ENERGY EFFICIENCY CODE
W, SCANNED BY FORM R405-2017 MIR, C`� FLORIDA ENERGY EFFICIENCY CODE FOR BUILDING CONSTRUCTION Florida Department of Business and Professional Regulation - Residential Performance_ Method Project Name: MICHIELSEN RESIDENCE Builder Name: MEL- RY CONSTRUCTI DN JJ Street: 1044 NETTLES BLVD Permit Office: ST LUCIE COUNTY Al City, State, Zip: JENSEN BEACH, FL, 34957 Permit Number: 1802-0647 Owner: RANDALL AND CHERYL MICHIELSEN Jurisdiction: ST LUCIE COUNTY ST. Lucie COunty, POrryuuing Design Location: 'PL, Fort Pierce County:: St. Lucie (Florida Climate Zone 2 1. New construction or existing New (From Plans) 9. Wall Types (1027.3 sqft.) Insulation Area 2. Single family or multiple family Single-family a. Concrete Block - Ext Insul, Exterior R=4.1 1027.30 ft2 b. N/A R= ft2 3. Number of units, if multiple family 1 c. N/A R= ft2 4. Number of Bedrooms 1 d. N/A R= ft2 5. Is this a worst case? No 10. Ceiling Types (802.0 sqft.) Insulation Area a. Roof Deck (Unvented) R=20.0 802.00 ft2 6. Conditioned floor area above grade (ft2) 802 b. N/A R= ft2 Conditioned floor area below grade (ft2) 0 c. N/A R= ft2 11. Ducts R ft2 7. Windows(78.0 sqft.) . Description Area a. Sup: Attic, Ret: Attic, AH: Attic 6 125 a. U-Factor: Sgl, U=0.30 78.00 ft2 SHGC: SHGC=0.21 b. U-Factor: N/A ft2 12. Cooling systems kBtu/hr Efficiency. SHGC: a. Central Unit 18.0 SEER:16.00 y c. U-Factor: N/A ft2 SHGC: 13. Heating systems kBtu/hr Efficiency d. U-Factor: N/A ft2 a. Electric Strip Heat 17.0 COP:1.00 SHGC: Area Weighted Average Overhang Depth: 1.000 ft. Area Weighted Average SHGC: 0.210 14. Hot water systems a. Electric Tankless Cap: 1 gallons 8. Floor Types (802.0 sqft.) Insulation Area EF: 0.990 a. Slab -On -Grade Edge Insulation R=0.0 802.00 ft2 b. Conservation features b. N/A R= ft2 None c. N/A R= ft2 15. Credits None Glass/Floor Area: 0.097 Total Proposed Modified Loads: 28.83 PASS Total Baseline Loads: 32.93 I hereby certify that the plans and specifications covered by Review of the plans and &IIAES.7r' this calculation are in compliance with the Florida Energy specifications covered by this Code. calculation indicates compliance � - y iip ' - "s 9 with the Florida Energy Code. ,aa C N li0? '= PREPARED BY Before construction is completedLU4' III DATE: 4t I elta this building will be inspected for compliance with Section 553.908 I herebycertify that this building, as designed, is in compliance fY 9� 9 P Florida Statutes. . with the Florida Energy Code. Op`yyE 1� OWNER/AGENT �- BUILDING OFFICIAL: DATE: DATE: - Compliance requires certification by the air handler unit manufacturer that the air handler enclosure qualifies as certified factory -sealed in accordance with R403.3.2.1. - Compliance requires an Air Barrier and Insulation Inspection Checklist in accordance with R402.4.1.1 and this project requires an envelope leakage test report with envelope leakage no greater than 7.00 ACH50 (R402.4.1.2). - File COPY'. 4/10/2018 6:05 PM EnergyGauge® USA - FlaRes2017 Section R405.4.1 Compliant Software Page 1 of 5 FORM R405-2017 PROJECT Title: • MICHIELSEN RESIDENCE Bedrooms: 1 Address Type: Street Address Building Type: User Conditioned Area: 802 Lot # Owner Name: RAND/jLL AND CHERYL MIC Total Stories: 1 Block/SubdMsion: # of Units: 1 Worst Case: No PlatBook: Builder Name: MEL- RY CONSTRUCTION Rotate Angle: 0 Street: 1044 NETTLES BLVD Permit Office: ST LUCIE COUNTY Cross Ventilation: No County: St. Lucie Jurisdiction: St LUCIE COUNTY Whole House Fan: No City, State, Zip: JENSEN BEACH, Family Type: Single-family FL, 34957 New/Ebsting: New (From Plans) Comment: CLIMATE / Design Temp Int Design Temp Heating Design Daily Temp V Design Location TMY Site 97.5 % 2.5 % Winter Summer Degree Days Moisture Range FL, Fort Pierce FL VERO_BEACH_MUNI 39 90 70 75 299 62 Low BLOCKS Number Name Area Volume 1 Entire House 802 6416 SPACES Number Name Area Volume Kitchen Occupants Bedrooms InfilID Finished Cooled Heated 1 MASTER