EVALUATION REPORT
Mule -Hide Products Co., Inc.
1195 Prince Hall Drive, Suite A
Beloit, WI 53511-5481
(608) 365-3111
J
�C -2-q�fILE COPY
EXTERIOR RESEARCH & DESIGN, I.I.C.
ll r�cN Certificate of Authorization #9503
^w�J` 353 Christian Street
Oxford, CT 06478
(203) 262-9245
Evaluation Report M15060.06.09-115
FL12772-R5
Date of Issuance: 06/24/2009
Revision 5: 09/11/2017
SCOPE:
This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of
construction materials in the State of Florida. The documentation submitted has been reviewed by Robert Nieminen,
P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for
compliance with the 6th Edition (2017) Florida Building Code sections noted herein.
DESCRIPTION: Mule -Hide TPO-c Single Ply Roof Systems
LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted
herein.
CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced
Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of
this Evaluation Report by the named client constitutes agreement to notify Robert Nieminen, P.E. if the product
changes or the referenced Quality Assurance documentation changes. Trinity ERD requires a complete review of this
Evaluation Report relative to updated Code requirements with each Code Cycle.
ADVERTISEMENT: The Evaluation Report number preceded by the words "Trinity I ERD Evaluated" may be displayed in
advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its entirety.
INSPECTION: Upon request, a copy of this entire Evaluation Report shall be provided to the user by the manufacturer or
its distributors and shall be available for inspection at the job site at the request of the Building Official.
This Evaluation Report consists of pages 1 through 4, plus a 27-page Appendix.
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
The facsimile seal appearing was authorized by Robert Nieminen,
P.E. on 09/11/2017. This does not serve as an electronically signed
document.
CERTIFICATION OF INDEPENDENCE:
1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financial interest
in any company manufacturing or distributing products it evaluates.
2. Exterior Research & Design, LLC. d/b/a Trinity I ERD is not owned, operated or controlled by any company manufacturing or
distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinity) ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
or=2!1&bi9L1Ws �, �uatj n_ReD,Qr_t pr previous versions thereof, is/was used for permitting or design guidance unless retained
specif Wj9 jbCQIB1::pDtA'QW
BUILDING DIVISI
REVI�lfdr'
FOR C®PA I
REVIEWED BY
DATE — a.
PLANS AND PERMIT
MUST 66 KEPT ON JOB OR
NO INOPMOTION WILL IDS MADE
THESE PLANS AND ALL PROPOSED `"WORK
ARE SURjECT TO ANY COVEC,'TIONS
REQUIRED 0W FIELD `irIAT
MAYBE NECESSAI Y Ifd ORDER TO
COMPLY WITH ALL AP PICA II g CODES,
CONCEALED FASTENERS OR ATTACHMENTS
ARE THE RESPONSIEIUTY OF THE
CONTRACTOR OF RECORD
TRINITY I ERD
ROOFING SYSTEMS EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Single Ply Roof Systems
Compliance Statement: Mule -Hide TPO-c Single Ply Roof Systems, as produced by Mule -Hide Products Co., Inc.
have demonstrated compliance with the following sections of the 6tn Edition (2017) Florida Building Code through
testing in accordance with the following Standards. Compliance is subject to the Installation Requirements and
Limitations / Conditions of Use set forth herein.
2. STANDARDS:
Section
Property
Standard
Year
1504.3.1
Wind
FM 4474
2011
1504.7
Impact
FM 4470
2012
1507.13.2
Physical Properties
ASTM D6878
2011
1523.6.2
Wind
TAS 114
2011
3. REFERENCES:
Entity
Examination
Reference
Date
ACRC (TST4671)
TAS 114
07-051
08/29/2007
ACRC (TST4671)
TAS 114
07-059
10/15/2007
ACRC(TST4671)
FM4470
10-009
05/19/2010
ACRC(TST4671)
FM4470
11-035
06/28/2011
ACRC (TST4671)
FM4470
10-018
08/25/2010
ACRC(TST4671)
FM4470
10-019
08/25/2010
ATI (TST1588)
FM4470
01-37050.01
03/13/2000
ATI (TST1588)
TAS 114
D7772.01-109-18
07/09/2014
ATI (TST1588)
TAS 114
D7772.02-109-18
07/14/2014
CTL (TST 1577)
TAS 114
CTLA-105R
10/13/2008
CTL (TST 1577)
TAS 114
CTLA-105R-1
10/13/2008
CTL (TST 1577)
TAS 114
CTLA-10511-2
10/13/2008
CTL (TST 1577)
TAS 114
CTLA-106R
10/16/2008
CTL (TST 1577)
TAS 114
CTLA-106R-1
10/16/2008
CTL (TST 1577)
TAS 114
CTLA-106R-2
10/16/2008
CTL (TST 1577)
TAS 114
CTLA-10611-3
10/16/2008
CTL (TST 1577)
TAS 114
CTLA-106R-4
10/16/2008
CTL (TST 1577)
TAS 117
CTLA 11111
01/13/2009
ERD (TST 6049)
FM4470 / FM 4474
02764.09.05-R1
1 12/10/2007
ERD (TST 6049)
FM 4474
M5830.10.07-111
01/23/2009
ERD (TST 6049)
FM 4474
M30780.09.09
09/23/2009
ERD (TST 6049)
Physical Properties
A35880.04.12-R1
10/26/2012
ERD (TST 6049)
Physical Properties
C46470.07.14-1A
07/16/2014
ERD (TST 6049)
Physical Properties
C46470.07.14-113
07/16/2014
ERD (TST 6049)
Physical Properties
C46470.07.14-4-R1
07/21/2014
ERD (TST 6049)
Physical Properties
C46470.07.14-2A
07/30/2014
ERD (TST 6049)
Physical Properties
C46470.07.14-2B
07/30/2014
ERD (TST 11294)
FM 4474
13380.01.17
01/27/2017
ERD (TST 6049)
Physical Properties
CRL-SC14240.17
03/21/2017
ERD (TST 11294)
FM 4474
CEL-CLT16160.08.17-1
08/28/2017
ERD (TST 11294)
FM 4474
CEL-CLT16160.08.17-2
08/28/2017
FM (TST1867)
FM4470
OV7A4.AM
06/10/1992
FM (TST1867)
FM4470
3Z9A1.A1VI
10/15/1997
FM (TST1867)
FM4470
3001522
03/26/1999
FM (TST1867)
FM4470
3003393
03/30/1999
FM Approvals (TST1867)
FM 4470
3012879
04/04/2003
Exterior Research and Design, I.I.C.
