> 4" - 2 LB. POLY ROOF 4" - 2 LB. POLY ROOF 4" - 2 LB. POLY ROOF w/ 0.030" SKIN w/ 0.030" SKIN w/ 0.030" SKIN RACE RACE 12" OVERHANG ALL AROUND I 38'-1 " I PLAN VIEW 11 11'-7" 11 1 V-7" 11 11'-7" I 9'-6" <-2' OVERHANG 2'-7" 2x3 TRANSOM BRACE 2x4H SEE SKETCH ON SHEET 5 < ROOF BEAM, 2x3x0.07 26'-0" BRACE, 2x4H Cl 4x4x0.125 =W RIGHT SIDE ELEVATION VIEW (LEFT SIDE ELEVATION VIEW IS ^- MIRROR IMAGE) 450 <-C1, C2 OR C3 -B1 4'-6" <-2x4H 450 4'-6" BRACING DETAIL - 8 BRACES TOTAL POLY ROOF CARPOR DWG. # AQC-2017-233, REV. 0 June 8, 2017 SHEET 2 OF 5 SITE DESIGN DRAWING HEIGHT 13'-6", 150 MPH, EXP. 'C' A QUALITY CONSTRUCTION, LLC 3531 S. 25TH STREET FORT PIERCE, FL 34981 OFFICE (772) 343-0805 FAX (772) 461-3038 LOCATION: NAME: HAMPSON RESIDENCE ADDRESS: 2401 TILTON ROAD CITY/STATE: PORT ST. LUCIE, FL 34952 COUNTY: ST. LUCIE DRAWINGS NOT TO SCALE R. A DUNLEA, P.E. 1513 CERVANTES PLACE THE VILLAGES, FLORIDA 32159 (772) 285-6444, (352) 750-6207 bobdunlea( centurVIink.net FLORIDA P.E. Lic. No. 42835 ®es PNI H C)Al y �aQ® o Cc e e '0 (Q e � � e TA OOR :•®'m • FRONT ELEVATION VIEW 1 26'-0" I 14'-0" I r 13'-6" LEFT SIDE ELEVATION VIEW 4'-6" 14'-0" 9'-6" SITE SPECIFIC DRAWING 1 6'-0" 1 30'-1" 1 BACK ELEVATION VIEW POLY ROOF CARPOR DWG. # AQC-2017-233, REV. 0 June 8, 2017 SHEET 3 OF 5 SITE DESIGN DRAWING HEIGHT 13'-6",150 MPH, EXP. 'C' A QUALITY CONSTRUCTION, LLC 3531 S. 25TH STREET FORT PIERCE, FL 34981 OFFICE (772) 343-0805 FAX (772) 461-3038 LOCATION: NAME: HAMPSON RESIDENCE ADDRESS: 2401 TILTON ROAD CITY/STATE: PORT ST. LUCIE, FL 34952 COUNTY: ST. LUCIE DRAWINGS NOT TO SCALE R. A DUNLEA, P.E. 1513 CERVANTES PLACE THE VILLAGES, FLORIDA 32159 (772) 285-6444, (352) 750-6207 bobdunlea(W-centurVlinkmet FLORIDA P.E. Lic. No. 42835 1 !f RUC-FURE .CORC'fZETE SNe=�0 %ORSPAiiG EEGENERL � ��'�� 5OLT �10'� O.C; _& EiUDSTO:•'2' SOUND _cCf , _ ENSC7RE FASCIA, IS'.SEGL1riELY FASTENED is . AG?;UN-. CEN;RR ACS O AA E(i? ENSURE 1 ' £tine retie 1 rtr l a.n PRE-DfQLL; H01=T ftl/OiD SPL1Tt1PoC ISII' .c rl CQVCRETE SEALED.T3 OR FILL WALL 0—P) MASONRI'�l sr4 ELTE Y4'Xl3/� EMBED .: ', IEP-73 TAPCON @ 2■' 1 r & 41,y FROM - ' ENDS BAL @ 18`, I MAX. O.C.* 2' NOMINAL STRUCTURAL— -cult" FACIA MINIMUM EP-23 aNOTE: isE �r4"xi)'.i EMBED Rldx?