HomeMy WebLinkAboutENGINEERING SPECIFICATIONSGENERAL NOTES �• 1. DESIGN CRITERIA: APPLICABLE CODES, REGULATIONS & STANDARDS: 1. THE 2014 FLORIDA BUILDING CODE, 5TH EDITION SPECIFICALLY CHAPTER 16 STRUCTURAL DESIGN, CHAPTER 20 ALUMINUM & CHAPTER 23 WOOD. 2. ASCE 7-10. & SE17 3. NDS NATIONAL DESIGN SPECIFICATION FOR WOOD. 4. AC1318 CONCRETE REFRENCE MANUAL. 5. PCI PRECAST & PRESTRESSED CONCRETE. 6. AA ASM 35 & AA ADM 1 WIND LOADS: 1. BUILDING OCCUPANCY CATEGORY, PARAGRAPH 1604.5 & TABLE 1604.5: RISK CATEGORY 1. 2. BASIC WIND SPEED, TABLE 1609C, STATE OF FLORIDA DEBRIS REGION & BASIC WIND SPEED, PARAGRAPH 1609.3.1 & TABLE 1609.3.1 EQUIVALENT BASIC WIND SPEED: 150 MPH EXPOSURE CATEGORY, PARAGRAPH 1609.4.3: B 3. SCREENED ROOF ENCLOSURE FBC 2014 CH. 20 TABLE 2002.4 CONCRETE & FOUNDATION DESIGN: 1. WHERE CONCRETE SPECIFICATIONS ARE REQUIRED, WHETHER IN THE SCREEN ENCLOSURE SCOPE OF NOT, BY ONE OR MORE REGULATORY AGENCY, THE FOLLOWING SPECIFICATIONS ARE APPLICABLE: A. CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING COMPONENTS: I. PORTLAND CEMENT TYPE 1 - ASTM C 150 II. AGGREGATES - LARGE AGGREGATE 3/4" MAX. - ASTM C 33 III. AIR ENTRAINING +/- 1 % - ASTM C 260 IV. WATER REDUCING AGENT - ASTM C 494 V. CLEAN POTABLE WATER VI. OTHER ADMIXTURES NOT PERMITTED B. METAL ACCESSORIES SHALL CONFORM TO: I. REINFORCING BARS - ASTM A615, GRADE 60 11. WELDED WIRE FABRIC - ASTM A185 C. CONCRETE SLUMP AT DISCHARGE CHUTE NOT LESS THAN 3" OR MORE THAN 5". WATER ADDED AFTER BATCHING IS NOT PERMITTED. D. PREPARE & PLACE CONCRETE PER AMERICAN CONCRETE INSTITUTE MANUAL OF STANDARD PRACTICE, PART 1, 2, & 3 INCLUDING HOT WHEATHER RECOMMENDATIONS. E. MOIST CURE OR POLYETHYLENE CURING PERMITTED. F. PRIOR TO PLACING CONCRETE, TREAT THE ENTIRE SUBSURFACE ARE FOR TERMITES IN COMPLIANCE WITH THE FBC. G. CONCRETE SHALL BE PLACED OVER A POLYETHYLENE VAPOR BARRIER. 2. IF A MINIMUM 4" CONCRETE SLAB IS PROVIDED IN SOUND CONDITION, FREE FROM STRUCTURAL CRACKING, SPALLING & OTHER DETERIORATION. NO ADDITIONAL FOOTING OR FOUNDATION SYSTEM IS REQUIRED BY THE PROPOSED CONSTRUCTION. 3. WHEN APPLICABLE FOR ATTACHING NEW FOOTER TO EXISTING, DRILL & EPDXY NEW STEEL INTO EX. FOUNDATION WITH 1" MIN. HOLE, EMBED 4" MIN W/ NON -SHRINKING SIMPSON EPDXY -TIE (OR EQUAL) TYP. ALL LOCATIONS. 