HomeMy WebLinkAboutPLAN & PROPOSED WORKCONTRACTOR: Master Craft Alu,,3��.Ln DESIGN CRITERIA: Applicable Codes, Regulations, and Standards 1. The 6th Edition (2017) Florida Building Code, specifically Chapter 16 Structural Design, Chapter 20 Aluminum, and Chapter 23 Wood. 2. AA ASM 35 and AA ADMI Specifications for Aluminum Structures, Part 1-A of the Aluminum Design Manual prepared by The Aluminum Association. and the AAF Guide to Aluminum Construction in High Wind Areas. 3. ASCE 7-10. Loading Criteria 1. Live Load: 10 PSF per 6th Edition (2017) Florida Building Code, Appendix I Section 105.1 2. Dead Load: 2 PSF 3. Wind Load: 3.1. Building Occupancy Category, Section 1604.5 and Table 1604.5: Risk Category 1. 3.2. Basic Wind Speed, Figure 1609.3(3), State of Florida Debris Region & Basic Wind Speed, Section 1609.3.1 and Table 1609.3.1 Equivalent Basic Wind Speed: V-T =150 MPH, V- =116 MPH 3.3. Exposure Category, Section 1609.4.3: Exposure C 3.4. Screen Enclosure Section 2002.4 4. Building Category for Aluminum Structures, Section 2002.6: Category Type 1- Screen Room: Non -Habitable, Unconditioned Roof Type 1. Roof Type: MONOSLOPE 2. Roof Material: 3" x 48"--x 0:024"-Elite 2000 Composite-Panel,4.0 # density foam, Florida Product Approval Number FL 7561-R4. Foundation Design Existing concrete. No additional concrete footing or slab is reauired to resist the loads imposed by the proposed construction if the existing slab is a minimum 4" thick with an 8" x 8" thickened slab edge and in sound condition, free from structural cracking,'spalling, or other deterioration. Specifications The following specifications are applicable to this project: 1. All work shall be in accordance with the 6th Edition (2017) Florida Building Code, and any other applicable local codes and regulations. 2. Aluminum extrusions shall be 6005 T5 Alloy. Due to quality control issues, no manufacturer substitution is acceptable without the specific written, signed and sealed authorization of Suncoast Aluminum Engineering, LLC. 3. Screen Material: Design based on 18/14 or 20/20 Better View. Any other material must be approved. 4. Fasteners are required to be corrosion resistant, minimum SAE Grade 2 or better zinc plated to ASTM B633, or coated stainless steel series "300", or uncoated stainless steel series "400". 5. All Self Mating Beam Sections are to be stitched with either #14 screws 6" from ends and 24" center to center or # 12 screws 6" from ends and 12" center to center. 6. Where concrete specifications are required, whether in the screen enclosure scope or not, by one or more regulatory agency, the following specifications are applicable: a. Concrete shall conform to ASTM C94 for the following components: i. Portland Cement Type 1,- ASTM C 150 ii. Aggregates - Large Aggregate 3/4" max - ASTM C 33 iii. Air entraining +/- l% - ASTM C 260 iv. Water reducing agent - ASTM C 494 v. Clean Potable water vi. Other admixtures not permitted b. Metal accessories shall conform