PROJECT INFORMATION
- - wrightsaft- Project Summary Entire House QUICK CALCS, INC. Job: Date: By: For. WYNNE DEVELOPMENT. THE WINDSOR, FT. `FLL `_PIERCE, Notes: Design Information Weather Fort'Pierce, FL, US Winter Design Conditions Summer Design Conditions . Outside db 42 OF Outside db 90. OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range L . Relative humidity 50 %. Moisture difference 61 gr/lb Heating Summary Sensible Cooling EquipmentLoad Sizing Structure 18467 Btuh Structure 17655 Btuh Ducts 6190 Btuh Ducts 9340 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 24657 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 25645 Btuh Method Simplified Latent Cooling Equipment'Load-Sizing . Construction quality Average Fireplaces 0 Structure 2453 Btuh Ducts 2554 Btuh Central vent (0-cfm) 0 Btuh Heatingg. Coolin . . (none) Area (W) 1753 17 Equipment latent load 5007 Btuh Volume (ft3) 14741 14741 Air changes/hour 0.38 0.20 Equipment total load 30652 Btuh Equiv. AVF (cfm) 93 49 Req. total capacity at 0.70 SHR 3.1 ton Heating.Equipment Summary Cooling Equipment Summary Make Carrier Make Carrier Trade CARRIERAIR CONDITIONING Trade CARRIER AIR CONDITIONING Model 25HBC536A*030 Cond 25HBC536A*030 AHRI ref 7914585 Coil FX4DN(B,F)037 . AHRl ref 7914585 Efficiency 8.5 HSPF Efficiency 12.0 EER, 15 SEER Heating input Sensible cooling 24360 Btuh Heating. output 34600 Btuh @ 47°F Latent cooling 10440 Btuh Temperature rise 27 °F Total cooling 34800' Btuh Actual air flow 1160: cfm . Actualair flow 1160.. cfm. Air flow factor 0.047 cfm/Btuh .Air flow factor 0.043 cfm/Btuh Static pressure 0.50 in H2O Static pressure 0.50 in H2O Space thermostat. '= Load sensible heat ratio 0.84 Capacity balance point 34 OF Backup: Input = 7 kW; Output = 23009 Btuh, 100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft• Right -Suite® Universal 2017 17.0.14 RSUPage 08101 2017-Apr-10 17:ge I 1 ...k CalcslDocuments\WYNNE-THE WINDSOR-REV.ISED.rup Calc = MJ8 Front Door faces: N - wrightsoft Right-JO Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-066-6796 Email: QUICKCALCS AOL.COM 1 Room name Entire House MASTER BEDROOM 2 . E)q)osed wall 153.0 ft 45.0 ft 3 Room height 8.4 ft d 8.0 ft heat/cool 4 Room dimensions 1.0 x 280.0 ft 5 Room area 1753.0 ftz 280.0 ftz Ty Construction U-value Or HTM Area (ft-) Load Area (ftz) Load number (Btuh/ftz-'F) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A416cs 0.143 ne 4.00 2.55 488 448 1795 1141 192 192. '769 489 1A c1om 1.270 ne : 35.56 70:43 7 0 247 488 0 ' 0 ;0 : 0 1A-clom .' 1C270 ne;'; 3556. 70.43 16 `. 0 581 1151 0 . 0 ... ; 0 0 1Ac1om 1.270 :nEi 35.56 ..45;24 A6 0 , 581 '• 739. 0'' 0': 0 0 11 13A4ocs 0.143 se 4.00 - 2.55 64 41 165 105 0 0 0 0 11D0 0.390 se 10.92 11.31 23 23 248 257 0 0 0 0 „•., .13A�ocs , , . • .. 0:143 w.. • " 4.00 2.55 437 396 1584 1007 " _ ' -..56 _ 56 . .. 224 1.43 0:770 ; sw:: .2156 ,2T.53 ' . 41' 45 , 893 1140 , .: A _ 0 : .:0 0 13A4ocs 0.143 nw 4.00 2.55 290 217 867 551 112 79. 318 202 1Aclom 1.270 nw 35.56. 45.24 33 0 1162 1478 33 0 1162 1478 " 0.770 21.56 36.90 41 0 880 1505 0 0 0, 0 ,4A5-2omd dr..... a091 ,nw .t..=- . :: 2'65, - .1.28 .... ,.308:.,. 