HomeMy WebLinkAboutPROJECT INFORMATION,. -- wrightsofte 317 ST. LUCIE LN., FT. Pro`ect hum' ma Job: SCANNED Da Entire House Byte. BY St Lucie County QUICK CALCS, INC. 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@OL.COM. For: WYNNE DEVELOPMENT THE WINDSOR, FT. PIERCE, FL Notes: Design Information Weather: Fort Pierce, FL, US Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside.db 75 OF Design TD 28 OF Design TD 15 OF Daily range L Relative humidity 50 % Moisture difference 61 gr/ib Heating Summary Sensible Cooling Equipment Load Sizing Structure 18467 Btuh Structure 17655 Btuh Ducts 6190 Btuh Ducts 9340 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh (none) (none) Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 24657 Btuh Use manufacturer's data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 25645 Btuh Method Simplified Latent Cooling Equipment Load Sizing Construction quality Average Fireplaces 0 Structure 2453 Btuh Ducts 2554 Btuh Central vent (0 cfm) 0 Btuh Heatingg Coolin (none) Area (ft') 1753 17 Equipment latent load 5007 Btuh VOlume (ft3) 14741 14741 Air changesthour 0.38 0.20 Equipment total load 30652 Btuh Equiv. AVF (cfm) 93 49 Req. total capacity at 0.70 S H R 3.1 ton Heating Equipment Summary- Cooling Equipment Summary - Make Carrier Make Carrier Trade CARRIER AIR CONDITIONING Trade CARRIER AIR CONDITIONING Model 25HBC536A*030 Cond 25HBC536A*030 AHRI ref 7914585 Coil FX41)N(B,F)037 AHRl ref 7914585 Efficiency 8.5 HSPF Efficiency 12.0 EER, 15 SEER Heating input Sensible cooling 24360 Btuh Heating output 34600 Btuh @ 470F Latent cooling 10440 Btuh Temperature nse 27 OF Total cooling 34800 Btuh Actual airflow. 1160 cfm Actual. air flow 1160 cfm Air flow factor 0.047 cfm/Btuh Air flow factor 0.043 cfm/Btuh Static pressure 0.50 in H2O Static pressure 0.50 in H2O Space thermostat Load sensible heat ratio 0.84 Capacity balance point = 34 OF Backup: Input = 7 kW, Output = 23009 Btuh, 100 AFUE Calculations approved byACCA to meet all requirements of Manual J 8th Ed. _,, + Wrightsoft- 2017-Apr-10 17:19:28 ACM Right -Suite® Universal 2017 17.0.14 RSU08101 Page 1 ...k CalcsWocuments\WYNNE-THE WINDSOR-REVISED.rup Cale = MJ8 Front Door faces: N -t - wriglhtsoft Rig6-A Worksheet Date: Entire House Date: QUICK CALCS, INC. By: 317 ST. LUCIE LN., FT..PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-166-6796 Email: QUICKCALCS AOL.COM 1 Room name Entire House MASTER BEDROOM 2 E)posedwall 153.0 ft 45.0 ft 3 Room height 8.4 ft d 8.0 ft heat/cool 4 Room dimensions 1.0 x 280.0 ft 5 Room area 1753.0 ft' 280.0 ftz Ty Construction U-value Or HTM Area (ftz) Load Area (ft') Load number (BtulVft'L-°F) (Btuh/ftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross WKS Heat Cool Gross N/P/S Heat Cool 6 13A-Aocs 0.143 ; ne 4 00: 2.95 488 44.8 1795 1141 192 192 769 ' 489 1Ac1om 1.270 ne 35 56 70.43 7 0 247. 488 0 0 : 0 0 1Ac16m.: 1.270 . ne 35.56 70.43 16 ' 0 581 : .1151 0 s 0 0 . 0 9Ac1om 1.270 ne 35.56 45.24 16. 0 581 739 0 0. 11 13A4ocs 0.143 se 4.00 2.55 64 41 165 105 0 0 0 0 11130 0.390, se 10.92 11.31 23 23 248 257 0 0 0 0 13A-4ocs 0.149 sw 4.00 2:55 ; . 437 396 1584 . 