M.A. CORSON & ASSOCIATES, Inc.
ARCHITECTURE * STRUCTURAL DESIGN
412 Colorado Ave., Stuart, Fl. 34994
(772) 223-8227 * Lic. #AR91665
To: St. Lucie County Building Department Date: January 12, 2022
Re: Malcolm Curtis
9650 S. Ocean Drive, Unit 409 (Middle)
Jensen Beach, Fl.,34957
It is acceptable to replace the existing entry door for the address listed
above as follows:
1) Entry Dr. - The Jeld-Wen Design Pro / Smooth Pro impact opaque fiberglass door has a FL
#16708.1 R11. The nominal wind speed is 132 mph and the ultimate wind
speed is 170 mph. It has a +65 /-65 design pressure and has a large missile "D" approval and
HVHZ .
The worst case scenario building design pressures of address listed above in Zone 4 is +58.7 / -
63.7 and Zone 5 is +58.7 / -78.5. The building has a type II classification and exposure category
"D" for the 7th Edition of the FBC (2020).
SCOPE OF WORK: New entry door.
DESIGN PARAMETERS AND ASSUMPTIONS USED:
1. DESIGN CODE: Florida Building Code Seventh Edition (2020)
2. Structure Designed: Enclosed
3. Risk Category: II Exposure Category: D
4. Design Wind Velocity 170 mph End Zone Width: 4 ft
5. Mean Roof Height 150 ft Roof Pitch: 0:12 Parapet: N/A ft
6. Components & Cladding Design Pressures Used: Zone 4: +58.7 / -63.7 P.S.F. &
Zone 5: +58.7 / -78.5 P.S.F. Worst case scenario has been calculated.
7. Design Loads: Floor: N/A Roof/Dead: N/A Roof/Live: N/A Balcony: N/A Dock: N/A
Deck: N/A Stairs: N/A Fence: N/A Railings: N/A
8. Were Shear Walls Considered For Structure? N/A Not Applicable Explain Why Not:
9. Is A Continuous Load Path Provided? N/A
10. Design Soil Bearing Pressure: N/A Soil Test Reports Submitted? N/A
Thank you for your time and consideration.
If you have any questions please call.
Respectfully,
Mark A Corson
Mark A. Corson A.I.A., NCARB
President