Evaluation Report M15060.06.09-RS
Certificate ojAuthori:ation #9503
6" EDITION (2017) FBC NON-HVHZ EVALUATION
FL12772-RS
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Revision 5: 09/11/2017
Page 2 of 4
UTRINITY ( ER®
Entity Examination Reference Date
FM Approvals (TST1867) FM 4470 3013584 06/27/2003
FM (TST1867) FM4470 3014692 08/05/2003
FM (TST1867) FM4470 / FM 4474 3017662 06/07/2005
FM (TST1867) FM4470 / FM 4474 3023032 07/20/2005
FM (TST1867) FM4470 / FM 4474 3020845 01/25/2006
FM Approvals (TST1867) FM 4470/4474 3023458 07/18/2006
FM (TST1867) FM4470 / FM 4474 3022174 09/25/2006
FM Approvals (TST1867) FM 4470/4474 3026964 07/25/2007
FM Approvals (TST1867) FM 4470/4474 3029840 09/08/2008
FM Approvals (TST1867) FM 4470/4474 3034985 12/15/2008
FM Approvals (TST1867) FM4470 3037400 09/02/2009
FM (TST1867) FM4470 3037525 09/25/2009
FM (TST1867) FM4470 3037770 10/22/2009
FM Approvals (TST1867) FM4470/4474 3036762 03/08/2011
FM Approvals (TST1867) FM4470/4474 3041535 06/08/2011
FM Approvals (TST1867) FM4470/4474 3039340 06/24/2011
FM Approvals (TST1867) FM4470/4474 3039762 09/07/2012
FM Approvals (TST1867) FM4470/4474 3056207 02/09/2016
FM Approvals (TST1867) FM 4470/4474 RR209155 04/03/2017
PRI CMT(TST5878) TAS 114 / FM 4474 CST-016-02-01 05/04/2011
UL, LLC (QUA9625) Quality Control MLA; R13850 08/22/2007
UL, LLC (QUA9625) Quality Control Inspection Report 06/01/2017
4. PRODUCT DESCRIPTION:
The following roof covers are mechanically attached or fully adhered to Approved substrates using fasteners, stress
plates and adhesives, as outlined in the Limitations / Conditions of Use herein.
4.1 Mule -Hide TPO-c membranes are nominal 45-mil (1.1mm) or 60-mil (1.5 mm) thick, polyester -scrim
reinforced, thermoplastic olefin (TPO) single -ply roof membranes.
4.2 Mule -Hide TPO-c EXTRA membranes are nominal 72-mil (1.8mm) or 80-mil (2.Omm) thick, polyester -scrim
reinforced, thermoplastic olefin (TPO), single -ply roof membranes.
4.3 Mule -Hide TPO-c Fleece Back membrane is a nominal 45-mil (1.1mm) or 60-mil (1.5 mm) thick, polyester -
scrim reinforced, thermoplastic olefin (TPO) single -ply roof membrane with a polyester fleece backing.
4.4 Mule -Hide SA-TPO membrane is a nominal 60-mil (1.5-mm) thick, polyester -scrim reinforced, thermoplastic
olefin (TPO) single -ply roof membrane laminated to an elastomeric pressure -sensitive adhesive.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity) ERD nor Robert Nieminen, P.E. are, in any way, the Designer
of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for
permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for use in FBC HVHZ jurisdictions.
5.3 Refer to a current UL Roofing Materials Directory for fire ratings of this product.
5.4 For steel deck installations, foam plastic insulation shall be separated from the building interior in accordance
with FBC 2603.4 unless the exceptions stated in FBC 2603.4.1 and 2603.6 apply.
5.5 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural
members shall be in accordance with FBC requirements to the satisfaction of the Authority Having
Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC
Approval documentation.
5.6 For recover installations, the existing roof shall be examined in accordance with FBC 1511.
Exterior Research and Design, I.I.C. Evaluation Report M15060.06.09-115
Certificate ofAuthorization #9503 6'" EDITION (2017) FBC NON-HVHZ EVALUATION FL12772-R5
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Revision 5: 09/11/2017
Page 3 of 4
PTRINITYIERD
5.7 For mechanically attached insulation or membrane or strip -bonded insulation, the maximum design pressure
for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC
Chapter 16. Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to
resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data
Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies
marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet
1-29 (January 2016) for Zone 2/3 enhancements.
5.8 For assemblies with all components fully bonded in place, the maximum design pressure for the selected
assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No
rational analysis is permitted for these systems.
5.9 For mechanically attached insulation or membrane over existing roof decks, fasteners shall be tested in the
existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison
to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-
1 or Testing Application Standard TAS 105.
5.10 For bonded insulation or membrane over existing substrates in a re -roof (tear off) or recover installation, the
existing deck or existing roof surface shall be examined for compatibility with the adhesive to be installed. If
any surface conditions exist that bring system performance into question, field uplift testing in accordance
with ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS
124 shall be conducted on mock-ups of the proposed new roof assembly.
5.11 For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system
shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority
Having Jurisdiction, as documented through field uplift testing in accordance with ASTM E907, FM Loss
Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
5.12 Metal edge attachment (except gutters), shall be designed and installed for wind loads in accordance with FBC
Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES-1 or Roofing Application Standard RAS
111, except the basic wind speed shall be determined from FBC Figure 1609.3(1), 1609.3(2) or 1609.3(3).
5.13 All products in the roof assembly shall have quality assurance audit in accordance with F.A.C. Rule 61G20-3.
INSTALLATION:
6.1 Mule -Hide TPO-c Single Ply Roof Systems shall be installed in accordance with Mule -Hide Products Co., Inc.
published installation instructions, subject to the Limitations / Conditions of Use noted herein.
6.2 System attachment requirements for wind load resistance are set forth in Appendix 1. "MDP" = Maximum
Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects
the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been
applied). Refer to FBC 1609 for determination of design wind pressures.
6.3 For mechanically fastened membrane systems (Type D) over profiled steel deck, membrane shall be installed
running perpendicular to steel deck flutes.
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of
this product.
8. MANUFACTURING PLANTS:
Contact the noted QA agency for information on product locations covered to F.A.C. Rule 61G20-3 QA requirements.
9. QUALITYASSURANCE ENTITY:
UL, LLC—QUA9625; (414) 248-6409; karen.buchmann@ul.com
- THE 27-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION REPORT -
Exterior Research and Design, I.I.C. Evaluation Report M35060.06.09-R5
Certificate ofAuthorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL12772-RS
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Revision 5: 09/11/2017
Page 4 of 4
"APPENDIX 1 ATTACHMENT,REQUIREMENTS FOR WIND UPLIFT RESISTANCE
-
Table
Deck
Application
Type
Description
Page
IA
Wood
New, Reroof (Tear -Off), Recover
C-1
Mechanically Attached Insulation, Bonded Roof Cover
4
1B
Wood
New, Reroof (Tear -Off), Recover
D-1
Insulated, Mechanically Attached Roof Cover
4
1C
Wood
New, Reroof (Tear -Off), Recover
D-3
Insulated, Mechanically Attached Base Sheet, Bonded Roof Cover
4
1D
Wood
New, Reroof (Tear -Off), Recover
E-1
Non -Insulated, Mechanically Attached Roof Cover
5
1E
Wood
New, Reroof (Tear -Off), Recover
E-2
Non -Insulated, Mechanically Attached Base Sheet, Bonded Roof Cover
5
IF
Wood
New Construction
F
Non -Insulated, Bonded Roof Cover
5
2A
Steel or Structural Concrete
New, Reroof (Tear -Off), Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
6-7
2B
Steel or Structural Concrete
New, Reroof (Tear -Off), Recover
C-1
Mechanically Attached Insulation, Bonded Roof Cover
2B
Steel
New, Reroof (Tear -Off), Recover
C-2
Mechanically Attached Insulation, Plate -Bonded Roof Cover
10-1,
2D
Steel or Structural Concrete
New, Reroof (Tear -Off), Recover
D-1
Insulated, Mechanically Attached Roof Cover
12-15
2E
Steel or Structural Concrete
New, Reroof (Tear -Off), Recover
D-2
Insulated, Mechanically Attached Roof Cover (RUSS Strips)
16
3A
Structural Concrete
New, Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
17-18
3B
Structural Concrete
New, Reroof (Tear -Off), Recover
C-2
Mechanically Attached Insulation, Plate -Bonded Roof Cover
18-19
3C
Structural Concrete
New, Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
19
4A
LWIC
New, Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
20
4A-1
LWIC over Steel
New, Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
20
4A-2
LWC over Structural Concrete
New, Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
21
5A
Gypsum
Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
22
6A
Various
Recover
A-1
Bonded Insulation, Bonded Roof Cover
23
6B
Steel
Recover
C-2
Mechanically Attached Insulation, Plate -Bonded Roof Cover
24
6C
Steel
Recover
D-1
Insulated, Mechanically Attached Roof Cover
25
6D
Steel or Structural Concrete
Recover
E
Non -Insulated, Mechanically Attached Roof Cover
26
6E
Various
Recover
F-2
New LWC over Existing Roof, Bonded Roof Cover
27
The following notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdictio,
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
2. Unless otherwise noted, fasteners and stress plates for insulation attachment shall be as follows. Fasteners shall be of sufficient length for the following engagements:
➢ Wood Deck: Mule -Hide Drill Point Fastener or Mule -Hide HDP Fastener with Mule -Hide 3 in. Insulation Plate. Minimum Y.-inch steel penetration, engage the top flute of the steel deck
➢ Steel Deck: Mule -Hide Drill Point Fastener or Mule -Hide HDP Fastener with Mule -Hide 3 in. Insulation Plate. Minimum Y.-inch steel penetration, engage the top flute of the steel deck.
