+� wrightsoft° Load Short Form House Air Calcs, LLC Job: 1592 Date: 8/18/2021 By: Chris Bateman 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyrrie@aircalcs.com For: Key Largo Spec Home, NisAirAir Conditioning 7803 Fort Walton Ave, Fort Pierce, FL 34951 Htg Clg Outside db (°F) 41 90 Inside db (°F) 70 75 Design TD (°F) 29 15 Daily range - L Inside humidity (%) 30 50 Moisture difference (gr/Ib) 2 57 HEATING EQUIPMENT Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat 100 EFF 7.9 kW 26975 Btuh 21 °F 1153 cfm 0.045 cfm/Btuh 0.70 in H2O Infiltration Method Construction quality Fireplaces Simplified Average 0 COOLING EQUIPMENT Make Lennox Trade LENNOX Cond ML14XC1S036-230C*" Coil CBA27UHE-036-230*++TDR AHRI ref 204289057 Efficiency 13.0 EER, 16 SEER Sensible cooling 24220 Btuh Latent cooling 10380 Btuh Total cooling 34600 Btuh Actual airflow 1153 cfm Air flow factor 0.051 cfim/Btuh Static pressure 0.70 in H2O Load sensible heat ratio 0.76 ROOM NAME Area (ft2) Htg load (Btuh) Clg load (Btuh) Htg AVF (cfm) Clg AVF (cfm) Laundry 36 423 859 19 44 Bed 2 136 2373 1995 108 103 Bath 42 58 91 3 5 Bath 2 55 811 672 37 35 Hall 30 0 0 0 0 Bed 3 149 3388 3221 154 166 Bed 4 157 2458 1542 112 79 Foyer GR 426 5154 4875 234 251 Kitchen DR 424 4590 5783 208 298 Master Bath 117 2065 884 94 45 WIC 20 401 158 18 8 R A--+—, D— A Otis) 120-(]!1 012124 4 G7 Or) Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft, 2021-Nov-16 13:33:41 AM— „1,— , nawa.=om — Right-Sute®Urrversa12021 21.0.10 RSU29066 Page l ACCP....ightsoft HVAC\7803 Fort Walton Ave PSL Prop.rup Calc= MJ8 Front Door faces: N House 1801 25411 22411 1153 1153 Other equip loads 1769 939 Equip. @ 0.95 RSM 22277 Latent cooling 7225 TnTAI C 1 Ant 771 An 11 rI2 11 rI2 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft® k,e—H,nawa.Co —, Right-Srite®Uriversa1202121.0.10RSU29066 ACCP....ightsoft HVAC\7803 Fort Walton Ave PSL Prop.rup Calc= MJ8 Front Door faces: N N1104o►rimM- BAIQUI Page 2 Building Analysis Job: 1592 +� wrightsoft° gnaDate: 8/18/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyrrie@aircalcs.com For: Key Largo Spec Home, NisAirAir Conditioning 7803 Fort Walton Ave, Fort Pierce, FL 34951 Location: Indoor: Heating Cooling St Lucie Co Intl, FL, US Indoor temperature (°F) 70 75 Elevation: 26 ft Design TD (°F) 29 15 Latitude: 28°N Relative humidity (%) 30 50 Outdoor: Heating Cooling Moisture difference (gr/Ib) 2.4 56.9 Dry bulb (T) 41 90 Infiltration: Daily range (T) - 15 (L ) Method Simplified Wet bulb (T) - 77 Construction quality Average Wind speed (mph) 15.0 7.5 Fireplaces 0 Component Btuh/ft2 Btuh % of load Walls 3.1 4601 16.9 Glazing 17.4 4040 14.9 Doors 0 0 0 Ceilings 1.0 1785 6.6 Floors 3.2 5736 21.1 Infiltration 2.2 3186 11.7 Ducts 6062 22.3 Piping 0 0 Humidification 0 0 Ventilation 1769 6.5 Adjustments 0 Total 27180 1 100.0 Component Btuh/112 Btuh % of load Walls 1.9 2835 12.1 Glazing 16.2 3769 16.1 Doors 0 0 0 Ceilings 1.5 2634 11.3 Floors 0 0 0 Infiltration 0.6 891 3.8 Ducts 6782 29.0 Ventilation 939 4.0 Internal gains 5500 23.6 Blower 0 0 Adjustments 0 Total 23351 100.0 Latent Cooling Load = 7225 Btuh Overall U-value = 0.105 Btuh/ft2--°F Data entries checked. Glazi u:1a•111 Floors Vantilatinn NPROM ." Uucts on Gains wrightsoft" 