to: i. Reinforcing Bars - ASTM A615, grade 60 ii. Welded wire fabric - ASTM A185 c. Concrete slump at discharge chute not less than 3" or more than 5". Water added after batching is not permitted. d. Prepare and place concrete per American Concrete Institute Manual of Standard Practice, Parts 1, 2, and 3 including hot weather recommendations: e. Moist cure or polyethylene curing permitted. f. Prior to placing concrete, treat the entire subsurface area for termites in compliance with the FBC. g. Concrete shall be placed over a polyethylene vapor barrier. h. All aluminum components embedded within concrete shall be coated with a bituminous paint or epoxy. 7. All flashing and weatherproofing shall be provided by the contractor. 8. Door location shall be determined by contractor in the field. 9. Use of these plans acknowledges and accepts a limit of liability not to exceed design and engineering fee. WIND SPEED AND EXPOSURE HAVE BEEN DETERMH U7' iING THE ADVANCED TECHNOLOGY CQ'__ , + 'S WEBSITE AND GOOGLE EARTH. CONCEALED FASTENERS OR A17ACHMENTS ARE THE RESPONSIBILITY OF THE CONTRACTOR OF RECORD 3X3X0.070 17 X N ,90ANNF-0 BY St Dacia COUMY ELITE 2000 COMPOSITE PANEL• (FPA:FL7561-R4) 150MPH/EXP C 3"x48%0.024" (1.0# DENSITY FOAM) MAX SPAN: q-q = 11'-3?" THESE PLAN: AND ALL PROPOSED WORK ARE SUBJECT t O yAN't COI�`r't,�, I IQIlS REQUIRED RY FiE-l_0 INOW TORS THAT MAY BE NE;CESSA„W lid ORDPR'11 �2X8SMB 4TH WALL 2X3 2X3 END END BEAM BEAM 3"X48"XO.024" 1.0#DENSITY FOAM COMPOSITE PANEL BEAM "--4 6'-6j" 14'-0" 3"X48"XO.024" COMPOSITE PANEL 0 0 X X X M 2X3 2X3 IF ST. LUCIE COUNTY BUILDING DIVISION nF-VIr-VY2D FOR COM>PLIA ' REVIEWED BY j ' DATE i PLANS AND PER IT MUST BE KEPT ON JOB OR NO INSPECTION WILL 02 MADS iOrII) b 3X3X0.070 XX MX 3X3X0.070M O N X X3X0.07OO 1X30B 1X308 C B A-2 A-2 6'-6J" 6'-6J" 7'-6" \�lllllll/!!/ Qcv) LL y; Co O J= = 0- wCD LLJ Q - Q O. N�.> Z rn tC'' Q` �'� • C PROFESSIONAL SEAL CC O w w U d d W PC �m �o 62 LL g W V W Q m W CEO °'� �C W �z Oz �z Qz Z X� O� W H LL Cc N N W t]C J J W a W� CM } J J mLO ZCOO! m v Qccoo0J G. v co a LL. DRAWN BY CD DATE DRAWN 01/15/18 SHEET NO: A-1 ALUMINUM MEMBERS DIlVI `1 3NS - i t t / / ///f f 1 l \�� SECTIONS HOLLOW 2 2: 2" 2" 0.046" x x x 2x3: 2"x3"x0.050" . �ri,.•/��i \ 2 x 4: 2" x 4" x 0.050" 2' 2 x 5: 2" x 5" x 0.050" Q, co et o OPEN BACK SECTIONS ; LU W Q ZE C) • _ 2 1 x 2: 1" x 2" x 0.040" 0 Nam, � I x 3: 1" x 3" x 0.045" > ��: SNAP SECTIONS I I I I • • ... �i� �i� 2 x 2 Snap: 2" x 2".x 0.045" ISI .. . ... 2 x 3 Snap: 2" x 3" x 0.050" I I I I �j� `� p ��� 2 x 4 Snap: 2" x 4" x 0.045" 3X3X0.070 // // 1 PRUd Sod L SEAL SELF MATING (SMB) I j CHAIR RAIL MEMBER I I 2 x 4 SMB: 2" x 4" x 0.044" x 0. 100" I I 2 x 5 SMB: 2" x 5" x 0.050" x 0.100" I I ❑ 2 x 6 SMB: 2" x 6" x 0.050" x 0. 