Metal Sales Manufacturing Corporation
545 South 3'd Street, Suite 200
Louisville, KY. 40202
SCOPE:
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be
used in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section
(In Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this product
or material tested for quality assurance purposes. If this product or material fails to perform in the accepted manner, the
manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or suspend the use
of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance, if it is
determined by Miami -Dade County Product Control Section that this, product or material fails to meet the requirements
of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: 5V Crimp Metal Roofing System
LABELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product, for .
sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any, section of
this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed by the
expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then it shall be done
in its entirety.
INSPECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall be available for inspection at the job site at the request of the Building Official. .
This renews NOA#09-0105.09 and consists of pages 1 through 9.
The submitted documentation was reviewed by Alex Tigera.
MIAMI-DADE COUNTY
File Copy
NOA No.: 13-0627.02
Expiration Date: 06/.29/18
Approval Date: 08/01/13
Page 1 of 9
ROOFING SYSTEM APPROVAL
Category
Roofing
Sub -Category:
Metal, Panels (Non -Structural)
Material:
Steel
Deck Type:
Wood
Maximum Design Pressure -196. i 5 psf
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
ITest Product
Product Dimensions Specifications Description
5V-Crimp Metal 1=varies TAS 110 Corrosion resistant, galvanized, preformed,
Roof w = 24" coated, pref nished, metal panels.
h
Trim Pieces
Min. Thicl
(2,
Min. Yield
w=
Min. Thict
in,
MANUFACTURING LOCATION:
1. Jacksonville, FL.
EVIDENCE SUBMITTED:
Test Agency
Akzo Coatings
Valspar Corporation
Underwriters Laboratory.
PRI Construction Materials
Celotex Corporation Testing
Services
Hurricane Test Laboratory, Inc.
Farabaugh Engineering and
Testing, Inc.
0.0179"
ath: 60ksi
TAS 110 Standard flashing and trim pieces.
Manufactured for each panel width.
0.0179"
Test Identifier
R9697
[SMC-003-02-01
MTS 520103
0103-1213-98
0103-0712-09
T181-6
T235-07
T240-09
Test Name/Report
Date
ASTM G 23
ASTM B 117
ASTM G 23
ASTM B 117
UL 790
July 1998
TAS-100
June 2006
ASTM E 8
Jan. 1999
TAS 125
Dec. 1998
TAS 125
Sept 2009
TAS 125
July 2005
TAS 125
July 2007
TAS 125
Sept 2009
NOANo.: 13-0.627.02
Expiration- Date: 06/29/18 -
Approval Date: 08/01/13
Page 2 of 9
APPROVED ASSEMBLIES:
System A:
5V-Crimp Metal Roof Panel
Deck Type:
Wood, Non -insulated
Deck Description:
New Construction 19/32" or greater plywood or wood plank, or for re -roofing 15/32" or
greater plywood.
Maximum Uplift
See Table A below.
Pressure:
Deck Attachment:
In accordance with applicable Building Code, but in no case shall it be less than 8d ring
shank nails spaced 6" o.c. In reroofing, where the deck is less, than 19/32" thick (Minimum
15/32") the above attachment method must.be in'addition to existing attachment.
Underlayment:
Minimum underlaymenf shall be an ASTM D 226 Type II installed with a minimum 4" side -
lap and 6" end -laps. Underlayment shall be fastened with corrosion resistant tin -caps and 12
gauge 1 '/a" annular ring -shank nails, spaced 6" o.c. at all laps and two staggered rows 12"
o.c. in the field of the roll. Or, any approved underlayment having a current NOA.
Fire Barrier:
Any approved fire barrier having a current NOA. Refer to a current fire directory listing for
fire ratings of this roofing system assembly as well as the location of the fire barrier within
the assembly. -See Limitation # 1.
Valleys:
Valley construction shall be in compliance with Roofing Application Standard RAS 133 and
with Metal Sales Manufacturing Corporation's current published installation instructions:
Metal Panels and
Install the 'W-Crimp Panels" and accessories in compliance with Metal Sales Manufacturing
Accessories:
Corporation's current, published installation instructions and details. Flashing, penetrations,
valley construction and other details- shall be constructed in compliance with the minimum
requirements provided in Roofing Application Standards RAS 133.
Panel fasteners shall be #945 x 1-%" self drilling, self tapping, hex head screws with sealing
washer of sufficient length to penetrate through the sheathing a minimum of 3/16 inch.
Fasteners shall be installed at a maximum spacing as listed in Table A below parallel to the
slope. Fasteners shall be installed at a maximum of 12" o.c. at panel edge. See detail herein.
TABLE A
MAXIMUM DESIGN PRESSURES
Roof Areas
Field'
Perimeter and Corner
Maximum Design Pressures
-74.8 psf
-196.75 psf
Maximum Fastener Spacing
16" o.c.