4. WHEN INSTALLING 4" CONCRETE SLAB -ADD ADJACENT TO EXISTING-DOWELL INTO EXISTING CONCRETE 48" O/C W/8" #5 REBARS- DRILL 3/4" HOLE 4" EMBEDMENT- EPDXY W/ NON -SHRINKING "SIMPSON EPDXY TIE" (OR EQUAL). 5. MINIMUM CONCRETE STRENGTH 3000 PSI UNLESS OTHER WISE NOTED. ALUMINUM SPECIFICATIONS: 1. ALUMINUM EXTRUSIONS SHALL BE 6005 T5 ALLOY UNLESS OTHERWISE SPECIFIED. 2. ALL SELF MATING BEAM SECTIONS ARE TO BE STITCHED WITH #12 SCREWS 6" FROM ENDS & 24" CENTER TO CENTER. 3. ROOF BRACING SHALL BE A MINIMUM 2"X2"X.050". 4. THE MINIMUM NORMAL THICKNESS OF PROTECTOR PANELS (KICKPLATES) SHALL BE AN INDUSTRY STANDARD OF 0.024 INCHES. 5. VINYL AND ACRYLIC PANELS SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH BE PER FBC. 6. SCREEN MATERIAL SHALL BE 18/14 SCREEN UNLESS APPROVED BY FLORIDA ENGINEERING LLC. FASTNER SPECIFICATIONS: 1. FASTENERS ARE REQUIRED TO BE SAE GRADE 2 OR BETTER ZINC PLATED. 2. IT IS THE OWNERS RESPONSIBILITY TO MAINTAIN THE SCREENS, AND FASTENERS TO MANUFACTURING SPECIFICATIONS. 3. WHERE WOOD DECK IS PRESENT USE 1/4"X3-1/2" GALV. LAG SCREWS IN LIEU OF MASONRY ANCHORS. UNLESS OTHERWISE SPECIFIED. 4. 1 "X2" NON STRUCTURAL MEMBERS ATTACHED TO HOST A. FOR MASONRY/CONCRETE APPLICATION USE GALVANIZED 1/4"X2-3/4" TAPCONS OR EQUAL AT 24" O.C. AND 6" FROM ENDS B. FOR WOOD APPLICATION USE #14X2-3/4" WOOD SCREW AT 24" O.C. AND 6" FROM ENDS. C. FOR ALUMINUM APPLICATION USE #10X1-1/2" SMS OR TEK SCREW AT 24" O.C. AND 6" FROM ENDS D. WHERE VX2" INSTALLED THROUGHOUT AN "OPEN VIEW" SPACING SHALL BE REDUCED TO 18" O.C. AND 6" FROM ENDS MASONRY SPECIFICATIONS: 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR. 2. ALL MORTAR SHALL BE TYPE M OR S. 3. ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4. PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS 5'-0" IN HEIGHT. MISCELLANEOUS: 1. SCREENED ENCLOSURES CONTAINING SWIMMING POOLS SHALL COMPLY WITH THE APPLICABLE REQUIREMENTS OF FBC R4101.17 RESIDENTIAL SWIMMING BARRIER REQUIREMENTS. 2. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPERATE 4TH WALL SUPPORT SYSTEM IS SO TO BE ENGINEERED SO THAT NO ADDITIONAL LOADING IS PLACED ON THE MANUFACTURED HOME. 3. DOOR LOCATION MAY BE RELOCATED BY CONTRACTOR IN THE FIELD. 4. WHERE PAVERS ARE UNDER ALUMINUM MEMBERS, CONTRACTOR SHALL EPDXY TO DECK OR GROUT TO DECK w/3000 PSI GROUT WITH BONDING AGENT. 