HomeMy WebLinkAboutPOLY ROOF GLASS ROOMTABLE OF ROOF BEAMS, COLUMNS, PURLINS AND GIRTS: HIS POLY ROOF SUN ROOM MEETS THE FLORIDA BUILDING CODE FOR A HEIGHT 10'-0", EXP. 'C', 150 MPH WIND SPEED. THE TABLES BELOW ARE BASED ON SIMULTANEOUS LOADING AS DEFINED IN THE FLORIDA BUILDING CODE (FBC),-CHAPTERS 16 AND 20, AND OTHER REFERENCES SUCH AS ALUMINUM ASSOCIATION OF FLORIDA (AAF) -GUIDELINES-TO ALUMINUM CONSTRUCTION IN HIGH WIND AREAS". STRUCTURAL VALUES FOR EXTRUDED ALLOY 6005T5 ARE TAKEN FROM THE ALUMINUM DESIGN MANUAL, 2015 EDITION. TABLE 1 MAIN ROOF MEMBER SCHEDULE MEMBER I MARK I MANF. 1, WEIGHT ATERI THICKNESS LENGTH DESIGN BASIS # SKIN I POLY I SKIN FT. FL. PROD. APPR. POLY ROOF PANEL # 1 PRP1 I ELITE I 1 ALUM 1 3" 1 0.024 1 14'41" FL7561-R4, DWG. OR = FL-1001, 8-12-17 TABLE 2 MAIN MEMBER SCHEDULE MEMBER MARK SIZE MATERIAL TYPE THICKNESS LENGTH DESIGN BASIS b x t I ALLOY I I W I F I FT. COLUMN # 1 COLUMN # 2 COLUMN # 3 COLUMN # 4 COLUMN # 5 GIRT # 1 GIRT # 2 GIRT # 3 CARRIER BEAM # 1 ROOF BEAM # 1 EDGE BEAM # 1 EDGE BEAM # 2 KNEE BRACE # 1 Cl 3x3-9 ALUM TUBE 1 0.090 0.090 10'-0" CALCULATION C2 2x3 ALUM HOLLOW 0.050 0.050 V-7.5" CALCULATION C3 2x3 ALUM HOLLOW 0.050 0.050 9'-3" CALCULATION C4 2x3 ALUM HOLLOW 0.050 0.050 V-11.5" CALCULATION C5 2x3 ALUM HOLLOW 0.050 0.050 8'-6" CALCULATION G1 2x3 ALUM HOLLOW 0.050 0.050 3'-3" CALCULATION G2 2x3 ALUM HOLLOW 0.050 0.050 3%11" CALCULATION G3 2x3 ALUM HOLLOW 0.050 0.050 3%0" CALCULATION CBI 2x6 ALUM SMB 0.050 0.120 10'-0" CALCULATION R1 2x3 ALUM HOLLOW 0.050 0.050 10'-0" CALCULATION EB1 2x3 ALUM HOLLOW 0.050 0.050 8'-8" CALCULATION EB2 2x3 ALUM HOLLOW 0.050 0.050 14'-0" CALCULATION KB1 2x3-7 ALUM HOLLOW 0.070 0.070 V-5" CALCULATION ADDITIONAL SITE SPECIFIC INFORMATION NOTE: • AVERAGE THIS POLY ROOF GLASS SUN ROOM IS LOCATED IN A RESIDENTIAL COMMUNITY NORTH OF SE WALTON ROAD AND EAST OF U.S. ROUTE 1 IN PORT ST. LUCIE. THE SUN ROOM HAS SOME OPEN AREAS AROUND IT. THE ENCLOSURE IS VERY CLOSE TO THE SAVANNAS PRESERVE STATE PARK. PER THE EXPOSURE CATEGORIES LISTED IN SECTION 1609.4.3 OF THE FLORIDA BUILDING CODE THIS ENCLOSURE SHALL CONSERVATIVELY BE CALLED AN EXPOSURE 'C'. ACCORDING.TO THE COMPUTER PROGRAM "WINDSPEED BY LOCATION", A PRODUCT OF 'APPLIED TECHNOLOGY COUNCIL' THE DESIGN WIND LOAD REQUIREMENTS FOR A RISK CATEGORY I ENCLOSURE IN THIS LOCATION IS DICTATED BY A WIND SPEED OF 148 MPH. HENCE, THE DESIGN PARAMETERS BEING USED HERE ARE 150 MPH WIND LOAD, EXPOSURE 'C', RISK CATEGORY 1. THE NEW POLY ROOF SUN ROOM IS BEING INSTALLED BECAUSE THE EXISTING SUN ROOM, WHICH WAS BUILT SEVERAL YEARS AGO WAS DAMAGED DURING A RECENT HURRICANE. THE FRONT HIGH POINT IS 10'-0" HIGH AND THE SIDES ARE 8'-6" HIGH. WITH RUNS OF 14'-2" TO THE LEFT AND 8'-8" TO THE RIGHT THE SLOPES ARE ABOUT 1.28 INCHES PER FOOT AND 2.07 INCHES PER FOOT, RESPECTIVELY. THE