HomeMy WebLinkAboutENGINEERINGGeneral Notes A. CONCRETE & FOUNDATION DESIGN: 1. ALL CONCRETE GRADE BEAMS AND FOOTINGS SHALL BE 3000 PSI MINIMUM. 2. ALL CONCRETE FILLED SUPPORTED SLABS SHALL BE 2500 PSI MINIMUM, 3 1/2" NOMINAL THICKNESS. 3. FIBERMESH (3/4" PER CUBIC YARD MIN.) MEETING APPROPRIATE ACI AND ASTM REQUIREMENTS MAY BE USED IN LIEU OF WELDED WIRE MESH 4. ALL SLABS ON GRADE SHALL BE 4" THICK WITH FIBERMESH. 5. ALL REINFORCING SHALL CONFORM TO ASTM A615, BE GRADE 60 (60 KSI MIN.) DEFORMED BARS, #3 BARS MAY BE GRADE 40 6. ALL OVER POUR CONCRETE FILLED SUPPORTED SLABS SHALL BE 3000 PSI MIN., 2" MINIMUM THICKNESS. 7. SOEL BEARING PRESSURE SHALL BE A MINIMUM OF 1500 PSF. 8. THE CONCRETE SHALL CONFORM TO ASTM C94 FOR THE FOLLOWING: OPC (PORTLAND CEMENT TYPE 1,- ASTM C 150). AGGREGATES - #6 STONE, ASTM C 33 SIZE NO. 67 LESS THAN 3/4". AIR ENTRAINING +/- 1%- ASTM C 260. WATER REDUCING AGENT - ASTM C 494. CLEAN POTABLE WATER - OTHER ADMIXTURES SHALL NOT BE PERMITTED. 9. METAL WELDED WIRE SHALL CONFORM TO ASTM A 185. 10. PREPARE & PLACE CONCRETE ACCORDING TO AMERICAN CONCRETE INSTITUTE MANUAL STANDARD PRACTICE, PART 1, 2, & 3 ALONG WITH HOT WEATHER CONDITIONS RECOMMENDATIONS. 11. IF UTILIZING EXISTING CONCRETE FOR FOUNDATION, CONCRETE SHALL BE A MINIMUM OF 4" IN THICKNESS, VISIBLY FREE OF ANY STRUCTURAL EXCESSIVE CRACKING, SPALLING OR OTHER DETERIORATION. B. MASONRY: 1. CONCRETE MASONRY UNITS (CMU) SHALL BE STANDARD HOLLOW UNITS AND SHALL BE 1900 PSI MINIMUM BASED ON TYPE M OR S MORTAR 2.ALL MORTAR SHALL BE OF TYPE M OR S. 3.ALL GROUT SHALL BE 2000 PSI MINIMUM AND HAVE MAXIMUM COARSE AGGREGATE SIZE OF 3/8". 4.PROVIDE CLEAN -OUTS FOR REINFORCED CELLS CONTAINING REINFORCEMENT WHEN GROUT POUR EXCEEDS 9-0" IN HEIGHT. C. ALUMINUM: 1. ALL STRUCTURAL ALUMINUM SHALL CONFORM TO THE MINIMUM REQUIREMENTS OF 6005-T5 FOR ALLOY WITH A MINIMUM THICKNESS OF 0.040" FOR SUPPORTING MEMBERS. 2. WHERE KICK PLATES ARE USED A MINIMUM THICKNESS OF 0.024" SHALL APPLY. 3. STRUCTURAL ALUMINUM DESIGN CONFORMS TO "PART 1-A - SPECIFICATIONS FOR ALUMINUM STRUCTURES - ALLOWABLE STRESS DESIGN" OR "PART 1-B - SPECIFICATIONS FOR ALUMINUM STRUCTURES - BUILDING LOAD AND RESISTANCE FACTOR DESIGN" OF THE ALUMINUM DESIGN MANUAL PREPARED BY T ASHINGTON D.C. THE FLORIDA BUILDING CODE 6th EDITION CHAPTER 16 ESUdAL& UMINUM). 4. WHERE ALUMINUM COMES INTO CONTACT WITH STEEL, OR PRESSURE TREATED LUMBER PROVIDE DIELECTRIC SEPARATION. 5. ALUMINUM MEMBERS SHALL BE STITCHED WITH NO LESS THAN # 10 SMS 6" FROM THE ENDS AND 12" ON CENTER, IF USING # 12 SPACING MAYBE 24" ON CENTER. 6. VINYL AND ACRYLIC PANELS SHALL BE REMOVABLE. THEY SHALL BE IDENTIFIED WITH A DECAL ESSENTIALLY STATING "REMOVABLE PANEL SHALL BE REMOVED WHEN WIND SPEEDS EXCEED 75 MPH". DECAL SHALL BE PLACED SO IT IS VISIBLE WHEN PANEL IS INSTALLED. 