1007 56 56 224 - 143 :4A52om = 0.770- sw: 2t56 27.53 41 45 893 :1140 0 0. A. 0 V(1 13A4o s 0.143 nw 4.00 2.55 290 217 867 551 112 79 318 202 1Aclom 1.270 nw 35.56 45.24 33 0 1162 1478 33 0 1162 1478 4A5-2omd 0.770 -nw 21.56 36.90 41 0 880 1505 0 0 0 0 P : 12G 0sw 0.091 .- -2.55 1.26 308 308 784 395 0 0 0 0 C 16A-30md 0.032 - 0.90 2.32 1753 1753 1571 4067 280 280 251 650 :F 22A401 . 0:989 - . 27.69 0.00 1753 - .153 ' 4237 0 280 cc)AED eicursion 1360 600 Envelope loss/gain 15594 15385 39701 3561 12 a) Infiltration 2873 810 809 228 b) Room ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 2 460 0 0 Appliances/other 1000 0 Subtotal (lines 6 to 13) 18467 17655 4779 3789 Less wdemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 18467 17655 4779 3789 15 Duct loads 34% 53% 6190 9340 34% 53%1 1602 2005 Total mom load 24657 26995 6380 5794 Air required (cfm) 1160 1160 3DDI 249 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. -F- wrightsexft- 2017-Apr-1017:19:28 AftRight-Suite® Universal 2017 17.0.14 RSU08101 Page 1 ..k Calcs%Documents%WYNNE-THE WINDSOR-REVISED.rup Cale = MJ8 Front Door faces: N = wrightsoft RighimA) Worksheet Date: Entire House QUICK CALCS, INC. By: 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCSIAOL.COM 1 Room name WIC M. BATH 2 Eq3osed wall 0 ft 7.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 7.0 x 9.0 ft 1.0 x 61.0 ft 5 Room area 63.0 ft2 61.0 ft2 Ty Construction U-value Or HTM Area (ft2) Load Area (ft2) Load number (13tuh/ft2L°F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross WP/S Heat Cool Gross WP/S Heat Cool 6 13A 400s 0.143 ,•ne 4:00 2.55 0 0 0 . • 0 .56 49 196 125 1Ac1om : " . 1.270 he' 35.56 70:43 ' 0 0 0 . 0 ' 7 0 . 247 488 1Ac1om : ' . 1.270 ne 35:56, 7043 0 0 0 0 0 0 0 0. 1A�b1om : 1.270 ne 35:56 45.24 0 0 0 .0 0 0. 0 ;. -0 11 VV 13A-4ocs 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 t-D 11130 0.390 se 10..92 11.31 0 0 0 0 0 0 0 0 13A-0ocs = AAQ sw ' 4.00 2:55 , . 0 0 0 _ .0 0 0 : --0 . 0. 4A5 tom • .: 0.770 %sw 21i56 . 27:53 0 0 0 0 0 0 0 0 yJ 13A4ocs 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 1Ac1om 1.270 nw 35.56 45.24 0 0 0 0 0 0 0 0 I�_GG 4A5-2omd 0.770. nw 21.56 36.90 0 0 0 0 0 0 0 0 P ' =12C-0 w, 0.001 - 2:55. , ' 1.28 : 0 .0 0 0 0 0 6 0 C 16A-30md 0.032 - 0.90 2132 63 63 56 146 61 61 55 142 F 22A-tpl: 0.'989 - 27.69 0.00 63 0 0. 0 :61 .7 194 0 6 e)AED oxursion -5 -26 Envelope loss/gain 56 141 692 729 12 a) Infiltration 0 0 126 35 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal pines 6 to 13) 56 141 817 764 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 56 141 817 764 15 Duct loads 1 340/6 53% 19 75 349/6 53% 274 404 Total room load 75 216 1091 1168 Air required (cfm) 4 9 51 50 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. A wrightsoft' Right -Suite@ Universal 2017 17.0.14 RSU08101 2017-Apr-10 1 Page 2 k Calcs\Documents\WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8 Front Door faces: N -- wrightsoft' l Right--J@ Worksheet Entire House QUICK CALCS, INC. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM Job: Date: By: 1 Room name LAUDRY BEDROOM 2 2 Bqposed wall 0 ft 12.