BATH 63 504 No 0 1 Yes Yes Yes 2 M WIC 36 288 No 0 1 Yes Yes Yes 3 DEN 179 1432 No 0 1 Yes Yes Yes 4 MASTER BEDROO 143 1144 No 0 1 1 Yes Yes Yes 5 KITCHEN 143 1144 Yes 0 1 Yes Yes Yes 6 LIVING ROOM 143 1144 No 0 1 Yes Yes Yes 7 FOYER 49 392 No 0 1 Yes Yes Yes 8 LAUNDRY 18 144 No 0 1 Yes Yes Yes 9 HALF BATH 28 224 No 0 1 Yes Yes Yes FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 1 Slab -Oh -Grade Edge Insulation MASTER BATH 16 It 0 63 ft2 _--_ 1 0 0 2 Slab -On -Grade Edge Insulation M W IC 8.4 ft 0 36 ft2 ____ 1 0 0 3 Slab -On -Grade Edge Insulation DEN 24 ft 0 179 ft2 1 0 0 4 Slab -On -Grade Edge Insulation MASTER BEDRO lift 0 143 ft2 ____ 1 0 0 5 Slab -On -Grade Edge Insulation KITCHEN lift 0 143 ft2 ____ 1 0 0 6 Slab -On -Grade Edge Insulation LIVING ROOM 28 ft 0 143 ft2 __e 1 0 0 7 Slab -On -Grade Edge Insulation FOYER 5.6 ft 0 49 ft2 ____ 1 0 0 4/10/2018 6:05 PM EnergyGauge® USA - FlaRes2017 Section R405.4.1 Compliant Software Page 2 of 5 FORM R405-2017 FLOORS # Floor Type Space Perimeter Perimeter R-Value Area Joist R-Value Tile Wood Carpet 8 Slab -On -Grade Edge Insulation LAUNDRY 12.8 ft 0 18 ft2 ____ 1 0 0 9 Slab -On -Grade Edge Insulation HALF BATH 11.3 ft 0 28 ft2 ____ 1 0 0 ROOF / Roof Gable Roof Solar SA Emitt Emitt Deck Pitch # Type Materials Area Area Color Absor. Tested Tested Insul. (deg) 1 Hip'. Metal 869 ft2 0 ft2 Light 0.6 No 0.9 No 20 22.6 ATTIC V # Type Ventilation Vent Ratio (1 in) Area RBS IRCC 1 Full attic Unvented 0 802 ft2 N N CEILING # Ceiling Type Space R-Value Ins Type Area Framing Frac Truss Type 1 Under Attic (Unvented) MASTER BATH 20 Blown 63 ft2 0.1 Wood ti 2 Under Attic (Unvented) M WIC 20 Blown 36 ft2 0.1 Wood 3 Under Attic (Unvented) DEN 20 Blown 179 ft2 0.1 Wood 4 Under Attic (Unvented) MASTER BEDRO 20 Blown 143 ft2 0.1 Wood 5 Under Attic (Unvented) KITCHEN 20 Blown 143 ft2 0.1 Wood 6 Urfder Attic (Unvented) LIVING ROOM 20 Blown 143 ft2 0.1 Wood 7 Under Attic (Unvented) FOYER 20 Blown 49 ft2 0.1 Wood 8 Under Attic (Unvented) LAUNDRY 20 Blown 18 ft2 0.1 Wood 9 Under Attic (Unvented) HALF BATH 20 Blown 28 ft2 0.1 Wood WALLS Adjacent Space Cavity Width Height Sheathing Framing Solar Below 1 SW Exterior Concrete Block - Ext InsLMASTER BA 4.1 9 0 8 0 72.0 ft2 0 0 0.6 0 2 NW Exterior Concrete Block - Ext InsiWIASTER BA 4.1 7 0 8 0 56.0 ft2 0 0 0.6 0 3 N Exterior Concrete Block- Ext Insul M W IC 4.1 8 6 8 0 68.0 ft2 0 0 0.6 0 4 N Exterior Concrete Block - Ext Insul DEN 4.1 11 4 8 0 90.7 ft2 0 0 0.6 0 5 E Exterior Concrete Block - Ext Insul DEN 4.1 12 9 8 0 102.0 ft2 0 0 0.6 0 6 SW Exterior Concrete Block - Ext InstWIASTER BE 4.1 11 0 8 0 88.0 ft2 0 0 0.6 0 7 SW Exterior Concrete Block - Ext Insul KITCHEN 4.1 11 0 8 0 88.0 ft2 0 0 0.6 0 8' NE Exterior Concrete Block - Ext InsdIlVING ROO 4.1 4 0 8 0 32.0 ft2 0 0 0.6 0 9 SE Exterior Concrete Block - Ext InsdIIVING ROO 4.1 13 0 8 0 104.0 ft2 0 0 0.6 0 10 SW Exterior Concrete Block - Ext InsLIIVING ROO 4.1 11 0 8 0 88.0 ft2 0 0 0.6 0 11 E Exterior Concrete Block - Ext Insul FOYER 4.1 5 8 8 0 45.3 ft2 0 0 0.6 0 12 N Exterior Concrete Block - Ext InSUILAUNDRY 4.1 4 3 8 0 34.0 ft2 0 0 0.6 0 13 E Exterior Concrete Block - Ext InsuILAUNDRY 4.1 5 0 8 0 40.0 ft2 0 0 0.6 0 14 S Exterior Concrete Block - Ext InsuILAUNDRY 4.1 3 7 8 0 28.7 ft2 0 0 0.6 0 15 N Exterior Concrete Block - Ext Insu11ALF BATH 4.1 11 4 8 0 90.7 ft2 0 0 0.6 0 4/10/2018 6:05 PM EnergyGauge® USA - FlaRes2017 Section R405.4.1 Compliant Software Page 3 of 5 7i7NJiI:ZrelF&Z1TiM WINDOWS Orientation shown is the entered, Proposed orientation. V # Wall Ornt ID Frame Panes NFRC Overhang U-Factor SHGC Imp Area Depth Separation Int Shade Screening 1 2 3 4 5 6 SW 1 . Metal Low-E Single N 4 Metal Low-E Single SW 6 Metal Low-E Single SW 7 Metal Low-E Single NE 8 Metal Low-E Single SE 9 Metal Low-E Single Yes Yes Yes Yes Yes Yes 0.3 ' 0.21 N 4.0 ft2 1 ft 0 in 1 ft 4 in 0.3 0.21 N 15.0 ft2 1 ft 0 in 1 ft 4 in 0.3 0.21 N 15.0 ft2 1 ft 0 in 1 ft 4 in 0.3 0.21 N 