POLY ROOF SUN ROOM IS ALREADY BUILT; ONLY THE POLY ROOF ON THE LEFT SIDE IS BEING RESTORED. BECAUSE OF THE PRESENT DAY REQUIREMENTS THE ENTIRE SUN ROOM IS BEING UPGRADED TO HAVE 4TH WALL CONSTRUCTION. THE EXISTING NOMINAL 4" SLAB IS IN • GOOD CONDITION. THIS FOUNDATION IS ACCEPTABLE FOR THIS SCREEN ENCLOSURE. THE DESIGN DRAWING IS SHOWN ON SHEET 2. THE POLY ROOF CONNECTION DRAWINGS ARE SHOWN ON SHEETS 3. ,THE HOST STRUCTURE IS A MODULAR HOME SO 4TH WALL CONSTRUCTION FOR COMPOSITE ROOFS WILL BE USED. THEREFORE, THE COLUMNS, BRACING AND CONNECTIONS SHOWN ON SHEET 2 ARE THE SAME IN THE BACK AS IN THE FRONT. THERE SHALL BE NO STRUCTURAL ATTACHMENT BETWEEN THE POLY ROOF SUN ROOM AND THE MOBILE HOME BUT IT IS ACCEPTABLE TO INSTALL FLASHING TO KEEP THE RAIN OUT. THE CARRIER BEAM TO COLUMN CONNECTION CAN BE MADE WITH 6" LONG CHANNELS AND TWELVE (12) #12 SMS, SIX (6) BETWEEN EACH CHANNEL AND COLUMN AND SEVEN (6) BETWEEN EACH CHANNEL AND CARRIER BEAM, SIMILAR TO KNEE BRACE CONNECTIONS ON SHEET 2. ALSO, SEE OPTIONAL CONNECTION DRAWINGS BETWEEN COLUMNS AND CARRIER BEAMS BELOW. ALSO, SEE ADDITIONAL CONNECTION DRAWING ON SHEET 4. BOLTED CONNECTION - OPTION # 1 BOLTED CONNECTION - OPTION # 2 THE ROOF BEAM CAN BE CONNECTED THE OF BEAM CAN BE CONNECTED TO THE COLUMN TO THE COLUMN WITH TWO 1/2" SS WITH TWO 1/2".SS.NUTS, BOLTS AND -SS WASHERS. _ NUTS., BOLTS AND SS WASHERS. COREDGEBIEMBEB M B EA( PLAN VIEW - CORNER COLUMN 2" WIDE CARRIER BEAM (CBI OR EDGE BEAM•(EB) PLAN VIEW - MIDDLE COLUMN SPECIFICATION NOTES AND DESIGN PARAMETERS: THIS DESIGN COMPLIES WITH THE GUIDELINES DEFINED IN CHAPTERS 16 & 20 OF THE 2017 FLORIDA BUILDING CODE, SIXTH EDITION, BUILDING, USING THE ALLOWABLE STRESS DESIGN PRESSURES LISTED IN TABLE 2002.4 AND TABLE 2002.4A AAF STANDARDS OF THE "GUIDELINES TO ALUMINUM CONSTRUCTION IN HIGH WIND AREAS" FOR THE TABLESLF A DESIGN BASICS: THIS POLY ROOF SUN ROOM IS A RISK CATEGORY I STRUCTURE. HEIGHT 10%0", EXP.'C',15 B THE BUILDING CLASSIFICATION RISK CATEGORIES ARE FROM FBC, TABLE 1604.5 AND AREA LOCATION WIND SPER FBC, FIGURE 1609C. BUILDING CLASSIFICATION PER TABLE 27.2-1, ASCE 7-10. C DESIGN PRESSURE: FOR SOLID ROOF @ 30.96 PSF PER TABLE 2002.4. D MAXIMUM HEIGHT: HEIGHTS HIGHER THAN LISTED ABOVE REQUIRE SITE -SPECIFIC DESIGN BY THE ENGINEER O E ALLOWABLE DEFLECTION: L 160 MINIMUM, AS SPECIFIED IN TABLE #1604.3 OF FBC. F CONTINUOUS LOAD PATH IS PROVIDED WITHIN THE CALCULATIONS USING ALLOWABLE STRESS DESIGN PRESSURES. MATERIALS (UNLESS OTHERWISE SPECIFIED BY THE ENGINEER OF RECORD): A ALL EXTRUSION MATERIALS SHALL BE ALUMINUM ALLOY # 6005T5 OR # 6061T6; ALLOY # 6063T6 IS NOT ACCEPTABLE. B FASTENERS: ALUMINUM ALLOYS #202444 & #7075-T6, DOUBLE CAD -PLATED STEEL, HOT -DIPPED GALVANIZED STEEL OR 300-SERIES STAINLESS STEEL. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE FOR SEPARATION OF DISSIMILAR MATERIALS AS DEFINED IN THE FBC. HE/SHE MAY IMPLEMENT ANY OF THE MEANS LISTED IN THESE SECTIONS. ALTERNATIVES MUST BE REVIEWED AND APPROVED IN WRITING BY THE ENGINEER OF RECORD PRIOR TO ANY INSTALLATIONS UTILIZING THE SUBJECT METHODS. C SCREEN CLOTH: SHALL BE VINYL -COATED, WOVEN FIBERGLASS, MAXIMUM DENSITY OF 18 X 14, 58% OPEN MINIMUM. OTHER SCREEN DENSITY REQUIRE ADDITIONAL ENGINEERING CONSIDERATION. D ANY CONNECTION USED, THAT IS NOT SHOWN ON THESE SHEETS, MUST MEET ALL FBC AND AAF GUIDELINES. E MATERIAL UPGRADES (STRONGER AND/OR HIGHER GRADE MATERIALS) CAN BE SUBSTITUTED AT ANY TIME. F A 2x2 OR A 2x3 SNAP MEMBER CAN ALWAYS REPLACE A 2x2 OR A 2x3 HOLLOW MEMBER, RESPECTIVELY. G WHEREVER SCREENING OR KICKPLATES•ABUTS THE HOUSE OR CONCRETE THE MEMBER USED TO SUPPORT THAT SCREENING OR KICKPLATE WILL BE A 1" x 2" x 0.046" O.B. OR STRONGER ALUMINUM MEMBER. H ALL DOOR JAMS (DJ) SHALL BE 2" x 2" x 0.046" ALUMINUM MEMBERS OR STRONGER. I IT IS ALWAYS ACCEPTABLE TO ADD OR RELOCATE A SCREEN DOOR AS LONG AS THE COLUMNS ARE NOT DISTURBED. 3 ALL HOUSE FASCIA DETAILS, BOLTING OR SCREW SELECTIONS, BEAM SPLICE DETAILS, DIAGONAL "K" BRACING DETAILS, COLUMN TO BEAM DETAILS, STRUCTURAL GUTTER DETAILS, WALL AND FASCIA DETAILS, CORNER,ANCHOR DETAILS, ROOF BRACING DETAILS, EAVE BRACING DETAILS, ETC., IF NOT EXPLICITLY OUTLINED ON THIS SPECIFICATION, SHALL BE IN ACCORDANCE WITHTHE LATEST FBC EDITION, INCLUDING THE AAF. ALL INTERNAL CONNECTIONS SHALL MEET THE FBC (AAF) AND THERE INSTALLATION ARE THE RESPONSIBILITY OF THE CONTRACTOR. 4 WHERE APPLICABLE, THE LOCATION OF ALL "K" BRACING, WIND BRACING, EAVE RAILS AND CHAIR RAILS, ALONG WITH ANY DESIGN ABNORMALITY, ARE SHOWN AND/OR LISTED ON SHEET 2, THE "SITE SPECIFIC DRAWING". POLY ROOF GLASS ROOM DWG. # RVC-2018-113, REV. 0 � ebruary 14, 2018 118 SHEET 1 OF 4 ,ermittM& ERIC DESIGN DATA HEIGHT 10'-0", EXP.'C', 150 MPH R V CONSTRUCTION 3318 COLUMBRINA CIRCLE PORT ST. LUCIE, FL 34952 OFFICE (772) 380-8253 LICENSE # CRC 1330965 LOCATION: NAME: CHRISTIANSEN RESIDENCE ADDRESS: 8215 WEST BITTERBUSH LANE CITY/STATE: PORT ST. LUCIE FL 34952 COUNTY: ST. LUCIE 5 ALL STRUCTURES ERECTED ON CONCRETE SLABS AND / OR FOOTERS SHALL BE CALCULATED FOR SUFFICIENT HOLD DOWN (THIS DRAWING IS ONLY ACCEPTABLE CAPABILITY TO MEET THE CODE REQUIREMENTS. ALSO, ALL TAPCONS, WEDGE ANCHORS (OR EQUAL) SHALL BE 24" O.C. FOR BUILDING PERMITS & ONLY WHEN IT (MIN.), BE 3" FROM THE EDGE OF THE SLAB AND HAVE A MINIMUM EMBEDMENT OF 2" INTO THE CONCRETE SURFACE. HAS THE ENGINEER OF RECORD'S RAISED 6 THE AVERAGE SPACING. BETWEEN BEAMS IS SHOWN ON THE "SITE SPECIFIC DRAWING". THE ACTUAL SPACING BETWEEN ANY TWO BEAMS MUST BE THE LISTED SPACING, +/- 2". THE OVERALL AVERAGE SPACING MUST BE EQUAL TO THE AVERAGE SPACING SHOWN ON THE "SITE SPECIFIC DRAWING". ALL SPACING MUST NEVER BE GREATER THAN 8.0' O.C. r 7 IN LIEU OF "SITE SPECIFIC ENGINEERING" AN EXISTING SLAB SHALL MEET THE FOLLOWING REQUIREMENTS: A THE SLAB MUST BE IN GOOD CONDITION, 4" OR GREATER THICKNESS, CONSTRUCTED WITH REBAR, WIRE OR FIBER MESH. B ALL HOLD DOWN FASTENERS MUST BE NO MORE THAN 24" ON CENTER WITH MINIMUM ENGAGEMENT OF 2". 