NOTICE OF ACCEPTANCE(NOA) www.miamidade.soWecononry
DaVinci Roofseapes, LLC R0
13890 W 101 ST MAR Lp1�
Lenexa, KS 66215
SCOPE: ST. Lucie County, Permitting
This NOA is being issued under the applicable rules and regulations governing the use of construction materials. The
documentation submitted has been reviewed and accepted by Miami -Dade County RER - Product Control Section to be
used'in Miami Dade County and other areas where allowed by the Authority Having Jurisdiction (AHJ).
This NOA shall not be valid after the expiration date stated below. The Miami -Dade County Product Control Section
(in Miami Dade County) and/or the AHJ (in areas other than Miami Dade County) reserve the right to have this
product or material tested for quality assurance purposes. If this product or material fails to perform in the accepted
manner, the manufacturer will incur the expense of such testing and the AHJ may immediately revoke, modify, or
suspend the use of such product or material within their jurisdiction. RER reserves the right to revoke this acceptance,
if it is determined by Miami -Dade County Product Control Section that this product or material fails to meet the
requirements of the applicable building code.
This product is approved as described herein, and has been designed to comply with the Florida Building Code
including the High Velocity Hurricane Zone of the Florida Building Code.
DESCRIPTION: Bellaforte Slate and Bellaforte Shake
LAOELING: Each unit shall bear a permanent label with the manufacturer's name or logo, city, state and following
statement: "Miami -Dade County Product Control Approved", unless otherwise noted herein.
RENEWAL of this NOA,shall be considered after a renewal application has been filed and there has been no change
in the applicable building code negatively affecting the performance of this product.
TERMINATION of this NOA will occur after the expiration date or if there has been a revision or change in the
materials, use, and/or manufacture of the product or process. Misuse of this NOA as an endorsement of any product,
for sales, advertising or any other purposes shall automatically terminate this NOA. Failure to comply with any section
of this NOA shall be cause for termination and removal of NOA.
ADVERTISEMENT: The NOA number preceded by the words Miami -Dade County, Florida, and followed
by tl} e expiration date may be displayed in advertising literature. If any portion of the NOA is displayed, then
it sha1 ll be done in its entirety.
INS ECTION: A copy of this entire NOA shall be provided to the user by the manufacturer or its distributors and
shall 11 be available for inspection at the job site at the request of the Building Official.
Thissrenews and revises NOA# 14-0922.02 consists of pages 1 through 11.
The submitted documentation was reviewed by Alex Tigera. c
•r
1
IAMI-DADE COUNTY
,...• i
s .
File COPY
�1
NOA No. 15-0812.22
Expiration Date: 12/16/19
Approval Date: 12/10/15
Page,1 of 11
ROOFING ASSEMBLY APPROVAL:
Catedory:
Roofing
Sub -Category:
Slate
Materials:
Composite
Deck;Type:
Wood
Maxi'inum Design Pressure:
—112.5 psf
Fire Classification Pressure:
See General Limitation #1
TRADE NAMES OF PRODUCTS MANUFACTURED OR LABELED BY APPLICANT:
Product
Dimensions Test Specifications Product Description
Bellafort6 Slate
Length = 15 '/2" TAS 110
Synthetic Self -Aligning Slate roof tile,
J
Width = 12"
available in all standard colors
offered by
Thickness ='/2" (at butt),
DaVinci Roofscapes, LLC prior to March
ti
3/8" (at tip)
1, 2015.
Bellafort6 Shake
Length = 15 '/2" —16" TAS 110
Synthetic Self -Aligning Shake roofing tile.
Width = 12"
Thickness = 1" average (at
butt), 3/8" (at tip)
Starter Slate
3 '/z" x 11 '/z" TAS 110
Starter Slate for use with Synthetic Self -
Aligning Slate roof tile
Starter Shake
4" x 11 '/2" TAS 110
Starter Shake for use with Synthetic Self -
Aligning Shake roof tile.
F
MANUFACTURING LOCATION:
1. Lenexa, KS
4
EVIDENCE SUBMITTED:
Test Agency
Test Identifier
Test Name/Report
Date
PRI Asphalt Technologies.
