HVAC Load Calculations
for
Express Homes
Prepared By:
Kristin Kelly
Florida Breeze
6928 Vickie Circle Suite B
West Melbourne, FI 32904
321-951-8767
Friday, October 28, 2016
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
Designed By: Kristin Kelly
I
Project Date: October 28, 2016
Client Name: Express Homes
Company Name: Florida Breeze
Company Representative: Kristin Kelly
Company Address: 6928 Vickie Circle Suite B
' Company City: West Melbourne, FI 32904
Company Phone: 321-951-8767
C)e n E1 a
Reference City: Fort Pierce,
Florida
Building Orientation: Front door faces South
Daily Temperature Range: Medium
`
Latitude: 27 Degrees
Elevation: 25 ft.
'
Altitude Factor: 0.999
Outdoor Outdoor Outdoor
Indoor
Indoor
Grains
Dry Bulb Wet Bulb Rel.Hum Rel.Hum
Dry Bulb
Difference
Winter: 42 39.4 n/a
n/a
70
n/a
Summer: 95 78 47%
50%
75
53
Claec F( ores
Total Building Supply CFM: 1,658
I
CFM Per Square ft.: 0.6+,
Square ft. of Room Area: 2,601
Square ft, Per Ton:
671
Volume (ft') of Cond. Space: 21,691
Buildin L�°crad�
Total Heating Required Including Ventilation Air. 35,738
Btuh
35.738
MBW
Total Sensible Gain: 36,441
Btuh
78
°f° !
Total Latent Gain: 10,072
Total Cooling Required Including Ventilation Air: 46,513
Stuh
Btuh
22
3.88
%
Tons (Based On Sensible + Latent) I
1 Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
E:\RHVAC\EXPRESS HAYDEN 2601 PSL LEFT NEW.rh9
i
I
i
Friday, October 28, 2016, 12:16 PM
_ - _
-- - jy,,>. 11rr ♦
j xi`;. f ^� h (",.i Y�f��Qi�i�IlW�t��Y�elo, �iQ �i l'Lf {��i`•!'
1\if�Ci* Rest�ec�#saf &i.igh#Commercial; 41V�L�L�aV�y - .�I -r �D �k K x. •f '�L% � Nw; ryj,tY $t' .YN 6.� jF°ar'N'f' ,y^
System 1-11h►ra iiou + tdoor Out ut In I oQr ins
uo Ftel. � u Diftere cs
I Inpu t� - uIh et u . �
42 39.4 80 /o nla 70 n/a
Winter.
95
78 47% 60% 75 52.90
j Summer:
Iau Sizirx Inffiffilzm9wl
Main Trunk
Runouts
Calculate: Yes
Yes
' Use Schedule: Yes
Yes
Roughness Factor: 0.01000
Pressure Drop: 0.1000 in.wg./100 ft.
0.01000 ;
0.1000 in.wg./l00 ft.
Minimum Velocity: 550 ft./min
450 ft./min
Maximum Velocity: 600 ft./min
760 ft./min
Minimum Height: 0 in.
0 in.
Maximum Height: 0 in.
0 in.
i
Winter -
Summer
Infiltration Specified: 0.410 AC/hr
0.210
148 CFM
CFM
Infiltration Actual: 0.410 AC/hr
0,210 AC/hr
Above Grade Volume: X 21.691 Cu.ft.