7. I "X2"X0.045" NON-STRUCTURAL MEMBERS SHALL BE ATTACHED TO HOST WITH 1/4"0 X 1-3/4" EMBEDMENT & 24" O.C. MASONRY SCREW FOR CONCRETE & EQUIVALENT SIZE WOOD SCREW WHEN IN WOOD & #IOX 1/2" EMBEDMENT SMS OR TEK SCREWS IN ALUMINUM MEMBERS TYPICAL. D. FASTENERS: 1. ALL LAG BOLTS SHALL CONFORM TO STAINLESS STEEL TYPE 30018-8, WITH STANDARD FLAT WASHER UNLESS MANUFACTURER GALVANIZES BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD. 2. HEX BOLTS HAS TO 1.. ;TM A 325, PLATED WITH STANDARD FLAT WASHERS AND ROTS. 3. ALL CONCRETE SCREWS SHALL BE, SIMPSON, HI-TI, RAWL, TAPCON, REDHEAD, DYNABOLT, PORTECT OR APPROVED EQUAL. 4. ALL METAL TIES AND ASSOCIATED ACCESSORIES SHALL BE HOT DIPPED GALVANIZED. 5. ALL LAG BOLTS SHALL HAVE A MINIMUM EMBEDMENT OF 8X BOLT DIAMETER INTO STRUCTURAL FRAMING (G=.42 MIN.). 6. LAG BOLTS AND SCREWS INTO WOOD FRAMING SHALL BE PROVIDED WITH PILOT HOLES HAVING A DIAMETER NOT GREATER THAN 70 PERCENT OF THE THREAD DIAMETER OF THE BOLT OR SCREW. ALL LAG BOLTS AND SCREWS SHALL BE INSERTED IN PILOT HOLES BY TURNING AND UNDER NO CIRCUMSTANCES BY DRIVING WITH A HAMMER. 7. ALL EXPANSION ANCHORS SHALL BE DESIGNED IN ACCORDANCE WITH THE SPECIFIC MANUFACTURER'S REQUIREMENTS AND ALLOWABLE LOADS AND SHALL ONLY BE APPLIED IN CONDITIONS ACCEPTABLE TO MANUFACTURER FASTENERS SHALL BE A MINIMUM OF SAE GRADE 45 OR BETTER ZINC PLATED. 8. ALL FASTENERS CONNECTING ALUMINUM COMPONENTS OR PRESSURE TREATED LUMBER ARE STAINLESS STEEL TYPE 300 18-8, UNLESS MANUFACTURER GALVANIZED BOLTS SPECIFIES FOR USE WITH ACQ PRESSURE TREATED WOOD, OR OTHERWISE NOTED ON PLANS. 9. ALL FASTENERS SHALL COMPLY WITH ASTM Al53. 10. ALL CONNECTORS SHALL COMPLY WITH ASTM A653 CLASS G-185. 11. FOR SMS, THE MINIMUM CENTER -TO -CENTER SPACING SHALL BE 3/4" AND MINIMUM CENTER -TO -EDGE SHALL BE 1/2" UNLESS NOTED OTHER WISE. E. REFERENCE STANDARDS: ASTM E 119 ASTM E 1300 CURRENT ASCE 7 CURRENT ALUMINUM DESIGN MANUAL -AA ASM35, AND SPEC. FOR ALUMINUM PART 1-A, & i-B ASTM C94 ASTM C150 ASTM C33 MAR ASTM C260 ASTM C494 ASTM A615 FLORIDA BUILDING CODE 61h EDITION CHAPTERS 16, 20 & 23). F. ABBREVIATIONS: THE FOLLOWING LIST OF ABBREVIATIONS IS NOT INTENDED TO REPRESENT ALL THOSE USED ON THESE DRAWINGS, BUT TO SUPPLEMENT THE MORE COMMON ABBREVIATIONS. 1. TYP --TYPICAL 2. SIM -- SIMILAR 3. UON - UNLESS OTHERWISE NOTED 4. CONT - CONTINUOUS 5. VIF - VERIFY IN FIELD G. RESPONSIBILITY: 1. ALL SITE WORK SHALL BE PERFORMED BY A LICENSED CONTRACTOR IN ACCORDANCE WITH APPLICABLE BUILDING CODES, LOCAL ORDINANCES, ETC. 2. CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND DETAILS, NOTIFYING ENGINEER OF ANY DISCREPANCIES BETWEEN DRAWINGS, FABRICATED ITEMS, OR ACTUAL FIELD CONDITIONS. 3. THESE DRAWINGS REPRESENT THE ACCEPTABILITY OF THE 'SUNROOM' ROOM ADDITION ELEMENTS AS PROVIDED BY THE CONTRACTOR. 