9.0 ft2 1 ft 0 in 1 ft 4 in 0.3 0.21 N 5.0 ft2 1 ft 0 in 1 ft4 in 0.3 0.21 N 30.0 ft2 1 ft 0 in 1 ft 4 in None None None None None None None None None None None None INFILTRATION # Scope Method SLA CFM 50 ELA EgLA ACH ACH 50 1 Wholehouse ProposedACH(50) .000356 748.5 41.09 77.28 .2598 7 HEATING SYSTEM # System Type Subtype Efficiency Capacity Block Ducts 1 Electric Strip Heat/ None COP:1 17 kBtu/hr 1 sys#1 COOLING SYSTEM ti # System Type Subtype Efficiency Capacity Air Flow SHR Block Ducts 1 Central Unit/ Split SEER: 16 18 kBtu/hr 540 cfm 0.8 1 sys#1 HOT WATER SYSTEM # System Type SubType Location EF Cap Use SetPnt Conservation 1 Electric Tankless Exterior 0.99 1 gal 55.1 gal 120 deg None SOLAR HOT WATER SYSTEM FSEC Cert # Company Name Collector System Model # Collector Model # Area Storage Volume FEF None None ft2 DUCTS # — Supply — Location R-Value Area — Return -- Air CFM 25 CFM25 Location Area Leakage Type Handler TOT OUT QN RLF HVAC # Heat Cool 1 Attic 6 125 ft2 Attic 13 ft2 Default Leakage Attic (Default) c(Default) c 1 1 4/10/2018 6:05 PM EnergyGauge® USA - FlaRes2017 Section R405.4.1 Compliant Software Page 4 of 5 IQVIT,MZ916-s►llm TEMPERATURES Programable Thermostat: N Ceiling Fans: CoolingJan HeatinJan Feb Feb Mar Mar Apr f Apr f May May Jun Jun Jul Jul [X] Auge [ ] Au4 Sep Oct f Oct Nov Nov Dec f X� Dec Vent in Jan Feb Mar [X] Apr [ May Jun Jul [ ] Aug [ Se [X] Oct Nov [ ]Dec Thermostat Schedule'. HERS 2006 Reference Hours Schedule Type 1 2 3 4 5 6 7 8 9 10 11 12 Cooling (W D) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 80 80 78 78 78 78 78 78 78 78 Cooling (WEH) AM 78 78 78 78 78 78 78 78 80 80 80 80 PM 80 80 80 80 78 78 78 78 78 78 78 78 Heating (W D) AM 65 65 65 65 65 65 65 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 Heating (WEH) AM 65 65 65 65 65 65 65 68 68 68 68 68 PM 68 68 68 68 68 68 68 68 68 68 68 68 4/10/2018 6:05 PM EnergyGauge@) USA - FlaRes2017 Section R405.4.1 Compliant Software Page 5 of 5 2017 - AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA ti TABLE 402.4.1.1 AIR BARRIER AND INSULATION INSPECTION COMPONENT CRITERIA Project Name: MICHIELSEN RESIDENCE Builder Name: MEL- RY CONSTRUCTION Street: 1044 NETTLES BLVD Permit Office: ST LUCIE COUNTY City, State, Zip: JENSEN BEACH, FL, 34957 Permit Number: 1802-0647 Owner: RANDALL'AND CHERYL MICHIELSEN Jurisdiction: ST LUCIE COUNTY Design Location: FL, Fort Pierce COMP.ONEAT AIR BARRIER CRITERIA INSULATION INSTALLATION CRITERIA General. A continuous air barrier shall be installed in the building envelope. Air -permeable insulation shall The exterior thermal envelope contains a continuous air barrier. not be used as a sealing material. requirements Breaks or joints in the air barrier shall be sealed. Ceiling/attic The air barrier in any dropped ceiling/soffit shall be aligned with the The insulation in any dropped ceiling/soffit insulation and any gaps in the air barrier shall be sealed. shall be aligned with the air barrier. Access openings, drop down stairs or knee wall doors to unconditioned attic spaces shall be sealed. Walls '° The junction of the foundation and sill plate shall be sealed. Cavities within corners and headers of frame walls shall The junction of the top plate and the top of exterior walls shall be sealed. be insulated by completely filling the cavity with a Knee walls shall be sealed. material having a thermal resistance of R-3 per inch minimum. Exterior thermal envelope insulation for framed walls shall be installed in substantial contact and continuous alignment with the air barrier. Windows, skylights The space between window/door jambs and framing, and and doors skylights and framing shall be sealed. Rim joists Rim joists shall include the air barrier. Rim joists shall be insulated. Floors The air barrier shall be installed at any exposed edge of insulation. Floor framing cavity insulation shall be installed to (including maintain permanent contact with the underside of