X 21,691 Cu.ft. I
8,893 Cu.ft./hr
4,555 Cu.ft./hr
X 0.0167
X 0.0167
Total Building Infiltration: 148 CFM
76 CFM
Total Building Ventilation: 0 CFM
0 CFM
i
--System 1---
Infiltration & Ventilation Sensible Gain Multiplier: 21.98
= (1.10 X 0.999 X 20.00 Summer Temp. Difference)
Infiltration & Ventilation Latent Gain Multiplier: 36.94
= (0.68 X 0.999 X 52.90 Grains Difference)
Infiltration & Ventilation Sensible Loss Multiplier: 30.77
= (1.10 X 0.999 X 28.00 Winter Temp. Difference)
Winter Infiltration Specified: 0.410 AC/hr (148 CFM), Construction: Average
Summer Infiltration Specified: 0.210 AC/hr (76 CFM), Construction: Average I
Duet tt� sec -tar See arios fair ste 1
//yy /ate
C
No. ': e
Lea a In 1 tfo era f
No
-
1 Supply Attic 16B
Attic 168
0
0.12 6 780 No I
1 Return
;
I
r
i
i
l
i
'
E:\RHVAC\EXPRESS HAYDEN 2601 PSL LEFT NEW.rh9
i
I
I
i
i
Friday, October 28, 2016, 12:16 PM
Load Prwiew Report
w11
fi.={
Sen i
Lad
Netj
Sen
Sys
sys
C{rj
sys
Ad
Dud
Scope
Ton
/Ton
Aram
Gain1
Garnl
Gainl
Lola
CFM
CFM
CFM[
SFte
J---u�_:.kf.._ing.._
B
3.88
671
2,601
36,441
10.072
46,513
35,738
465
1,658
1,658
System 1
3..88
671
2;601
36,441
10,072
46,513
35,738
465 j
1,658
17
Dud latent
3,144
3,144
2,601
$6,441
6,928
43,369
35.738
465
i
1,668
20x20
Zone 1
6,6,6,6,6,
1-First Floor
1,104
18,757
3,096
21,853
24,126
314
$53
6,6,6,6, g,
2-Second Floor
1,497
17,684
3,832
21,516
11.611
151
{
805
5,5,5,5,51
5,5
E:IRHVACIEXPRESS HAYDEN 2601 PSL LEFT NEW.rh9
i
Friday, October 28, 2016, 12:16 PM
IRhvac Residential&>L�ghtCammeeftG,Lssds�
fir , �: Y&'�pc
Total Bci�ldln Summari Loads _ -
'
Compo ,ens
n
C 2A-v-o: Glazing -Double pane low-e (e = 0.60), operable
window, vinyl frame, u-value 0.34, SHGC 0.35
2A-v-d: Glazing -Double pane low-e (e = 0.60), sliding
glass door, vinyl frame, u-value 0.63, SHGC 0.32
2B-v-d: Glazing -Double pane low-e (e = 0.60), fixed sash,
i vinyl frame, u-value 0,34, SHGC 0.35
i 11 J: Door -Metal - Fiberglass Core
13AB-Ofcs: Wall -Block, no blanket or board insulation,
filled core, siding finish
12C-Osw: Wall -Frame, R-13 insulation in 2 x 4 stud
cavity, no board insulation, siding finish, wood studs
168-38: Roof/Ceiling-Under Attic with Insulation on Attic
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane, R-38 insulation
22A-pm: Floor -Slab on grade, No edge insulation, no
insulation below floor, any floor cover, passive, heavy
dry or light wet soil
Subtotals for structure:
People:
Equipment:
Lighting:
Ductwork:
Infiltration: Winter CFM: 148, Summer CFM: 76
Ventilation: Winter CFM: 0, Summer CFM: 0
Total Building Load Totals:
Square ft. of Room Area: 2,601
Volume (W) of Cond. Space: 21,691
Total Heating Required Including Ventilation Air:
Total Sensible Gain:
Total Latent Gain:
Total Cooling Required Including Ventilation Air:
Neste
208.8
40.8
2.5
39.4
858
1491.8
2601
1,994
720
24
663
4,396
3,802
1,894
r�
t
2,988
789
35
733
3,517
3,597
3,720
2,988
789 !
35
733 1
3,517 1
3,597
3,720
154
5,088
0
0
0
i
I
18,581
0
15,379
15,379
6
1,200
1,380
2,580
3,000
2,700
5,700
0
0
01
12,596
3,144
15,313
18,457 1
4,561
2,728
1,669
4,397
0
0
0
0
35,738
10,072
36,441
46,513 .'
CFM Per Square ft.:
0.637. !