2021 -Nov-1 6 13:33:41 ^^^-k-I-11 1—,1^P1r', Right-Sute®Urrversa1202121.0.10RSU29066 Pagel ightsoft HVAC\7803 Fort Walton Ave PSL Prop.rup Calc= MJ8 Front Door faces: N Component Constructions Job: 1592 +� wrightsoft CpCi Date: 8/18/2021 House By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyrrie@aircalcs.com For: Key Largo Spec Home, NisAirAir Conditioning 7803 Fort Walton Ave, Fort Pierce, FL 34951 Location: St Lucie Co Intl, FL, US Elevation: 26 ft Latitude: 28°N Outdoor: Heating Cooling Dry bulb (T) 41 90 Daily range (T) - 15 (L Wet bulb (T) - 77 Wind speed (mph) 15.0 7.5 ) Indoor: Indoor temperature (T) Design TD (T) Relative humidity (%) Moisture difference (grAb) Infiltration: Method Construction quality Fireplaces Heating 70 29 30 2.4 Simplified Average 0 Cooling 75 15 50 56.9 Construction descriptions Or Area U-value Insul R Htg HTM Loss Clg HTM Gain ft' Btuh/ftUF ft2-7/Btuh Btuh/ft' Btuh Btuh/ft' Btuh Walls Blk Wall, Stucco Ext, R-4.1 Ext Bd inl, 8"Thk, 1/2" Gyp Bd Int Fnsh n 251 0.109 5.1 3.15 791 2.02 506 e 371 0.109 5.1 3.15 1169 2.02 748 s 387 0.109 5.1 3.15 1220 2.02 780 w 212 0.109 5.1 3.15 668 2.02 427 all 1221 0.109 5.1 3.15 3848 2.02 2461 Partitions Fnn Wall, 1/2" Gyp Bd Ext, R-11 Cav Ins, 1/2" Gyp Bd Int Fnsh, 2"A", 16" 257 0.101 11.0 2.94 754 1.46 374 OC Stud Windows Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.22); n 47 0.620 0 18.0 841 11.7 550 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); n 40 0.580 0 16.8 676 8.03 323 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 4.7 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); s 5 0,580 0 16.8 79 13.5 63 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.17 ft window ht, 1 ft sep.); 6.8 ft head ht Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); s 31 0.580 0 16.8 525 13.6 426 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht W 47 0.580 0 16.8 787 28.1 1317 all 78 0.580 0 16.8 1312 22.3 1742 Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.24); s 16 0.580 0 16.8 262 13.5 210 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 8 ft overhang (5.2 ft window ht, 1 ft sep.); 6.8 ft head ht wrightsoft"' 2021-Nov-1613:33:41 --k=de-•,.ea«a-a. ,P=. Right-Sute®Urrversal202121.0.10RSU29066 ACCA Pagel ightsoft HVAC\7803 Fort Walton Ave PSL Prop.n p Calc= MJ8 Front Door faces: N Impact, Clear Lowe: Impact, Clear Lowe; NFRC rated (SHGC=0.21); s 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 8 ft overhang (6.7 ft window ht, 1 ft sep.); 6.8 ft head ht Impact, Clear Low-e: Impact, Clear Low-e; NFRC rated (SHGC=0.24); w 50% blinds 45°, medium; 50% outdoor insect screen; foreground = green grass (0.23); 1 ft overhang (2.2 ft window ht, 1 ft sep.); 6.8 ft head ht Doors (none) Ceilings Attic, Metal Roof, R-30 Ceil Ins, 1/2" Gyp Bd Int Fnsh Floors On Grade Depth, Tile Flr Fnsh _ wrightsoft- e �Ch — = d k,,,.e a«a.a. o „_ . Right-Sritee Uriversal 2021 21.0.10 RSU29066 ightsoft HVAC\7803 Fort Walton Ave PSL Prop.rup Calc= MJ8 Front Door faces: N 40 0.650 0 18.8 758 14.0 563 7 0.580 0 16.8 111 28.1 186 1801 0.034 30.0 0.99 1785 1.46 2634 200 0.989 0 28.7 5736 0 0 2021-Nov-16 13:33:41 Page 2 +� wrightsoft° Project Summary House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyrrie@aircalcs.com