This letter serves as my response to comments:
Single Family Residence
N
1. Please submit the elevation of the invert for the septic system. This is required for
determination of the elevation and requirements for storm water. See section 107 of the 2014
Florida Building Code and section 7.04.01 (D) of the Land Development Code.
Response: See revised survey attached.
2. Please submit the elevation of the occupied and adjacent properties. This is required for
determination of the elevation and requirements for storm water. See section 107 of the 2014
Florida Building Code and section 7.04.01 (D) of the Land Development Code:
Response: See revised survey attached.
3. Structure is located in an AE-6 flood zone. Please specify the lowest floor elevation on the
survey. See section 107 of the 2014 Florida Building Code.
Response: See revised survey attached.
4. Structure is located in an AE-6 flood zone. Please put on the plans the elevation of the lowest
part of the garage floor. See section 107 of the 2014 Florida Building Code.
Response: See revised survey attached.
1
1441 N. Ronald Reagan Blvd. • Longwood, FL 32750 • Phone: (407) 774-6078 • Fax: (407) 774-4078
AA0003325
www ahriecianarnnn rnm
A R C H I T E C T S
1'06
eDesignoup
5. Please see plan page Cl Design Criteria, exposure is incorrect. Please see R301.2.1.4.2 of the
2014 Florida Residential Building Code.
Response: Revised Design Criteria to exposure "D" to match revised structural
drawings. See delta 1 on sheet C1.
6. Could not complete my review of the opening design pressures on the Product Review
Affidavit due to the Expose Category being incorrect. Please see section 107 of the 2014
Florida Building Code.
Response: Revised Design Criteria to exposure "D" to match revised structural
drawings. See delta 1 on sheet C1.
7. Could not complete my review of the opening design pressures on the Certificate for Design
Load Compliance due to Expose Category being incorrect. Please see section 107 of the 2014
Florida Building Code.
Response: Revised Design Criteria to exposure "D" to match revised structural
drawings. See delta 1 on sheet C1.
8. No Product approval number was submitted for the roofing underlayment. Please submit the
correct Product approval number on the plans or submit the product approval in duplicate.
See chapter 1 Section 107 of the 2014. '
Response: See Product Approval with number for roofing underlayment attached.
9. Insulation R-values stated on the Energy Calcs. do not match the submitted drawings for
review. See chapter 4 section 402 subsection 402.1.2 of the 2014 Florida Energy Code.
Response: See revised Energy Calcs. attached.
10. Worse case marked YES on the Energy Calc's. House does not meet the requirements for the
use of the exception. Please check the orientation of the house for the walls, windows and
doors. See section 405.4.2 exceptions.
Response: See revised Energy Calcs. attached.
11. Please add the cubic volume of the conditioned space to information block containing the
square foot information. See chapter 1 section 107 of the 2014 Florida Building Code.
Response: Revised the information block containing the square foot information to
show the cubic volume of the conditioned space. See delta 1 on sheet C1 and revised
sheet M-1.
2
1441 N. Ronald Reagan Blvd. • Longwood, FL 32750 • Phone: (407) 774-6078 • Fax: (407) 774-4078
AA0003325
www.abdesianizrouD.com
A R C H I T E C T S
eDesign
oupl��.
zoning
12. Please indicate on the survey the proposed or existing finished floor elevation from the lots
on both sides of subject property. We will need the info to determine if drainage is going to
be sufficient for the proposed FFE and septic height.
Response: See revised survey attached.
If you have any questions please contact me at (407) 774-6078.
Sincerely,
James Cantwell
Florida Architect # 12079
1441 N. Ronald Reagan Blvd. • Longwood, FL 32750 • Phone: (407) 774-6078 • Fax: (407) 774-4078
AA0003325
www.abdesigngroun.com
A R C H I T E C T S
Design
Groupl��.
Zoning
12. Please indicate on the survey the proposed or existing finished floor elevation from the lots
on both sides of subject property. We will need the info to determine if drainage is going to
be sufficient for the proposed FFE and septic height.