Square
ft. Per Ton:
671
35,738
Btuh
35.738
MBH
i
36,441
Btuh
78
%
10,072
Btuh
22
%
46,513
Btuh
3,88
Tons (Based On Sensible
+ Latent) 3
Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
E:\RHVAC\EXPRESS HAYDEN 2601 PSL LEFT NEW.rh9 Friday, October 28, 2016, 12:16 PM
Lcad <„
lhuac Re&edertbC & Ltgii 9m►mercia: ; f x Y
loap�mehnf, lac4„
Ela Sofwara�De-lrVC
x� aY.,3v t Le
tVC Spero r 'hAastars, -Lim
�' �
f�
i Systemi tii/hole H6us� Sutr�rnar} ©a s
i Co ponent A �� '.
i - . ton 4uarf L
2A-v-o: Glazing -Double pane low-e (e = 0,60), operable 208.8 1,1
window, vinyl frame, a -value 0.34, SHGC 0.35
2A-v-d: Glazing -Double pane low-e (e = 0.60), sliding
glass door, vinyl frame, u-value 0.63, SHGC 0.32
2B-v-d: Glazing -Double pane low-e (e = 0.60), fixed sash,
vinyl frame, u-value 0.34, SHGC 0.35
11 J: Door -Metal - Fiberglass Core
13AB-Ofcs: Wall -Block, no blanket or board insulation,
filled core, siding finish
12C-Osw: Wall -Frame, R-13 insulation in 2 x 4 stud
cavity, no board insulation, siding finish, wood studs
16B-38: Roof/Ceiling-Under Attic with Insulation on Attic
Floor (also use for Knee Walls and Partition
Ceilings), Vented Attic, No Radiant Barrier, Dark
Asphalt Shingles or Dark Metal, Tar and Gravel or
Membrane, R-38 insulation
22A-pm: Floor -Slab on grade, No edge insulation, no
insulation below floor, any floor cover, passive, heavy
dry or light wet soil
Subtotals for structure:
People:
Equipment:
Lighting:
Ductwork:
Infiltration: Winter CFM: 148, Summer CFM: 76
Ventilation: Winter CFM: 0, Summer CFM: 0
System 1 Whole House Load Totals:
Supply CFM: - . 1,00c
i Square ft. of Room Area: 2,601
Volume (ft3) of Cond. Space: 21,691
S stem Ldacis
Total Heating Required lnc{uding Ventilation Air:
Total Sensible Gain:
Total Latent Gain:
Total Cooling Required Including Ventilation Air:
40.8
2.5
39.4
858
1491.8
2601
720
24
663
4,396
3,802
1,894
0
0
0
0
0
0
0
789
35
733
3,517
3,597
3,720
789
35
733
3,517
I
3,597
3,720
154 5,088
0
0
i
i
0
18,581
0
15,379
15,379
6
1,200
1,380
2,680 i
3,000
2,7000
5,7000
0
12,596
3,144
15,313
18,457
4,561
2,728
1,669
4,397
0
0
0
0
35,738 10,072 36,441 46,513
1011. 0-0-
Square ft. Per Ton:
671
35,738
Btuh 35.738
MBH
36,441
Btuh 78
%
10,072
Btuh 22
%
46,513
Btuh 3.88
Tons (Based On Sensible + Latent)
j Rhvac is an ACCA approved Manual J and Manual D computer program.
Calculations are performed per ACCA Manual J 8th Edition, Version 2, and ACCA Manual D.
All computed results are estimates as building use and weather may vary.
Be sure to select a unit that meets both sensible and latent loads according to the manufacturer's performance data at
your design conditions.