8 ALL NEW SLABS, WITH OR WITHOUT FOOTERS, SHALL MEET THE FOLLOWING REQUIREMENTS AS A MINIMUM: A SOIL MUST BE WELL COMPACTED AND TREATED FOR TERMITES PER COUNTY REQUIREMENTS, B 4" NOMINAL PATIO SLAB REQUIRES A VAPOR BARRIER IF THE SLAB ABUTS LIVING QUARTERS, C 4" NOMINAL PATIO SLAB WITH CONCRETE @ 3000 PSI (MIN.) WITH FIBER MESH OR REBAR AND WIRE, D SHALL BE SECURED TO EXISTING CONCRETE WITH 45 REBAR EVERY ZV O.C. TO AVOID SETTLEMENT, IF APPLICABLE. 9 ALL NEW PERIMETER FOOTERS SHALL MEET THE FOLLOWING REQUIREMENTS AS A MINIMUM: A SOIL MUST BE WELL COMPACTED AND TREATED FOR TERMITES PER COUNTY REQUIREMENTS, B CONCRETE @ 3000 PSI (MIN.) WITH ONE #5 REBAR FOR 8" x 8" AND TWO #5 REBAR FOR LARGER FOOTERS. 10 ALL NEW PERIMETER FOOTER POURED WITH A SLAB SHALL -MEET THE FOLLOWING CONDITIONS: A PERIMETER FOOTER AND THE SLAB SHALL BE MONOLITHICALLY POURED, B ALL REQUIREMENTS OF ITEMS 8 AND 9 ABOVE. 11 ALUMINUM IN CONTACT WITH CONCRETE OR MASONRY SHALL BE PROTECTED WITH AN ALKALI RESISTANT COATING. 12 THIS DRAWING COVERS ONLY THE ITEMS LISTED IN THE TITLE BOX. ANY OTHER TASK, SUCH AS ELECTRICAL, PLUMBING, ETC, SHALL BElBY OTHERS AND SHALL BE COVERED BY A SEPARATE DESIGN DOCUMENT. SEAL. COPIES ARE NOT DEEMED VALID. THIS DOCUMENT IS THE PROPERTY OF R. A. DUNLEA, P.E. AND SHALL NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT THE WRITTEN CONSENT OF R. A. DUNLEA. R. A DUNLEA, P.E. 1513 CERVANTES PLACE 'THE VILLAGES, FLORIDA 32159 (772) 285-6444, (352) 750-6207 bobdunleaAlcenturvlink.net FLORIDA P.E. Lic. No. 42835 PNtHONY • • zTv • •;�LOR10P' 3'-0" 3'-0" 10'-0" 3'-0" SITE SPECIFIC DRAWING MOBILE HOME MOBILE HOME MOBILE HOME 5'-2" 1'-5" 3" 8._6" LEFT SIDE ELEVATION VIEW E X <-CB2 Ri-> I S <-2x3 2x3-> T S S SLOPEN Av G C A NEW 3" -1 LB POLY ROOF NEW 3" -1 LB POLY ROOF R w/ 0.024" SKIN w/ 0.024" SKIN P <-CB2 R1-> EXISTING 3"- 1 LB POLY ROOF O <-2x3 2x3-> w/ 0.024" SKIN R r 12" OVERHANG 12" OVERHANG I EB2, 2x3 V-6" MOBILE HOME EXT. 2x: 3 ORem T s ' KB- �� EK M, x . 2x3 . 2 10'-0"�' <-2x3 2x3-> 2x T-2" EXISTING EXISTING R7 OR R2-> 8'-6" GLASS GLASS WINDOW WINDOW �4 G1 EXT. 2x3 81 EXT. 2 V-6" KtG�KPL`ATE KICKPLATI KB C3 OR Cl KNEE BRACE CONNECTIONS NOTE: THE EDGE BEAMS. EB1 8: EB2. AND THE ROOF BEAMS. R1 $ R2. SHALL BE SECURED TO THE POLY ROOF WITH 1/4" LAGS. 3" LONG. 6" FROM EACH END AND 12" O.C. THROUGHOUT THE LENGTH. THERE SHALL BE A TOTAL OF SEVEN (7) KNEE BRACES. THREE (3) FROM THE EDGE BEAMS TO THE COLUMNS AT THE BACK WALL AND FOUR (4) BETWEEN THE COLUMNS AND THE ROOF BEAMS, R1 $ R2; TWO AT THE FRONT WALL AND TOW AT THE BACK WALL. SEE KNEE BRACE CONNECTION TO THE RIGHT. NOTE: THE CARRIER BEAMS AND THE ROOF BEAM SHALL BE CONNECTED TO THE COLUMNS AT EACH END WITH CHANNELS. THE LENGTH OF THE CHANNELS SHALL BE 3" FOR THE 2x3 BEAMS AND 6" FOR THE 6" CARRIER BEAM. THE CHANNELS SHALL BE SECURED TO THE COLUMNS WITH ONE (1) #14 SMS FOR EACH INCH IN LENGTH OF THE CHANNEL AND ONE #14 SMS BETWEEN THE CHANNEL AND THE BEAM. HALF ON EACH SIDE OF THE CHANNEL. 3'-3" 11 3'-3" 28'-11" PLAN VIEW EB1, 2x3 EKP ■ EKP EKP MOBILE HOME 3" V-5" 11 5'-2" 1'-6" 8'-6" RIGHT SIDE ELEVATION VIEW 2x3 A. 2x3 I' 2x3-I' I KNEE BRACE DETAIL EXISTING EXISTING EXISTING EXISTING GLASS GLASS GLASS GLASS �• vim° __��K - I'm FRONT ELEVATION VIEW 11 6'-8" 1 I 6'-8" 12' 8'-0" 11. BACK ELEVATION VIEW (VIEWED FROM THE INSIDE) COLUMN PER TABLE ■ ■ TOTAL FOUR � 2x3x0.070, BACK END 6 # 2 SMS MITERED W/ 118" U-CLIP, (6) #12 SMS INTO COLUMN / CARRY BEAM, (3) #12 SMS INTO EACH SIDE OF KNEE BRACE (TYP.) CHANNEL NOTE: KNEE BRACES (KB) SHALL BE 2x3x0.07 MEMBERS AND SHALL BE 1'-5" LONG AND EACH END SHALL BE CUT ON A 45° ANGLE. THIS WILL ALLOW FOR EACH END OF THE KNEE BRACE TO BE 2'-0" FROM THE CORNER. NOTE: THE KNEE BRACES (KB1 WILL BE ATTACHED TO THE COLUMNS AND CARRIER BEAMS USING A 2" x 2" x 2.25" x 0.125" THICK CHANNEL AS SEEN ABOVE. THERE WILL BE S(J #12 SMS BETWEEN'THE COLUMN AND THE CHANNEL AN . BETWEEN THE CARRIER BEAM AND THE CHANNEL AND BETWEEN THE BRACE AND THE CHANNEL, 3 ON EACH SIDE, AT EACH END OF THE KNEE BRACE. A TOTAL OF TWENTY-FOUR (24) SCREWS FOR EACH KNEE BRACE. TWO (2) 3/8" BOLTS CAN BE SUBSTITUTED FOR EACH EIGHT SCREW CONNECTION. POLY ROOF GLASS ROOM DWG. # RVC-2018-113, REV. 0 February 14, 2018 SHEET 2 OF 4 SITE DESIGN DRAWING HEIGHT 10'-0", EXP. 'C',150 MPH R V CONSTRUCTION 3318 COLUMBRINA CIRCLE PORT ST. LUCIE, FL 34952 OFFICE (772) 380-8253 LICENSE # CRC 1330965 LOCATION: NAME: CHRISTIANSEN RESIDENCE ADDRESS: 8215 WEST BITTERBUSH LANE CITY/STATE. PORT ST. LUCIE FL 34952 COUNTY: ST. LUCIE DRAWINGS NOT TO SCALE R. A DUNLEA, P.E. 1513 CERVANTES PLACE THE VILLAGES, FLORIDA 32159 (772) 285-6444, (352) 750-6207 bobdunlea(dcenturVlink.net FLORIDA P.E. Lic. No. 42835 p,NTIJO 74 ♦�ti •••�O • C e�.• Gig' v N ® e • 1� op0 AT F� �(I� ♦ T �4 .� ♦♦.��e.'c[ORI)P' e• ♦♦♦♦4.7-01VA L 4.1V'•TO STRUCTURE: 11fi`3{3D COR :C0*N.C#h7E ='ry; --`: , SEE GENERAL'°P7G+ c= O r0R 4SMi i ATiGt3 a•X-1;'(AG BOLT t@ 10` O.C; & ENDSTO'.2' SOUND. - • - �;i ,c', NSbAEFASCIA-LS'S€CUREII.Y FA9FENED S70 OZ4° -. Rr-rEti'VYiii�. (1., X' LnG rIIN: CENER ACS TC Ef�. ENSURE iiT,24 N) PENCTRMITCN-- CONCRETE EL?FrffNG ' PRE.DfaL,.HQLET4ANOifl SPLiTlNG SEALED.T3 >. �; _ OR FILLED Wart p) :fy MASONRY* �3N EXI ELT E OR7R Ss!i4��R y4'x:%EMBED. I/EP-23 ENDSBAL@ ti' % MAX. O.C.