HomeMy WebLinkAboutFLOOR & ROOF FRAMING PLANNOTES:
1) THE CONTRACTOR, SUBCONTRACTOR, SUPPLIER, ECT. SHALL VERIFY ALL
DIMENSIONS, CONDITIONS AT JOB SITE, PLANS, SPECIFICATIONS, ECT.
2) STRUCTURAL FEATURES NOT DETAILED ON THESE PLANS WILL BE
ADDRESSED BY THE ENGINEER AS CONSTRUCTION PROGRESSES.
3) ALL WRITTEN DIMENSIONS ON THESE DRAWINGS TAKE PRECEDENCE OVER
SCALED DIMENSIONS.
4) ALL CONSTRUCTION MUST COMPLY WITH THE FLORIDA BUILDING CODE
(FBC) 2014.
5) STRUCTURE' LOCATED IN NEGLIGIBLE WEATHERING AREA, AND IN VERY HEAVY
TERMITE INFESTA ION AREA.
STRUCTURAL NOTES
1) DESIGN LOADS IN ACCORDANCE WITH ASCE7-10.
2) SOIL BEARING CAPACITY: 2500 PSF (MIN.).
3) SPLITING OR CRACKING OF STRUCTURAL COMPONENTS DUE TO
INSTALATION OF HARDWARE IS NOT PERMITED,
4) UNLESS OTHERWISE NOTED, THE INSTALLATION OF SPECIFIED HARDWARE
SHALL CONFORM TO THE MANUFACTURES INSTRUCTIONS AND STANDARD
PRACTICI ES.
Planning & Development Services Department
Building & Regulations Division
Product Review Affidavit'
Building Permit # Owners Name Applicant:
Product
" opening Design
Product Rated
Manufacturer
Model Number
Product Approval
Glass
Method of Attachment
Pressures
Design Pressure
Number
Tvve
f
1S
(A'
b
rl 2 eooP >ASSUkll,Llj
Roofing Material
Z1 `6o':
�53•S
lie
ZI fo7.4I
22 '�f[o^
LINIoo
r�OElEu4-ATaXf
/�
2yAA ��
%�
-H
(
- 71,1
ZAj 'pI'tb
COWtFAJ1u. r-
I�� Ir I
I have reviewed the above components or cladding and I have approved their use in this structure. These products provide adequate resistance to the
wind loads and forces specified by current code provisions.
Name: PAUL WELCH PIE. Signature: ON PLAIN I
Design Prof: PAUL, WELCH PIE, Cert. No. 29945 Date:
1 Planning & Development Services Department
SEE DETAIL 1 Building &Code Regulations Division
THIS SHEET FASTENER SPACING AS PER LOAD SPAN - h(�jif
TABLE. SPACED O MAX 12' D.C. '• - 2300 Virginia Avenue, Fort Pierce, FL 34982 - (772) 462-15S3
PER PANEL I ACROSS WIDTH AT
INTERIOR SUPPORTS /-Pkti;,L
12' (TYP.) AND AT 7'-5'-7' AT PANEL ENDS, Certification for Design Load Compliance
Project Name: POLE BARN
Project Address: ST.LUCIE000NTY
eMEIAP FASTENER
(./4"-14 SOS WITH Permit Occupancy Type: U Construction T
MIN 16 GA., 50 KS, STEEL TYPICAL PANEL INSTALLATION X-SECTION WASHER o 24" O.C. INSTRUCTIONS FOR USE: P YP Type V
(DESIGN BY OTHERS)
• This certification must be completed, signed, and sealed by the design professional of record.
/12-14 X 1-1/4 LONG SIDELAP FASTENER %/12-14 x 1-%C4 LONG • Submit (2) copies for residential, (3) copies for commercial with all permit applications involving the following:
SELF DRLUNO SCREW 1/4"-14 SOS WITH SELF DRILLING $CREW
WITH WASHER m 12' O.C. WASHER O 24" O.C� WITH WASHER O o New Residences (single or multi -family)
7'-5'-7' O.0 o Residential Addition
o Any accessory structure requiring a building permit
0 Any non-residential structure.
pAeLRjtt ' Note: Form not required for interior renovations provided that no exterior structural elements are affected and
certain minor building permits at the discretion of the local building official. Contact the # above for questions.