120" I I 2x7SMB:2"xT'x0.057"x0.120" 2"x2"x3"x1/8"ALUMANGLE 1" x 3" OB W/ 1/4"CONCRETE I I EACH SIDE OF UPRIGHT — — — — — I I K Lu Lii 2 x 8 SMB: 2" x 8" x 0.072" x 0.124" I I SCREW ANCHOR 6`' FROM I I W/3/8" DIA. x 3"CONCRETE I � a a 2 x 9 SMB: 2" x 9" x 0.072" x 0.124" 2 x 10 SUB: 2" x 10" x 0.092" x 0.398" UPRIGHT & AT 24" O.C. I I ANCHORS ON EACH SIDE (MIN. 2 3/4" EMBED.) (3) #12 x 3/4" SMS SCREWS 2" x 2" x 1/8" x 3" LONG ANGLE W/ (3) #14 x 3/4" W MI1M4UM FASTENER EDGE DISTANCE: 1/2" — — — I I — — — — — EACH FLANGE I I 3 x UPRIGHT I,L �y e MEMAUM FASTENER SPACING: 3/4" — — n — — — I I am J m a a c 4 I I —+'z CONCRETE SCREW ANCHOR: a a Asa d Lu toz 0 SR,4PSON TITEN HD OR EQUIVALENT <6: N �z Qz SHEET METAL SCREWS (SMS): : n a C7 u 'ci ITW / BUILDER OR EQUIVALENT , : ° ' „6 ° • a'm o ' ' • , ; .. . ' Z W = 0 H LL OC LL C B CHAIR RAIL TO UPRIGHT DETAIL 3" x 3" POST TO DECK CONNECTION DETAILS A_2 SCALE: NTS Z A-2 SCALE: NTS J v a ? J J � g WOO N � � #14 x 5 7/8" SMS W/ ui Q W� I= z LL 3 1 1/2" DIA. NEOPRENE FACED WASHER @ 8" O.C. ri 0 u Z ^^ a cm ^ c 1/8"x2"xTEXTRUDED I • • (4) #14 x 3/4"SMS '� �::�: x 0062 3" ." ALUM asx a� Z oae = Z u� o ANGLE 5052 H-32 ALLOY • • INTO DJ �i4 ; hKtg p,, ti RECEIVING CHANNEL �' �p�a�T� " N) Lu W/ #10 x 3/4" TOP AND �'s� = «- ;��' •e•�pr,,mjt cSwa°*yz ,f: BOTTOM AS END CAP_r�c��:��'a�'`'•`°'" #14 x 4 7/&' SMS W/ ,.• ' : : p^:;fa1 ?F..H, £ 1 1/2" DIA. NEOPRENE FLASHING `, �• , . nc3 •� 3" COMPOSITE PANEL FACED WASHER @ 8" O.C. 21M MINCONC SLAB / FOOTING S a • , , ANCHOR EMBEDMENT W COMPOSITE ROOF PANEL SEE PLAN °� 2" x 3" x 0.070" TOP RAIL - a • „� ' NO ANGLE REQUIRED s ?' s �,• e a UNLESS SPLICED OR III; II CORNER-ATTACHLILI a.; ti i iS`w��'� 4" W/ (4) #10 x 4" LG ^` Wiz. Yr,ors (� SIDE VIEW II I# x <K ''�°s 3" x 3" x 0.070" • 1 § W UPRIGHT 2" x 3" x 0.070 • I EXISTING Q W U = END BEAM • BUILDING m 2" x V. x 0.070" _ —^ — — N W W 1 3/8" DIA CONCRETE () SCREWANCHORS I I UPRIGHT TOP RAIL W/?; rk ; ,o , . 4.>x *sn -raar_p+2n,s�.� 'sow} asp �+r-r (4)#10x4"SMS 't;''',�i,�"• ara k s ,, • 'rKa' g•.�r.,,, a. 3r•: ~`" F �'�'� "' �' ' I 1 1/8" x 21/8" x1 1/8" x 0.050 I co Lo 0 W_ � Lr (21/4" CONC. EMBED) I PRE -HUNG INTO POST w � d = n fix.: s 4$ v; ;''� :f g Vs t ALUM RECEIVING CHANNEL I c 0 t DOORJAMB <' � teE ma: {-` >,§ e'�.:, a sg"y4N aaxs?y; t.a a.•=2`: EACH I a U GGo J Cl) 0_ LL t .• && �s �. :•'L?e:..x: 2"x2"x3"LG� `�_ ••_ �r4. • 2"x2"x3"LG� �_ SIDE SIDE OF BEAM &(2)3/8 DIA I I x 1/8" ANGLE x 1/8" ANGLE THRU BOLTS INTO THE POST DRAWN BY 3/8" DIA THRU BOLT I (4 TOTAL) I I CD DATE DRAW N • 1" x 3" BASE PLATE (4) #10 x 314' (4)#10 x 314° 2"x 8" SMB � ANCHORED TO CONC W/ 1/4" " �', $ ? " s SMS INTO SMS INTO 01 /15/18 CONCRETE SCREW ANCHOR $ a "� - SCREW BOSSES I i SCREW BOSSES I I 3" x 3" x 0.093 POST REVISION (MIN. 1 114" EMBED) (2) INTO TOP RAIL ( I (2) INTO TOP RAIL Q 6" MAX EACH SIDE OF POST • •..' Y ; a� c°, (2) INTO POST (2) INTO POST AND 24" O.C. MAX •'� CONNECTION AT CORNER CONNECTION AT SPLICE $-, 3 0 COMPOSITE ROOF TO CORNER POST 4TH WALL DETAIL FRONT VIEW A_2 SCALE: NTS SHEET NO: DJA UPRIGHT TO CONCRETE PRE -HUNG $ X 3 TOP RAIL CONNECTION TO 3 X 3 UPRIGHT -2 DOOR LOCATION DETAIL SCALE: NTS SCALE: NTS A-2A-2