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 5 Room dimensions Room area 6.0 x 6.0 ft 36.0 ftz 15.0 x 12.0 ft 180.0 ftZ Ty Construction U-value Or HTM Area 2 Load Art-) Load number (Btuh/ft2L-°F) (Btuh/ftz) or perimeter (ft) (Btuh) ors perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 V�1 �p 13A-4ocs 1A�lorri ' �.1Ao1om .1A-61om 13A4ocs 0.143 1.270 1.270 1.270 0.143 ne, na ne . ne se 4.00 35.56 35.56. 35.56 4.00 . 2.55 70.43 .70.43. 45:24 2.55 • 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 96 0 16 0 0 80 1 0. .0 0 0 819 0, 581' 0 0 203 0 : 1151 0 0 11DO 4 6-2om.: 0.390 0:143 0:770 se : sw'. -sw 10.92 4.00 21.56.. 11,31 2.55 27.53: 0 '. p 0 0 p 0 0 0 0 0 - p '0.. 0 p 0' 0 0 .0 0 p 0. 0 p 0 �-G 13A4ocs 1A-c1om 0.143 1.270 nw nw 4.00 35.56 2.55 45.24 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 �_ G P ; C -0sw 4A5-2omd 12C 16A-30md 0.770 0:091 0.032 nw = - 21.56 2:55 0.90 36.90 128 2.32 0 0 36 0 .0 36 0 0 32 0 0 84 0 0 180 0 0 180 0 .. 0. 161 0 0 418 F . -i 22AAO . - 0.989 . - 27.69 0.06 36 0 0 0 190. 12 332 0 6 c)AED ecursion -3 -60 Envelope loss/gain 32 81 1394 1711 12 a) Infiltration 0 0 216 61 b) Room ventilation 0 0 0 0 13 Intemal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 32 81 1609 1772 Less exfemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 6 14 6 14 14 Subtotal 38 95 1615 1786 15 Duct loads 1 34% 53% 13 .50 349/6 53%j 541 945 Total room load 51 145 2156 2730 Air required (cfm) 121 61 1 101 117 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. A - - wrigFhtsoft- Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-10 1 Page 3 ... k CaicslDocuments%WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8 Front Door faces: N - - vvrightsoft° Right- icy Worksheet Job: Entire House Date: QUICK CALCS, INC. By. 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS a140L.COM 1 Room name DINING/GREAT ROOM KITCHEN 2 F)osed wall 50.0 ft 11.0 ft 3 Room height 8.9 ft heat/cool 8.9 ft heat/cool 4 Room dimensions 1.0 x 588.0 ft 19.0 x 11.0 ft 5 Room area 588.0 ft2 209.0 W Ty Construction U-value Or HTM Area (ft2) Load Area t- Load number (Btuh/ft2--"F) (Btuh/ft2) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A4ogs 0.143 ne 4.00 2.55 0 0 0 0 0. 0 0 0 ;1A-o1om " 1:270 ne 35:56 70.43 0 0 0 0 0 0• :0 0 IN-c1orrf 1.270 ne 35:56 70.43: 0 0 0. 0 0. 0 0 0 1A-c1om 1.270 ne' 35.56 45:24 0 0 0 0 0 0. 0 0 11 V�I 13A-4ocs 0.143 se 4.00 2.55 0 0 0 0 0 0 0 0 � D' 11DQ 0.390 se 10.92 11.31 0 0 0 0 0 0 0 0 W. 13A-4ocs' . 0.143 sw 4.00' 2.55 267 226 903 574 98 98 392 249. L-C 4A5.2om 0:770 'sw 21.56 : 27.53 . 41 22 893 > 1140 0 0 .0 ' - 0 13A4ocs ' 0.143 nw 4.00 2.55 178 137 549 349 0 0 0 0 IA-clom 1.270 nw 35.56 45.24 0 0 0 0 0 0 0 0 4A5.2omd 0.770 nw 21.56 36.90 41 0 880 1505 0 0 0 0 R : ;`12C11sw 0.091 ..- 2:55 1:28 0 0- 07 ' 0 = 116 ' : 116 ` 299 ` 148 C 16A30md 0.032 0.90 2.32 588 688 527 1364 209 209 187 485 F 22A-tpl.`' 0:989 •- : VA 0.00 588 .. 50 1385 '.: ' 0 209.. 