308: 784 395 - " .. "-0'. "Q - r . ' "•. Q :. ' -..:0 C . 16A-30md 0.032 - 0.90 2.32 1753 1753 1571 4067 280 280 251 650 'F " ` ", 22F,>^tpl : .. T. . 0.-989 = : 27,.69 . " 0.00 '. 1753:. - •163 '4237 : :0 280 . ." = 45 :. 1246 • " .01 6 c)AED excursion 1360 600 Envelope loss/gain 15594 15385 -3970 3561 12 a) Infiltration 2873 810 809 228 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 0 0 Appliances/other 1000 0 Subtotal (lines 6 to 13) 18467 17655 4779 3789 Less witemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 18467 17655 4779 3789 15 Duct loads 1 340/6 53%1 6190 9340 34% 53% 1602 2005 F[ Total room load 1 24657 26995 6380 5794 Air required (cfm) 11601 1160 300 249 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. AA -�- wrightsofC Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-10 1 Page 1 ...k Calcs\Doeuments\WYNNE-THE WINDSOR-REVISED.rup Cale = MJ8 Front Door faces: N 9 - wrightsoft, Right-J® Worksheet Entire House QUICK CALLS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS !AOL.COM Job: Date: By: 1 Room name WIC M. BATH 2 3 4 5 Exposed wall Room height 1 Room dimensions Room area 0 ft 8.0 ft heat/cool 7.0 x 9.0 ft 63.0 ft2 7.0 ft 8.0 ft heat/cool 1.0 x 61.0 ft 61.0 ft' Ty Construction U-value Or HTM Area ' (ftq Load number (Btuhtl`V-°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool i Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AAocs 1A�1om 1A''1om :: 0.143 1.270 1,270 : ne - be . ne 400 35.56 35;56 2.55 76.43 70.43 0 0 ,. .0 0 0 ;: .. 0 0 0 :'; 0.. 0 .0 0 56 7 0: 49 ' 0 0 196 247 : 0 125 488 : A 11 t� �D 1A clom 13AAocs 1.270, 0.143 'rie se 35 56 4.00 45r24 2.55 0 0 0 0 0 0 : 0 0 0 0 " 0 0 . <0 0 0 11DO 1-4ocs�.. 3A 4A�r2om''. 0.390 0.143 0:770 se sw sW 10.92, 4.00 21:56 11.31 2755 . .27:53 0 0 0 0 0 0 0 , - 0 0 0-" : :' 0 ' 0 0 0 0 0 .0 '-. 0 0 :" . 0 , "o 0 :.0. '0 \�1 �C V�/ 13AAocs 1A-clom 0.143 1.270 nw nw 4.00 35.56 2'55 45.24 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 I�-�-G 4A5-2omd ?12C-0sw: : 16A 30md 0.770 0.091 0.032 ,.nw .'"- - 21.56 '"2.55 0.90 36.90 , 1:28 2.32 0 : •U 63 0 .6 63 0 , 0 56 0 0 146 0 0. 61 0, ' , .; 'o 61 0 - .- ;.0 55 0 . ;.:. _'.0 142 P = •:" C . J. :22A-tpl : Oi989 - .27.69 ' 0:00 63 p : 0 '.. 0 ' : 61 -. ., .. j , ". .1g4 ;...: :0 6 c)AED exursion -5 -26 Envelope loss/gain 56 141 692 729 12 a) Infiltration 0 0 126 35 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 56 141 817 764 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 56 141 817 764 15 Duct loads 1 340A 53%1 19 75 341/10 53% 274 404 Total room load 75 216 1091 1168 Air required (cfm) 4 9 .51 50 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �P. -Fk- wrightsoft- 2017-Apr-10 17:19:28 Right -Suite® Universal 2017 17.0.14 RSU08101 Page 2 k CaIcskDocuments\WYNNE4HE WINDSOR-REVISED.rup Calc = MJ8 Front Door faces: N - wrightsci Right-M Woeksheet Job: Entire House Date: QUICK CALCS, INC. ey. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM 1 Room name LAUDRY BEDROOM 2 2 • wall 0 ft 12.0 ft 3 =ed Room height 8.0 ft heat/cool 8.0 ft heaUcool 4 Room dimensions 6.0 x 6.0 ft 15.0. x 12.0 ft 5 Room area 36.0 ft' 180.0 ftz Ty Construction U-value Or HTM Area (ft-) Load Area (ft-) Load number (Btuh/W "F) (Btuhlft2) or' perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 At- 1.13A-4ocs. 0.143' ne 4.00 . 