8" o.c.
1. Extrapolation shall not be allowed
MIAMMADE COUNTY
NOA No.: 13-0627.02
-Expiration,Datm-06/29/18
Approval Date: 08/01/13
Page 3 of 9
3
System B: 5V-Crimp Metal Roof Panel
Deck Type: Wood, N Iln-insulated
Deck Description: New Construction 19/32" or greater plywood or wood plank, or for re -roofing 15/32" or
greater t
ood.
Maximum Uplift See Tabelow.
Pressure:
Deck Attachment:
In accord
shank nails
1s
/32 1 the a
Underlayment:
Minimum u
lap and 6"e
gauge 1 Yy"I
o.c. in the fi
Fire Barrier:
Any approvl
fire ratings
the assembl
Panel fasts
washer of
Fasteners
slope. Fa
y.
shall be #9-15 x 1%" self drilling, self tapping, hex head screws with sealing
.ient length to penetrate through the sheathing a minimum of 3/16 inch.
be installed at a maximum spacing as listed in Table B below parallel to the
.s shall be installed at a maximum of 6" o.c. at panel edge. See detail herein.
ITABLE B
MAXIMUM DESIGN PRESSURES
Roof Areas
I Field
Perimeter and Corner
Maximum Design Pressures
I -84.5 psf
-131.3 psf
Maximum Fastener Spacing
. 24" o.c.
18'. o.c.
1. Extrapolation shall not be allowed
MIAMI•DADE COUNTY
....
NOA No.: 13-0627.02
Expiration -Date: _06/29/18
Approval Date: 08/01/13
Page 4 of 9
J
LIMITATIONS
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory for fire
ratings of this product.
2. The maximum designed pressure listed herein shall be applicable to all roof pressure zones (i.e. field, perimeters,
and corners). Neither rational analysis, nor extrapolation shall be permitted for enhanced fastening at enhanced
pressure zones (i.e. perimeters, extended corners and corners).
3. Panel shall be roll formed in continuous lengths from eave to ridge. Maximum lengths shall be described in the
Roofing Application Standard RAS 133.
4. All panels shall be permanently labeled with the manufacturer's name and/or logo, and the following statement:
"Miami -Dade County Product Control Approved" or with the Miami -Dade County Product Control Seal as seen
below. All clips shall be permanently labeled with the manufacturer's name and/or logo, and/or model.
5. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 9N-3 of the Florida Administrative Code.
MIAMI•DADE COUNTY
NOA No.: 13-0627.02
Expiration Date: -06/29/18
Approval Date: 08/01/13
Page 5 of 9
1
PROFILE DRAWINGS
i DETAIL A
5V-CRIMP METAL ROOF PANEL
24" Coverage
#9-15 x 1 1/2" Woodgrip Screw #9-15 x 1 1/2" Woodgrip Screw
5V-Crimp Pianel
/ \Moisture Barrier
Plywood Decking --Ill
� (By others)
(By others)
FASTENING PATTERN FOR 5V-CRIMP AT INTERIOR OF PANEL
24"
#9-15 x 1 1/2" Woodgrip Screw
T 5V-Crimp Panel
nel
Moisture Barrier
Plywood Decking (By others)
(By others)
FASTENING PATTERN FOR 5V-CRIMP AT EAVE
CMILA E.00UNTY
NOA No.: 13-0627.02
Expiration Date: 06/29/18
Approval Date: 08/01/13
Page 6 of 9
5V-CRIMP METAL ROOF PANEL
SeeTable A
NOA No.: 13-0627.02
Expiration Date: 06/29/18
Approval Date: 08/01/13
Page 7 of 9
\I
`I DETAIL B
24" Coverage
#9-15 x 1 1/2" Woodgrip Screw `#9-15 x 1 1/2"'Woodgrip Scre
5V-Crimp Panel /
\_Moisture Barrier
Plywood Decki g (By others)
(By others)
FASTENING PATTERN FOR 5V-CRIMP AT INTERIOR OF PANEL
24" (
#9-15 x 1 1/2" Woodgrip Screw
IT 5V Crimp Panel
Moisture Barrier
Plywood Decking (By others)
(By others)
FASTENING PATTERN FOR 5V-CRIMP AT EAVE
,NOA No.: 13-0627.02
Expiration Date: 06/29/18
Approval Date: 08/01/13
Page 8 of 9
1
>> ,
MIAMI•DADE COUNTY
,.... m
SeeTable B
Herein for Maximum
END OF THIS ACCEPTANCE
NOA No.: 13-0627.02
Expiration Date: 06/29/18
Approval Date: 08/01/13
Page 9 of 9