t
E:IRHVACIEXPRESS HAYDEN 2601 PSL LEFT NEW.rh9 Friday, October 28, 2016, 12:16 PM
Cooling
System Type:
Outdoor Model:
Indoor Model:
Tradename:
Outdoor Manufacturer:
Description:
AHRI Reference No.:
Capacity:
Efficiency:
Heating
System Type:
Model:
Tradename:
Manufacturer:
Description:
Capacity:
Efficiency:
Air Source Heat Pump
25HBC548A**30
FV4CNB006
CARRIER AIR CONDITIONING
CARRIER AIR CONDITIONING
Air Source Heat Pump
3646316
50267
15.5 SEER
Air Source Heat Pump
25HBC548A**30
CARRIER AIR CONDITIONING
CARRIER AIR CONDITIONING
Air Source Heat Pump
45000
8.5 HSPF
This-system's,_equipment was selected in accor-dance with ACCA'ManuaCS` - � -`
Manual S equipment sizing data: SODB: 95F, SOWS: 78F, WODB: 42F, Si B: 75F, SIRH: 50%, WIDB: 70F, Sen. gain:
36,441 Btuh, Lat. gain: 10,072 Btuh, Sen. loss: 35,738 Btuh, Entering clg. coil DB: 75F, Entering clg. coil WB: 62.5F,
Entering htg. coil DB: 70F, Clg. coil TD: 20F, Htg- coil TD: 70F, Req. clg. airflow: 1658 CFM, Req. htg. airflow: 465 CFM
i
E:IRHVACIEXPRESS HAYDEN 2601 PSL LEFT NEW.rh9
Friday, October 28, 2016, 12:17 PM
/
| b6i
---Zone 1--
� 1 First Floor 1.104 24,128 314
2 Second Floor 1,497 11.611 161
Duct Latent '
� System 1total 2,601 35,738 465
1Mo�Trunk G�e in.. GyshSystem� 17 �
` Velocity: 1,054 ft./min
74
� m mi. sto
h leg
6/S.8.G.
6,6,6,6,
5.5.5`Ei
5.5.5.5,
3.144
853 853
805 805 |
Duo o�enaou�oobuv�ova�n�mK8anmdDDucts�e.
— d��d��� results /
� Runo�dudve|o�Uemenmmd��n� u � |
See the Manual DDuctaizereport for duct velocities and other data.
,
'
10,072
Y�
Q O7/l�Y�
*�000
p�,n
|
|
|Heati
'xpu �
Ak�um���P�p
A��o�����mp )
�
' Model:—
25HBC548A°°3O
' Indoor
F\�K�N8UOG �
/
Brand.
C�RR|E�4JR�8W��ON|NG
~
CARRIER
(
Description:
�8ouruaHeatPump
Air
Air Source Heat Pump
�
Efficiency:
8.5HSPF
15.5 SEER |
Sound:
0
0 .
Capacity:
45,0808tuh
50,267Bhuh !
/
Sensible Capacity:
n/a
43 .88OBtuh
| Latent'�� `
Capacity:3646316
n/a
.
6.378 BtuhAHRI
Reference No.:
n/a
`—
'This system's ' —�hb/��CA�on��
*e����am��a�e�m u�- .
! equipment sizing SoDB�9�F 0OVV8�78F VVQDB'42F �|�8�75F,S}RH'5O96 ��DB'7OF,Sen. Qa/mc
�anuo|uoqupn�en�o�mg � . . . . � ` . . �
� 3�441 8tuh.'� gain: iO.O72Btuh.Sen. loss 35,738B1uh,Entering d0.coil D8:75F.Entering c1g.coil VVB:G25F
—UO��F���|��� ��7�F����1������������C� i
Enh*hngh¢l�co . .nq�� i
| |
. /
�
\
�
E:URH\6AC\E%9RESS HAYDEN 2601 PGLLEFT NEVV.dhQ Friday, Oob»ber2O. 2016. 12:17 PM
AC G-N
r*iT.i(¢xagciiftwHm -
Contractor Florida Breeze
Mechanical License # CAC1814113
Building Plan #
County, Town, Municipality, Jurisdiction
Header Information
Home Address (Street or Lot#, Block, Subdivision)
REQUIRED ATTACHMENTS'
Form
RIPER 1.01
8 Mar 10
ATTACHED
Manual J1 Form (and supporting worksheets):
Yes 0
No ❑
or MJ1AE Form' (and supporting worksheets):
Yes ❑
No X❑
OEM performance data (heating. cooling, blower):
Yes ❑X
No ❑
Manual D Friction Rate Worksheet:
Yes ❑
No ❑X
Duct distribution system sketch:
Yes ❑
No ❑X
Design Conditions Building Construction Information
Winter Design Conditions
Building
42 OF
Orientation (Front door faces)
South
Outdoor temperature
,
F
North, East, West, South, Northeast,
Northwest, Southeast, Southwest
Indoor temperature
70
Number of bedrooms
5
Total heat loss
35738 Btu/n
Conditioned floor area
2601 sq Ft
Summer Design Conditions
Outdoor temperature
95
OF Number of occupants
6