Response: See revised survey attached.
If you have any questions please contact me at (407) 774-6078.
Sincerely,
James Cantwell
Florida Architect # 12079
3
1441 N. Ronald Reagan Blvd. • Longwood, FL 32750 • Phone: (407) 774-6078 • Fax: (407) 774-4078
AA0003325
A R C H I T E C T S
eDesign
oupl��.
February 21, 2018
St. Lucie County
Planning & Development Services
Building & Code Regulation Division County
2300 Virginia Avenue
Fort Pierce, FL. 34982
Attn: Building Plan Examiner
RE: Standard Pacific Homes
Riverbend Lot 15
Permit No. # BLDG 1712-0567
Dear Sir/Madam,
This letter serves as my response to comments:
Single Family Residence
1. Please submit the elevation of the invert for the septic system. This is required for
determination of the elevation and requirements for storm water. See section 107 of the 2014
Florida Building Code and section 7.04.01 (D) of the Land Development Code.
Response: See revised survey attached.
2. Please submit the elevation of the occupied and adjacent properties. This is required for
determination of the elevation and requirements for storm water. See section 107 of the 2014
Florida Building Code and section 7.04.01 (D) of the Land Development Code.
Response: See revised survey attached.
3. Structure is located in an AE-6 flood zone. Please specify the lowest floor elevation on the
survey. See section 107 of the 2014 Florida Building Code.
Response: See revised survey attached.
4. Structure is located in an AE-6 flood zone. Please put on the plans the elevation of the lowest
part of the garage floor. See section 107 of the 2014 Florida Building Code.
Response: See revised survey attached.
1441 N. Ronald Reagan Blvd. • Longwood, FL 32750 • Phone: (407) 774-6078 • Fax: (407) 774-4078
AA0003325
www. abdesiL,neroUD.COM
A R C H I T E C T S
eDesign
oupin�.
5. Please see plan page C1 Design Criteria, exposure is incorrect. Please see R301.2.1.4.2 of the
2014 Florida Residential Building Code.
Response: Revised Design Criteria to exposure "D" to match revised structural
drawings. See delta 1 on sheet C1.
6. Could not complete my review of the opening design pressures on the Product Review
Affidavit due to the Expose Category being incorrect. Please see section 107 of the 2014
Florida Building Code.
Response: Revised Design Criteria to exposure "D" to match revised structural
drawings. See delta 1 on sheet C1.
7. Could not complete my review of the opening design pressures on the Certificate for Design
Load Compliance due to Expose Category being incorrect. Please see section 107 of the 2014
Florida Building Code.
Response: Revised Design Criteria to exposure "D" to match revised structural
drawings. See delta 1 on sheet C1.
No Product approval number was submitted for the roofing underlayment. Please submit the
correct Product approval number on the plans or submit the product approval in duplicate.
See chapter 1 Section 107 of the 2014.
Response: See Product Approval with number for roofing underlayment attached.
9. Insulation R-values stated on the Energy Calcs. do not match the submitted drawings for
review. See chapter 4 section 402 subsection 402.1.2 of the 2014 Florida Energy Code.
Response: See revised Energy Calcs. attached.
10. Worse case marked YES on the Energy Calc's. House does not meet the requirements for the
use of the exception. Please check the orientation of the house for the walls, windows and
doors. See section 405.4.2 exceptions.
Response: See revised Energy Calcs. attached.
11. Please add the cubic volume of the conditioned space to information block containing the
square foot information. See chapter 1 section 107 of the 2014 Florida Building Code.
Response: Revised the information block containing the square foot information to
show the cubic volume of the conditioned space. See delta 1 on sheet C1 and revised
sheet M-1.