DRM-034-02-01
TAS 100
06/20/12
DRM-025-02-01
TAS 125
06/20/12
DRM-037-02-01
TAS 100
08/07/12
DRM-035-02-01
TAS 125
06/18/12
DRM-001-02-01
ASTM G26
09/29/04
DRM-050-02-01
ASTM C 1549
10/06/15
DRM-053-02-01
TAS 100
10/02/15
k
DRM-054-02-01
ASTM D 635, D 1929, D 2843
11/16/15
DRM-155-02-01
TAS 125
10/02/15
DRM-156-02-01
ASTM G 155
DRM-156-02-02
ASTM D 635, D 1929, D 2843
i'.
DRM-154-02-01
ASTM D 638-14
10/07/15
Intertek ETL Semko
3087829
ASTM D 2843
01/25/06
3061879(d)
ASTM D 1929
01/25/06
3061879(b)
ASTM D 635
09/21/05
QAI Laboratories
RJ1956-F
ASTM E 108
06/18/12
MI • ADECOUNTY
NOA No. 15-0812.22
Expiration Date: 12/16/19
Approval Date: 12/10/15
Page, 2 of 11
APPROVED ASSEMBLIES:
E
System A: Bellaforte Slate
Deck Type: Wood, Non -Insulated
Deck` Description: 19/32" or greater plywood or wood plank.
Slope Range: 4": 12" or greater
Maximum Uplift -65 psf (See General Limitation #2)
Deck Attachment:
In accordance with the applicable Building Code; but in no case shall it be less than 8d
annular ring shank nails spaced 6" o.c.
V
Underlayment:
Minimum underlayment shall be an ASTM D 226 Type I felt installed in a double layer
with a minimum 19" side lap and 6" end -laps. Underlayment shall be fastened with
corrosion resistant tin -caps and 12 ga., 1'/4" annular ring -shank nails, spaced 6" o.c. at all
laps and two staggered rows 12" o.c. in the field of the roll, or any Miami -Dade County
Product Control Approved underlayment having a current NOA.
Fire `Oarrier:
Any approved fire barrier having a current NOA. Refer to a current fire directory listing for
fire ratings of this roofing system assembly as well as the location of the fire barrier within
the assembly. See Limitation # 1.
Valleys:
Valley metals shall be a minimum 16" wide. Valley metal shall be set over a minimum 36"
wide sheet of minimum ASTM D 226 Type I1 centered and applied parallel to the valley.
Underlayment shall be fastened to the deck with 12 ga. 1 1/4" long corrosion resistant ring
shank nails at 6" o.c. along each edge. Valley metal shall be centered on the valley over
'
underlayment and fastened to the deck with 12 ga., 1 1/4" long corrosion resistant ring shank
nails at 4" o.c. and 1" from each edge. Valley details shall be in accordance with the
manufacturer's current published literature.
Ridge & Hips:
See DaVinci Roofscapes LLC's published installation manual for details.
Starter:
Install required starter with a 3/" overhang at the;eave. Fasten each starter with four (4)
0.120" x 1 3/" long stainless steel ring shank nails. Nails shall be of sufficient length to
5
penetrate through the sheathing a minimum of 3/16". Starter tiles must be spaced 3/s" —'/2"
apart to allow for thermal expansion.
Metal Panels and
Bellaforte Slate shall be installed in accordance with DaVinci Roofscapes, LLC's current
Accessories:
published installation manual. Bellaforte Slate shall have a maximum 12" exposure and a
minimum 3" offset between courses at the sidelaps. (See Detail `B').
The first course of the Slate should seat directly on the starter tile and begin on the tab first
r
then on top of the tile in the left hand corner. It may be necessary to lift the edge of the left
hand tile to insert the valley of the installed tile underneath.
Bellaforte Slate shall be fastened with five (5) 0.120" x 1 3/" long stainless steel ring shank
nails. Four (4) nails through the pre -marked holes locations imprinted on the slate (see
Detail `B') and one (1) nail through the side tab. Bellafort6 Slate rake trim shall be
installed with a 12" exposure and two (2) 0.120" x 1 3/" long stainless steel ring shank
nails; one (1) nail shall be secured though the deck, and one (1) nail though the fascia.