For: Keyy Largo Spec Home, NisAirAir Conditioning 7803 Fort Walton Ave, Fort Pierce, FL 34951 Notes: Weather: St Lucie Co Intl, FL, US Winter Design Conditions Outside db 41 °F Inside db 70 °F Design TD 29 °F Heating Summary Structure 19348 Btuh Ducts 6062 Btuh Central vent (56 cfm) 1769 Btuh Outside air Humidification Piping Equipment load Infiltration Method Construction quality Fireplaces 0 Btuh 0 Btuh 27180 Btuh Simplified Average 0 Heating Coolingg Area (ft2) 1801 1801 Volume (ft3) 15786 15786 Air changes/hour 0.38 0.20 Equiv.AVF (cfm) 100 53 Heating Equipment Summary Make Trade Model AHRI ref Efficiency Heating input Heating output Temperature rise Actual airflow Air flow factor Static pressure Space thermostat 100 EFF 7.9 kW 26975 Btuh 21 °F 1153 cfm 0.045 cfm/Btuh 0.70 in H2O Job: 1592 Date: 8/18/2021 By: Chris Bateman Summer Design Conditions Outside db 90 °F Inside db 75 °F Design TD 15 °F Daily range L Relative humidity 50 % Moisture difference 57 gr/Ib Sensible Cooling Equipment Load Sizing Structure 15629 Btuh Ducts 6782 Btuh Central vent (56 cfm) 939 Btuh Outside air Blower 0 Btuh Use manufacturer's data n Rate/swin multiplier 0.95 Equipmen� sensible load 22277 Btuh Latent Cooling Equipment Load Sizing Structure 3033 Btuh Ducts 2047 Btuh Central vent (56 cfm) 2145 Btuh Outside air Equipment latent load 7225 Btuh Equipment Total Load (Sen+Lat) 29502 Btuh Req. total capacity at 0.70 SHR 2.7 ton Cooling Equipment Summary Make Lennox Trade LENNOX Cond ML14XC1S036-230C** Coil CBA27UHE-036-230*++TDR AHRI ref 204289057 Efficiency 13.0 EER, 16 SEER Sensible cooling 24220 Btuh Latent cooling 10380 Btuh Total cooling 34600 Btuh Actual airflow 1153 cfm Air flow factor 0.051 cfim/Btuh Static pressure 0.70 in H2O Load sensible heat ratio 0.76 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wriQhtsoft- 2021-Nov-16 13:33:41 Right-Sute®Uriversal 202l 2l.O.10 RSU29066 Page 1 ACCA ightsoft HVAC\7803 Fort Walton Ave PSL Prop.rup Calc= MJ8 Front Door faces: N + wrightsoft" Right-J® Worksheet Job: 1592 House Date: 8/18/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircalcs.com 1 Room name House Laundry 2 E)posed wal I 200.0 It 5.5 ft 3 Room height 8.8 ft 8.0 it heat/cool 4 Room dimensions 5.5 x 6.5 it 5 Room area 1800.8 fF 35.8 ft Ty Consh'ucton U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/ft2--°F) (Btuh/fl) or perimeter (it) (Btuh) or perimeter (it) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall, Stucco Ext 0.109 n 3.15 2.02 338 251 791 506 0 0 0 0 T-jImpact, Clear Lowe 0.620 n 17.98 11.74 47 0 841 550 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 8.03 40 0 676 323 0 0 0 0 W Blk Wall, Stucco Ext 0.109 a 3.15 2.02 371 371 1169 748 0 0 0 0 11 Blk Wall, Stucco Ext 0.109 s 3.15 2.02 479 387 1220 780 0 0 0 0 Impaa Clear Low-e 0.580 s 16.82 13.48 5 5 79 63 0 0 0 0 G Impaa Clear Low-e 0.580 s 16.82 13.64 31 26 525 426 0 0 0 0 Impaa Clear Low-e 0.580 s 16.82 13.48 16 16 262 210 0 0 0 0 Impact, ClearLow-e 0.650 s 18.85 14.02 40 40 758 563 0 0 0 0 Blk Wall, Stucco Ext 0.109 w 3.15 2.02 266 212 668 427 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 7 0 111 186 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 47 0 787 1317 0 0 0 0 P Fmi Wall, 1/2" Gyp B 0.101 