above -garage subfloor decking, or floor framing cavity insulation shall and cantilevered floors) be permitted to be in contact with the top side of sheathing, or continuous insulation installed on the underside of floor framing and extends from the bottom to the top of all perimeter floor framing members. Crawl space walls Exposed earth in unvented crawl spaces shall be covered with a Where provided instead of floor insulation, insulation �. Class I vapor retarder with overlapping joints taped. shall be permanently attached to the crawlspace walls. Shafts, penetrations Duct shafts, utility penetrations, and flue shafts opening to exterior or unconditioned space shall be sealed. Batts in narrow cavities shall be cut to fit, or narrow Narrow cavities cavities shall be filled by insulation that on installation readily conforms to the available cavity spaces. Garage separation Air sealing shall be provided between the garage and conditioned spaces. Recessed lighting Recessed light fixtures installed in the building thermal envelope shall Recessed light fixtures installed in the building be sealed to the drywall. thermal envelope shall be air tight and IC rated. Plumbing and wiring Batt insulation shall be cut neatly to fit around wiring and plumbing in exterior walls, or insulation that on installation readily conforms to available space shall extend behind piping and wiring. Sheiwer/tub The air barrier installed at exterior walls adjacent to showers and Exterior walls adjacent to showers and tubs shall be on exterior wall tubs shall separate them from the showers and tubs. insulated. Electrical/phone box on The air barrier shall be installed behind electrical or communication exterior walls boxes or air -sealed boxes shall be installed. HVAC register boots HVAC register boots that penetrate building thermal envelope shall be sealed to the sub -floor or drywall. Concealed When required to be sealed, concealed fire sprinklers shall only be sealed sprinklers in a manner that is recommended by the manufacturer. Caulking or other adhesive sealants shall not be used to fill voids between fire sprinkler cover plates and walls or ceilings. c.. u. a..wuv , —N-1— v. wy rvaua ai .11 uc ui 0"U1u011UU wuii uia N1UVI31UI1s U1 iVV-4UV. 4/10/2018 6:06 PM EnergyGauge® USA - FlaRes2017 FBC 6th Edition (2017) Compliant Software Page 1 of 1 FORM R405-2017 ENERGY PERFORMANCE LEVEL (EPL) DISPLAY CARD ESTIMATED ENERGY PERFORMANCE INDEX* = 88 The lower the EnergyPerformance Index, the more efficient the home. 1044 NETTLES BLVD, JENSEN BEACH, FL, 34957 1. New construction or existing New (From Plans) 9. Wall Types Insulation Area . ' 2. Single family or multiple family Single-family a. Concrete Block - Ext Insul, Exterior R=4.1 1027.30 ftz b. N/A R= ftz 3. Number of units, if multiple family 1 c. N/A R= ftz 4. Number of Bedrooms 1 d. N/A R= ftz 5. Is this a worst case? 10. Ceiling Types No Insulation Area a. Roof Deck (Unvented) R=20.0 802.00 ftz 6. Conditioned floor area (ftz) 802 b. N/A R= ftz 7. Windows— Description Area c. A R= z a. U-Factor: Sgl, U=0.30 78.00 ftz 11. Ducts a. Sup: Attic, Ret: Attic, AH: Attic R ftz 6 125 SHGC: SHGC=0.21 b. U-Factor: N/A ftz SHGC: 12. Cooling systems kBtu/hr Efficiency ' c. U-Factor: N/A ftz a. Central Unit 18.0 SEER:16.00 SHGC: d. U-Factor: N/A ftz 13. Heating systems kBtu/hr Efficiency SHGC: a. Electric Strip Heat 17.0 COP:1.00 Area Weighted Average Overhang Depth: 1.000 ft. Area Weighted Average SHGC: 0.210 8. Floor Types Insulation Area 14. Hot water systems Cap: 1 gallons a. Slab -On -Grade Edge Insulation R=0.0 802.00 ftz a. Electric EF: 0.99 b. N/A R= ftz c. N/A R= ftz b. Conservation features None 15. Credits None I certify that this home has complied with the Florida Energy Efficiency Code for Building Construction through the above energy saving features which will be installed (or exceeded) in this home before final inspection. Otherwise, a new EPL Display Card will be