5. INTEGRITY OF EXISTING/ HOST STRUCTURE SHALL NOT BE COMPROMISED WITH THE ATTACHMENT OF THE PROPOSED STRUCTURE. RESPONSIBILITIES: 1. ALL SITE WORK SHALL BE PERFORMED BY A LISCENED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDANANCES, AND THE ENGINEER SHALL BE NOTIFIED OF ANY DISCREPANCIES. TIES" 7'L,:I AR SUBJ ;CT T C ANY ca.,.19E 7N f1£CUIRED BY FIELD INSPECTORS THAT Mu"Y BE NECESSARY IN ORDER To COU17KY WITH ALL APPLICABLE CCODES. ���\` ❑� ^�'��i cILL 'co o O _ -_ uj c� -�.W to Fw- ;v>'> z° "' I/r/11!II!II 2. FOR FASTENERS WHICH ARE NOT VISIBLE AFTER INSTALLATION, THE CONTRACTOR SHALL VERIFY AND INSURE INSTALLATION HAS BEEN ACCOMPLISHED IN ACCORDANCE WITH MANUFACTURERS SPECIFICATIONS AND IN ACCORDANCE WITH THE ATTACHED DETAILS. 3. FOR "PICTURE WINDOW" MODIFICATION TO EXISTING SCREEN ENCLOSURES, ALL OTHER "EXISTING SCREEN ENCLOSURE" FEATURES ARE TO MEET THE TYPICAL DETAILS AS PROVIDED IN THESE DETAILS. CONTRACTOR IS TO VERIFY & ASSURE EXISTING SCREEN ENCLOSURE IS STRUCTUALLY SOUND. LEGEND: (ALL MAY NOT APPLY) SCR = SCREEN KP = KICK PLATE PW = PICTURE WINDOW FILIt X = HORIZ. SLIDING WINDOW O = HORIZ. STATIONARY WINDOW DH = DOUBLE HUNG WINDOW SH= SINGLE HUNG WINDOW SIP =SOLID INSULATED PAN 1f �Aj N ��5NEBS ORATTACHMEM CT = CABLE TIE 1i�� ''" SG = SUPER GUTTER PONSIBUTY OF THE CS CLEAR SPAN KB = KNEE BRACEO�nOTlaFREOgRg ALUMINUM MEMBERS DIMENSIONS HOLLOW SECTIONS 2 x 2: 2"x2"4.044" 2 x 3: 2"x3"x0.044" 2 x 4: 2"x4"4.044" 2 x 5: 2"x5"x0.050" OPEN BACK SECTIONS 1 x 2: 1 "x2"0.044" (D z_ W z w Q 0 0 LL F- z co O) M p 0 U olf p U J � IL L0 i I- co C H C Of 0') up 2 U W_ a_ 0 N W 1` w U U o_ It M cM ti 1 x 3: 1 "x3"x0.044" SNAP SECTIONS S1. Y LUCIE COUNTY 2 x 2 SNAP: 2"x2"x0.050" BUILDING DIVISION 2 x 3 SNAP: 2"x3"x0.050" REVIEWED < 2 x 4 .SNAP: 2"x4"x0.045" F COMPLIANC _ REVIEWED Y z 0 W SELF MATING (SMB) W LLI 2 x 4 SMB: 2"x4"x0.044"x0.100 P NS AND ER T Q U 2 x 5 SMB: 2"x5"x0.050"x0.100 MUST E KEPT ON OB OR 2 x 6 SMB: 2"x6"x0.050"x0.120' NO INSP CTION WILL BE MADE Q U) H 0 I_ 2 x 7 SMB: 2"x7"x0.057"x0.120 W uj 0 W U) 2 x 8 SMB: 2"x8"x0.072"x0.124" o Z o F- 2 x 9 SMB: 2"x9"x0.082"x0.124"0 0 2 x 10 SMB: 2"x10"x0 � U O a NOTE: AS INDICATED ABOVE ALL z O MEMBER PROFILES ARE INDICATED a IN INCHES. DESIGN DATE: 12/11/2017 REVISION 1: DATE PAGE: REVISION 2: DATE SCALE: NTS I of l i THESE PLANS WERE PREPARED BASED O 1, E PREMISE THAT THE EXISTING STRUCTURE WAS DEIGNED BY A PROPERLY LICENSED't