2.55 0 0 0 0 96 80 '319 203. 1Ac1om 1.270 ne.. 35:56 70.43 - 0 0 0 , 0 .- 0 0 . 0, :0 IA-c1om ; 1.270 he . 35 56 70.43 0 0 0 0 .. :16 •. A , 561 1151' 1Ac1om .1.270 . ne 35:56 . . 45.24 0 0 0 :. 0 ` - . 0 6 r' 0� 0 11 13AAocs 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11D0 0.390 se 10.92 11.31 0 0. 0 0 0 0 0 0 13A flocs 0.143 sw •: 4:00 .2.56 :. p .. , p 0 , .. ..0 0 : ' 0 0 p . G; .4A52om 0.770 ;sw .21:56 " .27.53 0 � 6 0 0 .. 0 - 0 .. -, ' .0 . 0. �1 I-C 13AAocs 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 1Aclom 1.270 nw 35.56 45.24 0 0 0 0 0 0 0 0 4AS-29md. 0.770 nw 21.56 36.90 0 0 0 0 0 0 0 0 P 12C' 9W 0:091 .- 2;55 1.28 p 0 0 0 . 0 . = 0 C 16A30md 0.032 - 0.90 2.32. 36 36 32 84 180 180 161 418 .. 0:989 : - .. 27.69 :.' . 0.00 . 36 p p p .. 1$0 . .. '' 12 :.:332 6 c)AED excursion -3 -60 Envelope loss/gain 32 81 1394 1711 12 a) Infiltration 0 0 216 61 b) Room ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 32 81 1609 1772 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 6 14 6 14 14 Subtotal' 38 95 1615 1786 15 Duct loads 34% 53% 13 50 34% 53% 541 945 Total room load 51 145 2156 2730 Air required (cfm) 1 1 2 6 101 117 of Manual J 8th Ed. - A - wrightsoft� 2017-Apr-10 17:1e 3 Right -Suite® Universal 2017 17.0.14 RSU08101, Page 3 ... k CalcslDocuments\WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8 Front Door'faces: N -' wrightsoft, Right-J® Worksheet Job: Entire House Date: By: QUICK CALLS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772A66-6799 Fax 772-466-6796 Email: QUICKCALCS@,AOL.COM 1 Room name DINING/GREAT ROOM KrrCHEN 2 3 Eq)osed wall Room height 50.0 ft 8.9 ft heat/cool 11.0 ft 8.9 ft heat/cool 4 5 Room dimensions Room area 1.0 x 588.0 ft 588.0 ft2 19.0 x 11.0 ft 209.0 ftz TY Construction U-value Or HTM Area (ft') Load Area (ftj Load number (Btuh/ftl "F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13AAocs 0143 ne 4:00 2.55 0 0 0 0 0 0 0 .6 1A!clom X.clorr 1 270 1.270 ne a- 35.56 35.56 .70.43 70.43 0 .. .0 0 .0 0 0. 0 0 0 . • 0 0 0. 0 0 ':0 -0 1A�1om : 1.270 - ne� 35:56 45;24 0 0 0. 0 V)/ I-p 11 13A-4ocs 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 11D0., 0.390 0143 . se sw 10.92 `'4:00 11.31 2'55 0 . 267 0 ; : 226 0 903 0 ' 574 0 98 0 98 0 - - 392 0 ,249. `4A5 tom. 0 770 ; sw' 21.56 27.53 :' 41 . < 22 893 _ 1140 %.. 0 . 0 ' `0 0 13AAocs 0.143 nw 4.00 2.55 178 137 549 349 0 0 0 0 1Aclom 1.270 nw 35.56 45.24 0 0 0 0 0 0 0 0 ,P.-:" ,'`: 4A5-2omd `12C-0suv: ..... 0.770. =0:091 nw .::=' . 21.56 2:55 36.90 ' 1:28 41 0 0 0' 880 0 1505 _ 0 0. - 116 0 ... 116 0 . . ' 295 0 ' : "..748 C. 16A-30md 0.032 - 0.90 2.32 588 588 527 1364 209 209 187 485 tpl `,' ..: 0.989 _ . _ :. . 27.69 0.'00 .: 5E 8 50 :1385 ';' 0 209 11 ' 305 6 c)AED excursion 1004 -64 Envelope loss/gain 5136 5937 1179 818 12 a) Infiltration 1000 282 220 62 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 0 0 Appliances/other 0 1000 Subtotal pines 6 to 13) 6136 6679 1399 . 