* 2' NOMINAL smucTURAL� 'ELITE FACIA MINIMUM EP-23 ?NOTE: USE ;l,"Xl3'1.j EMBED 41dx?q' SMS @ 7' O.C. (8) PEP_4' PANELTOP &/ TAPCONS, 2�1 AL ph, FROM ENDS, BOTTOM• ADD (2) SMS Z' R 4` FFiORd EACH 14" MAX O.C. TO HOLLOW BLOCK ENCLOSURE END TOP & BOTTOM. HEAVY ,ADHESIVE CAULK TOP 14 BOTTOM CONTINUOUS ZTN%LOZD 1 O CiJNC% TE uECK i�LI'�Ci-ii�r ING L'�ETA.LL SEE GENERAL NOTE #1.0 FOR ATION COLUFIN• PGRL TABLES bk [3'x3'x3s_%' ANGLE WIM (2) %"xl 4 EN. BE), SEALED. SITE S PECIFIC TAPCONS W/ W MIN. WASHER DIAMETER TO DRAWINGS/CALCULATIONS SLAB, 2%' APAILT & 3' FROM SLAB EDGE & (fi) 414 SMS TO COLUMN, ij' FROM ANGLE EDGES, ONE EACH SIDE OF COLUMN I: - J• a - a a a 6 aswim NPN�ING CONCRE IT SLAB & FOOTING_ SEE SITE SPECIFIC 13ETAm-m ADDI L 09AL FOOTING ENGINEERING $1EEf :EAVE BEAM CONNECTION @ WALL SEE GEiVERAL NOTE *10 FOR LIMIT TIO EFS FLkY - (USED AS RI=QURIED WHEN ROOF CONNECTING TO WALL) • J/4' THRLISOLT THR000H G 2'%3-A' ANGLE TO ROOF, ANGLE FASTENED TO INSIDE & BOTrom OF CARRY SEAM W/ (2.) BEAM L=--4 THRLrWL s SIDE, (5) 414SM5 BOTTOM, FASfEdEDTD CBS WALL W/ (2) 3%i XI3V EMBED TAPCONS OR TO WOOD (M-TN ZX, -^--.-ST SPEC?FIC _TNT=,RITY BY OTHERS) WITH (3)r14x%' ' iLrlJ-`7 4 S : i)SION �� D9?' TOP IiYP 3cTrOM) SEETABL.E_BELOW iMEEhgQri0 l:OE �,IGIq I IFrtNs��J��•-2.42r1Ii:'�7',+JSE. •jl TEPiVAA ;E14CryE=yZIhIC- hVIH Ij 3 X 3 I rZ7. f?' i?I[dEhISOI'15 BOX 4 = z r^irfp7J',9'rf0�� a 5:>i.IED ,.; 2E$Nl I ,�-+ �EINi'.f LL EtUSI-KS TO BE -,--n :tilJrrt uM I : •'• rJl 2 X VARM Imam UP BF -Ali - _ •055,- :_��w 1 2 X 3 ;, SNAP BE?li TOP STOc 2 4 2�2E;_: I v 3 1Z�0 _ 4'IA50'I MIS 210' .072" ROOF 1 Ai E ONNE�I ffrq FRONT ELE'V t'ON sEsi IOIrr1----- = r­---NUCU S _ '- MIN ;ccF .=c;-! SECTION k' 3EAR11NG COLUMN lE+.3 �G=PAGfNC- TASL= ?0 3 SIB 17 is °C4 Xlf � 3l �1 PEA �-3ZEL I IOU C 30 PS 3' O_G i0' O.C. "0 C '�0 C 7� PEP (O� PEZ '�0 C P3 PSF ANii s' . ANEL L50 C ' /si�4e SMS @ 3-L-� TYP. TOP a 3�OM GLff k`f A ° _ ° WL = WALL LOAD ° zr v a ° ° RL = ROOF LOAD a . - ° ° CaM BEAM PERTABLS OR OPTION 1: USE Y' L.A.6 BOLTS STALED •SITE SPECIFIC l W/ 1' MIN. WASHER OIAMEfE . ' DRAVMG91C, L.CLILATIONS 1' WN. LONG2R THAN PANE- BOTH ONIONS.- (213/'THR OLTS, T.43004E55 SPACED PER'. LAG CARRY SEAM TO COLUMN SPACING TABLE THIS OET_4IL. D Q a o NOTCH -COLUMN IN C€ FfM TO FrT OPTION 2: }'.,= THRUBOLTS TO r1 CARRY BE4M SNUG ROOF, 4- FROM ENDS & 17' BOTH OPTIONS, 3A 3'�;%' ANGLE, (6) O.C. TO 2'a2�' AN tCLE9 �14 SMS EA I-% EA SIDE OF COW M14 (EI-HER TIER SIDE IF REQUIRED BY ' BUILIIIPIG D€PT). COLUMN pC-R TABLcS OR SEAL SITE: SPECIFIC DRAWING/CALcULATILINr. ' SECTION. AT SIDE OF ROOF PANEL 14' L.A65, 4' FROM ENd35 & 24` MAY- O.G, 1° MEN LON- ER THAN PANEL 7HICKt�S TO SECURE ROOF ST45 2a TO NOpi-PRD ARY WALLS ONLY- CAULK ALL SCRSIN TfP. TOP & HEADS' eo i TON . ° _ E ifE ROGF ° PANEL ° n =°" 3ITc 2 X 2 BOX END CAP MIN. OR