MIN 16 G4 SUPPORTS LW 60' QC.
(DESIGN BY OTHERS) �- FOR ALLOWABLELOADSTABLE
I DESIGN PARAMETERS AND ASSUMPTIONS USED: (complete all that aoolv)
AND SPA) 1. DESIGN CODE: Florida Building Code 2014 Edition with 20 _Supplements using ASCE 7-10 '
SECTION VIEW 2. Structure Designed as (check one): X Enclosed -Partially Enclosed Open
3, Risk Category: _I X11_III IV Exposure Category: _B_X_C_D
2 1/2• 4. Design Wind Velocity 160 mph 124 ASD N A LRFD End Zone Width: J ft
SIpEtAP FASTENER I S. Mean Roof Height: 11 ft Roof Pitch: a :12 Parapet: N/A ft
1 /4I-A 4 SOS WITH
WASHER o 24' O.C. 1,16E . NOTFs 6. Components & Cladding Design Pressures Used: (PSF, based on 10sgft @ 15'MRH, clearly label on all plan openings):
/12-14 X 1-1/4 LONG I. STRUCTURAL ROOF PANEL HAS BEEN DESIGNED IN ACCORDANCE WITH THE 19.3 19.3 19.3 33.6 33.6 N/A
SELF DRILLING SCREW FLORIDA BUILDING CODE (FBC). Zone 1: Zone 2: Zone 3: Zone 4: Zone 5: Garage:
WITH WASHER 2. PANELS SHALL BE MIN. 26 GA_ (t R 0.0175"). EFFECTIVE COVERING WIDTH -30.7 -53.5 -79.1 -36.4 -44.9 g '' _N/A
OF PANEL = 30'.
3. ROOF PANELS SHALL BE INSTALLED OVER STRUCTURE AS SPECIFIED ON THIS 7. Design Loads: Floor: N/A PSF Roof/Dead: 5 PSF Roof/Live: 20 Balcony: L N/A PSF
PBR PANEL DRAWING.
(MIN 26 GA) 4. REQUIRED DESIGN WIND LOADS SHALL BE DETERMINED FOR EACH PROJECT.,- THIS Dock: N/A PSF Deck: N/A PSF Stairs: N/A PSF Fence: N/A PSF Railings: N/A pli' /CONCENTRATED
PANEL SYSTEM MAN NOT L INSTALLED WHEN THE REQUIRED DESIGN VnKDRAWING.
LOADS g• Were Shear Walls Considered For Structure? X Yes Not Applicable Explain Why Not:
ARE GREATER THAN THE ALLOWABLE WIND LOADS SPECIFIED ON THIS DRAWING. PP ' p Y
5. ALL FASTENERS MUST BE IN ACCORDANCE WITH THIS DRAWING k THE FLORIDA
BUIL04NG CODE. IF A DIFFERENCE OCCURS BETWEEN THE MINIMUM
REQUIREMENTS OF THIS DRAWING 6: THE COOS, THE CODE SHALL CONTR01.. 9. Is A Continuous load Path Provided? X Yes Not Applicable Explain Why Not:
MIN 18 GA.. 50 K51 STEEL 6, PURLINS/JOISTS/TRUSSES MUST BE DESIGNED TO WITHSTAND WIND LOADS AS ---
REQUIRED FOR EACH APPLICATION AND ARE TIIE RESPONSIBILM OF OTHEAS.
(DESIGN BY OTHERS) .10. Design Soil Bearing Pressure: 2500 PSF Soil Test Reports Submitted?- Yes
DETAIL I PJSIGN PROFESSIONAL CERTIFICATION STATEMENT:
I certify that, to the best of my knowledge and belief, the attached plans & specifications have been designed to
_ comply with the applicable structural portions of the building codes currently adopted and enforced by St. Lucie
County. 1 also certify that structural elements depicted on these plans provide adequate resistance to the design
ROvFITR,fP ASSMBLY nts... forces specified:
PER FL4 118711 r7.1 EtPaul Welch P.E. - _ 29945 / 5115
Print Name. Cert # & Co. Cert Auth.