1886 -Less e)demal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 6 14 0 0 14 Subtotal 6142 6693 1399 1880 15 Duct loads 34% 53% 2058 3541 34°/u 63% 469 995 Total room load 8200 10234 1861 2875 Air required (cfm) 386 440 88 124 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. L 4J-4- wriSihtsoft- 2017-Apr-10 17:19:28 Ae't5A Right -Suite® Universal 2017 17.0.14 RSU08101 Page 4 ...k. Calcs\Documents\WYNNE-THE WINDSOR-REVISED.rup Cale = MJ8 Front Door faces: N - + wrightsoft Right-M Worksheet Job: Entire House Date` QUICK CALLS, INC. By. 317 ST. LUCIE LN., FT PIERCE, FL 34946-Phone: 772-466-6799 Fax 772-466.6796 Email; QUICKCALCS@AOL.COM 1 Room name BATH HALL 2 Exposed wall 5.0 ft 0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 5 Room dimensions Room area 10.0 x 5.0 ft 50.0 ft2 5.0 x 5.0 ft 25.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area. (ft2) Load number Btuh/ft2-°F ( ) (Btu or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross WP/S Heat Cool Gross N/PIS Heat Cool 6 11 13A-0ocs 9Aclom 1Ac1om '. 1Ac1om'. 13AAocs 0.143 11270 1:270 .1:270 0.143 ne ne ne<; ne:, se .4.00', 35 56 3556 , 35`56 4.00 2.55 70.43 70.43 .45.24 2.55 40 0 .° p 0 0 40 . ;0. 0 0 0 160 0 0, • 0 0 102 •.0 '0 - 0 0 0 0 0:'.. 0 0 0 0 �6 0 0. 0 , 0 0 0 :. p 0 0 L-D 11DO 13A flocs r' .4A5 tom :., 0.390. 0143 0 770 se sw' sw 10.92 4,00, 21:56 11.31 2 55 .. 27C53 - 0 0 0 0 . p � 0 0 , .. 0 .. p 0 : .. 0 : 0 0 _ . .. 0: :: 0 0. 0_" . 0. 0 0 ' 0. 0 0 0 ' 13AAocs 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 IA-c1om 1.270 : nw 35.56 . 45.24 0 0 0 0 0 0 0 0 4A5.2omd ,:12C-0sw;,. 0.770 0;091.. nw - . 21.56, 2:55 . 36.90 •.1.28 0 0 0 -0 0 .0 0 . 0 0 : 0 0. : " 0 0 0,:0 0 P : C 16A30md 0:032 - 0:90. 2.32 50 50 45 116 25 25 22 58 F ;• .22Atpl 0:989 •. -. 27:69 0:00 50 5 ... :..138 : ... . 0 .: :25. .. 0 6 c)AED excursion -8 -2 Envelope loss/gain 343 210 22 56 12 a) Infiltration 90 25 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal Qines 6 to 13) 433 235 22 56 Less external load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 6 14 -22 -56 14 Subtotal 439 249 0 0 15 Duct loads 34% 53% 147 132 34% 53% 0 0 Total room load 586 381 0 0 Air required (cfm) 28 16 0 0 Calculations approved byACCA to meet all reguirements.of Manual J 8th Ed. 41- wrightsoft- 2017-Apr-1017:19:28 �cA Right -Suite@ Universal 2017 17.0.14 RSU08101 Page 5 ...k Calcs%DocumentslWYNNE-THE WINDSOR-REVISED.rup Cale = MJ8 Front Door faces: N +- wrightsoft, Right-M Worksheet Job: Entire House Date: By: QUICK CALCS, INC. 317 ST LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772.466-6796 Email; QUICKCALCS@,AOL.COM 1 Room name FOYER BEDROOM-3 2 3 Exposed wall Room height 9.0 ft 8.0 ft heat/cool 14.0 ft 8.0 ft heattcool 4 5 Room dimensions Room area 1.0 x 92.0 ft 92.0 ft2 13.0 x 13.0 ft 169.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/ft2.aF) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat I Cool 6 13A-4ocs 1Ac9om 0.143 .1.270 ne . ne 4.00 35.56 2.55 70.43 0. 6 0 0 0 0 0 0 104 0" 88 0, 351 0 223 0 %clom .: 1.270 : ne". 35.56' 7043'. .0 0. -0. 0 .. • .0 : 0 ; 0 0 :1Ac1om : 1.270 •>ne 35:56 . ,:4524 0 0 .0 0 16 11 V!! 13AAocs 0.143 se 4.00 2.55 64 41 165 105 0 0 0 0 11D0 13A�ocs: , 4Ar2om. 0.390 0.143 . 0.770 se"- sw _sw:: 10.92 4:00, 21:56 11,31 2;55 27:53 23 ,: 8 0 23 8 0 . 