2
1441 N. Ronald Reagan Blvd. • Longwood, FL 32750 • Phone: (407) 774-6078 • Fax: (407) 774-4078
AA0003325
www shrlrcionornnn nnm
BREN ,,_,. =LN ENGINEERING,
1600 S. DIXIE HWY. SUITE 400, BOCA RATON, FL. 33432
Office: (561) 392-3748 Fax: (561) 392-4833
February 26, 2018
St. Lucie County
Planning and Development Services
Building & Code Regulation Division
2300 Virginia Ave
Fort Pierce, Fl. 34982
772-462-2172
Re: Standard Pacific Homes
Riverbend
Lot 15 - Model 6519B
Permit #: 1712-0567
To Whom This May Concern:
The following corrections have been made to the construction documents which are pertinent only to
our portion of the design of the.above referenced project, as clouded and tagged as Delta #1 with
revision date on plans.
Structural Comments:
1. Incorrect exposure category on plans, per R301.2.1.4.2 of 2014 Florida Residential Building Code.
Sheet SO:
1. Revised filled cells at both garage door openings to be #7 bars.
2. Revised spacing of filled cells to 64" O.C. max, typ.
3. Revised filled cells at opening in Master Bath to be #7 bars.
4. Added filled cells to each side of Sliding Glass Doors at Family Room and Casual Dining.
5. Revised filled cells at opening in Dining Room to be #7 bars.
6. Mono footings beneath 4"/6"W Interior Bearing Wall revised to M30i. See added info in Footing Schedule.
7. Added Double Wire Mesh beneath 4"/6"W Interior Bearing Wall.
Sheet S1:
1. Revise anchor connections at trusses on 4"/6"W Interior Bearing Wall.
Sheet S2:
1. Revise anchor connections and uplifts at trusses (7 locations).
Sheet SDI:
1. Revised Design Criteria accordingly
a. Revised Wind Exposure Category to "D"
b. Revised Basic Wind Pressure accordingly.
e`\Otll q I?-j9y)s d Mean Roof Height accordingly.
!tions or require additional information, please feel free to contact our office.
ass
ince
N 787
v
e® TEOF ;���
°
° v
.eve
STRUCTURAL ENGINEERING AND INSPECTIONS
BREN-r AN'ENGINEERING, IN
1600 S. DIXIE HWY. SUITE 400, BOCA RATON, FL. 33432
Office: (561) 392-3748 Fax: (561) 392-4833 -
February 26, 2018
St. Lucie County
Planning and Development Services
Building & Code Regulation Division
2300 Virginia Ave
Fort Pierce, Fl. 34982
772-462-2172
Re: Standard Pacific Homes
Riverbend
Lot 15 - Model 6519B
Permit #: 1712-0567
To Whom This May Concern:
The following corrections have been made to the construction documents which are pertinent only to
our portion of the design of the above referenced project, as clouded and tagged as Delta #1 with
revision date on plans.
Structural Comments:
1. Incorrect exposure category on plans, per R301.2.1.4.2 of 2014 Florida Residential Building Code.
Sheet SO:
1. Revised filled cells at both garage door openings to be #7 bars.
2. Revised spacing of filled cells to 64" O.C. max, typ.
3. Revised filled cells at opening in Master Bath to be #7 bars.
4. Added filled cells to each side of Sliding Glass Doors at Family Room and Casual Dining.
5. Revised filled cells at opening in Dining Room to be #7 bars.
6. Mono footings beneath 4"/6"W Interior Bearing Wall revised to. M30i. See added info in Footing Schedule.
7. Added Double Wire Mesh beneath 4"/6"W Interior Bearing Wall.
Sheet S1:
1. Revise anchor connections at trusses on 4"/6"W Interior Bearing Wall. 1
Sheet S2:
1. Revise anchor connections and uplifts at trusses (7 locations).
Sheet SD1:
1. Revised Design Criteria accordingly
,a. Revised Wind Exposure Category to "D"
b. Revised Basic Wind Pressure accordingly.
`\c.\(�o'jis�o/I e n Roof Height accordingly.
If r� G apXg. �Jdrjs or require additional information, please feel free to contact our office.