mOFESSIONAL ENGINEER OF THE STATE OF FLORIDA, WAS PERMITTED BY THE APPROPRIATE PERMITTING AGENCY, WAS CONSTRUCTED BY A FLORIDA LICENSED CONTRACTOR AT THE TIME OF CONSTRUCTION, HAS NOT BEEN SUBJECT TO DAMAGE BY A MAJOR EVENT, AND HAS BEEN CERTIFIED BY THE CONTRACTOR THAT THE EXISTING STRUCTURE CURRENTLY SHOWS NO DEVIATIONS OR DEFECTS FROM THE STATE OF THE STRUCTURE AS PERMITTED BY THE FINAL INSPECTION OF THE PERMITTING AGENCY. ALSO, THE OWNER AND ALL PARTIES CONCERNED WILL co Ply INDEMNIFY FLORIDA ENGINEERING LLC FROM ANY DAMAGES OR CHANGES TO THE EXISTING STRUCTURE AS A RESULT OF ANY MODIFICATION OR FOR ANY OTHER REASON. FILL ROOF RISE 4'-0- (MAX.) F----------- 3 a I � I a I � I I w I 3' CHAIR RAIL L-1--------- ROOF RISE PROFILE i 1 X2 2X2 DJ r-o 2X2 DJ 2X4 SMB N X X Lo N �I 1 X2 _ —8'-6" I HOST 24" O/H STRUC. GUTTER o \2X 2X2 m U) /2X2 X N N f 10'-0" m m X U) W N N N co co 2X2 (TYP.' 1 X2 (TYP. �--- 6-0" --1 o 6-0" -- - THESAE PL!,NS :R►'1D ALL Pr CPQSCDARE SULJECT To ANY CORK-CT10,, f1LL;:,l�f7;g,T !�'i s l�l� Ir�SP�CTCr1� 1��PAt ua NECESSARY IN ORDER TO Cf-'j!l,riKf WITH All APPLIll-ULE EXISTING APPROVED 3" POLY ROOF EXISTING WALL WITH ACRYLIC WINDOWS AND 36" KNEEWALL o \\\��C-i, coo =�:w O Q QJ p: Z= o L i z a - A C9 Ld 41IIIIII111\\```\\\` U CD z 0i LLI z 0 W 00-0 0 LL C) 00 rn M (y) p o U p U O� LJLLoc: r W W (y) � U a N tb C) 0 w 0 U 0 M cM � a _LL z W .J U � ~ Q � J H U W � 0 W U) o Z o - F- U O q F- a 0 UFO u) w(nM0- Z O 0 ly U O_ DESIGN DATE: 12/11/2017 REVISION 1: DATE PAGE: n L REVISION 2: DATE SCALE: NTS D ' FLASHING \ 'HORIZONTAL OR SLOPED 1"&' FASTEN TO COL. (INTERNAL) W/(2) #10xl-1/2" SMS, FASTEN TO EAVE RAILS ABOVE W/ #10X7-1/2" SMS 24" O.C. AND 6" FROM END. TABLE D BEAM QTY EACH SIDE/SIZE 2x3 4/12 2 x 4 5/12 2x5 5112 2x6 6/12 2x7 7/12 2x8 8/14 2x9 9/14 2 x 10 9/14 MAINTAIN MIN, OF 5/8" SEPERATION FROM EDGE OF BEAM SMS O.C. DETAIL E - UPRIGHT TO BEAM CONNECTION SCALE: NTS BEAM PER PLAN NOTCHED TO RECEIVE COLUMN WITHIN SMS, (EACH SIDE) QTY PER TABLE D NOTCH PROFILE MAY VARY TO PERMIT CORRECT # SMS COLUMN PER PLANS NOTE: WHERE PAVERS ARE PRESENT USE 5/16" TAPCON XL (RED HEAD MFG.) MASONRY ANCHORS TO PENETRATE UNDERLYING CONCRETE FOOTING 2-1/4" (MIN.) ALTERNATELY 5" x 1/4" QUICKSETS 2-1/4" EMBEDMENT 1/8"x2"x2"xANGLE 5032 H-32 ANGLE I I 2-#10 SMS INTO COLUMN 1/4" MASONRY ANCHOR EACH o o ANGLE - EACH SIDE