completed based on installed Code compliant features. Builder Signature: Date:�� Address of New Home: City/FL Zip: `Note: This is not a Building Energy Rating. If your Index is below 70, your home may qualify for energy efficient mortgage (EEM) incentives if you obtain a Florida EnergyGauge Rating. Email EnergyGauge tech support at techsupport@energygauge.com or see the EnergyGauge web site at energygauge.com for information and a list of certified Raters. For information about the Florida Building Code, Energy Conservation, contact the Florida Building Commission's support staff. **Label required by Section R303.1.3 of the Florida Building Code, Energy Conservation, if not DEFAULT. 4/10/2018 6:05 PM EnergyGaugeO USA - FlaRes2017 - Section R405.4.1 Compliant Software Page 1 of 1 -1- wrrightsoft® Project Summary Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS ,AOL.COM Project Information For: MICHIELSEN RESIDENCE, MEL- RY CONSTRUCTION 1044 NETTLES BLVD, JENSEN BEACH, FL Notes: Design Information Weather: Fort Pierce, FL, US Job: Date: Feb 15, 2018 By: Winter Design Conditions Summer Design Conditions Outside db 42 OF Outside db 90 OF Inside db 70 OF Inside db 75 OF Design TD 28 OF Design TD 15 OF Daily range M Relative humidity 50 %. Moisture difference 61 gr/lb Heating Summary Sensible Cooling Equipment Load Sizing Structure 12944 Btuh Structure 11429 Btuh Ducts 2144 Btuh Ducts 2114 Btuh Central vent (0 cfm) 0 Btuh Central vent (0 cfm) 0 Btuh Humidification 0 Btuh Blower 0 Btuh Piping 0 Btuh Equipment load 15088 Btuh Use manufacturers. data n Rate/swing multiplier 0.95 Infiltration Equipment sensible load 12866 Btuh Method Simplified Latent Cooling Equipment Load.Sizing Construction quality Average Fireplaces 0 Structure 2329 Btuh Ducts 847 Btuh Heating Coolin Central vent 0 cfm) 0 Btuh Area (ftz) 802 80 Equipment latent load 3177 Btuh Volume (ft3) 6416 6416 Air changes/hour 0.61 0.32 Equipment total load 16043 Btuh Equiv. AVF (cfm) 65 34 Req. total capacity at 0.70 SHR 1.5 ton Heating Equipment Summary Cooling Equipment Summary Make Make Rheem Trade Trade RHEEM Model Cond RA1618AJlNA AHRI ref Coil RH1T2417STANJA AHRI ref 7940565 Efficiency 100 EFF Efficiency 13.0 EER, 16 SEER Heating input 4.4 kW Sensible cooling 12600 Btuh Heating output 15088 Btuh Latent cooling 5400 Btuh . Temperature rise 23 OF Total cooling 18000 Btuh Actual air flow 600 cfm Actual air flow 600 cfm Airflow factor 0.040 cfm/Btuh Airflow factor 0.044 cfm/Btuh Static pressure 1.00 in H2O Static pressure 1.00 in H2O Space thermostat Load sensible heat ratio 0.81 Calculations approved byACCA to meet all requirements of Manual J 8th Pe ` PP + wrightsoft" Right -Suite® Universal 2017 17.0.08 RSU08101 ..rightsoft WACIMICHIELSEN RESIDENCE- MEL-RY.rup Calc = MJ8 Front Door faces: SE 2018-Feb-15 10:13:17 . Pagel -f - wrightsoftRight-M Worksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM Job: Date: Feb 15, 2018 By: 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area Entire House 128.1 ft 8.0 ft 802.0 ft2 MASTER BATH 16.0 ft 8.0 ft heat/cool 7.0 x 9.0 ft 63.0 ft' Ty Construction number U-value (Btuh/ft7-°F) Or HTM (Btuh/ft') Area (ft') or perimeter (ft) Load (Btuh) Area (ft-) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 G- 13A-4ocs 2 glazing, _clr low-e _ __ 13A-4ocs 2 alazinq,_clr low-e ___,-_____0_650 13A-4ocs - 13A-4ocs 2 glazing, dr low-e '13Q ocs__ p _.� 13A-4ocs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, cir low-e __ _ _ 13A-flocs ..___ 16A-30md 22AtPh___ _ '.`�__ 0.143 0.650 0.143 0.143 __. __0.390 0.143 0_650 -_ __0:143 0.143 0.650 0.650 _ 0.650 0.032 �L•358'�� :n n , ne _ne _ . e -e_. se _se . _s_ sw sw sw sw -- - __.4.00 _._18.20 4.00 __ _18.20 4.00 __ 10:92 4.00 _ : 18.20 __ .4.00 4.00 18.20 18.20 18.20 0.90 �_ 36.02 V2.19 - 14.99 2.19 -__-26.88 2.19 _ 10.34 2.19 -^25.63 2.19 2.19 23.49 24.68 25.63 2,19. 