Inspection/ Pump
y�' ���
out ports.
see notes 3-5
All plumbing and
venting must use
water tight gaskets
3"[8] 0 MIN
see notes 2-5
Vent
see note 2
Pipe clamp
see note 9
4" [ 10] 0
FAST@ effluent pipe
see note 7
16 3/8" MIN see note 11
[41.6 MIN]
35"±1 /8"
[88.9±0.3]
41 1/4 MIN
[105 MIN]
Lconnection between zones 6 3/8" MIN
[ 16.2 MIN ]
Settling Zone Treatment Zone see note 6 & 12
350 Gallon MIN [1300 L MIN] 450 Gallon MIN [1700 L MIN]
•-------------------
15"-1/4" 2-93/4"-1/4"
[38.1±0.6] ; - ��� 75.6±0.61
30"} _ 31 1/4" MIN
�`✓�/ [76.6.2] � � Ck I [79.4 MIN]
I 59 1 /2"
[151.1] i 1
Minimum clearance to L 0 12" MIN
insert FAST@ liner into tank [30.5 MIN]
1. Airline piping to FAST@ may not exceed 100 FT [30m] total length and
have a maximum of 4 elbows in the piping system. For distances
greater than 100 FT [30m] consult factory. Blower must be located
above flood levels on a concrete base 26" X 20" X 2" 165 X 50 X 5cm]
min.
2. Vent to desired location and cover opening with a vent grate with at
least 7 sq in.[45 sq, cm] open surface area. Secure with stainless steel
screws. Vent piping must not allow condensate build up or create
back pressure. Vent must be above finished grade or higher (see
sheet 4 of 4).
3. All appurtenances to FAST@ (e.g. tanks, access ports, electrical, etc.)
must conform to all applicable country, state, province, and local
Plumbing and electrical codes. Pump out access shall be adequate
to thoroughly clean out both zones.
4. All inspection, viewing and pump out ports must be secured to
prevent accidental or unauthorized access.
5. Tank, piping, conduit, etc. are provided by others. Blower control
system by Bio-Microbics, Inc. See Installation Manual.
6. If less than the specified minimums are considered necessary, consult
factory for guidance.
7. All piping and ancillary equipment installed after FAST must not
impede or restrict free flow of effluent.
8. The tank(s) shall be designed to prevent. air passage between the
settling zone/tank and the treatment zone and preventing an air lock.
Examples include a baffle wall sealed to the lid or treatment zone
inlet line with a pipe cap. Consult factory for guidance.
9. The air supply line into the FAST@ unit must be secured to prevent
vibration induced damage. The air supply line should be secured with
a non -corrosive clamp every 2' min [60 cm]. See alternate air supply
option on sheet 4 of 4.
10. Specialized treatment levels may require specific features to be
incorporated into the design. Consult factory for guidance.
11. Min. height may be reduced, consult factor and reference "Low
Profile Module Procedure.pdf'
12. Refer to sheet 4 of 4 for leg extensions requirements.
67 1 /2" MIN
[171.5 MIN]
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF BIO-MICROBICS INC. ANY REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN PERMISSION OF BIO-MICROBICS INC. IS PROHIBITED. DESIGN AND INVENTION RIGHTS ARE RESERVED. IN THE BIO-MICROBICS ©2014
INTEREST OF TECHNOLOGICAL ADVANCEMENT, ALL PRODUCTS ARE SUBJECT TO DESIGN AND OR MATERIAL CHANGE WITHOUT NOTICE.
DO NOT SCALE
UNLESS NOTED
© . r 0
DIMENSIONS
ARE IN INCHES
®'
[CENTIMETERS]
`
TOLERANCES
BETTER WATER.`BETTER WORLW
± 0.02 IN/IN
[±0.05 CM/CM]
MicroFAST 0.50 FAST Unit
IEIGHT
Ib
:S;lIZEDR�AWINGBERNAMEDATE
AST@ 0.5�,w(iith et
iOF
RAWN "C
Izneiz16
Specifications for MicroFAST 0.50 Wastewater Treatment System
1. GENERAL
The contractor shall furnish and install (1) MicrOFAST60.50 treatment system as manufactured by Bio-Microbics, Inc. The treatment system shall be complete with all needed equipment as
shown on the drawings and specified herein.
The principal items of equipment shall include the FASTO system insert, blower assembly, blower controls and leg extensions or lid. All other items will be provided by others.