COL, o 0 I MIN 4" SLAB 3000 PSI CONC. w/FIBERMESH CONC. FOOTING 1/4" MASONRY ANCHOR AT EACH ANGLE -�_ SIDE VIEW (2) #10) INTO BI BEAM INSTAL TO COI SELF -MATING OR SNAP SECTION TYP. PER PLAN / 1"x2"'O.B. BASE PLATE-TYP. 1-1/4" MIN. CONC. ANCHOR EMBEDMENT 2" MIN. INCREASE DISTANCE WHEN GREATER THAN 2x4 UPRIGHT IS USED 2 - #12 SMS 1/4" TAPCON XL (RED HEAD MFG. OR EQUAL) 2 @ lx2 BASE 2 @ SLAB (BEYOND) CONC. FOOTING BELOW---� FRONT VIEW DETAIL "B" - 2"x4" OR LARGER SELF MATING UPRIGHT TO DECK DETAILS SCALE: NTS 1"x2" BASE PLATE ANCHORED TO CONC w/ 1/4" MASONRY ANCHOR 6" MAX EACH SIDE OF POST AND 24" O.C. MAX (2) #10x3" SMS INTO SCREW BOSSES FOR EDGE MEMBER-,,",. EDGE MEMBER 0 0 OR PURLIN arq DETAIL "D" - ROOF BRACING CONNECTION DETAIL SCALE: NTS EDGE MEMBER OR PURLIN 0.0625" 6063-T6 FLAT PLATE w/(8) #10x3/4" SMS, MIN. 1/2" .EDGE DISTANCE, PLATE MAY BE FASTENED INTERNALLY TO BRACE ALUMINUM INTERNAL OR EXTERNAL RECEIVING CHANNEL w/(4) #10x75" INTO GIRT OR PURLIN & (2) #14x75" INTO BEAM OR UPRIGHT 0.062 ANGLE CLIPS MAYBE USED PURLIN IN UPRIGHT, BEAM -SNAP, SELF MATING, OR HOLLOW rim opy_R Y t�. :�. III T MEMBER DETAIL "C" - GIRT OR PURLIN TO BEAM OR POST DETAIL SCALE: NTS #10x2" SMS INTO REW BOSSES Lij U) :z= z CO J M UI M Z z a E THESE. FLAWS ND ALL PROPM-C VV01M D � (°.) ARE.SMr•.'CT TOANYdiO RECdICsl1-5 fy_ I•'I" I J 0� p OJ 00 U REQUIRED BY FIELD INSPECTORS 1"W''k W Q/ rn � iV)6rsJ�a.i�I1IL U_ Lo •� N rJi3� ryi CC)IM1�: T INI T H PULL Aml PULL UE OWES. � � W M a) "ALL MEMBERS PER PLAN 2"x2"x.063" - DIM. TO MATCH PURLIN "MEMBERS VARY PER PLAN SIZE RECEIVING CHANNEL SMS INTERNAL EAVE RAIL ( INTO #12 EACH SIDE INTO PURLIN FASTEN TOP OF HEADER TO INTERSECTING n tl I MEMBER w/(2) #10 SMS w/1" PENETRATION INTO SCREW BOSS OF ii ii EAVE RAIL - SEE PLAN -- MEMBER - TYP. BOTH SIDES lx2 OPEN BACK EXTRUSION DOORJAMB it PER PLAN (2) #10x2" SMS THRU 1x2 INTO 9 EAVE RAIL EACH SIDE OF COLUMN ' FASTEN HEADER w/(2) #10x3" / u I INTO SCREW BOSS OF HEADER__---- EADER u DETAIL "G" - SLOPED PURLIN o CONNECTION SCALE: NTS ALTERNATE HEADER CONNECTION WHEN Z-BAR IS USED - FASTEN Z-BAR TO COL/HEADER AT EACH CORNER AND 18" O/C (12) #12xl" SMS @ V SPACING u li ALTERNATE BASE PLATE CONNECTION p p 2"x2" EDGE BEAM ATTACH MEMBER TO BASE PLATE I (INTERNAL) w/(2) #10xZSMS it o (2) #10x3" SMS - ATTACH BASE PLATE TO MEMBER u INTO SCREW BOSSES w/(2) #10x3" SMS INTO SCREW ii u CONNECTING EDGE BOSS OF BASE PLATE ii ii BEAM TO PURLIN ............ ;. I I I 1/4" TAPCON (RED HEAD MFG. OR EQUAL) WITHIN 6" OF COLUMN 1-1/2" PENETRATION INTO UNDERLYING FOOTING ALTERNATE DETAIL"G" SLOPED DETAIL "I"' - DOOR JAMB &HEADER PURLIN CONNECTION SCALE: NTS CONNECTION SCALE: NTS W N co r o co W U U V wC G F" ^ 0) 00 PURLIN Q U T_ o O M o LL (\ I I I I I I UPRIGHT O Z U W � O 1-1/2"x 1/16" PLATE (TOP OR BOTTOM) Y puR��N LL z W W U 1"x2" FASTENED TO COLUMN � J Q Q J w/(2) #10xl-1/2" SMS INTO W ~ �- SCREW BOSSES FOR SMB 0 W OR SNAP COLUMN W 0_ 1"x2" SNAP O Q 2 ~ UItO NOTCH COLUMN AS REQ'D. F w � U)(7 (L COLUMN PER PLAN z n DESIGN DATE: 12/11/2017 REVISION 1: DATE PAGE: 3 REVISION 2: DATE SCALE: NTS GIRT FASTENED INTERNALLY AT EACH END w/ #10 ,1.5" EACH SCREW GROOVE. FASTEN "TO•BEAM w/ 2x2x125 ANGLE (2) #12 SMS INTO BEAM & (2) #10xl-1/2" THRU ANGLE INTO GUTTER WHERE NO GIRT IS PRESENT, ATTACH ANGLE DIRECTLY TO GUTTER - 2"x2"xl18" ANGLE w/(2) #12 SMS-_ EACH LEG FOR BEAMS ABOVE 2x8 INSTALL GUTTER BRACE AT MIDPOINT BETWEEN BEAMS & INCLUDE 2" GUTTER BRACE AT EACH BEAM LOCATION 0 BEAM o (2) #14x2" WOOD (2) #12 SMS SCREW 18" O.C. CLOSE BOTTOM OF\ BEAM WHEN TRIMMED 044 RECEIVING CHANNEL, FASTEN w/(2) #12 SMS EACH SIDE OF BEAM/ #10 SMS WITHIN 6" OF BEAM & 24" O.0 2x2xl/8" ANGLE EA. SIDE OF BE w/(2) #12 SMS EACH LEG EACI FOR BEAM OVER 2x5 .044 RECEIVING CHANNEL FASTEN TO STRUCTURAL GUTTER INTERNALLY w/(2) #12 SMS ALTERNATELY 2x2xl/8" ANGLE BELOW GIRT, (2) #14 SMS INTO BEAM & (2) #12 SMS INTO STRUCTURAL GUTTER SIDE VIEW TOP VIEW DETAIL"H" SCALE: NTS NOTE F INSTALL FASTENERS ALONG PERIMETER OF GUSSET -BEAM JOINT 3/8" MIN, FROM EDGE. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 FASTENER PATTERN MAY APPEAR DIFFERENT FROM ILLUSTRATION. MAINTAIN 1/2" SEPARATION BETWEEN FASTENERS. MAINTAIN 3/8" MIN, FASTENER SEPARATION FROM BEAM JOINT OR EDGE OF BEAM LAP FASTENERS MAY BE EVENLY SPACED AROUND EDGE OF GUSSET WITHIN 3/8" OF BEAM JOINT. FASTENERS MAY BE STAGGERED TO INSURE PROPER QUANTITY PER TABLE B-1 FASTEN GUTTER TO FASCIA w/ #14x2" WOOD SCREW 18" O.C. (2) #12 SMS (2) #14x2" WOOD SCREW FASCIA (2"x6" MIN. EXISTING) STRUCTURAL GUTTER "ALTERNATELY SEE PAGE 5 5052-H32 GUSSET TABLE B-1 BEAM SIZE COL. TO BEAM QTY SMS/ SIDE OF COL. BEAM TO BEAM CITY SMS/ FACEISIDE 2 x 4 (5) #12 (9) #12 2 x 5 (5) #12 (9) #12 2 x 6 (7) #12 (9) #12 2 x 7 (10) #12 (10) #12 2 x 8 (12) #12 (14) #12 2 x 9 (14) #14 (14) #14 2 x 10 (16) #14 (15) #14 DETAIL "K" GUSSET CONNECTION SCALE: NTS 050" GUTTER STIFFNER FASTEN TO FASIA w(2) #12x2" WOOD SCREW FASTEN TO GUTTER w(2) #12 SMS "ALTERNATELY SEE PAGE 5 DETAIL "M" BEAM & PURLIN TO GUTTER CONNECTION SCALE: NTS 2x2xl/8" ANGLE w/(2) #12 SMS EA LEG - 1/8"&'x4" STRAP (2) #12 SMS INTO FIL 0�_ �AAA111111111///// c\jjcli (D ILI 2mo py THr,SEE Pig"•,`4S 4ilaD ALL Pr'r0, WHEN BEAM &PURLIN flLs iII° f 1 HIT ON CORNER - f.* FASTEN OUTSIDE OF IN' -A B� INE0ESiy+ RY IKi 0�pjLn- R ; 'BEAM&PURLIN ^C�'• ,/IVY ' !r 1fL' w/ 1/8"xZ" Q" ANGLE �'JEil l �f I �s�I Ti 7 YAisL r i��' �r� �f P ^" '� & (4) #12 SMS EACH LEG L1 CM E G 37.,ES. FASTEN INSIDE CORNER (BEAM TO PURLIN) w/ 1/8"x2"x2" ANGLE w/(2) #12 SMS INTO EA. MEMBER (BEAM & PURLIN) (2) #14 WOOD SCREWS (2) #12 SMS r INTO FASCIA 18" O.C. GIRT \ SMB ° 0 0 0 0 1/8"x2"x4" STRAP GIRT GIRT (2) #12 SMS INTO BEAM (2) #12 SMS INTO GUTTER FASCIA 2x2xl/8" ANGLE w/(2) #12 SMS EA. LEG (2) #12 SMS SMB GIRT STRUCTURAL GUTTER (2T-GOTTER-BRACES - EACH w/(2) #12 SMS INTO GUTTER & (2) #14 WOOD SCREWS INTO FASCIA (EACH w (2) #1 SMES INTO GUTTER & (2) #14 WOOD SCREWS INTO FASCIA 1/8"x2"x4" STRAP (2) #12 SMS INTO BEAM GIRT (2) #12 SMS INTO GUTTER STRUCTURAL GUTTER TOP VIEW DETAIL "L" CORNER CONNECTION SCALE: NTS (9) #10x2" SN 1/8" PLATE ON 45° ANGLE OR 1/8"x2"x2" ANGLE w/(4) #12 SMS INTO EACH INTERSECTING MEMBER PERIMETE FRAMING DETAIL 1-2" CABLE CONNECTION AT CORNER SCALE: NTS 1/8" STAINLESS STEEL 40° MIN. BRAIDED CABLE 60° MAX. Z `� 1 � � w ¢ ' Q _ uo, eo\i ��i v •••'o ............ '. '•'V ��\ � w N ca Li 0 U�cli o 0 00 cM M EY ZZ o o Q U p U W --I O 06 W L � 'c LU V M C z O YEBOLT FOR W O7 ABLE TENSION Q 1/8" STAINLESS STEEL U BRAIDED CABLE cNN < 5 I.L., co O O a 00 LL ti I` ` 4" MIN. SLAB w/FOOTING 318" DIA x 3" EMBED CONC. SCREW ANCHOR (TAPCON OR EQUAL) 3000 PSI CONC. 40° MIN. 6x6-M0 40° MAX. WWM OR FIBERMESH \ `� 0 4" MIN. SLAB/ \ w/FOOTING 1.5x5.5" ALUM. STRAP w/(2) 14' DIA x 2-1/4" MASONRY ANCHOR (TAPCON OR EQUAL) DETAIL 1-1" CABLE CONNECTION AT FOUNDATION SCALE: NTS 3000 PSI CONC. 6x6-10x10 WWM OR FIBERMESH O Z F-- U W O Y LJL Z �0 J ~ Q W J o F- 0 LLI 0W(n Z o I— O F¢ 2O� W (n m 0_ DESIGN DATE: 12/11/2017 REVISION 1: DATE PAGE : 4_ REVISION 2: DATE SCALE: NTS �d