➢ Structural Concrete: Mule -Hide HDP Fastener or Mule -Hide Fluted Concrete Nail with Mule -Hide 3 in. Insulation Plate. Minimum 1-inch embedment. Fasteners installed with a pilot hole in accordance with the
fastener manufacturer's published installation instructions.
3. Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate, polystyrene, fiberboard, perlite and/or gypsum -based insulation board that meets the QA requirements of F.A.C. Rule
61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover.
4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type C-2 (plate bonded roof cover) or Type D (mechanically attached membrane),
whereby the membrane fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater type, thickness and strength to the steel and concrete
deck listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through
proper codified and/or FBC Approval documentation.
Exterior Research and Design, I.I.C. d/b/a Trinity I ERD Evaluation Report M15060.06.09-R5 for FL12772-RS
Certificate of Authorization #9503 6'" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 1 of 27
QOTRINITYIERD.
5. Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016).
6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published instructions:
➢ Mule -Hide Helix° Low -Rise Adhesive (HELIX): Continuous % to 1-inch wide beads, 12-inch o.c.
➢ ICP Adhesives CR-20: Continuous 2Y. to 3%-inch wide ribbons, 12-inch o.c.
➢ OlyBond 500 (OB-500): Continuous Y. to 1-inch wide ribbons, 12-inch o.c. using PaceCart or SpotShot application devices.
➢ Note: When multiple loyers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, adhesive ribbons shall be staggered from layer -to -layer a distance of one-half the ribbon spacing.
➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
7. Unless otherwise noted, all insulations are flat stock or taper board of the minimum thickness noted. Tapered polyisocya n u rate at the following thickness limitations may be substituted with the following Maximum
Design Pressure (MDP) limitations. In no case shall these values be used to 'increase' the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then
the thinner board listed below may be used as a drop -in for the equivalent thicker material listed in the table:
➢ ICP Adhesives CR-20: MDP -117.5 psf (Min. 1.0-inch thick)
➢ OlyBond 500 (OB500): MDP -315.5 psf (Min. 0.5-inch thick Poly ISO 1, H-Shield or ENRGY 3)
➢ OlyBond 500 (OB500): MPD -487.5 psf (Min. 0.5-inch thick Poly ISO 2 or ACFoam II)
8. Bonded polyisocyanu rate insulation boards shall be maximum 4 x 4 ft.
9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC
Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD-1, FM Loss
Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 or Roofing Application Standard RAS 137. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss
Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
10. For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no
rational analysis is permitted.
11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105.
12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing
roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with
ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13. For System Type D, steel deck applications, the roof membrane shall be run with its length perpendicular to the steel deck flutes.
14. For Structural Concrete Deck or Recover Applications using System Type C-2 (Plate Bonded Roof Cover) or Type D (Mechanically Attached Roof Cover), the insulation is optional. Alternatively, min. 0.5-inch Ir
Recovery Board, Poly ISO 1-HD, H-Shield HD or SecurShield HD or min. 0.25-inch to 0.625-inch Dens Deck, Dens Deck Prime, SECUROCK Gypsum -Fiber Roof Board or SECUROCK Glass -Mat Roof Board or min. 3/8-in l
Insulfoam R-Tech EPS or Fan -Fold may be used as a separator board, preliminarily attached prior to roof cover installation. The separator component shall be documented as meeting FBC 1505.1 and, for foam plastic,
FBC Chapter 26, when installed with the roof cover in Recover applications.
15. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to current LWC
Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness is 2-inches.
For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1.
Exterior Research and Design, LLC. d/b/a Trinity ) ERD Evaluation Report M15060.06.09-R5 for FL12772-R5
Certificate of Authorization #9503 6'" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 2 of 27
QOTRINITYIERD.'
16. For adhered membrane systems, side laps shall be minimum 2-inch wide sealed with min. 1.5-inch heat weld. Unless otherwise noted, membrane adhesive application rates are as follows:
Membrane',
Adhesive
Method
Rate
Mule -Hide TPO-c
Mule -Hide TPO-c Bonding Adhesive (TPO-c BA)
Contact (both sides)
60 ft2/gal
Mule -Hide TPO-c
Aqua Base 120 BA
Contact (both sides)
120 ft2/gal
Mule -Hide TPO-c Fleece Back
Aqua Base 120 BA
Wet lay (substrate)
120 ft2/gal
Mule -Hide TPO-c Fleece Back
Mule -Hide Helix® Low -Rise Adhesive (HELIX)
Wet lay (substrate)
FULL= continuous ribbons, maximum 4-inch o.c.
17. For membrane systems attached using TPO 10-inch Pressure -Sensitive RUSS, the underside of the membrane which comes in contact with the tape shall be primed with HP-250 Primer. The membrane shall be
secured by placing the primed portion onto the tape portion of the TPO 10-inch Pressure -Sensitive RUSS and roll with a steel hand roller to ensure contact.
18. For bonded membrane systems, unless otherwise noted, reference to "Mule -Hide TPO-c" membrane below also includes "Mule -Hide TPO-c EXTRA".
19. Vapor barrier options for use over structural concrete deck followed by adhesive -applied insulation carry the following Maximum Design Pressure (MDP) limitations. The lesser of the MDP listings below vs. those)
Table 3A applies.
VAPORBARRIEROPTIONS;STRUCTURALCONCRETEDECK, FOLLOWED BYADHESIVE-APPLIED INSULATION PERTABLE3A:
Option #
Primer
Vapor Barrier
Insulation Adhesive
MDP (psf)
Type
Application
VB-1.
Carlisle CAWGRIP Primer
F5- Air & Vapor Barrier or Carlisle VapAir Seal 72STR
Self -adhering
HELIX (RIBBON, 12-inch o.c.)
-97.5
VB-2.
ASTM D41
Carlisle SureMB 90TG Base or SureMB 120 TG Poly Base
Torch -applied
HELIX (RIBBON, 12-inch o.c.)
-97.5
VB-3.