VALANC- a 2 Skye' ANGLE, 131 114 SUS EA LEG, EA SIDE OF BEAM FE.aM'SPLICE- .OVER COLUMN , SIDE Cl) ya' LAG BDLT�IN7Q 15E: EACH _TARRY BEAM E19G; tAlILLE (5) 414 SMS SS. 1' MLY LONGEP THAI4'•'^ OE OF PLATE PANE THICKNESS 6' CH 1.DNa f waFs�� '•L4 SMS 24 D.C. MAX TOP SOTTOM ?JM ps rc•ON 1'C'• 't'` ' SECTION AT BEARING COLUMN ELITE TYPE 'E GUTTER OPTIONAL USE �" LAG BOLTS W/ 1" MIN.. WASHER DIAMETER, 1" MIN. LONGER THAN PANELTHICKNESS SPACED 3X3 POST #14 SMS ; 3SMS PER SIDE (6 TOTAL) o0 a 'I o #12XY4" SMS @ 16" TYP. TOP & BOTTOM c EPS POLY 0 o ROOF �36/12 SLOPE ADAPTOR SHOWN BEAM PER TABLES : -. `. -' YyriCt{I•r/jl) L-(+jIf11Li 4CI . :A JMiI.�iUly '�:TRUFASTI�ix (•�" ; 3/4) AT 8. O.G. FC R SIP- FOR -GOMPOSF1 EROOFS: I O. 130 •MPH')MND-8PE-D 910 x (L +112 i 6; &S, W/ .E_XP0SURE'D'-; Fr O.E.-FOP, 1-1/4'0FENgE R VYAS'riERS • ABOVE 130 IIMPI+AIjtD Up I O _1� MPH VAND-SPEED PANEL TrtICKN�SS +' 1'} E�QSURE 13, @ ROOF BfARt1~IG 1=LEISttF -(SHOWN) AND.24r'OIG. @ CAULii ALL EXr OSED S%R� NQN-3FARIt�IG ELE iEt ENT(SIDE' - --- :HEADS !�5 ER5 W : - ALE1i"vtft+tEJA�#PAI�kW;�,SF(ER -: = --- ITOOFPA'NE* L SUPPORTF NG• BEAM ROOF_ -PAN -EL TO BE FA I ENING_D.ETAIL POLY ROOF GLASS ROOM DWG. # RVC-2018-113, REV. 0 February 14, 2018 SHEET 3 OF 4 POLY ROOF CONNECTIONS HEIGHT 10'-0", EXP. 'C',150 MPH R V CONSTRUCTION 3318 COLUMBRINA CIRCLE PORT ST. LUCIE, FL 34952 OFFICE (772) 380-8253 LICENSE # CRC 1330965 LOCATION: NAME: CHRISTIANSEN RESIDENCE ADDRESS: 8215 WEST BITTERBUSH LANE CITY/STATE: PORT ST. LUCIE FL 34952 COUNTY: ST_ LUCIE THIS "CIRCLED" CONNECTIONS ON THIS SHEET ARE BEING USED FOR THIS PROJECT. 1 2 3 4 5 6 7 8 9 10 11 NOTE: DRAWINGS ARE NOT TO SCALE. R. A DUNLEA, P.E. 1513 CERVANTES PLACE BUCKET THICKNESS . NOTE: THE TAPCONS CAMBE REPLACED THE VILLAGES, FLORIDA 32159 MUST BE 1/8 MIN WITH TWO (2)1/2" WEDGE ANCHORS (772) 2$5-6444, (352) 750-6207 4r:•' w.t `, M,y-xd+ist•" (REDCAP, HILTI, OR EQUAL) WITH 2-1/4" bobdunleaCa)_centurVlink.net MINIMUM EMBEDDMENT. ALSO, IF BUCKET r� FLORIDA P.E. Lic. No. 42835 7 3a8 CKET IS BEING ATTACHED TO WOOD USE THE 318" 3" WOOD SCREWS, W/ 1-1/4" WASHERS, TO SECURE THE BUCKETS. WEDGE ANCHOR ',e0sptt®®�AII�n��4N' MUST BE EQUAL OR HIGHER STRENGTH. ���Q'(•NtAT� Ny0 CONCRETE TWO (2) 3/8' - 3" ---LDT38212-> TAPCONS (OR EQUAL) 2" Min. TCONCRITE 2-114" 1 (MIN. EMB.=2.1/4") 3" x 3" BUCKET CONNECTION Q ' *• N •� S TA • ORIoN.• �� ,o��os�ONAL . EDGE BEAM- 1" x 2" OPEN BACK ATTACHED TO FRONT POST w/ #10 x 2" LONG S.M.S. MAX. 6" FROM EACH END OF POST AND 24" O.C. • NOTE: THIS CONNECTION IS ALSO GOOD FOR 1x3 OPEN BACK MEMBERS, 2x2H AND 2x3H MEMBERS. FRONT WALL GIRT 1' x 2' OPEN BACK ATTACHED TO FRONT POST w/ #10 x 2" LONG S.M.S. MAX. 6" FROM EACH END OF POST AND 24" O.C. 1-- VMIN. 4- #10 S.M.S. FROM INSIDE FACE OF POST INTO SCREW SPLINES OF HOLLOW GIRT (2" SCREWS