Indoor temperature
75
of Windows
Roof
Grains difference 53
A Gr @ 50 % Rh Eave overhang depth
1.7 Ft
Sensible heat gain
36441
Btu/h Internal shade
Eave
Latent heat gain
10072
Btu/h Blinds, drapes, etc
Depth
Window
Total heat gain
46513
Btu/h Number of skylights
0
EQUIPMENT SELECT•
4
Heating Equipment Data
Coolinq Equipment Data
Blower Data
Equipment type
Heat pump
Equipment type Heat pump
CFM
Heating CFMQ1
Furnace, Heat pump, Boiler, etc.
Air Conditioner, Heat pump, etc
Model
25HBC548A**30
Model 25HBC548A* 30
Cooling CFM 1401 CFM
Heating output capacity
45000 Btu/h Sensible cooling capacity 43888 Btu/h
Heat pumps - capacity at winter design outdoor conditions
Latent cooling capacity Btu/h
6 37 8
Auxiliary heat output capacity
Btu/h Total cooling capacity 50267 Btu/h
+ ! !
•
! . .a
Design airflow
1662 CFM
Longest supply duct: 59 Ft Duct Materials Used (circle)
Trunk Duct: Duct board Flex, Sheet metal,
External Static Pressure (ESP)
0.33 IWC
Longest return duct: 30 Ft
Lined sheet metal, Other (specify)
Component Pressure Losses (CPL) 0.25 IWC Total Effective Length (TEL) 89 Ft
Available Static Pressure (ASP) 0,076 IWC Friction Rate: 0.09 lWC
ASP = ESP - CPL Friction Rate = (ASP x 100) - TEL
Contractor's Printed Name Kristin Kel
Contractor's Signature
Branch Duct: Duct board, lex Sheet metal,
Lined sheet metal, Other (specify)
Date 812412015
The AHJ shall have the discretion to accept Required Attachments ,pfinted from approved ACCA software vendors, see list on page 2 of instructions.
If abridged version of Manual J is used for load calculation, then verify residence meets requirements, see Abridged Edition checklist on page 13 of instructions.
Form generated by ACCA-appreved Manual J Eighth Edition Version 2 Elite Software Rhvac program.
Air Conditioning Contractors of America
Manual'S (Residential Equipment Selection)
Project Information Cooling Design Information
Name: Outdoor Design Temp: 91 IF db Summer
City: I Outdoor Design Temp: 43 "F db lWinter
Stater Attitude: Altitude Adjustment: 1 _65-1 Indoor Design Temp: 75 IF db 50 %RH F 63 IF wb
Manual J Load Calculations
Total Load Sensible Latent SHR Heat Loss
46513 36441 10072 0.783
OEM Information
Airflow Calculations
Design TD for Airflow
18
Design Sensible CFM
F1840
T Manufacturer. lCanrier Furnace Model #: t AFUE: u
Coil or Fan -Coil Model #: I FV4CNB006 Condenser Model #: 125HBC548A I SEER: 15.5 HSPF: 8.50
(A) Manufacturer's Cooling Performance Data
Lower Return Air
Outdoor Temperature =
F-95-1 IF db)
Entering Coil Temperature = 75 (F db) CFM (F wb)
Total BTUH
Sensible BTUH
Latent BTUH
SHR
Rated CFM @ Rated RA Temperature 67
51,800
36590
15,610
0.6 886
Rated CFM @Design RA Temperature 1400 ®
48,016
41,374
67642
0.8617
Rated CFM @ Rated RA Temperature 62
47.070
42,670
4.400
0.9065
(B) Manufacturer's Cooling Performance Data
Higher Return Air
Outdoor Temperature =
95 (F db)
Entering Coil Temperature = 75 (F db) CFM (F wb)
Total BTUH
Sensible BTUH
Latent BTUH
SHR
Rated CFM @ Rated RA Temperature 67
- 53,740
40,740
13,000
0.7581
Rated CFM @ Design RA Temperature F 1800 63
50,060
47,012
3,048
0.9391
Rated CFM @ Rated RA Temperature 62
49,140
48,580
560
0.9886
- Manufacturer's Cooling Performance Data (Interpolated)
Design Return Air Outdoor Temperature = 95 (F db)
CFM (F wb) Total BTUH Sensible BTUH