2.24 � 0.00 ` 283 - - 15 32 __ _r_ 5 187 __. - 20 104 - 30 _29 336 4 9 15 -_�_-56 802 T_ 802 --- - 268 0 27 _ 0 168 __:_ 20 74 __._ 4 _---- --29 308 1 2 2 ,56 _ _ 802 �^__128 1074 _265 108 91 '- 671 -__-213 296 "�_-, 546 . 115 �- 1233 73 164 273 --__ 224 719 _,�4870 --- 587 219 59 _- 134 - 367 -__202 162 769 ___._. _ 674 94 222 384 123 1796 _ _____,0 - -- 0 0. 0 0 - 0 ____-0 0 0 ____'_0 _- 0 0 0 ---0 -____0 0 0 - 0 . 0 0 _. 0 -- 0 -.____0 0 0 - 272 73 0 _ - 0 56 -_- _ 0 _ - 0, 0 0 - - --0 -.-__0. 0 0 �- __Q 149 94 0 _ 0 1_41 v� _-G- V+/ L-G W_ C F _- .___,._ �0 72 4 0 _ 0 :_...._._ �56224_ 63 0 68 1 0 _ 0 _-_ 63 _ - -- 16 �.608 _,_.__ 0_ _��fi3 6 c)AED excursion 0 15 Envelope loss/gain 10937 5855 1234 521 12 a) Infiltration b) Room ventilation 2007 0 564 0 250 0 70 0 13 Internal gains: Occupants @ 230 Appliances/other 2 460 4550 0 0 0 Subtotal (lines 6 to 13) 12944 11429 1484 592 14 15 Less wdemal load Less transfer Redistribution Subtotal Duct loads 17% 19% 0 0 0 12944 2144 0 0 0 11429 2114 17% 19% 0 0 160 1644 272 0 0 44 636 118 Total room load Air required (cfm) 15600 600 13600 600 1916 76 753 33 Calculations approved bvACCA to meet all reouirements of Manual J 8th Ed. 4 wrightsoft• Right -Suite® Universal 2017 17.0,08 RSU08101 2018-Feb-.15 10:13:17 A ...rightsoft HVAC\MICHIELSEN RESIDENCE- MEL-RY.rup Calc = MJ8 Front Door faces: SE Page 1 - t- wrightsoft Right-J® Worksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772.466-6799 Fax 772-466-6796 Email: QUICKCALCS@AOL.COM Job: Date: Feb 15, 2018 By: 1 2 3 4 5 Room name E)posed wall Room height Room dimensions Room area M W IC 8.4 ft 8.0 ft heat/cool 1.0 x 36.0 ft 36.0 ftz DEN 24.0 ft 8.0 ft heat/cool 1.0 x 179.0 ft 179.0 ftz TY Construction number U-value (Btuh/ft2L°F) Or HTM (Btuh/ftz) Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/PIS Heat Cool 6 11 V�/ ' G..2.glazing, 13A�ocs - "- 13A-4ocs 2 olazinq clr low--e 13A-4ocs - - _.11D0_ 13A4ocs 2 glazing, clr low a 13AVb-flocs 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, cir low-e '13Aflocs- ,_:� 16ASOmd _ Oi143 650 0.143 0.650 0.143 °.0.390 0.143 _0.650 43.`s_4.09 0.143 0.650 0.650 0.650 0.143 _0.032 n,' n;_ ne ne- a, -a., se se sw sw sw sw wnw'. - 4.00 ' 18.20 4.00 18.20 4.00 _,`10.92 4.00 18.20 4.00 18.20 18.20 18.20 400.' _ 0.90 -_'38 02 '- :2.19 :� 14.99 2.19 26.88 2.19 _ :-10.34 2.19 25.63 '68 e_•0 0 0 Y 0 _ ___._0 0 0 - -8 �., ', _0 0 0. 272 _0 0 _� 0 - - 0 :� 0 ~- T49 �,_ 0 0 -0 ' - 0 _ �0 0 0 -' 91 15 •'�- 76 0 -- 304 265 0 .---0. 408 __._-0 0 0 219 0 0 0 0 0 0 __ 102 =. D 0 0 .� VVVV}}}}//// '_ C 0 ___-__._.0 0 _ 102 ,-_0 0 _ 223 -_-_.0. 0 0 0 0 2.19 23.49 24.68 25.63 2.19 2 24 'w0A0 0 0 0 0 . -0 _0 w 0 0 0 0 36 .- : 8 _ 0 0 0 0 32 320 _ 0 0 0 0 81 024 _0 _ 0 0 0 0 179 0 0 0 0 _ 160 _ 013 O 0 0 0 0 179 0 0 0 0 JO -' - 401 _ _ 36 _�36 6 c) AED excursion -11 . -82 Envelope loss/gain 624 218 2050 927 12 a) Infiltration b) Room ventilation 133 0 37 0 376 0 106 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 900 Subtotal (lines 6 to 13) 757 256 2426 1932 14 151 Less a)denial load Less transfer Redistribution Subtotal Duct loads 17% 19% 0 0 160 916 152 0 0 44 300 55 17% 19% 0 0 433 2859 474 0 0 200 2133 395 Total room load Air required (cfm) 1068 42 355 16 3333 133 2527 112 Calculations approved byACCA to meet all requirements of Manual J 8th Ed. 410efvrigFftsoft' 2018-Feb-15 10: Right -Suite® Universal 2017 17.0.08 RSUD8101 age 2 ACCk ...rightsoft HVACIMICHIELSEN RESIDENCE- MEL-RY.rup Calc = MJ8 Front Door faces: SE Page 2 - wrightsoft' RighWO Worksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772466-6799 Fax 772466-6796 Email: QUICKCALCS AOL.COM Job: Date: Feb 15, 2018 By: 1 2 3 4 5 Room name E)posed wall Room height Room dimensions Room area MASTER BEDROOM 11.0 ft 8.0 ft heat/cool 13.0 x 11.0 ft 143.0 ft2 KITCHEN 11.0 ft 8.0 ft heat/cool 13.0 x 11.0 ft 143.0 ft2 Ty Construction number LI-value (Btuh/ft2-°F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 y/ �._ G: 13A flocs �- _2.glazing,-clr low_e .