4. ALL DETAILS ON THESE DRAWINGS ARE ENGINEERED BASED ON INFORMATION PROVIDED BY THE CONTRACTOR AND MANUFACTURER 5. ANY DETAILS NOT SHOWN ARE TO BE ENGINEERED BY A LICENSED P.E. IN ACCORDANCE WITH STANDARD ENGINEERING PRACTICES. H. MISCELLANEOUS: I. ALUMINUM ADDITIONS ARE NOT TO BE INSTALLED ON A MANUFACTURED HOME, TRAILER HOME, OR PRE-FAB HOME. IF THE EXISTING STRUCTURE IS ONE OF THESE, A SEPARATE 4TH WALL SUPPORT SYSTEM MUST BE ENGINEERED SO THAT NO ADDITIONAULOADING'IS PLACED ON THE MANUFACTURED HOME. 2. IF ENCLOSURE CONTAINS A SWIMMING POOL OR SPA, THE BARRIER REQUIREMENTS OF THE FLORIDA BUILDING CODE 6th EDITION R 4501.17 IN ITS ENTIRETY. 3. CONTRACTOR 4. IF PAVERS ARE UNDER ALUMINUM MEMBERS THEY SHALL HAVE EPDXY ADHESIVE TO CONCRETE OR IF USING GROUT, ENSURE BONDING AGENT IS USED FIRST. 5. SCREENING MATERIAL SHALL BE 18X14X0.013 OR EQUIVALENT DENSITY SCREEN MESH ONLY UNLESS NOTED ON DRAWING S-2. 6. PLEASE NOTE: 2x2 (typ) DIAGONAL BRACING SHALL BE 2"XTWO.055" MATERIAL, UNLESS OTHERWISE NOTED ON S-2. 7. ALL ALUMINUM SCREENED ENCLOSURES SHALL BE DESIGNED SPECIFICALLY FOR THE APPLICATION STATED IN RULE 61G20-1-002: TO REMOVE SCREEN PANELS IN THE EVENT OF FORECAST WINDS THAT EXCEED 75 MPH. LABELS SHALL BE PLACED ON CHAIR RAIL MEMBERS ON ALL SCREEN WALLS IN A LOCATION THAT CAN BE EASILY SEEN AND FOR ALL PANELS ABOVE THE DESIGNED CHAIR RAIL ON ALL SCREEN WALLS SHALL BE CUT AS PRESCRIBED IN THE RULE AND THE CONTRACTOR SHALL COMPLY WITH ALL THE REQUIREMENTS STATED IN RULE 61G20-1.002 AND SECTION 19 LAWS OF FLORIDA, 553.76, 553.77., ONLY APPLIES IF SHOWN ON PAGE S-2 DRAWING PAGE. S7 LUCIE COUNTY BUILDING DIVISION FOR COMPLIA, REVIBVED BY DATE 3-S_ PLANS AND PER IT MUSY BE KEPT ON JOB OR NO INSPECTION `� III L BE MADE T HF"�F PLANS AND AU PROPOSED WORK ARE SUEJ'JFCT -I'C AW COR;FIFC T IONS "F(!UIhFU 0-yFIE 0INSPI;OTOPIS THAT WAY 0I* NIXhSSki, Y IN Of-i6)rn To ►VITIi AU/WpUr,/VjW, DESIGN DATA: 1. ULTIMATE DESIGN WIND SPEED Vult, (3 SECOND GUST): 150 MPH NOMINAL DESIGN WIND SPEED Vasd: 15. MPH 2. RISK CATEGORY: 1 3. WIND EXPOSURE: B 4. WIND LOADS: SCREEN ROOF: C+19.00/-32.48 SCREEN WALLS: SF SOLID ROOF (SCREEN WALL): SF COMPONENTS AND CLADDING LOAD: PSF 5. FACTOR APPLIED TO SCREEN WIND LOADS FOR 18X14X0.013 OR EQUIVALENT DENSITY SCREEN MESH: 0.88 6. FACTOR APPLIED TO SCREEN WIND LOADS FOR ALLOWABLE STRESS DESIGN: 0.6 7. LIVE LOAD: 3001b. VERTICAL DOWNLOAD ON PRIMARY SCREEN ENCLOSURE MEMBERS. 2001b. VERTICAL DOWNLOAD ON SCREEN ENCLOSURE PURLINS. 8. EXISTING SLAB AND OR FOOTING MEETS THE REQUIREMENTS TO RESIST THE UPLOADS FOR THE PROPOSED STRUCTURE. 