2.94 1.46 257 257 754 374 44 44 129 64 C Attic, Metal Roof, R 0.034 0.99 1.46 1801 1801 1785 2634 36 36 35 52 F On Grade Depth, Tile 0.989 28.68 0.00 1801 200 5736 0 36 6 158 0 6 c) AED excursion 131 -17 Envelope loss/gain 16162 9238 322 99 12 a) Infiltration 3186 891 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 5 1150 0 0 Appliances/other 4350 500 Subtotal (lines 6 to 13) 19348 15629 322 599 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 0 0 14 Subtotal 19348 15629 322 599 15 Dud loads 31% 43% 6062 6782 31% 43%1 101 260 FFTotal room load 25411 22411 423 859 Airrequired(dm) 1153 1153 19 44 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed rigl- tsoft- 2021-Nov-1613:33:41 �� ..i htsoft HVAC\78 Right -Suite@ Universal 2021 21.0.10 RSU29066 Page 1 g 03FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft" Right-J® Worksheet Job: 1592 House Date: 8/18/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircalcs.com 1 Room name Bed 2 Bath 2 E)posed wal I 24.0 It 0 It 3 Room height 8.0 It heat/000l 8.0 ft heat/000l 4 Room dimensions 1.0 x 135.8 It 7.0 x 6.0 It 5 Room area 135.8 fF 42.0 tt Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall, Stucco Ext 0.109 n 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact, Clear Lowe 0.620 n 17.98 11.74 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 8.03 0 0 0 0 0 0 0 0 W Blk Wall, Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 0 0 0 0 11 Blk Wall, Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 s 16.82 13.48 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.580 s 16.82 13.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 s 16.82 13.48 0 0 0 0 0 0 0 0 Impact, ClearLow-e 0.650 s 18.85 14.02 0 0 0 0 0 0 0 0 Blk Wall, Stucco Ext 0.109 w 3.15 2.02 84 68 216 138 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 16 0 262 439 0 0 0 0 P Fmi Wall, 1/2" Gyp B 0.101 2.94 1.46 108 108 317 158 0 0 0 0 C Attic, Metal Roof, R 0.034 0.99 1.46 136 136 135 199 42 42 42 61 F On Grade Depth, Tile 0.989 28.68 0.00 136 24 688 0 42 0 0 0 6 c) AED excursion 151 -2 Envelope loss/gain 1618 1084 42 60 12 a) Infiltration 184 51 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 250 0 Subtotal (lines 6 to 13) 1802 1385 42 60 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 4 6 2 4 14 Subtotal 1807 1391 44 63 15 Dud loads 31% 43% 5661 604 31% 43%1 14 27 FFTotal room load 2373 1995 58 91 Airrequired(dm) 108 103 3 5 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed rigl- tsoft- 2021-Nov-1613:33:41 �� ..i htsoft HVAC\78 Right -Suite@ Universal 2021 21.0.10 RSU29066 Page 2 g 03FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft" Right-J® Worksheet Job: 1592 House Date: 8/18/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircalcs.com 1 Room name Bath 2 Hall 2 E)posed wal I 6.5 it O ft 3 Room height 8.0 it heat/cool 8.0 ft heat/cool 4 Room dimensions 8.5 x 6.5 it 3.5 x 8.5 it 5 Room area 55.3 ft' 29.8 tt Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (it) (Btuh) or perimeter (it) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall, Stucco Ext 0.109 n 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact, Clear Lowe 0.620 n 17.98 11.74 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 8.03 0 0 0 0 0 0 0 0 W Blk Wall, Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 0 0 0 0 11 Blk Wall, Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 s 16.82 13.48 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.580 s 16.82 13.