- - 13A-4ocs 2 glazmq,.clr low e,-_ 13A-4ocs 13A-4ocs 2 glazing, clr low-e -13A11ocs ._---- -- 13A-4ocs 2 glazing, clr low-e 2 glazing, cir low-e 2 glazing, clr low-e 16A30md 0.143 _ __ �0.650 0.143 0 650 0.143 0:390 0.143 0.650 -----.,_Qj- 3 0.143 0.650 0.650 0.650 0.032 n ri , ne ne a __e se se ems' sw sw sw sw 4'.00 - 18.20, 4.00 18.20 4:00 -10.92 4.00 18.20 _ _ 4.00. 4.00 18.20 18.20 18.20 0.90 2.19 �14.99 2.19 26 88 219 _._ 10.34 2.19 25.63 _ _ 2.19 2.19 23.49 24.68 25.63 2.24 0 -70 0 ��"- 0 0 ____ 0 0' _ _d _0 0 0 160 0 0 384 320 T 0 0 0 0 0 __��_0 0 _ ._0 0 0 _9 79 0 2 0 0 _ 0 1�/ 1�_ 0 0 0 „_0 0" _ _ _ --0 0 0 0 73 0 0 2 143 0 ____. 0 0 _'.__-_.0 0 0 _, 292 0 0 273 128 0 __-� 0 0 0 0 -__-__ Q 316 0 164 0 0 �__- 0 0 0 0 - --_0 173 0 222 0 320 . W _ �C W:.. _ C � 0 .,_____ ..A 0 0 . , 0 88 0 0 15 143 0 _.___._._.0 0 0 88 0 9 0 143 143 128 71 00" 14311 ....... 6 c)AED excursion 54 -26 Envelope loss/gain 1112 919 1027 690 12 a) Infiltration b) Room ventilation 172 0 48 0 172 0 48 0 13 Internal gains: Occupants @ 230 Appliances/other 2 460 750 0 0 2000 Subtotal (lines 6 to 13) 1284 2177 1199jr 2738 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 17% 19% 0 0 160 1443 239 0 0 44 2221 411 17% 19% 0 0 353 1552 257 0 0 154 . 2892 535 Total room load Air required (cfm) 1682 67 2632 117 1809 721 3427 152 Calculations approved bvACCA to meet all requirements of Manual J 8th Ed. wrigtftsoft' RightSuite® Universal 2017 17.0.08 RSU08101 2018-Feb-15 1 Pa3 .4LCA e 3 ...rightsoft HVACIMICHIELSEN RESIDENCE- MEL-RY.rup Calc = MJ8 Front Door faces: SE 9 M +�- wrightsoft Right-M Worksheet Entire House QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM Job: Date: Feb 15, 2018 By: 2 3 4 5 Exposed wall Room height Room dimensions Room area LIVING ROOM 28.0 ft 8.0 ft heat/cool 13.0 x 11.0 ft 143.0 ft2 FOYER 5.6 ft 8.0 ft heat/cool 1.0 x 49.0 ft 49.0 ft' Ty Construction number U-value (Btuh/ft' °F) Or HTM (Btuh/ft2) Area (ft2) or perimeter (ft) Load (Btuh) Area (ft2) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 - V�! ! C_ - --- - 13A-0ocs .2 glazing; clr low-e ,2 4lazina.-clr lower _ 13A-flocs 13A-4ocs 2 glazing, clr low-e _ flocs--- ---- u 13A-4ocs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr lower 16A-30md _ ~0.143 0.650 0.143 0:143 ___0.390 .0.143 0.650 i_ 0J.41 0.143 0.650 0.650 _ 0_650 0.032 - - n _n:, ne ; e .-'e._ se se � s - sw sw sw sw - 4.00 �18.20. 4.00 .: 4.00 _�_..•10.92 4.00 M 18.20 - -_• 4..00 4.00 18.20 18.20 18.20 _ 0.90 02 - 2 99 14 99 2.19 2:19 . _10.34 2.19 25.63 219 2.16 23.49 24.68 _ 25_63 _ 2.24 _000 - - '0 _ _�_ 32 " 0 _, �:0 104 30 - _0 88 0 0 _0 143 - " 143 - 0 -=_ 0 27 --0 a-_.___0 74 4 0 88 0 0 _0 - 143 28 .0 _ _ �. _0 108 0" _..�,._.• 0 296 546 = __ �0 352 0 0 0 �..-� _Q 128 - - 1065 ��0 __ _0 59 -- 134 0 ___..-_0 162 769 _ ' ___0 193 0 0 _ _ 0 � _0 0 __ Q 0 0 0 __ ; 0 0 103 _..._._�213 0 0 - _ _6 0 0 0 0 _0 ! : 0 0 0 �- 56 ____202 0 0 0 0 0 0 0 _,.,__..._.Q 110 __ _ 0 _ ,,13A-4ocs . �j1 '-. _D V�J L--G C F ,��Q 0 26 . _._ ._20 0 0 -___ 0 0 0 0 0 �___ Q 45 _-�_:20 0 0 _ 0 0 0 0 _0 `,•�___,_0 _ 49 �__4.9_ _ 320 �. _ . _ 0 49 . 3 44 ��_- 212 77 6 c)AED excursion 91 -18 Envelope loss/gain 2587 17281 573 352 12 a) Infiltration b) Room ventilation 438 0 123 0 88 0 25 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 900 0 0 0 Subtotal (lines 6 to 13) 3024 2751 661 377 14 15 Less external load Less transfer Redistribution Subtotal Duct loads 17% 19% 0 0 353 3378 659 0 0 154 2905 537 17'/6 19% 0 0 -661 0 0 0 0 -377 0 0 ITTotal room load Air required (cfm) 3937 157 3443 153 1 0 0 0 0 - ' Calculations. approved by ACCA to meet all requirements of Manual J 8th Ed Aftk � WrigF7t5oft, Right -Suite® Universal 2017 17.0.08 RSU08101 2018-Feb-15 10:13:17 Page 4 ..,rightsoft HVAC\MICHIELSEN RESIDENCE- MEL-RY,rup Calc = MJ8 Front Door faces: SE -1- wrightsoft' Right-J® Worksheet Entire House QUICK CALCS, INC. ' 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS a(iAOL.COM I Job: Date: Feb 