/c SMS @ T O.C. (S) PEP 4' PANEL TOP &/ TAPCCNS, 2�1 l4 43'L` FROM ENDS, BOTTOM. ADD (2) SMS 2' ik 4" FROM EACH 14" MAX D.C. TO HOLLOW BLOCK ENCLOSURE END TOP & BQ rOM. HEAVY ADHESIVE CAULK TOP & BOTTOM CONTINUOUS ENC.LO�URc TO CON RATE vECK T1 � DETAIL cbfJ SEE 3_DiB AL NOTE •-tiD FOR ATION COLU1414' P�R . TABLES OR 3'x3'x3'-%' ANGLE WITH (2)-y4'Yl3/4* EMBED, SEALED. SITE SPECIFIC TAPCONS W/ %' MIN. WASHER DIAMETER TO DRAWINGS;JMCLIL A IONS SLAB, 2W APART & 3' FROM SLAB EDGE & (fi) f-14 SMS TO COLUMN,;4' FROM ANGLE EDGE=S; [ONE EACH SIDE OF COLUMN . a o ,a a (ifFW�iNG CC)NCAEIE SLAB & FOOTING. SEE SITE SPECIFIC RETAII_P ADDl-110uAL FOOTING ENGINEERING S IFEr -EAVE BEAM C:ONNECnON @ WALL SEE GENERAL NOTE #' 0 FOR LIMIT TIO EPS PD`Y (USED AS REQURIEO WHEN ROOF CONNECTING TO WALL) 144' THRLIBOLT THROUGH OF -A. ANGLE TO ROOF, i a ti 3-X3"�6fi• ANFASTENED TO INSIDE & 13OTrOI4OF CARRY BEAM W/ (2) Y4 ARFLY BEAM PER Lr� THRLl3r OLD SIDE, (5) �14 SM_ BOf iOM, FASTENED TO CBS WALL W/ (2) t/i'XfY4' TA1 L E50R.SEALED EMBED TAPCONS OR TO WOOD (MIN 2X, -MHC _TNT--GkfTY-BY OTHERS) WrfH (3):!�14xlX- q : IIaN I �� .D9T E•SiGN I r, i !P, -� TJ.USE. RIAIC- VALL 2 ; 3 i-0EMSONS BOX i SPPCj-r>.ED ,y aE4r4 16KS ' JII J 1 , j 2X3 I • ,.i E}Id � T.O 3E 3Z-!I 1'U=�1:313UIq_ 4 ;'.5; ,I . • �SOL•'�.P� l'BE 1M ti SriOIAlFN1_ i ROOF PAN tL L:UNN E-� j � 0 FRONT ELEVATION tr-NUCU= � rdln4 iCOF T:.� :: �i _R SECTI�0N 41 i BEAIRI lIN!G COLUMN t 9 ° (OPT_) v P ` OPTION 1: USE ii' LA6 BOLTS W/ 1` MIN. WASHER OLV-ETEIZ, 11 ► M. L_ONGfft TFIAN PANEL T. t3CKNESS SP.4LD PER LAG SPACING TABLE THIS DET-AIL OFFICIN 2: V4" THRUBOLTS TO ROOF, 4- FROM ENDS & 17 O.G To 2'YL"X}a' ANGI E (ETTHEFL SIDE IF REQLQRTD BY BLIILDMiS. D€PT). ! AG=P.AC�TNG TASI.= 1110.31 P� 11' G,G I.13" Q.i.. <30 3 j0 5 t 7 IP-Sr i s P=4 z�,jhid.l?�AMEI ffff � p`y �f°o � 3D t=D C P� 3° O.� 10' D.C. 130 C 30 �Ea �� (a PEZ j. �ANEL 1?D C PSF 150 C ' -1/4" SMS @.:.i-x' TYP. TOP �i TOM ° a s WL = INAL L LOAD RL = ROOF LOAD CARRY BEAM PER TABLES OR L SEEALED.SIM SPECIFIC ORAWINE51CALCULATIONS BOTH OPTIONS: (21 �/'THRU80LTS, n Q CARRY SEAM 710 COWMN 0 o NOTC}I COLUMN IN OTTER TO FIT � CARRY BEAN SNUG BATH OPTIONS: 3'C3's',ANGLE, (5) �14 SMS EA Lam, EA SIDE OF COWMN CDLUNN PER TABLES OR SEALED SI E �CIFIC DRAWING/CALC LA-11ONS SECTION. AT SIDE •O•F ROOF PANEL ampvmm— • 14' LAGS, 4' FROM EN435 a 24' MAX. O.G, 1° MIN i 1? /° LONGER THAN PANELTi-IICXNE=S TO SECURE ROOF SMS la" �TO NOPi-PRIMPAY WALLS OPlLY- CAULK ALL 5CFLl:W T(P. TOP a HEADS' I B0-1 TON ELITE ROOF ° a ° PANEL 0 2X2BOX E140 CAP mm. OR VALANCZ Z Zee' ANGLE, 13) 114 SKS EA a LEG, EA SIDE OF BEAM 1 , . rTOP(TYP 3CITTOH) SEETABLE.o'L7W C n nn P L 17't SrLIC� I OVER COLUMN SIDE (1) '+'A BOLL- T-A46 (Sr= CARRY EACH r+. RY BEAN EI , IP:BL= (5) >1-4 SMS 1' i IN LOr4GEP_ T14Ahl`"" a„ BELO'0,1) IpEOFPLATc PANELTIMCKNESS p 2 X VARIES 6• MQI:aL1Y aHT _- LAP BE.&A 14 SPdS @ E(GS ? 