MIN.) GIRT OR CHAIR RAIL I SELF MATING POST--4 - ... POLY ROOF GLASS ROOM ALTERNATE CONNECTION: (2) # 10 x 2" - "- LONG S.M.S. THRU SPLINES GROOVES DWG. # RVC-2018-113, REV. 0 2" x 3" COLUMN SCREEN February 14, 2018 SIX 6 #14 SMS P 2" x 2" x 1/8" ANGLE EACH SIDE SHEET 4 OF 4 3 -#14 SMS EACH SIDE 318" DIA. CONCRETE ANCHORi(I"O.C. MIN. CONNECTION DRAWINGS (TAPCON OR EQUAL) wi 1-1/4" EMBEDMENT MIN. 2" MIN. ■ ■ HEIGHT 10'-0", EXP. 'C', 150 MPH R CONSTRUCTION SIDE WALL HEADER ■ ATTACHED TO 1" x 2" 1"x2" O.B. BASE PLATE 3318 18 COLUMBRINA CIRCLE OPEN BACK w/ MIN. PORT ST. LUCIE, FL 34952 TWO (2) #10 S.M.S. 2" MIN OFFICE (772) 380-8253 LICENSE # CRC 1330965 SIDE WALL GIRT ATTACHED TO 1" x 2" OPEN BACK w/ MIN. THREE (3) #10 x 1-112" S.M.S. IN SCREW BOSSES sm LOCATION: FRONT AND SIDE BOTTOM RAILS ATTACHED TO CONCRETE w/ 1'4" x 2-1/4" CONCRETE / MASONRY ANCHORS @ 6" FROM EACH POST AND 24" O.C. MAX. AND WALLS MIN 1" FROM EDGE OF CONCRETE. (OR =) ANGLE (CAPRI) CLIPS MAY BE SUBSTITUTED FOR INTERNAL SCREW SYSTEM CONNECTION wr/ CONCEALED FASTENERS PARTIAL ELEVATIONS / GIRT TO POST CONNECTIONS COLUMN / FOUNDATION FASTENER FOR 2x2 & 2x3 NOTE: LOAD CONDITIONS: CONNECTION UPLIFT CAPACITY=1,1009, SHEAR CAPACITY = 228#. 1) THIS DETAIL MAY NOT BE USED FOR COLUMNS LARGER THAN V x 3", 2) Two (2) EACH X 3/8" DIA. BOLTS MAYBE SUBSTITUTED FOR THE 3 EACH #14 SMS (2 THRU BOLTS REPLACE 6 SCREWS) 3) CONCRETE FASTENER SPECIFICATIONS: CONCRETE FASTENERS MUST HAVE A (MIN.) ULTIMATE ULTIMATE TENSION CAPACITY OF 2,560 # OR,A WORKING (MINIMUM) TENSION CAPACITY OF 640#, AND, A (MINIMUM) WORKING SHEAR CAPACITY OF 300A (DO NOT SUBSTITUTE 3/8" DIA. CONCRETE ANCHORS FOR LARGER SIZE ANCHORS.) RISER PANELS FOUR (4) 1/4" x 4" LAG BOLTS w/ 1-1/4" FENDER WASHERS BEAM OR HEADER PER 4'-0" PANEL ACROSS THE FRONT & ALONG THE SIDES 7 7 HEADER ATTACHED TO POST 2x2 OR 2x3 ANGLE CLIPS MAY w/ THREE (3) #10 x 2" LONG HOLLOW BE SUBSTITUTED FOR S.M.S. INTO SCREW BOSS ---% INTERNAL SCREW SYSTEM ANCHOR 1" x 2" POST ATTACHED TO EXTRUSION TO BOTTOM W/ MIN THREE CONCRETE w/ 1/4" x (3) #10 x 2" LONG S.M.S. 3-1/4" CONCRETE INTO SCREW BOSS ANCHORS WITHIN 4" OF 4" MAX 4" MAX. POST 24'EO.C. MAX. I I _ ,/IBOTTOMPRAII BACK NOMINAL 4' SLAB, 3000 PSI CONC., `� , � � ' a � ' VAPOR BARRIER UNDER CONCRE. x 6 -10 x 10 W.W.M. SLAB, IF NEEDEC OR FIBER MESH TYPICAL UPRIGHT DETAIL NAME: CHRISTIANSEN RESIDENCE ADDRESS: 8215 WEST BITTERBUSH LANE CITY/STATE: PORT ST. LUCIE, FL 34952 COUNTY: ST. LUCIE THE "CIRCLED" CONNECTIONS ON THIS SHEET ARE BEING USED FOR THIS PROJECT. 1 2 3 4 DRAWINGS NOT TO SCALE THE CONNECTIONS ON THIS SHEET ARE OPTIONAL. R. A DUNLEA, P.E. 1513 CERVANTES PLACE THE VILLAGES, FLORIDA 32159 (772) 285-6444, (352) 750-6207 bobdunlea(a)-centurviink.net FLORIDA P.E. Lic. No. 42835 '�-OTHONy _.•_' ®PV; 7T/ �p F �f4 • ••�'•�i:S1ONAL •ov?.1$01