ASTM D41
Carlisle SureMB 90 Base or SureMB 120 Poly Base
Hot -asphalt
HELIX (RIBBON, 12-inch o.c.)
-97.5
20. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads.
Exterior Research and Design, LLC. d/b/a Trinity ) ERD Evaluation Report M15060.06.09-R5 for FL12772-RS
Certificate of Authorization #9503 6'" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 3 of 27
TABLE 3A: WOOD PECKS - NEW CONSTRUCTION, REROOF (Tear
;. " -Off) or, RECOVER
SYSTEM TYPE C: MECHANICALLY ATTACHED INSULATION,' BONDED ROOF COVER
System
No.
Deck
(Note 1)
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 16)
MDP
Type
Fasteners
Attach
(psf)
W 1
Min. 19/32" plywood or
(Optional) One or more layers,
Min. 1.5-inch Poly ISO 1, H-Shield, ACFoam II,
Mule -Hide TPO-c / TPO-c BA or A
Aqua
q
wood plank
any combination, loose laid
Poly ISO 2 or ENRGY 3
Note 2
1 per 2 ftz
Base 120 BA
-45.0*
TABLE 13; WOOD'DECKS-= NEW`CONSTRUCTION; REROOF{Tear-Off) or RECOVER
SYSTEM TYPE D-1: INSULATED, MECHANICALLY HANICALLY ATTACHED ROOF COVER: - -
.
System
Roof Deck
Insulation Layer (Note 14)
Roof Cover
MDP!
Type
Attach
Membrane
Fasteners
Spacing
No
(psf)
Min. 19/32-inch plywood or wood plank at max. 24" spans
One or more
Mule -Hide EHD
W-2
attached using 8d ring shank nails spaced 6" o.c. in the field
layers, any
Preliminarily
Mule -Hide
Fasteners and 2.4
6-inch o.c. within 5.5-inch wide laps spaced 90.5-inch
-52.5
and #10 ring shank nails spaced 4" o.c. at the perimeter
combination
attached
TPO-c
Seam Plates
O.C. Outside of lap sealed with 1.5-inch heat -weld
Min. 19/32-inch plywood or wood plank at max. 24" spans
One or more
Mule -Hide EHD
W-3
attached using 8d ring shank nails spaced 6" o.c. in the field
layers, any
Preliminarily
Mule -Hide
Fasteners and 2.4
6-inch o.c. within 5.5-inch wide laps spaced 66.5-inch
-67.5
and #10 ring shank nails spaced 4" o.c. at the perimeter
combination
attached
TPO c
Seam Plates
O.C. Outside of lap sealed with 1.5-inch heat -weld
6-inch o.c. within 5-inch wide laps spaced 67-inch o.c.
Min. 23/32-inch OSB at max. 24-inch spans attached using
One or more
Preliminarily
Mule -Hide
Mule -Hide EHD
Outside of lap sealed with 1.5-inch heat -weld and 6-
W-4
8d ring shank nails spaced 6" o.c. in the field and 8" o.c. at
layers, any
attached
TPO-c
Fasteners and 2.4
inch o.c. in one row centered between the laps.
-67.5
intermediate supports
combination
Seam Plates
Center row covered with 6-inch wide cover strip
sealed with 1.5-inch heat weld at all edges
TABLE iC:` WOOD DECKS - NEW, CONSTRUCTION; REROOF,(TEAR-OFF)`OR RECOVER
SYSTEM TYPED-3: INSULATED, MECHANICALLYATTACHED BASE SHEET, BONDED ROOF COVER
System
Deck (Note 1)
Insulation (Note 14)
Base Sheet
Roof Cover
MDP
Type
Attach
Base Sheet
Fasteners
Attach
Membrane
Adhesive
No.
(psf)
Min. 19/32-inch plywood at
One or more
Atlas Summit
Mule -Hide Drill Point
12-inch o.c. at the 4-inch laps and 12-
W-5
max. 24-inch spans; #10 x 2-
layers, any
Loose -laid
Synthetic
Fastener and Mule -Hide 2"
inch o.c. at three, equally spaced
Mule -Hide SA-TPO
Self-
-120.0
inch wood screws, 6-inch o.c.
combination
Underlayment
Seam Plate
rows in the center of the sheet.
adhered
Exterior Research and Design, I.I.C. d/b/a Trinity I ERD Evaluation Report M15060.06.09-R5 for FL12772-RS
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 4 of 27
TRINITYIERD.
... . . . .TABI*0OD Dtt(S' N'EW1CONSTRUCTION, 1EROOFITearnOfflorREkVER
INSULATED; L
MTkIM. TYPE -1: ON -IMN � ' ' lib,�MEC14AICA LY'ATTACHED: R6bFCO,!A1k _
Thermal Barrier
Roof Cover
System
No.
Roof Deck
MDP
(psf)
Type
Attach
Membrane
Fasteners
Fastener
Lap Width
Lap Spacing
Seam Weld
Spacing (inch)
(inch)
(inch)
(inch)
Min. 19/32-inch thick Mule -Hide FR Deck Panel A or C or
Barrier Technology Corp "Blazeguard A or C" at max. 24-inch
(Optional) Any
Mule -Hide
Mule -Hide EHD
W-6
spans attached using No. 8 x 2%-inch long course thread
approved
Loose -laid
TPO-c
Fasteners and 2.4
12
5
48
1.5
-30.0
screws spaced 6" o.c.
thermal barrier
Seam Plates
Min. 19/32-inch thick Mule -Hide FR Deck Panel A or C or
Barrier Technology Corp "Blazeguard A or C" at max. 24-inch
(Optional) Any
Mule -Hide
Mule -Hide EHD
W-7
spans attached using No. 8 x 2%-inch long course thread
approved
Loose -laid
TPO-c
Fasteners and 2.4
6
5
72
1.5
screws spaced 6" o.c.
thermal barrier
Seam Plates
Min. 19/32-inch thick Mule -Hide FR Deck Panel A or C or
Barrier Technology Corp "Blazeguard A or C" at max. 24-inch
(Optional) Any
Mule -Hide
Mule -Hide EHD
W-8
spans attached using No. 8 x 2Y2-inch long course thread
approved
Loose -laid
TPO-c
Fasteners and 2.4
6
5
48
1.5
-75.0
screws spaced 6" o.c.
thermal barrier
Seam Plates
Min. 19/32-inch plywood at max. 24-inch spans attached
(Optional) Any
Mule -Hide
Mule -Hide EHD
48 (over
W-9
using 8d ring shank nails spaced 6-inch o.c.
approved
Loose -laid
TPO-c
Fasteners and 2.4
6
5.5
structural
1.5
-75.0
1
thermal barrier
I I
I
Seam Plates
members)
TA 66 0*&iN9TRUCTIO lkE0Q0(T R-O F R p RECbVER't
E -1E- F
,SYSTEM TYPE E-2- NON -IN C C OF VE11"
�q�ATED,,IVIE HANI ALL�YATTA�kigDWE,�HEET,,jPONDEDRO CO
System
Deck (Note 1)'
Thermal Barrier
Base Sheet
Roof Cover
MDP
Type
Attach
Base Sheet
Fasteners
I Attach
Membrane
Adhesive
No.
(psf)
Min. 19/32-inch plywood at
(Optional) Any
Atlas Summit
Mule -Hide Drill Point
12-inch o.c. at the 4-inch laps and 12-inch
W-10
max. 24-inch spans; #10 x 2-
approved
Loose -laid
Synthetic
Fastener and Mule -Hide
T2"
o.c. at three, equally spaced rows in the
Mule -Hide SA-
Self-
-120.0
inch wood screws, 6-inch o.c.
thermal barrier
Underlayment
Seam Plate
center of the sheet.