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 s 16.82 13.48 0 0 0 0 0 0 0 0 Impact, ClearLow-e 0.650 s 18.85 14.02 0 0 0 0 0 0 0 0 Blk Wall, Stucco Ext 0.109 w 3.15 2.02 52 45 143 91 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 7 0 111 186 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 P Fmi Wall, 1/2" Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic, Metal Roof, R 0.034 0.99 1.46 55 55 55 81 30 30 29 44 F On Grade Depth, Tile 0.989 28.68 0.00 55 7 186 0 30 0 0 0 6 c) AED excursion 68 -1 Envelope loss/gain 495 426 29 42 12 a) Infiltration 114 32 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 609 457 29 42 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 8 11 -29 -42 14 Subtotal 617 469 0 0 15 Dud loads 31% 43%1 1931 203 31% 43%1 0 0 qT.0, tal room load 811 672 0 0 quired (dm) 37 35 0 0 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed rigl- tsoft- 2021-Nov-1613:33:41 �� ..i htsoft HVAC\78 Right -Suite@ Universal 2021 21.0.10 RSU29066 Page 3 g 03FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft" Right-J® Worksheet Job: 1592 House Date: 8/18/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircalcs.com 1 Room name Bed 3 Bed 4 2 E)posed wal I 25.0 ft 21.0 It 3 Room height 8.0 It heat/000l 8.0 ft heat/000l 4 Room dimensions 1.0 x 149.0 It 1.0 x 157.0 It 5 Room area 149.0 fF 157.0 fF Ty Consh'ucton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall, Stucco Ext 0.109 n 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact, Clear Lowe 0.620 n 17.98 11.74 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 8.03 0 0 0 0 0 0 0 0 W Blk Wall, Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 64 64 202 129 11 Blk Wall, Stucco Ext 0.109 s 3.15 2.02 96 80 253 162 104 88 279 178 Impaa Clear Low-e 0.580 s 16.82 13.48 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.580 s 16.82 13.64 16 13 262 213 16 13 262 213 Impaa Clear Low-e 0.580 s 16.82 13.48 0 0 0 0 0 0 0 0 Impact, ClearLow-e 0.650 s 18.85 14.02 0 0 0 0 0 0 0 0 Blk Wall, Stucco Ext 0.109 w 3.15 2.02 104 73 229 147 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 31 0 525 878 0 0 0 0 P Fmi Wall, 1/2" Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic, Metal Roof, R 0.034 0.99 1.46 149 149 148 218 157 157 156 230 F On Grade Depth, Tile 0.989 28.68 0.00 149 25 717 0 157 21 602 0 6 c) AED excursion 247 -31 Envelope loss/gain 2135 1864 1501 719 12 a) Infiltration 439 123 368 103 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 250 250 Subtotal (lines 6 to 13) 2573 2236 1869 1072 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 7 10 2 4 14 Subtotal 2580 2246 1871 1075 15 Dud loads 31% 43% 8081 975 31% 43%1 586 467 FFTotal room load 3388 3221 2458 1542 Airrequired(dm) 154 166 112 79 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed rigl- tsoft- 2021-Nov-1613:33:41 �� ..i htsoft HVAC\78 Right -Suite@ Universal 20212 1.0.10 RSU29066 Page 4 g 03FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft" Right-J® Worksheet Job: 1592 House Date: 