Please accept the following responses to the comments dated 3/9/2018 from your agency. Response shown on plans
corresponding (if required) to these comments are noted.
Could not complete my review, plans were designed to the 2014 Florida Building Code. Please check all areas of components and
cladding, structural and foundation design.
Response: Plans updated to current code. Refer to sheet A1.00
Product review affidavit on page A1.00 specifies shingle roof, page A2.00, A3.00 specifies metal roofing. Please correct drawings.
See section 107 of the 2017 Florida Building Code.
Response: Product review affidavit has been updated to match drawing
Plans callout shingle roof and metal roof, energy calc specified metal roof. Please correct. See section 107 of the 2017 Florida
Building Code.
Response: Sheet A1.00 Product review affidavit has been updated to match
The signature on the truss engineering is not its original form.
Response: Contractor to provide
*Please furnish truss engineering in duplicate per chapter 8 section R802 subsection R802.1.7.1 of the 2017 Florida Residential
Building Code.
Response: Contractor to provide
*Please furnish a duct plan showing a balanced system, duct size, grill size, and room by room CFMS per 107.2.1 of the 2017
Florida Building Code.
Response: Contractor to provide
*Energy calc's information block at the op of the page are incomplete, see section 405.4.2(1) of the 2017 Florida Energy Code.
Response: Contractor to provide
*Line seven of the energy calc's are incorrect. Multiple types and sizes of glazed openings on plans. Please correct energy calc's
as per section R401.3 of the 2017 Florida Building Code Energy Conservation 511 Edition.
Response: Contractor to provide
*Please submit the energy performance sheets or submit a the NFRC fenestration manufacture certificate for the u-factors and the
SHGC for each glazed opening showing compliance with chapter 4, section 402.1.1 of the 2017 energy code fifth edition.
Response: Contractor to provide
*Please add the cubic volume of the conditioned space to information block containing the square foot information or a letter from
the design profess' ecifying the cubic volume of the conditioned space. See chapter 1 section 107 of the 2017 Florida
Building Co
Respon _ trrM adore of A1.00