HomeMy WebLinkAboutPLAN REVIEW FORMSAINT LUCIE COUNTY FIRE DISTRICT
PLAN REVIEW FORM
5160 N.W. Milner Drive
Port Saint Lucie, FL 34983
'015
Telephone: 772-621-3322:
Fax: 772-621-3604
Web Address: www.sidO.com
Building Dept SLC, FMO Permit # B-18-229
,Project Name St James Christian Academy BLDG Permit # 1807-0177
• Address 5200 Oleander Avenue City Ft Pierce
Contractor Integ-Crete Construction
Address 10550 West Midway Road City Ft Pierce
State FL Zip 34945 Telephone (772) 577-1449
Architect/Engineer Robert T Haug Telephone (407) 859-7925
Occupancy Type Education Construction Type lv-B Square Feet 11,152
Occupant toad 558 per plans Number of stories F Access Box Required Access Key Switch
AFS Permit FA Permit Required 'FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a.CD is required. The file format shall be.pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm, panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in field to maintain code compliance.
9. Automatic fan shutdown is required for HVACsystem/s'that exceed 2,000 cfm design capacity.
10. The installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2015 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVECODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING.
A CERTIFICATE, OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. The Installation or Alteration of a Fire Alarm System requires a separate review and permit.
2. The Fire Alarm System shall be of voice evacuation.
3. Portable fire extinguishers from a licensed contractor are required.
4. Place Emergency lights in both men and women bathrooms.
5. Educational occupancies with an occupant load greater than 100 persons require panic hardware or fire exit hardware on the
required means of egress doors.
Page F of 11 Reviewed' by Tony J'erger' Date 08-07-2018