. TPO
adhered
STRUCTION TABLE 4,66D,D'
ECKS�"NEW,.CON
STEM'TVPE F: NON -INSULATED, MATED, BONDED RO OF'C OVER,-
System
Roof Deck
Roof Cover (Note 16)
MDP
Membrane
Application
No.
(psf)
Min. 15/32-inch thick Mule -Hide FR Deck Panel A or C or Barrier Technology Corp "Blazeguard A or C" at
W-11
max. 24-inch spans attached using No. 8 x 2Y2-inch long course thread screws spaced 6" o.c.
Mule -Hide TPO-c
Aqua Base 120 BA
-45.Q
rW-12
Min. 19/32-inch thick Mule -Hide FR Deck Panel A or C or Barrier Technology Corp "Blazeguard A or C" at
max. 24-inch spans attached using No. 8 x 2Y2-inch long course thread screws spaced 6" o.c.
Mule -Hide TPO-c
Aqua Base 120 BA
-52.5
Exterior Research and Design, I.I.C. d/b/a Trinity I ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M15060.06.09-115 for FL12772-RS
Revision 5: 09/11/2017
Appendix 1, Page 5 of 27
TABLE 2A; �STEEL.or STRUCTURAL CONCRETE'DECKS .- NEW CONSTRUCTION,;REROOF (Tear-Off).or-'RECOVER-
SYSTEM'TYPE B:,,MECHANICALLYATTACHIED BASE INSULATION,BONDED TOP]NSULATION,;BONDED"ROOF ,COVER
System
Deck
Base Insulation Layer
Top Insulation Layer
MDP
No.
(Note 1)
Roof Cover (Note 16)
(psf)
Type Fastener Attach
Type Attach
MULETHIDE TPO-C APPLICATIONS:
Min. 22 ga., type B, Grade 33
Min. 1.5-inch Poly ISO 1, H-
Min. 1.0-inch base insulation and/or
Mule -Hide TPO-c / TPO-c BA or
SC-1
steel or min. 2,500 psi
Shield, Polyiso HP-H
Note 2
1 per 3.2 ft a
Min. 0.25-inch Dens Deck Prime or
HELIX
Aqua Base 120 BA
-45.0*
structural concrete
SECUROCK Gypsum -Fiber Roof Board
Min. 22 ga., type B, Grade 33
Min. 2-inch Poly ISO 1, H-
Min. 1.0-inch base insulation and/or
Mule -Hide TPO c / TPO-c BA or
SC-2
steel or min. 2,500 psi
Shield, Polyiso HP-H
Note 2
1 per 4.0 ftZ
Min. 0.25-inch Dens Deck Prime or
HELIX
Aqua Base 120 BA
45.0 -
'.
structural concrete
SECUROCK Gypsum -Fiber Roof Board
Min. 22 ga., type B, Grade 33
Min. 0.5-inch Dens Deck or
Min. 1.5-inch ACFoam II, Poly ISO 2,
Mule -Hide TPO-c / TPO-c BA or
SC-3
steel or min. 2,500 psi
Dens Deck Prime
Note 2
1 per 2.0 ftZ
ENRGY 3, Poly ISO 1 or H-Shield followed
OBSOD
Aqua Base 120 BA
-37.5*
structural concrete
by Min. 0.25-inch Dens Deck Prime
Min. 22 ga., type B, Grade 33
SC-4
steel or min. 2,500 psi
Min. 2-inch Poly ISO 1. H-
Note 2
1 per 4.0 ft Z
Min 0.25-inch SECUROCK Gypsum -Fiber
OB500
Mule -Hide TPO-c / TPO-c BA or
-37.5*
structural concrete
Shield, H-Shield CG
Roof Board
Aqua Base 120 BA
Min. 22 ga., type B, Grade 33
Min. 1.5-inch ACFoam II, Poly
Mule -Hide TPO-c / TPO-c BA or
SC-5
steel or min. 2,500 psi
ISO 1, Poly ISO 2, H-Shield CG,
Note 2
1 per 2.0 ftZ
Additional layers of base insulation
OB500
-45.0*
structural concrete
ENRGY 3
Aqua Base 120 BA
Min. 22 ga., type B, Grade 33
Min. 1.5-inch ACFoam II, Poly
Min. 0.25-inch Dens Deck, Dens Deck
Mule -Hide TPO-c / TPO-c BA or
SC-6
steel or min. 2,500 psi
ISO 1, Poly ISO 2, H-Shield CG,
Note 2
1 per 2.0 ftZ
OB500
-45.0*
structural concrete
ENRGY 3
prime
Aqua Base 120 BA
Min. 22 ga., type B, Grade 33
SC-7
steel or min. 2,500 psi
Min. 0.5-inch Dens Deck or
Note 2
1 per 2.0 ftZ
Min. 1.5-inch ACFoam II, Poly ISO 2,
08500
Mule -Hide TPO-c / TPO-c BA or
_45.0*
structural concrete
Dens Deck Prime
ENRGY 3, H-Shield or Poly ISO 1
Aqua Base 120 BA
Min. 22 ga., type B, Grade 33
Min. 2.0-inch ACFoam II, Poly
SC-8
steel or min. 2,500 psi
ISO 1, Poly ISO 2, H-Shield CG,
Note 2
1 per 4.0 ft2
Additional layers of base insulation
OB500
Mule -Hide TPO-c /TPO-c BA or
-45.0*
structural concrete
ENRGY 3
Aqua Base 120 BA
Min. 22 ga., type B, Grade 33
Min. 2.0-inch ACFoam II, Poly
SC-9
steel or min. 2,500 psi
ISO 1, Poly ISO 2, H-Shield CG,
Note 2
1 per 4.0 ft2
Min. 0.25-inch Dens Deck, Dens Deck
OB500
Mule -Hide TPO-c / TPO-c BA or
-45.0*
structural concrete
ENRGY 3
Prime
Aqua Base 120 BA
Min. 22 ga., type B, Grade 33
SC-10
steel or min. 2,500 psi
Min. 1.5-inch Poly ISO 1, H-
Note 2
1 per 3.2 ft :
Min. 0.25-inch SECUROCK Gypsum -Fiber
OB500
Mule -Hide TPO-c / TPO-c BA or
-45.0*
structural concrete
Shield, H-Shield CG
Roof Board
Aqua Base 120 BA
SC-11
Min. 22 ga., type B, Grade 33
steel or min. 2,500 psi
Min. 2-inch Poly ISO 1, H-
Note 2
1 per 2.67 ftZ
Min 0.25-inch SECUROCK Gypsum -Fiber
OB500
Mule -Hide TPO-c / TPO-c BA or
-45A*
structural concrete
Shield, H-Shield CG
Roof Board
Aqua Base 120 BA
Min. 22 ga., type B, Grade 33
Min. 2-inch Poly ISO 1, H-
Min 0.25-inch SECUROCK Gypsum -Fiber
Mule -Hide TPO-c / TPO-c BA or
SC-12
steel or min. 2,500 psi
Shield, H-Shield CG
Note 2
1 per 1.6 ft2
Roof Board
OB500
Aqua Base 120 BA
_60.0
structural concrete
MULE -HIDE TPO-C FLEECE BACK APPLICATIONS:
Exterior Research and Design, LLC. d/b/a Trinity I ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M15060.06.09-R5 for FL12772-RS
Revision 5: 09/11/2017
Appendix 1, Page 6 of 27
\ TRINITY
ER® -
= .".TABLE 2A: STEEL oe STRUCTURAL CONCRETE DECKS -. NEW,CONSTRUCTION;.REROOF (Tear -Off) or:RECOVER
y, , ,SYSTEM TYPE B, 'MECHANICALLY ATTACHED BASE INSULATION,`BONDED.T.OP'INSULATION, BONDED, ROOF COVER
System
Deck
Base Insulation Layer
Top Insulation Layer
MDP
No.
