HomeMy WebLinkAboutENGINEERING- FLOOR SUPPORT ANALYSISFDN Engineering, LLC GGANNP-D
By
�t
Date:
October 6, 2022
Project:
Fitzsimmons Residence
Address:
4201 Sunrise Blvd
Fort Pierce, FL 34982
Floor Support Analysis - Completion Report
This report is prepared for LRE Foundation Repair (contractor) by FDN Engineering (engineer). Floor support
jacks (SmartJacks) were installed at the above referenced project. The support system is intended to stabilize
and potentially lift the existing floor structure - reducing deflections In the floor and reducing pressure on
existing soils. The original design instructed the contractor to install footings, Smartlacks, supplemental
support girders and all related components per the support manufacturer's installation instructions and
according to their technical specifications, as well as industry standards. See original engineering report for
the design and details of the floor support system. See page 2 for the field logs provided by the contractor.
See page 3 for a layout of the floor supports as identified by contractor on the field log.
The installation of the supports was visually inspected by engineer, and the contractor has supplied engineer
a written log of the installed support locations and measured lift. Upon review, the installed support jacks
conform to the original design and plans.
To the best of my professional knowledge and belief, the design of the floor support system meets the
structural requirements of the 2020 Florida Building Code, Seventh Edition to the extent that it applies to our
scope of work.
This item has been digitally signed and sealed by Chad A. Keller, P.E. on the
date adjacent to the seal.
Printed copies of this document are not considered signed and sealed and
* ; No. 70316 : * the signature must be verified on any electronic copies.
* = 2022.10.06 13:05:41-05'00'
.p : STATE OF 1
/O�NA%-�
FDN Engineering, LLC
2412 N 179th St.
Omaha, NE 68116
(402) 739-9642
Page 1 of 3
off, d« 3 - C�/ / VDI
FDN Engineering, LLC
CRAWLSPACE INSTALLATION LOG
FOREMAN: DATE: -'--- r-91 �a J08 #: Q JOB NAME: / , Z
ns
SMARTJACKS
SMARTJACK #
i
LIFT: '/Ir _
SMARTJACK #
$
LIFT: 1
SMARTJACK #
cQ
/
LIFT:
SMARTJACK #
f
LIFT: 1!- l�
SMARTJACK #
?J
LIFT: I&
SMARTJACK #
tb
LIFT: I I(,
SMARTJACK#
4
LIFT: f��
SMARTJACK#
LIFT:
SMARTJACK#
5
LIFT: 116
SMARTJACK#
LIFT: 1�fb
SMARTJACK #
t;
LIFT: ��O
SMARTJACK #
t 3
1
LIFT : f f6
SMARTJACK #
LIFT: J,6
SMARTJACK
#
LIFT:
SMARTJACK FOOTER
POURED CONCRETE:
J 3 CRUSHED STONE: . CONCRETE PADS:
CLEANSPACE
SQ. FT. CLEANSPACE: DUHUMIDIFYER USED:
WOOD REPLACEMENT
TYPE OF WOOD USED: BOARD FT. WOOD REPLACEMENT:
SQ. FT SUBFLOOR REPLACED: HOW MANY PLY:
NOTES:
The above information is the field logs provided by the contractor.
FDN Engineering. LLC
2412 N 179th St.
Omaha, NE 68116
(402)739-9642
Maui u
* ; No. 70316 ;
.o STATE OF ;°o:L-
Ov
lit
fillN
October 6, 2022
This item has been digitally signed and sealed by
Chad A. Keller, P.E. on the date adjacent to the seal.
Printed copies of this document are not
considered signed and sealed and the signature
must be verified on any electronic copies.
Page 2 of 3
o+-�A V1_)-Ur51
Notes:
1 l 1. Shown below is the as -built layout of
supports per contractor's field log.
I! I
l i I I I I I I
I�
���
��l
I I
i�
i��
i
(—;—�
l�
I
i i►
i
�—
1
1
1
!--
l l l l► i
I I I I I I_
f
i►
i
i -�`
I
l
l i
i
l
f
I t
DRAWING NOT TO SCALE
rolect.
FDN Engineering, LLC
.......
j......
.
f
.�°�G?\C EHSE �F,fj%,,
This item has been digitally signed and
sealed by Chad A. Keller, P.E. on the date
Fitzsimmons Residence
2412 N 179th St.
° +r No. 70316 t -Si
adjacent to the seal.
4201 Sunrise Blvd
Omaha, NE 68116
STATE OF � � ;
Fort Pierce, FL 34982
(402) 739-9642
=?p •., F
' <`
Printed copies of this document are not
considered signed and sealed and the signature
must be verified on any electronic copies.
Page 3 of 3
October 6, 2ozz
.93�:. .$dx^,:4'. n:r+D JS..-'j( 'W ik'Y3w'+ .^ffh:.. Jrz.m:i.: ef""-%f.. nf'-. ":.Yy »i?r `kil v. 31:."..SKL�'• .••���.
SmartJack Project Assumptions (contractor to confirm assumptions):
1. Structure is two-story, single family residential with wood -frame floors.
2. Soil bearing pressure at the site is a minimum of 2,000 psf.
3. Smartlack model size 288 is specified.
4. Smartlacks and supplemental girders assumed to support interior load -bearing walls or columns.
5. Contractor will install footings, Smartlacks, supplemental girders and all related components per the
support manufacturer's installation instructions and according to their technical specs.
6. Contractor to select support base that adequately transfers load from Smardack to soil.
7. Supplemental support girders are restrained against lateral rotation at an interval equal to or less
than the Smartlack spacing.
