SAINT LUCIE COUNTY FIRE DISTRICT
UMY PLAN REVIEW FORM
5160 N.W. Milner Drive
N Port Saint Lucie, FL 34983
x x Telephone:772-621-3322
9FUI Fax: 772-621-3604
Web Address: www.slcfd.com
fi
Building Dept. Saint Lucie County FMO Permit # B-13-44
Project Name River Park, Unit 3/ New Life Counseling Center BLDG Permit # 1211-0272
Address 887 East Prima Vista Blvd., Unit 3 City Port Saint Lucie
Contractor I Richie the Roofer
Address 8004 Georges Road City Fort Pierce
State Florida Zip 34950 Telephone 772.473.6197
Architect/Engineer Raymond Chladny Telephone 772.631.5709
Occupancy Type Assembly <300 Construction Type VB Square Feet 3292
Occupant Load 194 per plan Number of Stories F Access Box Access Key Switch
AFS Permit FA Permit FFP Permit
General Notes
1. An electronic copy of the construction documents submitted on a CD is required. The file format shall be .pdf only.
2. All revisions, including the electronic copy must be received prior to permitting.
3. The Fire Marshal requires 24 hour notice on all inspections.
4. The respective Building Department shall schedule all final inspections through the Fire Marshal's Office.
S. Failed inspections require payment of fee prior to rescheduling of further inspections.
6. Penetrations through rated assemblies shall be of the proper UL design. Design criteria shall be submitted with the construction plans.
7. Fire alarm panels shall be located indoors within air conditioned space.
8. Plans and construction are subject to corrections in the field to maintain code compliance.
9. Automatic fan shutdown is required for HVAC system/s that exceed 2,000 cfm design capacity.
10. The Installation or Alteration of Fire Sprinklers, Fire Alarms, and Fixed Fire Protection Systems require a separate review and permit.
THE FLORIDA FIRE PREVENTION CODE, 2010 EDITION IS CURRENTLY ENFORCED.
BUILDINGS WITH LIGHT -FRAME TRUSS -TYPE CONSTRUCTION SHALL BE MARKED WITH APPROVED FIREFIGHTER SAFETY
WARNING SIGNS IN ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODES 69A-3.012 AND 69A-60.0081 PRIOR TO RECEIVING
A CERTIFICATE OF OCCUPANCY.
See General Notes Above and Required Revisions Below
1. The doors located in the corridor shall swing in the direction of egress. One door is indicated to meet this criteria the other is
not.
f The 1-hr rated exit access corridor requires the door and jamb assemblies located in the rated wall to have a minimum of a 20
minute rating. In addition, the doors shall be equipped with self -closing devices.
3. The doors located in the gathering room shall swing in the direction of egress.
PageF1 of I2 Reviewed by T. Liento Date 01-31-2013
s-
Page' of [2 Reviewed by T.L'ient0 Date F01-31-2013