(Note 1)
Roof Cover (Note 16)
(psf)
Type
Fastener
Attach
Type
Attach
Min. 22 ga., type B, Grade 33
Min. 1.5olyis Poly ISO 1, H-
Min. 1.0-inch base insulation and/or
TPO-c Fleece Back /
SC-13
steel or min. 2,500 psi
Shield, Polyiso HP-H
Note 2
1 per 3.2 ftZ
Min. 0.25-inch Dens Deck Prime or
HELIX
HELIX (FULL)
HELIX (FULL)
-45.0*
structural concrete
SECUROCK Gypsum -Fiber Roof Board
Min. 22 ga., type B, Grade 33
2-inch Poly ISO 1, H-
Min. 1.0-inch base insulation and/or
TPO-c Fleece Back /
SC-14
steel or min. 2,500 psi
Shield, Polyiso HP-H
,
Note 2
1 per 4.0 ft2
Min. 0.25-inch Dens Deck Prime or
HELIX
HELIX (FULL)ide
HELIX (
-45.0*
structural concrete
SECUROCK Gypsum -Fiber Roof Board
--
SC-15
Min. 22 ga., type B, Grade 33
steel min. psi
Min. 2-inch Poly ISO 1, H-
Note 2
1 per 1.6 ftz
Min 0.25-inch SECUROCK Gypsum -Fiber
HELIX
Mule -Hide TPO-c Fleece Back /
structural concrete
Shield, Polyiso HP-H
Roof Board
HELIX (FULL)
-60.0
Exterior Research and Design, U.C. d/b/a Trinity I ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M15060.06.09-R5 for FL12772-RS
Revision 5: 09/11/2017
Appendix 1, Page 7 of 27
TRINITY
ERD -
TABLE 29: STEEL or STRUCTURAL,CONCRETE, DECKS --NEW CONSTRUCTION, REROOF (Tear -Off) or RECOVER
SYSTEM TYPE,C-1: MECHANICALLY ATTACHED, INSULATION,;BONDED: ROOF COVER
System
Deck
Top Insulation Layer
MDP
No.
(Note 1)
Base Insulation Layer
Roof Cover (Note 16)
(psf)
Type Fasteners Attach
MULE-CAPPLIGATIONS:-.-•. .:. _ - .., - t. -. ._ .._ .. .. - - -.. ..
SC-16
Min. 22 ga., type B, Grade 33 steel
Min. 1.5" thick, one or more layers,
Min 7/16" APA or TECO rated OSB
Trufast SIP LD
1 per 3.2 ft2
Mule -Hide TPO-c / TPO-c BA or Aqua
-37.5*
any combination, loose laid
Fasteners
Base 120 BA
SC-17
Min. 22 ga., type B, Grade 33 steel or
(Optional) One or more layers, any
Min. 1-inch Poly ISO 2, ACFoam II
Note 2
1 1.6 ft2
Mule -Hide TPO-c / TPO-c BA or Aqua
min. 2,500 psi structural concrete
combination, loose laid
or ENRGY 3
per
Base 120 BA
-37.5*
SC-18
Min. 22 ga., type B, Grade 33 steel or
Min. 1.5-inch thick, one or more
Min. 0.5-inch H-Shield HD
Note 2
1 per 2.67 ft2
Mule -Hide TPO-c / TPO-c BA
-37.5*
min. 2,500 psi structural concrete
layers, any combination, loose laid
Min. 22 ga., type B, Grade 33 steel or
Min. 1.5-inch thick, one or more
Min 0.25-inch SECUROCK Gypsum-
Mule -Hide TPO-c / TPO-c BA or Aqua
SC-19
min. 2,500 psi structural concrete
layers, any combination, loose laid
Fiber Roof Board
Note 2
1 per 2.67 ft2
Base 120 BA
-37.5*
SC-20
Min. 22 ga., type B, Grade 33 steel or
Min. 1.5-inch thick, one or more
Min 0.50-inch SECUROCK Gypsum-
Note 2
1 3.2 ft2
Mule -Hide TPO-c /TPO-c BA or Aqua
min. 2,500 psi structural concrete
layers, any combination, loose laid
Fiber Roof Board
per
Base 120 BA
-45.0*
SC-21
Min. 22 ga., type B, Grade 33 steel or
Min. 1.5-inch thick, one or more
Min 0.625-inch SECUROCK
Note 2
1 4.0 ft2
Mule -Hide TPO-c /TPO-c BA or Aqua
min. 2,500 psi structural concrete
layers, any combination, loose laid
Gypsum -Fiber Roof Board
per
Base 120 BA
-45.0*
SC-22
Min. 22 ga., type B, Grade 33 steel
Min. 1.5" thick, one or more layers,
Min 7/16" APA or TECO rated OSB
Trufast SIP LD
1 per 2.67 ft2
Mule -Hide TPO-c / TPO-c BA or Aqua
-45.0*
any combination, loose laid
Fasteners
Base 120 BA
SC-23
Min. 22 ga., type B, Grade 33 steel or
One or more layers, any combination,
Min 7/16" APA or TECO rated OSB
Note 2
1 per 3.6 ft2
Mule -Hide TPO-c /TPO-c BA or Aqua
-45.0*
min. 2,500 psi structural concrete
loose laid
Base 120 BA
SC-24
Min. 22 ga., type B, Grade 33 steel or
(Optional) One or more layers, any
Min. 1-inch Poly ISO 1, H-Shield, H-
Note 2
1 1.6 ft'
Mule -Hide TPO-c / TPO-c BA or Aqua
45.0*
min. 2,500 psi structural concrete
combination, loose laid
Shield CG
per
Base 120 BA
Min. 22 ga., type B, Grade 33 steel or
(Optional) One or more layers, any
Min. 1.5-inch ACFoam II, Poly ISO
Mule -Hide TPO-c / TPO-c BA or Aqua
SC-25
min. 2,500 psi structural concrete
combination, loose laid
2, H-Shield, Poly ISO 1, H-Shield
Note 2
1 per 2.0 ft'
Base 120 BA
-45.0*
CG, ENRGY 3
Min. 22 a., type B, Grade 33 steel or
g Yp
(Optional) One or more layers, any
Min. 2.0-inch ACFoam II, Poly ISO
Mule -Hide TPO-c / TPO-c BA or Aqua
SC-26
min. 2,500 psi structural concrete
combination, loose laid
2, H-Shield, Poly ISO 1, H-Shield
Nate 2
1 per 4.0 ft2
Base 120 BA
-45.0*"
CG, ENRGY 3
SC-27
Min. 22 ga., type B, Grade 33 steel or
Min. 1.5-inch thick, one or more
Min. 0.5-inch H-Shield HD
Note 2
1 per 2.0 ft2
Mule -Hide TPO-c / TPO-c BA
-45.0*
min. 2,500 psi structural concrete
layers, any combination, loose laid
SC-28
Min. 22 ga., type B, Grade 33 steel or
Min. 1.5" thick, one or more layers,
Min 7/16" APA or TECO rated OSB
Note 2
1 per 1.9 ft2
Mule -Hide TPO-c / Aqua Base 120
-52.5
min. 2,500 psi structural concrete
any combination, loose laid
BA
SC-29
Min. 22 ga., type B, Grade 33 steel or
Min. 1.5-inch thick, one or more
Min 0.5-inch Dens Deck Prime
Note 2
1 per 1.6 ft'
Mule -Hide TPO-c / TPO-c BA
-60.0
min. 2,500 psi structural concrete
layers, any combination, loose laid
SC-30
Min. 22 ga., type B, Grade 33 steel or
Min. 1.5" thick, one or more layers,
Min 7/16" APA or TECO rated OSB
Note 2
1 per 1.9 ft'
Mule -Hide TPO-c / TPO-c BA
-75.0
min. 2,500 psi structural concrete
any combination, loose laid
Min. 22 ga., type B, Grade 33 steel or
(Optional) One or more layers, any
Min 2.0-inch ACFoam II, Poly ISO 1,
SC-31
min. 2,500 psi structural concrete
combination, loose laid
Poly ISO 2, H-Shield, H-Shield CG,
Note 2
1 per 1.6 ft'
Mule -Hide TPO-c /TPO-c BA
-75.0
ENRGY 3
Exterior Research and Design, LLC. d/b/a Trinity ( ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6'" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M15060.06.09-R5 for FL12772-R5
Revision 5: 09/11/2017
Appendix 1, Page 8 of 27
-
TABLE 2Bc STEEL or STRUCTURAL CONCRETE�DECKS ,= NEW^CONSTRUCTION; REROOF (Tear -Off) or,RECOVER
SYSTEM TYPE C-1: MECHANICALLY ATTACHED INSULATION; BONDED•ROO,F COVER
System
Deck
Top Insulation Layer
MDP
No.