Pau: Welch Inc.
ON PLAN
ALL ROOFING INSTALLATIONS SHALL BE IN ACCORANNCE WITH F.BC 2014. signature, Date, and Seal 1984 S.W. Biltmore St. Suite #114 Port St. Lucie, FL
Company Name & Address
- - --- - SLCCDV Form # 020-12 Revised 3/15/12 (JS)
r -
Vs?_.03 A }Tz�"I, f-;,r:ri'6,IMI�t,1,.,.
eQ A i-
` ne f(�� S' r�• f 4
iD tt •,.�` _ `.,._.. I'..A�-E'h ��,� Rc �f,9 v,1 d't.t^z �L•a Y F `Cj�,f�"„ F'P J `�
_.
1 i
�y�F'!F- T.� 1.vs a. r., t �1 ,n .. ,+e, ,,.,f T a• , k;� '{ 1 /.� v,n (HS ,`�S )a i?.+.Hy�N A,i �1
i 6°
•.., ...-.. -- y r�� �,�, _,--•~..A�` 1,, aY�, �' ICE rA ��- �� � ^�t�l., i y��i l�4> f"� 1�At.C�M:,.)_.i t.....i I�1
1 M1j 1 \
0
0,
;4 I:-Ii...�,r_I-f'� �Ir�LI►�'�.'�:�
i
11iI�Illlll Till III=111 Ills I1TTi.IM-IlTsllt li!`III' '=1UI„ (IG11TT ,.._ ..,...........ww
l
x� GGb
lI,II I).r �B
..
Ill.
I:It .1
F,
1111a=111 (II 'Alf, rPld ., k{@r..=a�
�(k r lei
T1 '"' FIT
Iris E'11,F`�
V Lv,!�4•= ICI A / 11
z 4 1- a ,I
I'%4 VIA-
ST. LUCIE COUNTY
BUILDING DIVISIO
REVIEVIC
FOR
REVIEWED BY
DATE _ l' C
PLANS AND PERMIT
MUS i BE KEPT ON JOB OR
NO INSPECTION yV?I.1, �E MQr`E
THESE PLANS ANO AU PROPOSED WORK
ARE SUI�1EGT TO TAN i, CM i! (,.TIONS
REGUREC D'YRL:i 0 ? a ; TPiAT
MAYBE NECESSA: rY Aar Ct)ER 1'c�
COMPLY WITN A" APOW0: 6; 4OI)ESt
�aNCFAIED FASII MS OR ATTACHMENTS
ARE THE RESRONSIBILp OF THE
CONTRACTOR OF RECORD
Mn� r
pbi
...-�.�.._..v...:«.._...«...„,.......w.�..�....w,.a.e.,•..�.�..,,,w.a.,•. �wa•+n..�,.•o.,� .n.n.>.ew.,.:,.. .,snw:e,a..-xnx.yv...r..w.,,,.4.....nrmm�.'m�„«m,..aw�...;.,manse.m,:�r..,.m",.yam.�.,.mv,...r..ma.+r,�,..w.,.u.;..:...em.�s.e,,,:.u..�- �' m„�•,,,-u ....u,.:. „ . .,nrr,x. ,.-.- ;cam: ,.,. ,.-:.....__ ,...,.,...
-• y:
I;
SCANNED
BY
ST LUCIE COUNTY
SHEET NUMBE
Ch INC.
MECHANICALELECTRICAL CIVIL ENGINEERING
1984 S. W. BILTMORE SST. SUITE # f l.4'
PORT ST. LUCIE, FL 34984.
PHONE ('772)785-9888 EMAIL PWELCH/NCCaAQL.COM
PA UL WEL CH, P. E: FLA REG No. 29945
NOV -2 L 2017