11" , 305 < : 0 6 c)AED ecursion 1004 34 Envelope loss/gain 5136 5937 1179 818 12 a) infiltration 1000 282 220 62 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 2 460 0 0 Appliances/other 0 1000 Subtotal pins 6 to 13) 6136 6679 1399 1880 Less e#emal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 6 141 0 0 14 Subtotal 6142 6693 1399 1880 15 Duct loads 34 0 53% 2058 3541 34 0 53%1 469 995 Total room load 8200 10234 1 1 1867 2875 Airrequired (cfm)' 386 440 88 124 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wrightsoft- Right -Suite® Universal 2017 17.0.14 RSU08101 2017-Apr-10 1 Page 4 k Calcs%Documents\WYNNE-THE WINDSOR-REVISED.rup Calc = MJB Front Door faces: N + wrightsoft' Rigl %,,A Worksheet Entire House QUICK CALCS, INC. 1 317 ST. LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@,10L.COM Job: Date: By: 1 Room name BATH HALL 2 3 Erq)osed wall Room height 5.0 ft 8.0 ft heaticool 0 ft 8.0 ft heat/cool 4 5 Room dimensions Room area 10.0 x 5.0 ft 50.0 ft2 5.0 x 5.0 ft 25.0 ftz Ty Construction number U-value (Btuh/ft'L°F) Or HTM (Btuh/ftz Area or 6mete pe O r ft Load (Btuh) Area (ft-) or perimeter (ft) Load) (Btuh Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 W 3A-4ocs 1A 9m 1Aclom 1A�1om-: 13A-4ocs 0.143 1.270 1.276 1.270 0.143 ne ne he ne. se 4 00. 35 56 35.56 35.56 4.00 2.55. 70,43 70.43 45.24 2,55 40. 0 0 0. 0 40 0 0 0 0 160. . 0 0 0 0 102 :0 0 0. 0 0 0 0 0 0 -0 ' :0 .0 0, 0 0 " ' 0 0: 0 0 0 0. 0: 0 0 t-D. Val `G. 11DO 13A4ocs ,: 4P5.26m : ::. 0.390 0:143 0.770 se ; sw -sw 10.92 4 00. 21.56 11.31 Z55 . 27.53 0 0 0 0 0 0 0 01 0 0 0 0 0 0 0 0. 0 . 0 0 -.0, 0. 0 - 0 0 V11 13A4acs IA-c1om 0.143 1.270 nw nw 4.00 35:56 2.55 45.24 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 L�_GG 4A5-2omd 12C-0sw 16A 30md 0.770 6.091 0.032 nw - - 21.56 2.55 0.90 36.90 .1.28 2.32 0 0 50 0 0 50 0 0 45 0 0 116 0 0. 25 0 0 25 0 0 22 0 0 58 P. C F mA tpl 0.989 - 27.69 0.00 50 5 138 : 0 25 0 0- 0 6 c)AED emursion -8 -2 Envelope loss/gain 343 210 22 56 12 a) Infiltration 90 25 0 0 b) Room ventilation 0 0 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 433 235 22 56 Less wdemal load 0 0 0 0 Less.transfer 0 0 0 0 Redistribution 6 14 -22 -56 14 Subtotal 439 249 0 0 15 Duct loads 34% 53% 147 132 34% 53% 0 0 Total room load 586 381 0 0 Air required (cfm) 28 16 0 0 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. �A - wrightsoft' Right -Suite® Universal 201717.0.14 RSUD8101 2017-Apr-10 1 Page 5 k CalcslDocuments%WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8 Front Door faces: N ag - w' rightsoft- Rigl � I ) Worksheet -- Joe: Entire House Date: QUICK CALCS, INC. By. 317 ST LUCIE LN., FT. PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM 1" Room name FOYER BEDROOM 2 Exposed wall 9.0 ft 14.0 ft 3 Room height 8.0 ft heat/cool 8.0 ft heat/cool 4 Room dimensions 1.0 x 920 ft 13.0 x 13.0 ft 5 Room area 92.0 ft2 169.0 fto Ty Construction U-value Or HTM Area (ft Load Area ) Load number (Btuh/ft2 °F) (BtuWftz) or perimeter (ft) (Btuh) or perimeter (ft) (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 13A116cs 0.143 no. 4.00 2:55 0 . 0 0 0 104 88 - 351. 223 MIA-c1om ' " : " 1:270 'rie 35.66 70.43 " 0 0 0 0- 0 0. 0 '0 1Ac1om' 1:270 ne. 35.56 70.43 0 0: 0 0 ,0 :0 0 0; 1Ac.1orn 1.270 ne 35.513 45 24 0 0 "' 0 0 16 6, : 581. .739 11 y/ 13A-4ocs 0.143 se 4.00 2.55 64 41 165 105 0 0 0 0 �D 11D0 0.390 _se 10.92 11.31 23 23 248 257 0 0 0 0 W 13,"p_s , 0.143 sw 4.00 255 8 8 - 32 ; " 20 8 S 37 20 �f AW2om 0:770 ":sw- 21.56' : 27.53 " 0 U . 