Nails shall be of sufficient length to penetrate through the sheathing a minimum of 3/16"
MIAMI•DADECOUNTY NOA No. 15-0812.22
. , ... Expiration Date: 12/16/19
Approval Date: 12/10/15
Page 3 of 11
I
System B:
Bellaforte Shake
i
DecK Type:
Wood, Non -Insulated
f
Deck Description:
19/32" or greater plywood or wood plank.
Slope Range:
4": 12" or greater
Maximum Uplift
-80 psf (See General Limitation #2)
Pressure:
Deck, Attachment: In accordance with applicable Building Code, but in no case shall it be less than 8d annular
ring shank nails spaced 6" o.c.
Underlayment: Minimum underlayment shall be an ASTM D 226 Type I felt installed in a double layer
with a minimum 19" side lap and 6" end -laps. Underlayment shall be fastened with
corrosion resistant tin -caps and 12 ga., 1'/4" annular ring -shank nails, spaced 6" o.c. at all
laps and two staggered rows 12" o.c. in the field of the roll, or any Miami -Dade County
Product Control Approved underlayment having a current NOA.
Fire:Barrier: Any approved fire barrier having a current NOA. Refer to a current fire directory listing for
V fire ratings of this roofing system assembly as well as the location of the fire barrier within
^' the assembly. See Limitation # 1.
Valleys: Valley metals shall be a minimum 16" wide. Valley metal shall be set over a minimum 36"
wide sheet of minimum ASTM D 226 Type II centered and applied parallel to the valley.
Underlayment shall be fastened to the deck with 1,2 ga. 1 '/4" long corrosion resistant ring
fshank nails at 6" o.c. along each edge. Valley metal shall be centered on the valley over
underlayment and fastened to the deck with 12 ga., 1 '/4" long corrosion resistant ring shank
nails at 4" o.c. and 1" from each edge. Valley details shall be in accordance with the
manufacturer's current published literature.
Ridge & Hips: See DaVinci Roofscapes LLC's published installation manual for details.
Starter: Install required starter with a 3/4" overhang at the- eave. Fasten each starter with four (4)
i 0.120" x 1 3/4" long stainless steel ring shank nails. Nails shall be of sufficient length to
penetrate through the sheathing a minimum of 3/16". Starter tiles must be spaced 3/a" —'iz"
apart to allow for thermal expansion.
Metal Panels and Bellaforte Shake shall be installed in accordance with DaVinci Roofscapes, LLC's current
Accessories: published installation manual. Bellafort6 Shake shall have a maximum 12" exposure and a
minimum 3" offset between courses at the sidelaps. (See Detail `D').
The first course of the Shake should sit directly on the starter tile and begin on the tab first
then on top of the tile in the left hand corner. It may be necessary to lift the edge of the left
hand tile to insert the valley of the installed tile underneath.
Bellaforte Shake shall be fastened with five (5) 0.120" x 1 3/4" long stainless steel ring
shank nails. Four (4) through the holes locations imprinted on the slate (see Detail `C') and
one(1) through the side tab. Bellaforte Shake rake trim shall be installed with a 12"
exposure and two (2) 0.120" x 1 3/4" long stainless steel ring shank nails; one (1) nail shall
be secured though the deck, and one (1) nail though the fascia. Nails shall be of sufficient
length to penetrate through the sheathing a minimum of 3/16"
NOA No. 15-0812.22
MIAMI•DADE COUNTY
- , ... Expiration Date: 12/16/19
Approval Date: 12/10/15
Page 4 of 11
System C:
Bellaforte Shake
a�.
Deck -Type:
Wood, Non -Insulated
Deck Description:
19/32" or greater plywood or wood plank for new decks, 15/32" for existing decks.
Slope Range:
4": 12" or greater
Maximum Uplift
See Table C Below '
Pressure:
Deck Attachment: In accordance with applicable Building Code, but in no case shall it be less than 8d annular
ring shank nails spaced 6" o.c.