24% - ' .32 0--- 257 ' 20 0 0 8 .0 0 • -. 8 • -. 0 0 ; •4:32 0 0 20: , . -0 -D 1N 1- G 13AAocs 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 IA-c1om 1.270 nw 35.56 45.24 0 0 0 0 0 0 0 0 4A5-2omd 12C 0sw: 0.770 0:091 nw - 21.56 . 2 55. 36.90 ' 1:28 0 .-: 88 0 88 0 -224 0 113 0 : 104'. 0 104 0 `_ 265 0 .. 133 P " C 16A-30md 0.032 - 0.90 2.32 92 92 82 . 213 169 169 151 392 F 22A tpl ' o 0.-989 -_ =:... • 27 69 :;, , "0.00 :• 92 9 249 ,' ;0:. ; - .169 . :�' 14 T. 6 c)AED excursion -25 -52 Envelope loss/gain 1002 6841 1768 1456 12 a) Infiltration 162 46 252 71 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 1 0 0 Subtotal (lines 6 to 13) 1163 730 2020 1527 Less eMemal.load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1163 730 2020 1527 15 Duct loads 34% 53% 390 386 34% 53%1 677 808 Total room load 1553 1116 2697 2335 Air required (cfm) 73 48 127 100 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. __71 P -Fk wrightsoft' 2017-Apr-1017:19:28 Right -Suite® Universal 2017 17.0.14 RS1108101 Page 6 ...k Calcs\Documents\WYNNE-THE WINDSOR-REVISED.rup Calc = M,18 Front Door faces: N Duct System Summary Job:, wrightsoft . y Date: Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799Fax 772-46M796 Email:. QUICKCALCS AQL.COM ii-roject intormation For. WYNNE DEVELOPMENT THE WINDSOR, FT. PIERCE, FL External static pressure Pressure losses Available static pressure Supply[ return available_ pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250. -in H2O 0.2.73 in/100ft 1160 cfm Cooling 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.273 in/100ft 1160 cfm 183 ft Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Mat[ Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 586 28 16 0.372 4.0 Ox0 VIFx 19.5 115.0 st1 BEDROOM c 2730 101 117 0.384 7.0 Ox0 VIFx 15.0 115.0 st1 BEDROOM 3 h 2697 127 100 0.353 6.0 Ox 0 VIFx .' 26.8 115.0 st1 DINING/GREAT ROOM C 3411 129 147 0.292 7.0 Ox 0 VIFx 36.5 135.0 st2 DINING/GREAT ROOM-8 C 3411 129 147 0.371 7.0 OxO VIFx 19.9 115.0 st1 DINING/GREAT ROOM-C C 3411 129 147 0.278 7.0 Ox 0 VIFx 44.9 135.0 st2 FOYER h 1553 73 48 0.490 4.0 Ox0 VIFx 7.0 95.0 KITCHEN c 2875 88 124 0.366 6.0 Ox0 VIFx 21.8 115.0 st1 LAUDRY c 145 2 6 0.371 4.0 Ox0 VIFx 19.9 115.0 st1 M. BATH h 1091 51 50 0.282 6.0 Ox0 VIFx 42.3 135.0 st2 MASTER BEDROOM h 3190 150 124 0.273 6.0 Ox 0 VIFx 48.4 135.0 st2 MASTER BEDROOM -A h 3190 150 124 0.284 6.0 Ox0 VIFx 40.9 135.0 st2 wic c 216 4 9 0.292 4.0 Ox 0 VIFx 36.0 135.0 st2 Supply Trunk Detail Table Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 Peak AVF 612 602' 0.273 780 12.0 0 x 0 VinlFlx st1 st1 Peak AVF 1087 1112 0.273 796 16.0 0 x 0 VinlFlx ., wri htsoft' 2017-Apr-1017:19:29 9 Right -Suite® Universal 2017 17.0A4 RSU08101 Page 1 '� ...k CalcslDocuments\WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8 Front Door faces: N Return Branch Detail Table Name Grille Size (in) Htg (cfm) CIg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox0 1160 1160 0 0 0 0 Ox 0 VIFx wri htsoft' : 2017-Apr-1017:19:29 f 9 Right -Suite® Universal 2017 17.0.14 RSU08101 Page 2 k CalcslDocuments\WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8' Front Door faces: N