10. SOLID ROOF TYPE: ALUMINUM STRUCTURAL MEMBERS HOLLOW SECTIONS 2 x 2:---------------------------------------2" x 2" x 0.044" 2 x 3:-------------------------------------2" x 3" x 0.050" 2 x 4:---------------------------------------2" x 4" x 0.050„ 2 x 5:---------------------------------------2" x 5" x 0.050" daitv6UliAIIrI,Id7ilLl l� ARE THE RESPONSIRILU OF THE CONTRACTOR OF RECORD OPEN BACK SECTIONS RKIJ ---1" x 2" x 0.04 1 x 3:------- ----- ----- --- -- ---- --- 5" SNAP SECTIONS 2 x 2 Snap: ---------------------------------- 2" x 2" x 0.045" 2 x 3 Snap:---------------------------------2" x 3" x 0.050" 2 x 4 Snap:--------------------------------- 2" x 4" x 0.045" SELF MATING (SMB 2 x 4 SMB:---------------------- 2" x 4" x 0.044" x 0.100" 2 x 5 SMB:---------------------- 2" x 5" x 0.050" x 0.118" 2 x 6 SMB:---------------------- 2" x 6" x 0.050" x 0.120" 2 x 7 SMB:---------------------- 2" x 7" x 0.057" x 0.120" 2 x 8 SMB:---------------------- 2" x 8" x 0.072" x 0.224" 2 x 9 SMB:---------------------- 2" x 9" x 0.072" x 0.224" 2 x 10 SMB:------------------- 2" x 10" x 0.092" x 0.374" Elf St Lude, Cad 0-W ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P. FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE: 73968 .Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineering's Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph#(813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@tbcplans.com Website-www.fbcplans.com C.O.A.429054 DATE: 1-9-2018 DRAWN BY: TLK REVISION: DATE: RO1 DATE: 2-23-2018 RO 2 RO 3 RO 4 PROJECT ADDRESS: GALLEGOS 1830 WELL RD FT PIERCE, FL 34945 -ONTRACTOR: K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 NOTES S 1 THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT EXPRESSED WRITTEN PERMISSION OF TRAC DESIGN. LLC 0 I 2X6 EDGE BM %n in N r N r X X to x x M P7 10'-0" (tYP) �v ,/ p0000 /�I• 4 ° ° o � A/o. 0 p 7 66 � ° � pc� o ST ° ® O o TA OF s e ° `A", CC ®®® assD P®o GAL/ ®°°rq ENGINEER OF RECORD: David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P.E. FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE: 73968 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph# (813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com W ebsite-www.fb cplans.com C.O.A.-#29054 DATE: 1-9-2018 DRAWN BY: TLK REVISION: DATE: RO 1 RO 2 RO 3 RO 4 PROJECT ADDRESS: GALLEGOS 1830 WELL RD FT PIERCE, FL 34945 K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 FLOOR PLAN S-2 THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT EXPRESSED WRITTEN PERMISSION OF TRAC DESIGN. LLC J (4) - 3/8" 0 CONCRETE NOTE:MINIMUM EMBEDMENT OF I f SCREW WITH 2-3/4" ANCHORS INTO CONCRETE FOOTING SHALL EMBEDMENT (MIN EDG — — BE 2-3/4" AT ALL POST LOCATIONS. ALL EXISTING HOST STRUCTURE DISTANCE=3" SCREW LENGTHS AT POST CONNECTIONS MIN SPACING 2') SHALL BE OF SUFFICIENT LENGTH FOR REQUIRED EMBEDMENT INTO CONCRETE BREAK FORM HEADER OR FOOTING WHEN A PAVER DECK IS PRESENT. RECEIVING CHANNEL (3) -1/4" 0 MACHINE BOLTS WITH WASHERS TOP VIEW (MIN. EDGE DISTANCE = 