Underlayment: Minimum underlayment shall be an ASTM D 226 Type I felt installed in a double layer
with a minimum 19" side lap and 6" end -laps. Underlayment shall be fastened with
corrosion resistant tin -caps and 12 ga., 1'/4" annular ring -shank nails, spaced 6" o.c. at all
laps and two staggered rows 12" o.c. in the field of the roll, or any Miami -Dade County
z4 Product Control Approved underlayment having a current NOA.
Fire ';Barrier: Any approved fire barrier having a current NOA. Refer to a current fire directory listing for
fire ratings of this roofing system assembly as well as the location of the fire barrier within
the assembly. See Limitation # 1.
Valleys: Valley metals shall be a minimum 16" wide. Valley metal shall be set over a minimum 36"
wide sheet of minimum ASTM D 226 Type II centered and applied parallel to the valley.
Underlayment shall be fastened to the deck with 12 ga. 1 '/4" long corrosion resistant ring
shank nails at 6" o.c. along each edge. Valley metal shall be centered on the valley over
underlayment and fastened to the deck with 12 ga., 1 '/4" long corrosion resistant ring shank
nails at 4" o.c. and 1" from each edge. Valley details shall be in accordance with the
?i manufacturer's current published literature.
r.
Ridge & Hips: See DaVinci Roofscapes LLC's published installation manual for details.
Starter: Install required starter with a 3/4" overhang at the eave. Fasten each starter with four (4)
0.120" x 1 3/4" long stainless steel ring shank nails. Nails shall be of sufficient length to
penetrate through the sheathing a minimum of 3/,6'. Starter tiles must be spaced 3/s" —''/z"
apart to allow for thermal expansion.
Metal Panels and Bellaforte Shake shall be installed in accordance with DaVinci Roofscapes, LLC's current
Accessories: published installation manual. Bellafort6 Shake shall have a maximum 12" exposure and a
minimum 3" offset between courses at the sidelaps (See Detail `D').
The first course of the shake should sit directly on the starter tile and begin on the tab first
then on top of the tile in the left hand corner. It may be necessary to lift the edge of the left
hand tile to insert the valley of the installed tile underneath.
Bellaforte Shake shall be fastened with five (5) 0.120" x 1 3/" long stainless steel ring
shank nails. Four (4) through the holes locations imprinted on the shake (see Detail `C')
and one(1) through the side tab. Bellaforte Shake_ rake trim shall be installed with a 12"
exposure and two (2) 0.120" x 1 3/" long stainless steel ring shank nails; one (1) nail shall
be secured though the deck, and one (1) nail though the fascia. Nails shall be of sufficient
length to penetrate through the sheathing a minimum of 3/16"
NOA No. 15-0812.22
MIAMI•DADE COUNTY= Expiration Date: 12/16/19
Approval Date: 12/10/15
Page 5 of 11
Bellafort6 Shake Perimeter and Corner shall be fastened as above with one (1) additional
#9 x 2" HWH wood screw placed in the split or middle of each shake in line with the nail
tab. (See Detail E).
BELLAFORTE SHAKE
MAXIMUM DESIGN PRESSURES
Roof Areas
Field
Perimeter and Corner'
Maximum Design Pressures
-75 psf
-112.5 psf
Number of Fasteners per panel
5
6
1. Extrapolation shall not be allowed
r
ri
GENERAL LIMITATIONS:
1. Fire classification is not part of this acceptance; refer to a current Approved Roofing Materials Directory for ,fire
ratings of this product.
2. The maximum designed pressure limitation listed shall be applicable to all roof pressure zones (i.e. field,
perimeters, and corners). Neither rational analysis, nor extrapolation shall be permitted for enhanced fastening at
enhanced pressure zones (i.e. perimeters, extended corners and corners).
3. All panels shall be permanently labeled with the manufacturer's name and/or logo, city and state of manufacturing
facility, and the following statement: "Miami -Dade County Product Control Approved" or with the Miami -Dade
bounty Product Control Seal as seen below.
CMIAMI•DADE COUNTY
4. All products listed herein shall have a quality assurance audit in accordance with the Florida Building Code and
Rule 61 G20 3 of the Florida Administrative Code.
Y
f:
i
MIAMI•DADE COUNTY NOA No. 15-0812.22
. , , � Expiration Date: 12/16/19
vj
Approval Date: 12/10/15
Page 6 of 11