The MicroFAST 0.50 unit shall be situated within a 450 Gallon [1700L] minimum compartment as shown on the drawings. Suggested maximum settling zone is 1) X the daily flow. Tank must
provide adequate pump out access and conform to local, state, and all other applicable codes. The contractor shall coordinate the proper fabrication of the tank between the FAST
system and tank supplier with regard to fabrication of the tank, installation of the FAST unit, and delivery to the job site.
2. OPERATING CONDITIONS
The MicroFAST 0.50 treatment system shall be capable of treating the wastewater produced by typical family activities (bath, laundry, kitchen, etc.) ranging from (1) one to
(8) eight people and not to exceed 500 US Gallons per day (1800 LPD) provided the waste contains nothing that will interfere with biological treatment. The FAST system is a biological
treatment system not meant for non -biodegradable or industrial wastewater.
3. MEDIA
The FASTO media shall be manufactured of rigid PVC, polyethylene, or polypropylene and it shall be supported by the polyethylene insert. The media shall be fixed in position and contain
no moving or wearing parts and shall not corrode. The media shall be designed and installed to ensure that sloughed solids descend through the media to the bottom of the septic tank.
4. BLOWER
The MicroFAST 0.50 unit shall come equipped with a regenerative type blower capable of delivering 17-25 CFM 131-46 m3/hr]. The blower assembly shall include an inlet filter with metal filter
element. The blower shall be mounted outside the tank on a contractor supplied concrete base. Blower piping to the tank shall use non -corrosive material (PVC, Galvanized, or stainless
Steel). Do not run galvanized pipe inside the treatment tank. Refer to Installation Manual for further details.
5. REMOTE MOUNTED BLOWER
The blower shall be placed on a contractor supplied concrete base. The blower must not sit in standing water and its elevation must be higher than the tank and normal flood level. A two-
piece, rectangular housing shall be provided. The discharge air line from the blower to the MicrOFAST@ System shall be provided and installed by the contractor.
6. ELECTRICAL
e within
Wiring distances must prevenl source shouldt significant v oltage loss Input powerblower
on 6OHz electrical systems 110/220VAC er 10,distances.
.7 FLAIL n1f 50 Hz electricmust al conform
ems to all applicable
f0, 1.9 FLA. O her voltages
and phase -are also available. Actual power consumption varies with site conditions. All conduit and wiring shall be supplied by contractor.
7. CONTROLS
The control panel provides power to the blower and contains an alarm system consisting of a visual and audible alarm capable of signaling blower circuit failure and high water conditions.
The control panel is equipped with SFRO (Sequencing Fixed Reactor) timed control feature. A manual alarm silence button is included.
8. INSTALLATION AND OPERATING INSTRUCTIONS
All work must be done in accordance with local codes and regulations. Installation of the FAST 0.50 shall be done in accordance with the written instructions provided by the manufacturer.
Manuals shall be furnished, which will include a description of system installation, operation, and maintenance procedures.
9. FLOW AND DOSING
FAST@ systems have been successfully designed, tested and certified receiving gravity, demand -based influent flow. When influent flow is controlled by pump or other means to help with
highly variable flow conditions, then multiple dosing events should be used to maximize performance. The flow rate shall not exceed 5 gpm (19 Lpm) with a maximum hourly flow not to
exceed 10% of the design daily flow (50 gph (190 LPH)).
1 O.WARRANTY
Bio-Microbics, Inc. warrants all new residential FASTO models (Micro FAST@ 0.50, 0.625, 0.75, 0.90, and 1.5) against defects in materials and workmanship for a period of two years after
installation or three years from date of shipment which ever occurs first. All other FAST@ system models are warranted for a period of one year after installation or eighteen months from date
of shipment, whichever occurs first. All are subject to the following terms and conditions below:
During the warranty period, If any part is defective or fails to perform as specified when operating at design conditions, and If the equipment has been installed and Is
being operated and maintained in accordance with the written Instructions provided by Blo-Microbics, Inc., Blo-Microbics, Inc. will repair or replace at Its discretion such
defective parts free of charge. Defective parts must be returned by owner to Blo-Microblcs, inc.'s factory postage paid, If so requested. The cost of labor and all other
expenses resulting from replacement of the defective parts and from Installation of parts furnished under this warranty and regular maintenance Items such as
filters or bulbs shall be bome by the owner. This warranty does not cover general system misuse, aerator components which have been damaged by flooding or any DO NOT SCALE
componenis that have been disassembled Iy unauthorized persons, improperly Installed or damaged due fo altered or improper wiring or overload protection.