(Note 1)
Base Insulation Layer
Roof Cover (Note 16)
(psf)
Type
Fasteners
Attach
SC-32
Min. 22 ga., type B, Grade 33 steel or
Min. 1.5-inch thick, one or more
Min 0.5-inch SECUROCK Gypsum-
min. 2,500 psi structural concrete
layers, any combination, loose laid
Fiber Roof Board
Note 2
1 per 1.6 ftZ
Mule -Hide TPO-c / TPO-c BA
-82.5
SC-33
Min. 22 ga., type B, Grade 33 steel or
Min. 1.5-inch thick, one or more
Min 7/16-inch APA or TECO rated
min. 2,500 psi structural concrete
layers, any combination, loose laid
OSB
Note 2
1 per 1 ftz
Mule -Hide TPO-c / TPO-c BA
-97.5
Min. 20 ga., type B, Grade 33 steel or
(Optional) Min. 1.5-inch thick, one or
Min. 0.625-inch SECUROCK
SC-34
min. 2,500 psi structural concrete
more layers, any combination, loose
Gypsum -Fiber Roof Board
Note 2
1 per 1.33 ftZ
Mule -Hide TPO-c / TPO-c BA
-112.5
laid
SC-35
Min. 18 ga., type B, Grade 33 steel or
Min. 2-inch thick, one or more layers,
Min. 0.5-inch SECUROCK Gypsum -
min. 2,500 psi structural concrete
any combination, loose laid
Fiber Roof Board
Note 2
1 per 1.33 ft�
Mule -Hide TPO-c / TPO-c BA
112.5
SC-36
Min. 22 ga., type B, Grade 33 steel or
(Optional) One or more layers, any
Min 2-inch H-Shield CG
Note 2
1 per 1 ftZ
Mule -Hide TPO-c/TPO-c BA
-120.0
min. 2,500 psi structural concrete
combination, loose laid
Min. 22 ga., type B, Grade 33 steel or
(Optional for Recover) Min. 1.5-inch
SC-37
min. 2,500 psi structural concrete
thick, one or more layers, any
Min. 2-inch Insulfoam SP
Note 2
1 per 2.7 ftZ
Mule -Hide SA-TPO, self -adhered
-30.0*
combination, loose laid
Min. 22 ga., type B, Grade 33 steel or
(Optional for Recover) Min. 1.5-inch
SC-38
min. 2,500 psi structural concrete
thick, one or more layers, any
Min. 2-inch Insulfoam SP
Note 2
1 per 2.0 ft'
Mule -Hide SA-TPO, self -adhered
-45.0*
combination, loose laid
(Optional for Recover) Min. inch
Min. 0.25-inch Dens Deck Prime or
SC-39
Min. 22 ga., type B, Grade 33 steel or
y1.
thick, one or more layers, any
SECUROCK Gypsum -Fiber Roof
Note 2
1 per 2.0 ftZ
Mule -Hide SA-TPO, self -adhered
45.0*
min. 2,500 psi structural concrete
combination, loose laid
Board or min 7/16-inch APA or
TECO rated OSB
Min. 22 ga., type B, Grade 33 steel or
(Optional) Min. 1.5-inch thick, one or
Min. 1.5-inch Poly ISO 1, H-Shield,
SC-40
min. 2,500 psi structural concrete
more layers, any combination, loose
Polyiso HP-H, SecurShield, H-Shield
Note 2
1 per 2.0 ftZ
Mule -Hide SA-TPO, self -adhered
-45.0*
laid
CG
Min. 22 ga., type B, Grade 33 steel or
(Optional) Min. 1.5-inch thick, one or
Min. 2.0-inch Poly ISO 1, H-Shield,
SC-41
min. 2,500 psi structural concrete
more layers, any combination, loose
Polyiso HP-H, SecurShield, H-Shield
Note 2
1 per 1.6 ftZ
Mule -Hide SA-TPO, self -adhered
-60.0
laid I
CG
Exterior Research and Design, I.I.C. d/b/a Trinity ) ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
e" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M35060.06.09-R5 for FL12772-R5
Revision 5: 09/11/2017
Appendix 1, Page 9 of 27
QOTRINITYIERD'
TABLE 2C:.STEEL DECKS -NEW CONSTRUCTION, REROOF (Tear -Off) or RECOVER
SYSTEM TYPE C=2>"dVIECHANICALLY ATTACHED INSULATION, PLATE -BONDED ROOF COVER .
System
Deck
Insulation Layer
Attachment
Roof Cover
MDP
Fasteners
Density
No.
(Note 1)
(Psq
Min. 22 ga., type B,
Min. 1-inch thick, one or more
Mule -Hide EHD Fastener and
1 per 5.33 ft' (6 per 4 x 8 ft board)
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
SC-42
Grade 33 steel
layers, any combination. Note
RhinoBond Plate - TPO or
Per FM Loss Prevention Data Sheet 1-29;
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-45.0
A.
RhinoBond Treadsafe Plate - TPO
Note B
per manufacturer's instructions.
Min. 22 ga., type B,
Min. 1-inch thick, one or more
Mule -Hide EHD Fastener and
1 per 4 ft' (8 per 4 x 8 ft board)
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
SC-43
Grade 33 steel
layers, any combination. Note
RhinoBond Plate - TPO or
Per FM Loss Prevention Data Sheet 1-29;
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-52.5
A.