3/4" 3" X 3" _'POST #10 SMS AT EACH RISER MIN. SPACING 3/4 (SEE S-2 FOR SIZE) FOR PAN OR #10 SMS @ 8" O.C. FOR COMPOSITE PANEL OR (4) #11 3/4" SMS 2"x2"x 0.125" ANGLE (EXTERNAL OR EA SIDE INTERNAL) OR 0.125"RECEIVING CHANNEL (4) - 3/8" 0 CONCRETE SOLID ROOF SCREW WITH 2-3/4" EMBEDMENT (MIN EDGE DISTANCE =3" MIN SPACING 2 .a A 1-1/4" #10SMS@8"O.c. a.. a �, A (MIN) FOR COMPOSITE PANEL v d a (2) #10 SCREWS PER 12" WIDTH CONNECTING 2" (min) PAN TO HEADER (BOTTOM OR BACK OF PAN) FRONT VIEW (2) #10 X 2" SCREWS PER 12" WIDTH CONNECTING HEADER OR CHANNEL TO FASCIA. NOTE: CONCRETE SCREW ANCHOR DESIGNS ARE BASED ON TITEN HD 3/8" 0 SCREW S 1 ROOF PANEL TO FASCIA CONNECTION DETAILS ANCHORS, OTHER SIZE OR TYPE OF ANCHORS SHALL NOT BE USED. S_3 SCALE: NTS G 3"13"POST CONNECTION DETAIL S-3 SCALE: NTS 1"X2"OPEN BACK (6)- #14 X 3/4"SMS ATTACHED TO HOST W/ (1) ATTACHING ANGLE 1/4"0 CONCRETE SCREW TO BEAM EACH SIDE OR LAG WITHIN 6" OF BEAM (1" MIN. SPACING) - #10 SMS ALUMINUM RISER PAN i & @ 24" O.C. MAX BETWEENa. W/ 1" 0 NEO-WASHERS @ 8" O.C. - -- - E- BEAMS o (USE SCREW LENGTH EQUAL TO COMPOSITE PANEL THICKNESS (4] #10 SMS W/ 3/4"°� i PLUS (1) INCH) WASHERS PER 12" PANEL iv m SEE DETAIL C2 FOR ALUMINUM RISER PANS Detail C2 ����°� o � o (B) -1/4" 0 CONCRETE SCREW W/ p 1 1-1/2" EMBEDMENT INT OLi (4) 3/8"0 MACHINE MASONRY (1-1/2" MIN. SPACING i BOLTS WITH 3/4" OR (B)-1/4" 0 X 2" LAG SCREWS WASHERS EACH SIDE NOTE: IF 2X4 THRU 2X7 SME (� INTO WOOD 1' MIN SPACING) SLOPED OR FLAT 010 REDUCE THRU BOLTS BY Cl) (TYP 2 LOCATIONS) ROOF BEAM (SEE 3/8"0 MACHINE BOLT SHEET S-2 FOR SIZE) BEAM "B" 2"X2"X 0.125"ANGLE INTERMEDIATE BEAM 2X4 1 NOTES: EA. SIDE OF BEAM 1. THE MINIMUM EDGE DISTANCE 2x5 2 IS 3" FOR MASONRY EXISTING HOST STRUCTURE NOTCH POST FOR BEAM ZX6 2 STRUCTURES. (CONCRETE, GROUT FILLED POST 2, IF A RECEIVING CHANNEL IS CMU OR WOOD) 2x7 3 USED, USE TWICE THE NUMBER "B" ANCHORS INTO THE HOST S 2x8 3 STRUCTURE. ALL MINIMUM ROOF PANEL TO EDGE BEAM CONNECTION DETAIL 2x9 3 SPACING SHALL BE APPLICABLE. S_3 SCALE: NTS 2x10 4 S2 BEAM TO HOST TO CONNECTION DETAIL S-3 SCALE: NTS David W. Smith P.E. FLORIDA LICENSE: 53608 Thomas L. Hanson P FLORIDA LICENSE: 38654 Mark R. Dunn P.E. FLORIDA LICENSE: 73968 Joel Falardeau P.E. FLORIDA LICENSE: 70667 Erik Stuart P.E. FLORIDA LICENSE: 77605 FBC Plans & Engineering Services, Inc. 6272 Abbott Station Dr. Unit 101 Zephyrhills, FL 33542 Ph# (813)788-5314 Fax# 1-(866)824-7894 E-mail-erb@fbcplans.com Website-www.ibcplansxom C.O.A. #29054 DATE: 1-9-2018 DRAWN BY: TLK REVISION: DATE: RID 1 RO 2 RO 3 RO 4 PROJECT ADDRESS: GALLEGOS 1830 WELL RD FT PIERCE, FL 34945 K & S INDUSTRIES, INC. 1379 SW BILTMORE ST. PORT ST LUCIE, FL 34983 DETAILS S-3 THIS DOCUMENT SHALL NOT BE REPRODUCED IN WHOLE OR IN PART WITHOUT EXPRESSED WRITTEN PERMISSION OF TRAC DESIGN, LLC