This warranty apples only to the treatment plant and does not Include any of the structure wiring, plumbing, drainage, septic tank or disposal system. BIo-Mlcrobics, Inc. UNLESS NOTED uEb��w
reserves the righttorevise,change ormodifythe construcfion and/ordeDIMENSIONStomake such changes or modiftcatians in present equipment. Blo-Mico,qenaorncdental damages of any nature resulting fromsuch thingsas,butnotlimited to,defectin design,material,orworkmanshipor delays In deriveryrelacements oiARE IN INCHES
THIS WARRANTY IS IN LIEU OF ALL OTHER WARRANTIES EXPRESS OR IMPLIED. BIO MICROBICS SPECIFICALLY DISCLAIMS ANY IMPLIED [CENTIMETERS] BETTER WATER. BETTER WORLD'
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. TOLERANCES
NO REPRESENTATIVE OR PERSON IS AUTHORIZED TO GIVE ANY OTHER WARRANTY OR TO ASSUME FOR BIO-MICROBICS, INC., ANY ± 0.02 IN/IN
OTHER LIABILITY IN CONNECTION WITH THE SALE OF ITS PRODUCTS. Contact your local distributor for parts and service. [+ 0.05 CM/CM] MicroFAST 0.50 FAST Unit
WCICiMI Ib SQE �:DRAWINGNUMBERTHE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF BIO-MICROBICS INC. ANY REPRODUCTION IN PART OR AS A NAME DATEA STO 0.50 S ecifications SHEET
WHOLE WITHOUT THE WRITTEN PERMISSION OF BIO MICROBICS INC. IS PROHIBITED. DESIGN AND INVENTION RIGHTS ARE RESERVED. IN THE BIO-MICROBICS ©2014 DRAWN cTc Ip�1e/2oo6 p
INTEREST OF TECHNOLOGICAL ADVANCEMENT, ALL PRODUCTS ARE SUBJECT TO DESIGN AND OR MATERIAL CHANGE WITHOUT NOTICE. 130F4
LV
6
[1
Minimum leg extension assembly
see note 1-4
screws
er side
Icluded
FAST@ Vent Option
j//j
I l �j
���
Alternate Air Supply
Non-corros
every 2 fee
NDS Grate MIN 7 in
SQ [45 cm SQ] of
open surface area
Fasten with non- O 12" MIN
corrosive screws [30.5 MIN]
Non -corrosive
every 2 feet 10,
DETAIL
SCALE 1 : 5
DETAIL
SCALE 1:4
Notes
1. Secure leg extension to the FAST@ unit by placing two screws on each side of the leg extension (4 screws per foot are
included).
2. Cut 4" schd. 40 PVC pipe (not included) to obtain the desired height. Minimum pipe length of 6 1/8" 115.56cm] will
provide minimum clearance of 10". For heights greater than 18" [45.7cm] use schd. 80 PVC pipe (not included).
Consult factory for extending leg beyond 36"[90 cm].
3. Anchor the leg extensions to the tank with non -corrosive hardware (not included) at the provided mounting points.
4. If less than the specified minimums are considered necessary, consult factory for guidance.
5. The air supply line into the FAST@ unit must be secured to prevent vibration induced damage. The air supply line should
be secured with a non -corrosive clamp every 2ft [0.6m] minimum.
6. Tank, anchors, piping conduit, blower, housing pad and vents are provided by others.
THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF BIO•MICROBICS INC. ANY REPRODUCTION IN PART OR AS A
WHOLE WITHOUT THE WRITTEN PERMISSION OF BIO-MICROBICS INC. IS PROHIBITED. DESIGN AND INVENTION RIGHTS ARE RESERVED. IN THE BIO-MICROBICS ©2014
INTEREST OF TECHNOLOGICAL ADVANCEMENT, ALL PRODUCTS ARE SUBJECT TO DESIGN AND OR MATERIAL CHANGE WITHOUT NOTICE.
FAST@ Air Lift
2" Air
Supply
Line
FAST@ Air Lift
Ifs �I
DO NOT SCALE
UNLESS NOTED
DIMENSIONS
ARE IN INCHES
[CENTIMETERS]
TOLERANCES
ETBETTER WATER. BTER WORLD'
± 0.02 IN/IN
[± 0.05 CM/CM]
MicroFAST 0.50 FAST Unit
(EIGHT
Ib
SIZE
DRAWING NUMBER
NAME
F DATE
A
MicroFAST@ 0.50 Details
140F4
SHEET
RAWN CTC