8/18/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircalcs.com 1 Room name Foyer GR Kitchen DR 2 E)posed wal I 34.5 ft 28.0 ft 3 Room height 9.5 ft heat/000l 9.5 ft heat/000l 4 Room dimensions 1.0 x 426.3 ft 1.0 x 424.3 ft 5 Room area 426.3 fF 424.3 ft' Ty Conshvcton U-value Or HTM Area (ft2) Load Area (ft2) Load number (Btuh/R2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall, Stucco Ext 0.109 n 3.15 2.02 223 152 478 306 0 0 0 0 T-jImpact, Clear Lowe 0.620 n 17.98 11.74 31 0 561 366 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 8.03 40 0 676 323 0 0 0 0 W Blk Wall, Stucco Ext 0.109 a 3.15 2.02 0 0 0 0 71 71 224 144 11 Blk Wall, Stucco Ext 0.109 s 3.15 2.02 0 0 0 0 195 139 438 280 Impaa Clear Low-e 0.580 s 16.82 13.48 0 0 0 0 0 0 0 0 G Impaa Clear Low-e 0.580 s 16.82 13.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 s 16.82 13.48 0 0 0 0 16 16 262 210 Impact, ClearLow-e 0.650 s 18.85 14.02 0 0 0 0 40 40 758 563 Blk Wall, Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 P Fmi Wall, 1/2" Gyp B 0.101 2.94 1.46 105 105 307 152 0 0 0 0 C Attic, Metal Roof, R 0.034 0.99 1.46 426 426 423 624 424 424 421 621 F On Grade Depth, Tile 0.989 28.68 0.00 426 35 989 0 424 28 803 0 6 c) AED excursion -98 -116 Envelope loss/gain 3435 1673 2906 1702 12 a) Infiltration 489 137 583 163 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 3 690 2 460 Appliances/other 900 1700 Subtotal (lines 6 to 13) 3924 3400 3489 4025 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 6 8 14 Subtotal 3924 3400 3495 4033 15 Dud loads 31% 43% 12301 1475 31% 43%1 1095 1750 FFTotal room load 5154 4875 4590 5783 Airrequired(dm) 234 251 208 298 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed rigl- tsoft- 2021-Nov-1613:33:41 �� ..i htsoft HVAC\78 Right -Suite@ Universal 20212 1.0.10 RSU29066 Page 5 g 03FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft" Right-J® Worksheet Job: 1592 House Date: 8/18/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircalcs.com 1 Room name Master Bath WIC 2 E)q)osed wall 19.5 it 4.0 ft 3 Room height 8.0 it heat/000l 8.0 it heat/000l 4 Room dimensions 1.0 x 116.5 it 5.0 x 4.0 it 5 Room area 116.5 fF 20.0 ft' Ty Consh'ucton U-value Or HTM Area (ft) Load Area (ft) Load number (Btuh/ft2--°F) (Btuh/fl) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Blk Wall, Stucco Ext 0.109 n 3.15 2.02 0 0 0 0 0 0 0 0 T-jImpact, Clear Lowe 0.620 n 17.98 11.74 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 n 16.82 8.03 0 0 0 0 0 0 0 0 W Blk Wall, Stucco Ext 0.109 a 3.15 2.02 72 72 227 145 32 32 101 64 11 Blk Wall, Stucco Ext 0.109 s 3.15 2.02 84 79 250 160 0 0 0 0 Impaa Clear Low-e 0.580 s 16.82 13.48 5 5 79 63 0 0 0 0 G Impaa Clear Low-e 0.580 s 16.82 13.64 0 0 0 0 0 0 0 0 Impaa Clear Low-e 0.580 s 16.82 13.48 0 0 0 0 0 0 0 0 Impact, ClearLow-e 0.650 s 18.85 14.02 0 0 0 0 0 0 0 0 Blk Wall, Stucco Ext 0.109 w 3.15 2.02 0 0 0 0 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 Impact, ClearLow-e 0.580 w 16.82 28.13 0 0 0 0 0 0 0 0 P Frm Wall, 1/2" Gyp B 0.101 2.94 1.46 0 0 0 0 0 0 0 0 C Attic, Metal Roof, R 0.034 0.99 1.46 117 117 115 170 20 20 20 29 F On Grade Depth, Tile 0.989 28.68 0.00 117 20 559 0 20 4 115 0 6 c) AED excursion -18 -3 Envelope loss/gain 1230 521 