Latent BTUH SHR
47.582
2.685 0.9466
Excess Latent Capacity Calculation + -3,694
-3,694
Capacity @Design CFM / RA (F wb) 1$40.5 63 50,267 43,888
6.378 0.873
Equipment Capacity as a % of Design 108.079/6120.44%
F 63.33%
Manufacturer's Heat Pump Data
FManufacturer's Furnace Data
Capacity Capacity Balance Supplemental
@ 47 IF db @ 17 IF db Point Heat Required
46,280 26,680 -23.8 -15.87
Input Output
Desired Calculated
r FEATURES
Environmentally Sound Refrigerant Technology
• PuronO, chlorine -free non -ozone depleting refrigerant
• Thermostatic Expansion Valve (TXV) designed to maximize performance with Purono refrigerant
Energy Efficient Operation
• Electronically Commutating Motor (ECM) operates efficiently at all speeds
• Maximizes efficiency of heating and cooling systems
• Ultra low power consumption during fan only operation
Indoor Weather Control
• Warm, comfortable heating air temperatures
• Unmatched humidity control, especially with Carrier's Thermidistat" Control
Airflow and Sound Technology
• Diffuser air discharge section for high airflow efficiency and quiet, smooth operation
• High duct static capability
i0itcii:ofstitt`cIsrari
Condensate Control and Disposal Technology
• Minimal standing waterless microbial growth for improved IAQ and reduced condensate line clogging and related condensate leakage
• Condensate fittings relocated away from turbulent airflow patterns at the blower entrance for improved condensate control performance
• Overflow feature for slope coil units allows condensate to exit the unit without damage to product under clogged primary and secondary
line conditions
• Tested for condensate disposal at conditions much more severe than those required by AHRI
• Primary and secondary drain connections to comply with HUD
• All pans constructed of an injection molded glass -filled polycarbonate engineered resin material, with brass drain connections.
• High density, super thick cabinetry insulation with vapor barrier
• Pre -painted galvanized sheet metal cabinet
Heat Transfer Technology
• Grooved copper tubing
• Lanced sine wave aluminum fins
• Discreet refined counter -flow refrigerant circuitry
• Bi-flow hard shut-off TXV metering device
• ArmarCoat'" coil protection available
Quality Assisting, Ease of installation and Service Features
• All units multipoise
• Provision made for suspending from roof or ceiling joints
• Modular cabinet on 003 thru 006 units
• Sweat connections for leak free service
• Multiple electrical entry for application flexibility (high and low voltage)
• Low voltage terminal strip, to safely hold connections within the cabinet
• Inspection plate on A -coil models for quick coil cleanliness inspection
• Cabinet construction features innovations designed to prevent cabinet sweating
Controls and Electrical Features
• Easv Select'" Board to maximize comfort, efficiency, and safe beater airflow operation
• Easy plug connection provided for quick installation of accessory heater packages
• 40VA 208/230v transformer
• Replaceable 5-amp blade -type auto fuse protects against transformer secondary short
Filter Features
• Factory supplied filter
• Cleanable polyester filter media
• Filter "springs" out for easy access - no tools required
• Newly improved filter rack area - filter door insulation added for an improved air seal
2