8. Smartlacks supporting existing girders are not spaced farther than the original/existing supports; and
the existing girder/joist's condition is adequate to support the new compression load.
9. Supports are not placed on sinkholes.
10. The design assumes the original structure was constructed of conventional means and methods.
11. Where supplemental girders are specified, use S4x7.7 ASTM Gr. 50 (or equal).
Smartlack Analysis Notes and Results:
12. Interior floor load is assumed to not exceed 55 psf nominal load (15 psf DL + 40 psf LL), per Code.
13. SmartJacks are designed to support axial compression load only; with a max height of 9'-0".
14. Maximum total load on Smart.lack is 7,700 Ibs.
15. Smardack spacing along the supported girder (or tributary length) shall not exceed 6'-0" O.C.
FDN Engineering, LLC
2412 N 179th St.
Omaha, NE 68116
(402) 739-9642
`vtntrninrgriq
* ; No. 70316
.p �. STATE OF : 4
:rC0RIQA�G��;���
,",
sS1OrNAL0
August 12, 2022
This item has been digitally signed and sealed by
Chad A. Keller, P.E. on the date adjacent to the seal.
Printed copies of this document are not
considered signed and sealed and the signature
must be verified on any electronic copies.
Page 2 of 5
FDN Engineering, LLC
d errs^UiC3-r
Wood Screw
01 1" All -Thread Rod
FDN Engineering, LLC
2412 N 179th St.
Omaha, NE 68116
(402) 739-9642
Base (Varies)
Note:
See manufacturer's specifications for more
information regarding the post, top bracket
and base plate's material and capacities.
Existing Wood Girder
or New Wood Beam
Top Plate Bracket (Varies)
Threaded Post Cap
3.50" Square Tube Post
(Field Cut to Length)
Base Support
(Varies)
General SmartJack Detail
Shown with Top Plate for Wood Attachment
(See Following Page for Acceptable Variations)
��CENSf��F;P
* , No. 70316
STATE OF ;
WN A t ti 0���`.
August 12, 2022
1
This item has been digitally signed and sealed by
Chad A. Keller, P.E. on the date adjacent to the seal.
Printed copies of this document are not
considered signed and sealed and the signature
must be verified on any electronic copies.
Page 3 of 5
ybk C�V5—U / 6 /
FDN Engineering,
All below variations shown are structurally acceptable and may be used at the contractor's
discretion based on field conditions.
0�" Bolts
with Nuts —k I i— Splice Plate
Butt Joint 84x7.7 Beam
(Direct Contact within 1" of Bracket Center) (Both Sides of Bracket)
Threaded Post Cap
01 4" All -Thread Rod
3.50" Sq. Post
(Field Cut to Length)
Splice Bracket with New
S4x7.7 Supplemental Beam
6" Base Plate
C-Bracket—"
01 4" All -Thread Rod
S4x7.7 Beam
(Continuous over Support)
Threaded Post Cap
3.50" Sq. Post
(Field Cut to Length)
C-Bracket with S4x7.7
Supplemental Beam
--3.50" SmartJack
36x36x12" Concrete
U ; ' a Footing (3,000psi
28-Day Strength)
(4) #4 Each Way
Base Plate with CIP Footing
* ; No. 7031 ti This item has been digitally signed and sealed by
_ * = Chad A. Keller, P.E. on the date adjacent to the seal.
�-o STATE OF
FDN E �=
ngineering, LLC ' �'•. Printed copies of this document are not
%2412 N 179th St. '%,DES CAA ` considered signed and sealed and the signature
Omaha, NE 68116 '''��rlrlllllll",``must be verified on any electronic copies.
(402) 739-9642 August 12, 2022
Page 4 of 5
LEGEND:
# •Indicates SmartJack
and Mark Number
Existing Pier
-----•--• Existing Girder
�• Supplemental Girder
Revised 8/12/2022
1 Changed Locations of Supports and
Added a Steel Supplemental Girder.
Smartlack Notes:
1. Residential construction, two-story.
2. Layout of (13) Smardacks Model 350 for
floor support at W-0" O.C., max.
3. Install per SmartJack manufacturer's
instructions and technical specifications.
4. Notify engineer if design assumptions are
discovered inaccurate.
<,:.
..............
........ }:r ...... -... }: xO:Y .. .. ,fi''..y.... ..In:if:;...........
l ..........Ir:�:.1.......... M:i: ) .........1�:{.1. ....... -,yj�.?s
1 2
Z
--•Supplemental Girder
3 AMIL
4 5 6 7 8 9
....... i'....... ........... IFr: l a;Y Yt.
.L'.
............fA:i:i,.... . . .h.. . k:�:.. .V"'I-...........
10 11 12
GARAGEr4�ii -- ------------- ------------- ...... a .. ............. 5i-mr ...........
13
FRONT PORCH <:<,:, ............ ----.... .. T ----
FOOTPRINT OF
RESIDENCE
,WING NOT TO SCALE
PrOleCt.
�.""`�A;f""'', This item has been digitally signed and
Cj P�ic sf� F
FDN Engineering, LLC
e sealed by Chad A. Keller P.E. on the date
Fitzsimmons Residence
2412 N 179th St.
_ *,' No.7031s ; *" adjacent tathe seal.
4201 Sunrise Blvd
Omaha, NE 68116
= ':
Fort Pierce, FL 34982
(402) 739-9642
srarE of Printed copies of this document are not
F�aR��p.: `a0V
''�,,SS/ONAL�aG� �` signed and
must beconsidered
verified an any elect one copiesthe .
August 12, 2022 Page 5 of 5