235 91 12 a) Infiltration 342 96 70 20 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants@ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1573 616 306 110 Less extemalload 0 0 0 0 Less transfer 0 0 0 0 Redishibution 0 0 0 0 14 Subtotal 1573 616 306 110 15 Dud loads 31% 43% 4931 268 31% 43%1 96 48 FFTotal room load 2065 884 401 158 Airrequired(dm) 94 45 18 8 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed rigl- tsoft- 2021-Nov-1613:33:41 �� ..i htsoft HVAC\78 Right -Suite@ Universal 2021 21.0.10 RSU29066 Page 6 g 03FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N + wrightsoft" Right-J® Worksheet Job: 1592 House Date: 8/18/2021 By: Chris Bateman Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircalcs.com 1 Room name Master Bed 2 E)posed wall 32.0 it 3 Room height 8.5 it heat/000l 4 Room dimensions 13.5 x 15.5 it 5 Room area 209.3 fF Ty Construction U-value Or HTM Area (ft2) Load Area Load number (BtuhV-°F) (Btuh/fF) or perimeter (ft) (Btuh) or perimeter Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 Wall, Stucco Ext 0.109 n 3.15 2.02 115 99 312 200 1�:Blk G Impact, Clear Low-e 0.620 n 17.98 11.74 16 0 280 183 G Impact, Clear Low-e 0.580 n 16.82 8.03 0 0 0 0 W Blk Wall, Stucco Ext 0.109 e 3.15 2.02 132 132 415 266 11 W Blk Wall, Stucco Ext Impact, Clear Low-e 0.109 0.580 s s 3.15 16.82 2.02 13.48 0 0 0 0 0 0 0 0 G Impact, Clear Lowe 0.580 s 16.82 13.64 0 0 0 0 G Impact, Clear Lowe 0.580 s 16.82 13.48 0 0 0 0 Impact, Clear Lowe 0.650 s 18.85 14.02 0 0 0 0 W Blk Wall, Stucco 6d 0.109 w 3.15 2.02 26 26 80 51 Impact, Clear Lowe 0.580 w 16.82 28.13 0 0 0 0 Impact, Clear Lowe Frm Wall, 1/2" Gyp B 0.580 0.101 w 16.82 2.94 28.13 1.46 0 0 0 0 0 0 0 0 P C Attic, Metal Roof, R 0.034 0.99 1.46 209 209 207 306 F On Grade Depth, Tile 0.989 28.68 0.00 209 32 918 0 6 c) AED excursion -47 Envelope loss/gain 2214 959 12 a) Infiltration 596 167 b) Room ventilation 0 0 13 Internal gains: Occupants@ 230 0 0 Appliances/other 500 Subtotal (lines 6 to 13) 2810 1626 Less e)demal load 0 0 Less transfer 0 0 Redistribution 0 0 14 Subtotal 2810 1626 15 Dud loads 31% 43% 8801 706 FFTotal room load 3690 2331 Air required (cfm) 167 120 Calculations aDDroved bvACCA to meet all reauirements of Manual J 8th Ed rigl- tsoft- 2021-Nov-1613:33:41 �� ..i htsoft HVAC\78 Right -Suite@ Universal 2021 21.0.10 RSU29066 Page 7 g 03FortWaltonAvePSLProp.rp Calc=MJ8 Front Door faces: N +� wrightsoft° Duct System Summary House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircalcs.com For: Key Largo Spec Home, NisAirAir Conditioning 7803 Fort Walton Ave, Fort Pierce, FL 34951 External static pressure Pressure losses Available static pressure Supply / return available pressure Lowest friction rate Actual airflow Total effective length (TEL) Heating 0.70 in H2O 0 in H2O 0.70 in H2O 0.490 / 0.210 in H2O 0.281 in/100ft 1153 cfm 249 Job: 1592 Date: 8/18/2021 By: Chris Bateman Cooling 0.70 in H2O 0 in H2O 0.70 in H2O 0.490 / 0.210 in H2O 0.281 in/100ft 1153 cfm Name Design (Btuh) Htg (cfm) Clg (cfm) Design FIR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk Bat, c 91 3 6 0.453 4.0 Ox0 VIFx 13.1 95.0 st1 Bath h 811 44 42 0.336 4.0 Ox0 VIFx 25.7 120.0 st3 Bed 2 h 2373 129 123 0.452 6.0 Ox 0 VI Fx 13.3 95.0 st1 