Loading...
HomeMy WebLinkAboutSOIL COMPACTION REPORTTRIANGLE TESTING LAB, INC. CoA#3101 4750 ROYAL PALM BEACH BOULEVARD WEST PALM BEACH, FLOR/DA 33411 (561)790-3049 e-mail: triangle2992(a?gmail.com Date: April 30, 2018 To: Palm Beach County Building Department Re: Soil Compaction Report -Density of In -Place Compacted Soil DAN FITZPATRICK — FRONT ATTACHED ADDITION 7003 SOUTH INDIAN RIVER DRIVE FORT PIERCE, FL SCANNED BY St Lucie CcuntY Test Date Test # Test Location Elevation In -Place Readings MMPD Values % Densit Moisture—' Densit Moisture 04/26/18 1 Southeast Area 1'-2' 105.6 4.1 109.5 5.6 96.4 04/26/18 2 Center Area 0-1' 104.5 3.5 109.5 5.6 95.4 04/26/18 3 Northwest Area 1'-2' 105.4 3.6 109.5 5.6 96.3 Remarks: All elevations are measured from top of pad grade. . (Mod Proctor Test #1) Verification Statement This statement shall serve as verification that the soil beneath the proposed structure has been tested in accordance with Section R401.4 of the 2017 Florida Building Code, Residential edition. The tests were conducted from the existing grade. Density tests were taken at a minimum of three (3) locations throughout the total depth of fill. The depth of fill was approximately 1_5 feet. The foundation setbacks were based on information furnished by the client, at the time of testing. Based on the location and depths tested, we verify that the fill has been compacted to a minimum of 95% of the maximum dry density as determined by ASTM D-1557 and that the minimum soil bearing value beneath the proposed foundation area is 2,500 pounds per square foot, 130 Respectfully submitted, ••• T ', G F�. 42485 Richard Boyette, FL PE #4248q Vice President STATE� OF ; � April 30, 2018 �� OR�pP File # 20819