0 : 0 0 0 0 ` "" 0 V1! 1=0m 0.143 nw 4.00 2.55 0 0 0 0 0 0 0 0 1A�1om 1.270 nw 35.56 45.24 0 0 0 0 0 0 0 0 i�GG 4A5-2omd 0.770 nw 21.56. 36.90 0 0 0 0 0 0 0 0. Pi' 12C-0sw 0.091 • - 2:55 .1.28 88 88 224 113 104 104 265 133 C 16A-30md 0.032 - 0.90 232 92 92 82 213 169 169 151 392 -F 22A-tpl " 0.989 - - 27.69 0.00 92 9 249 0 169, 14 " 388 '" 0 6 c)AF_D excursion -25 -52 Envelope loss/gain 1002 684 1768 1456 12 a) Infiltration . 162 46 252 71 b) Room ventilation 0 01 0 0 13 Internal gains: Occupants @ 230 0 0 0 0 Appliances/other 0 0 Subtotal (lines 6 to 13) 1163 730 2020 . 1527 Less extemal load 0 0 0 0 Less transfer 0 0 0 0 Redistribution 0 0 0 0 14 Subtotal 1163 730 2020 1527 15 Duct loads 1 349/6 53%1 390 386 34o/a 53% 677 808 Total room load 1553 1116 1 2697 2335 Air required (ofm) 73 48 1 127 100 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. wr1gtitsoft- 2017-Apr-10 17:19:28 �� RightSuite® Universal 2017 17.0.14 RSU08101 Page 6 m ...k CaIcs%DOCUents\WYNNE-THE WINDSOR-REVISED.rup' Calc = IVIJ8 Front Door faces: N Job: -�- wrightsoftDuct.System Summary Data: Entire House By: QUICK CALCS, INC. 317 ST. LUCIE LN., FT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM ?-'roject Intormation For: WYNNE DEVELOPMENT THE WINDSOR, FT. PIERCE, FL External static pressure Pressure dosses Available static pressure Supply / return available pressure Lowest friction rate Actual air flow Total effective length (TEL) Heating 0.50 in,H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.273 in/100ft 1160 cfm Cooling 0.50 in H2O 0 in H2O 0.50 in H2O 0.250 / 0.250 in H2O 0.273 in/100ft 1160 cfm 183 ft Supply Branch Detail Table Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk BATH h 586 28 16 0.372 4.0 Ox 0 VIFx 19.5 115.6 st1 BEDROOM 2 c 2730 101 117 0.384 7.0 Ox0 VIFx 115.0 st1 BEDROOM 3 h 2697 127 100 0.353 6.0 Ox0 VIFx .15.0 26.8 115.0 st1 DINING/GREATROOM c 3411 129 147 0.292 7.0 Ox0 VIFx 36.5 135.0 st2 DINING/GREATROOM-B C 3411 129 147 0.371 7.0 Ox0 VIFx 19.9 115.0 st1 DINING/GREAT ROOM-C C 3411 129 147 0.278 7.0 Ox 0 VIFx 44.9 135.0 st2 FOYER h 1553 73 48 0.490 4.0 Ox0 VIFx 7.0 95.0 KITCHEN c 2875 88 124 0.366 6.0 Ox0 VIFx 21.8 115.0 st1 LAUDRY c 145 2 6 0.371 4.0 Ox 0 VIFx 19.9 115.0 st1 M. BATH h 1091 51 50 0.282 6.0 Ox 0 VIFx 42.3 135.0 st2 MASTER BEDROOM h 3190 150 124 0.273 6.0 OxO VIFx 48.4 135.0 st2 MASTER BEDROOM -A h 3190 150 124 0.284 6.0 Ox0 VIFx 40.9 135.0 st2 wlc c 216 4 9 0.292 4.0 Ox0 VIFx 36.0 135.0 st2 Trunk Htg Cig Design Veloc Diam H x W Duct Name Type (cfm) (cfm) FR (fpm) (in) (in) Material Trunk st2 PeakAVF 612 602 0.273 780 12.0 0 x 0 VinlFlx st1 st1 Peak AVF 1087 1112 0.273 796 16.0 0 x 0 VinlFlx .� {J{} . htsoft° 2017-Apr-1017:19:29 AC%" f . 9 Right -Suite® Universal 2017 17.0.14 RSU08101 Page 1 ..k Calcs\Documents\WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8 Front Door faces: N r Name Grille Size (in) Htg (cfm) Clg (cfm)- TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox 0 1160 1160 0 0 0 0 Ox 0 VIFx wri htsofte 2017-Apr-9017:19:29 9 RightSuite® Universal 2017 17.0.14 RSU08101 Page 2 Arm ..k Calcs\Documents\WYNNE-THE WINDSOR-REVISED.rup Calc = MJ8 Front Door faces: N