Bed 3 c 3221 185 199 0.328 7.0 Ox 0 VI Fx 29.2 120.0 st3 Bed 4 h 2458 134 95 0.339 6.0 Ox 0 VI Fx 24.2 120.0 st3 FoyerGR c 2438 140 151 0.382 6.0 Ox0 VIFx 33.2 95.0 st2 Foyer GR-A c 2438 140 151 0.382 6.0 Ox0 VIFx 33.1 95.0 st2 Kitchen DR -A c 2891 125 179 0.382 7.0 Ox 0 VI Fx 33.0 95.0 st2 Kitchen DR-B c 2891 125 179 0.383 7.0 Ox 0 VI Fx 32.7 95.0 st2 Laundry c 859 23 53 0.455 4.0 Ox0 VIFx 12.6 95.0 st1 Master Bath h 2065 112 55 0.284 6.0 Ox 0 VI Fx 52.2 120.0 st4 Master Bed h 1845 100 72 0.288 6.0 Ox 0 VI Fx 50.2 120.0 st4 Master Bed -A h 1845 100 72 0.297 6.0 Ox 0 VI Fx 44.8 120.0 St4 WIC h 401 22 10 0.281 4.0 Ox 0 VI Fx 49.0 125.0 St4 Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FIR (fpm) (in) (in) Material Trunk st3 PeakAVF 363 336 0.328 821 9.0 0 x 0 VinlFlx st1 st1 PeakAVF 518 518 0.328 660 12.0 0 x 0 VinlFlx st2 PeakAVF 866 866 0.281 811 14.0 0 x 0 VinlFlx st4 PeakAVF 335 208 0.281 759 9.0 0 x 0 VinIFIX st2 wrightsoft® A� k,I,-1_,.-yI-p-, Right-Sute®Urrversa1202121.0.10RSU29066 ACCP....ightsoft HVAC\7803 Fort Walton Ave PSL Prop.rup Calc= MJ8 Front Door faces: N 2021-Nov-16 13:33:41 Page 1 Grille Htg Clg TEL Design Veloc Diam H x W Stud/Joist Duct Name Size (in) (cfm) (cfm) (ft) FIR (fpm) (in) (in) Opening (in) Matl Trunk rb5 Ox0 134 95 74.8 0.281 501 7.0 Ox 0 VIFx rt1 rb6 Ox0 185 199 66.7 0.315 570 8.0 Ox 0 VIFx rt1 rb7 Ox0 129 123 62.8 0.335 484 7.0 Ox 0 VIFx rt1 rb1 Ox0 714 813 58.0 0.363 582 16.0 Ox 0 VIFx rt1 rb8 Ox0 223 154 0 0 0 0 Ox 0 VIFx Name Trunk Type Htg (cfm) Clg (cfm) Design FIR Veloc (fpm) Diam (in) H x W (in) Duct Material Trunk rt1 PeakAVF 1161 1230 0.281 696 1&0 0 x 0 VInIFIX Bolditalic values have been manually overridden wrightsoft® A k,1,- _ -.-p,, Right-Sute®Urrversa1202121.0.10RSU29066 ACCP....ightsoft HVAC\7803 Fort Walton Ave PSL Prop.n p Calc= MJ8 Front Door faces: N 2021-Nov-16 13:33:41 Page 2 +� wrightsoft° Manual S Compliance Report House Air Calcs, LLC 7550 Hidden Hammock Ln, Vero Beach, FL32966 Phone: 772.800.8413 Email: vickilyme@aircalcs.com For: Key Largo Spec Home, NisAirAir Conditioning 7803 Fort Walton Ave, Fort Pierce, FL 34951 Design Conditions Job: 1592 Date: 8/18/2021 By: Chris Bateman Outdoor design DB: 90.4°F Sensible gain: 23351 Btuh Entering coil DB: 76.9°F Outdoor design WB: 77.4°F Latent gain: 7225 Btuh Entering coil WB: 64.0°F Indoor design DB: 75.0°F Total gain: 30576 Btuh Indoor RH: 50% Estimated airflow: 1153 cfm Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: SplitAC Manufacturer: Lennox Model: ML14XC1S036-230C**+CBA27UHE-036-230*++TDR Actual airflow: 1153 cfm Sensible capacity: 24220 Btuh 104% of load Latent capacity: 10380 Btuh 144% of load Total capacity: 34600 Btuh 113% of load SHR: 70% Heating Equipment Design Conditions Outdoor design DB: 41.0°F Heat loss: 27180 Btuh Entering coil DB: 68.1°F Indoor design DB: 70.0°F Manufacturer's Performance Data at Actual Design Conditions Equipmenttype: Elecstrip Manufacturer: Model: Actual airflow: 1153 ch Output capacity: 7.9 kW 99% of load Meets all requirements ofACCA Manual S. Temp. rise: 50 °F wrightsoft, 2021-Nov-16 13:33:41 IIT—Io-„1,,, ,,,.,—,�, Right-Sute®Urrversa1202121.0.10RSU29066 Pagel ACCk ightsoft HVAC\7803 Fort Walton Ave PSL Prop.rup Calc= MJ8 Front Door faces: N