15, 2018 By: 1 2 3 4 5 Room name Exposed wall Room height Room dimensions Room area LAUNDRY 12.8 ft 8.0 ft heat/coot 1.0 x 18.0 ft 18.0 ftz HALF BATH 11.3 ft 8.0 ft heat/cool 1.0 x 28.0 ft 28.0 ftz Ty Construction number U-value (Btuh/ftz-"F) Or HTM (Btuh/ftz) Area (ftz) or perimeter (ft) Load (Btuh) Area (ftz) or perimeter (ft) Load (Btuh) Heat Cool Gross N/P/S Heat Cool Gross N/P/S Heat Cool 6 11 V�-/ �G 13A-0oc's --- ; - -� - .2.glazing, clr,low 2 glazinq, clr low-e _ _ _ 13A flocs _11D0_ __ _._ _. _ 13A4ocs 2 glazing, clr low-e _ 13A•40c5_ __ `___ 13A-4ocs 2 glazing, clr low-e 2 glazing, clr low-e 2 glazing, clr low-e 13A•40cs_ - - -- 16A-30md -'-'0:143 :_ _ 4.650 0.143 -_ 0.650 0.143 -_.-__0.390 0.143 0.650 n ,--.n_ ne _ J ne - e __.e_ se se 4.00 _- __�18.20, 4.00 18.20 4.00 - 10:92 4.00 18.20 2.19 .. 14.99 2.19 _ _�26.88 '2.19 -;,-10.34 2.19 25.63 34 ��_',__:0 0 0 �'^ 40 .0 0 0 ,:--29 0 0 0 0 ..,• _0 18 ^, --Si _ 0 0 _ _ _0 40 .___�0 0 _ 0 -. _29 0 0 0 0 �_ 18 -' - 136 _ _- _0 0 0 - 160 - ~ .__A 0 _ 0 ___115 0 0 0 _ 0 --- 0 16 -' 74 _-___ 0 0 0 '^ 88 -_.- _0 0 _0 ---'63 0 0 0 0 -- ---0 40 --�-- -91 �_ 0 0 _ 0 _ 0 ___..�.0 0 ___ 0 . -_ _0 -�- 198 ________A 0 0 .-_.--_0. 0 0 91 __0 0 ^� _ 0 ' 0 ` __._.0 0 0 -- - 362' _�_Q 0 _ _ 0 _.___-_0. �13A•4ocs _ _ _�. y/ W ._ _ W c 0 0 `0:1.4433 0.143 0.650 0.650 0.650 - -'- 0;143 _ 0.032 s,, sw sw sw sw `: nw -_ .' . 4 OQ 4.00 18.20 18.20 18.20 -, 4,00. 0.90 _-- 2.19 2.19 23.49 24.68 25.63 _ a 2,19 2.24 _ 0 0 0 _0 -= 0 28 0 0 0 0 - - ^ __0 28 0 0 0 _ 0 0 25 0 0 0 0 T - 0. 63 6 c)AED excursion -13 -13 Envelope loss/gain 916 252 815 248 12 a) Infiltration b) Room ventilation 201 0 56 0 177 0 50 0 13 Internal gains: Occupants @ 230 Appliances/other 0 0 0 0 0 0 Subtotal (lines 6 to 13) 1117 309 992 298 14 15 Less extemal load Less transfer Redistribution Subtotal Duct loads 17% 19% 0 0 -1117 0 0 0 0 -309 0 0 17% 19% 0 0 160 1152 191 0 ' 0 44 342 63 Total room load -7 Air required (cfm) 1 0 0 0 0 1 1342 53 405 18 r Calculations approved byACCA to meet all requirements of Manual J 8th Ed wrightsoft• 2018-Feb-15 10:13:17 ACON RightSuiteO Universal 2017 17.0.08 RSU08101 Page 5 ...rightsoft HVACIMICHIELSEN RESIDENCE- MEL-RY.rup Calc = MJ8 Front Door faces: SE Duct System SJob: wrightsoft yemumma Date: Feb 15, 2018 Entire House By: QUICK CALCS, INC. 317 ST LUCIE LANE, FORT PIERCE, FL 34946 Phone: 772-466-6799 Fax 772-466-6796 Email: QUICKCALCS AOL.COM Project• • For. MICHIELSEN RESIDENCE, MEL- RY CONSTRUCTION • 1044 NETTLES BLVD, JENSEN BEACH, FL Heating Cooling External static pressure 1.00 in H2O 1.00 in H2O Pressure losses 0 in H2O 0 in H2O Available static pressure 1.00 in H2O 1.00 in H2O Supply / return available pressure 0.500 / 0.500 in H2O 0.500 / 0.500 in H2O Lowest friction rate 1.000 in/100ft 1.000 in/100ft Actual air flow 600 cfm 600 cfm Total effective length (TEL) 162 ft Name Design (Btuh) Htg (cfm) Clg (cfm) Design FR Diam (in) H x W (in) Duct Matl Actual Ln (ft) Ftg.Egv Ln (ft) Trunk DEN h 3333 133 112 1.000 7.0 Ox0 VIFx 27.5 135.0 st2 HALF BATH h 1342 53 18 1.000 4.0 Ox0 VIFx 9.3 115.0 st1 KITCHEN C 3427 72 152 1.000 8.0 Ox0 VIFx 23.4 135.0 st2 LIVING ROOM h 3937 157 153 1.000 8.0 Ox0 VIFx 24.4 135.0 st2 M WIC h 1068 42 16 1.000 4.0 Ox0 VIFx 5.4 115.0 st1 MASTER BATH h 1916 76 33 1.000 5.0 Ox 0 VIFx 8.1 115.0 st1 MASTER BEDROOM c 2632 67 117 1.000 7.0 Ox 0 VIFx 6.5 115.0 SO Trunk Htg Clg Design Veloc Diam H x W Duct Name Type (cfm) (Cfm) FR (fpm) (in) (in) Material Trunk st2 Peak AVF 361 416 1.000 763 10.0 0 x 0 VinlFlx st1 st1 Peak AVF 600 600 1.000 764 12.0 0 x 0 VinlFlx Return Branch Detail Table Name Grill Size (in) Htg (cfm) Clg (cfm) TEL (ft) Design FR Veloc (fpm) Diam (in) H x W (in) Stud/Joist Opening (in) Duct Matl Trunk rb1 Ox 0 600 600 0 0 0 0 Ox 0 VIFx a 2018-Feb-15 10:13:18 .+ + wrightSoft Right-SuiteA Universal 2017 17.0.08 RSU08101 Page 1 A+CA ...rightsoft HVACIMICHIELSEN RESIDENCE- MEL-RY.rup Calc = MJ8 Front Door faces: SE