24 O.C. ' r4AX TOP 1 t t urL¢Y. aEAla . BEAM TOP S:Gc J. v' `HIDE x.%a" �, 2w4 1 o'I.G45' I ?JM. PIJ rc•ON 1`L j• _ 3 r l o : =4'IA50'jI SIDE OF C :v2. -5--At Z; Z T,.;' '2�=' -0S-ii I CJLUMN PER 7ABL.=5 '- - • • i tc 5 p I2xlD .36Gl.D92' . -. ... =.;a=.... _ SECTION AT BEARING COLUMN - #12x�" SMS @ 16" TYP. TOP & 1 o EPS POLY o ROOF fqlTOM ELITE TYPE 'E J Y, / 12 GUTTER OPTIONAL SLOPE ADAPTOR SHOWN USE Y4" LAG BOLTS W/ 1" MIN. WASHER DIAMETER, 1" MIN. LONGER CARRY BEAM PER TABLES Z. THAN PANELTHICKNESS SPACED YVfiEN.FAS_rff4 N�0 aLI: MINUAdUSETRURASTHIrx ('t" : 3/4) AT 1 O.E. FQR Up— i FOR-COMPOSF�E•ROOFS: iai3Q'lytP3i IiYIIVa�PapD 910 x (,+1/216 -.SW/ LXPOSURE -D"; a' O.t,. FOR i 1-1/4.0 FENgE R WASIHERS ASOVF130 LMP14ANND UP 10 a(1-12`D•V,•(C E- .16G MPH 1MNa-SPEED PA!4E[ TrtICKAt SS f' 17 E�QS0RE'D' @ ROOF BEARING (SHaaNPE)',4�ID.245 uC. CAUUK ALL t)CPOSED WREW '-N_0N-9FAPdNG ELEMENT(SIDE - H WS. t3�;,WAS!i ERS - YY FOP. PAN_ ROOFS: t :.'.::::: _:•_ :.:::._ _: _-: _- :_:'::::_::._. - (31EACH #Sx 112".LONG S_M_ P-ER:12'.PAAFELw/13F4" -': ':: = > `ALU I,hfWfvr-PA 4=1R1;�S.HER R OFF71WEEL : SCIPPORT[N BEAM ROaF-_PANEL' TO BF�M•I;A:I ENIG;DE"AI 4x4 POST--> BUCKET THICKNESS NOTE: THE TAPCONS CAN BE REPLACED WITH MUST BE 1/8 MIN TWO (2)1%2" WEDGE ANCHORS (REDCAP, HILTI, ` #14 SMS, � l,, �1­1� r � ,�s�� � OR EQUAL) WITH 2-1/4" MINIMUM EMBEDDMENT. 3 SMS ° , I `� ALSO, IF BUCKET IS BEING ATTACHED TO WOOD PER SIDE 7 4'4BUCKETW USE THE 3/8" - 3" WOOD SCREWS, W/ 1-1/4" (6 TOTAL), $4 WASHERS, TO SECURE THE BUCKETS. WEDGE t< a " ANCHOR MUST BE EQUAL OR HIGHER STRENGTH. CONCRETE TWO (2) CONCRETE LDT38212--> 3/8" - 3" 2-1/4" ! (OR EQUAL) TAPCONS I (MIN. EMB.=2-1/4") 2" Min. �L I 4" x 4" BUCKET CONNECTION POLY ROOF CARPOR DWG. # AQC-2017-233, REV. 0 June 8, 2017 SHEET 4 OF 5 POLY ROOF CONNECTIONS HEIGHT IT-6", 150 MPH, EXP. 'C' A QUALITY CONSTRUCTION, LLC 3531 S. 25TH STREET FORT PIERCE, FL 34981 OFFICE (772) 343-0805 FAX (772) 461-3038 LOCATION: NAME: HAMPSON RESIDENCE ADDRESS: 2401 TILTON ROAD CITY/STATE: PORT ST. LUCIE, FL 34952 COUNTY: ST. LUCIE THIS "CIRCLED" CONNECTIONS ON THIS SHEET ARE BEING USED FOR THIS PROJECT. 1 2 3 4 5 6 7 8 9 10 11 NOTE: DRAWINGS ARE NOT TO SCALE R. A DUNLEA, P.E. 1513 CERVANTES PLACE THE VILLAGES, FLORIDA 32159 (772) 285-6444, (352) 750-6207 bobdunlea(&,centurvlink.net FLORIDA P.E. Lic. No. 42835 THE ROOF BEAM CAN BE CONNECTED TO THE THE ROOF BEAM CAN BE CONNECTED TO THE COLUMN AS SHOWN BELOW WITH TWELVE COLUMN AS SHOWN BELOW WITH TWELVE (12) #14 SMS PER CONNECTION. OR WITH (12) #14 SMS PER CONNECTION. OR WITH TWO (2) 112" SS BOLTS, NUTS & WASHERS. TWO (2) 112" SS BOLTS, NUTS & WASHERS. 3 x 3 POST 3 x 3 POST C131. 2x6 SMB CB1. 2x6 SMB PLAN VIEW - MID COLUMN PLAN VIEW - CORNER COLUMN TWELVE (12) #14 SMS, SIX (6) EACH SIDE TWELVE (12) #14 SMS, SIX (6) EACH SIDE CB1, 2x6 SMB CB1, 2x6 SMB #14 SMS 3 x 3 POST #14 SMS 3 x 3 POST SIDE VIEW - CORNER COLUMN SIDE VIEW - MID COLUMN T T • l �j I 1 2.25" 1 CHANNEL 2" x 2.25" x 2" x 0.125" COLUMN OR ROOF BEAM 2" FOUR 4 #12 SMS 1" LONG (TYP.) EACH SIDE 2"x2"x2.25"x0.125 x 1/8" THICK CHANNEL 4" 2x4H KNEE BRACE 2" PLAN VIEW NOTE: THE 2.25 x 2 x 2 x 0.125" CHANNEL SHALL BE ATTACHED TO THE COLUMN AND TO THE ROOF BEAM WITH EIGHT (8) #12 SMS EACH. THE 2x4H KNEE BRACE SHALL BE SLIPPED INTO THE CHANNEL AT EACH END AND SECURED WITH EIGHT (8) #12 SMS AT EACH END. THE KNEE BRACE SHALL BE POSITIONED SO THE ANGLE BETWEEN THE KNEE BRACE AND THE OTHER MEMBERS IS ABOUT 45 DEGREES. KNEE BRACE CONNECTION CONCRETE DECK ANCHORING DETAIL The detail to the left shall be secured with two (2) 2" x 2" x 2" x 1/8" thick angle (Capri Clip) w/ two (2) #14 SMS securing the angle to the upright and two (2) securing the angle to the base plate. The base plate shall be secured to the slab w/ one (1) 1/4" Tapcon, embedded a min. of 2" in the slab w/ 5/W' min. washer dia. Tapcon must be within 6" of the upright. KNEE BRACE DETAIL 2x4x0.050, BACK END MITERED W/ 1/8" U-CLIP, (6) #12 SMS INTO COLUMN / CARRY BEAM, (3) #12 SMS INTO EACH SIDE OF KNEE BRACE (TYP.) NOTE: KNEE BRACES (KB) SHALL BE 2x4H MEMBERS AND SHALL BE 6'-4" LONG AND EACH END SHALL BE CUT ON A 450 ANGLE. THIS WILL ALLOW FOR EACH END OF THE KNEE BRACE TO BE 4'-6" FROM THE CORNER. NOTE: THE KNEE BRACES (KB) WILL BE ATTACHED TO THE COLUMNS AND CARRIER BEAMS USING A 2" x 2" x 2.25" x 0.125" THICK CHANNEL AS SEEN ABOVE. THERE WILL BE EIGHT (8) #12 SMS BETWEEN EACH CHANNEL AND EACH END OF THE KNEE BRACE. A TOTAL OF THIRTY-TWO (32) SCREWS FOR EACH KNEE BRACE. TWO (2) 1/2" BOLTS CAN BE SUBSTITUTED FOR EACH EIGHT SCREW CONNECTION. POLY ROOF CARPOR DWG. # AQC-2017-233, REV. 0 June 8, 2017 SHEET 5 OF 5 OPTIONAL CONNECTIONS HEIGHT 13'-6", 150 MPH, EXP. 'C' A QUALITY CONSTRUCTION, LLC 3531 S. 25TH STREET FORT PIERCE, FL 34981 OFFICE (772) 343-0805 FAX (772) 461-3038 LOCATION: NAME: HAMPSON RESIDENCE ADDRESS: 2401 TILTON ROAD CITY/STATE: PORT ST. LUCIE, FL 34952 COUNTY: ST. LUCIE DRAWINGS NOT TO SCALE R. A DUNLEA, P.E. 1513 CERVANTES PLACE THE VILLAGES, FLORIDA 32159 (772) 285-6444, (352) 750-6207 bobdunleaa-centurvlink.net FLORIDA P.E. Lic. No. 42835 H01d 0�o0'pP�1 b" O, p NO cc TONAL