RhinoBond Treadsafe Plate - TPO
Note B
per manufacturer's instructions.
Min. 22 ga., type B,
Mule -Mule
EHD Fastener and
-Hide TPO-c (minimum 60-mil) bonded to
SC-44
Grade 40 steel; 6 ft
Min. 1.5-inch thick, one or
RhinoBond
RhinoBond Plate - TPO or
1 per 4 ftZ
P
RHINOBOND Insulation Plate (TPO) or RHINOBOND
-52.5
spans; 5/8" puddle
more layers, any combination.
RhinoBond Treadsafe Plate
ate - TPO
(2 x 2 ft grid pattern)
TreadSafe Plate (TPO) with RHINOBOND tool per
welds 6" o.c.
manufacturers instructions.
Min. 22 ga., type B,
Min. 1-inch thick, one or more
Mule -Hide EHD Fastener and
1 per 4 ft' (8 per 4 x 8 ft board)
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
SC-45
Grade 80 steel
layers, any combination. Note
RhinoBond Plate - TPO or
Per FM Loss Prevention Data Sheet 1-29;
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-60.0
A.
RhinoBond Treadsafe Plate - TPO
Note B
per manufacturers instructions.
Min. 22 ga., type B,
Min. 1.5-inch thick, one or
Mule -Hide EHD Fastener and
1 per z per 4 x 8 ft board)
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
SC-46
Grade 33 steel
more layers, any combination.
RhinoBond Plate - TPO or
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-97.5
Note C.
RhinoBond Treadsafe Plate - TPO
Per FM Loss Prevention Data Sheet 1-29
Loss ev
per manufacturers instructions.
Min.1.5-inch thick, one or
Mule -Hide EHD Fastener and
Mule -Hide TPO-c (minimum 60-mil) bonded to
SC-47
Min. 22 ga., type B,
more layers, any combination,
RhinoBond Plate - TPO or
12-inch o.c. in rows 120-inch o.c.
RhinoBond Plate - TPO or RhinoBond Treadsafe Plate -
-30.0
Grade 80 steel
prelim attach (Note 14)
RhinoBond Treadsafe Plate - TPO
TPO with RHINOBOND tool per manufacturers
instructions.
Min. 22 ga., type B,
Min. 1.5-inch thick, one or
Mule -Hide EHD Fastener and
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
SC-48
Grade 80 steel
more layers, any combination,
RhinoBond Plate - TPO or
6-inch o.c. in rows 120-inch o.c.
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-37.5
prelim attach (Note 14)
RhinoBond Treadsafe Plate - TPO
per manufacturers instructions.
Min. 22 ga., type B,
Min. 1.5-inch thick, one or
Mule -Hide EHD Fastener and
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
SC-49
Grade 80 steel
more layers, any combination,
RhinoBond Plate - TPO or
12-inch o.c. in rows 60-inch o.c.
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-37.5
prelim attach (Note 14)
RhinoBond Treadsafe Plate - TPO
per manufacturers instructions.
Min.1.5-inch thick, one or
Mule -Hide EHD Fastener and
Mule -Hide TPO-c (minimum 60-mil) bonded to
SC-50
Min. 22 ga., type B,
more layers, any combination,
RhinoBond Plate - TPO or
12-inch o.c. in rows 60-inch o.c.
RhirioBond Plate - TPO or RhinoBond Treadsafe Plate -
-45.0
Grade 80 steel
prelim attach (Note 14)
RhinoBond Treadsafe Plate - TPO
TPO with RHINOBOND tool per manufacturers
instructions.
Min. 1.5-inch thick, one or
Mule -Hide EHD Fastener and
Mule -Hide TPO-c (minimum 60-mil) bonded to
SC-51
Min. 22 ga., type B,
more layers, any combination,
RhinoBond Plate - TPO or
6-inch o.c. in rows 120-inch o.c.
RhinoBond Plate - TPO or RhinoBond Treadsafe Plate -
-52.5
Grade 80 steel
prelim attach (Note 14)
RhinoBond Treadsafe Plate -TPO
TPO with RHINOBOND tool per manufacturers
instructions.
Exterior Research and Design, I.I.C. d/b/a Trinity ) ERD Evaluation Report M15060.06.09-R5 for FL12772-R5
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 10 of 27
TABLE 2C: STEEL DECKS - NEW ,CONSTRUCTION, REROOF (Tear -Off) or RECOVER
SYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, PLATE -BONDED ROOF COVER
System
Deck
Insulation Layer
Attachment
Roof Cover
MDP
Fasteners
Density
No.
(Note 1)
(pso
Min. 22 ga., type B,
Min. 1.5-inch thick, one or
Mule -Hide EHD Fastener and
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
SC-52
Grade 80 steel
more layers, any combination,
RhinoBond Plate - TPO or
6-inch o.c. in rows 60-inch o.c.
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-67.5
prelim attach (Note 14)
RhinoBond Treadsafe Plate - TPO
per manufacturer's instructions.
Notes:
A. For these assemblies, the 8 ft insulation board length is placed perpendicular to the steel deck ribs.
B. The plate/fastener combination offset 12 inch from adjacent rows.
C. For these assemblies, the 8 ft insulation board length is placed perpendicular to the steel deck ribs and each row of insulation is staggered by 1 foot.
Exterior Research and Design, LLC. d/b/a Trinity ( ERD Evaluation Report M15060.06.09-R5 for FL32772-R5
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 11 of 27
QOTRINITYIERD'
= TABLE 2D: STEEL or STRUCTURAL CONCRETE DECKS - NEW CONSTRUCTION, REROOF (Tear -Off) or RECOVER
SYSTEM TYPE p-1: INSULATED, MECHANICALLY ATTACHED ROOF COVER
System
Insulation Layer (Note 14)
Roof Cover
No.
Roof Deck
Type
Attach
Membrane
Fasteners
Fastener Spacing
Lap Width
Lap Spacing
Seam Weld
MDP
inch
inch
inch(inch)(Psfl
SC-53
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
more layers, any
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener and Mule -Hide
18
5.5
66.5
80 steel
combination
attach
or TPO-c EXTRA
2.4" Seam Plate
1.5
-30.0
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener (steel only) or
SC-54
33 steel or min. 2,500 psi
more layers, any
attach
or TPO-c EXTRA
HDP Fastener (concrete only) and Mule-
12
5.5
138.5
1.5
-30.0
structural concrete
combination
Hide 2.4" Seam Plate
�
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener (steel only) or
SC-55
33 steel or min. 2,500 psi
more layers, any
HDP Fastener (concrete only) and Mule-
12
5.5
91
1.5
-30.0
structural concrete
combination
attach
or TPO-c EXTRA
Hide 2.4" Seam Plate
Min. 22 ga., type B, Grade
Min. 1-inch, one or
33 steel, 6 ft span, 5/8"
more layers, any
SC-56
diameter puddle welds 6"
combination (optional
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Plus Fasteners and
o.c., side laps secured 24"
for recover) followed
attach
or TPO-c EXTRA
Mule -Hide 2.4" PLUS Seam Plate
12
5.5
90.5
1.5
-30.0
o.c. w/ Y4"-14x1" long self-
by 3/8-inch Insulfoam
tapping hex -head screw
R-Tech EPS or Fan -Fold
Min. 22 ga., type B, Grade
33 steel, 6 ft span, 5/8"
Min. 1-inch, one or
Mule -Hide TPO-c
SC-57
diameter puddle welds 6"
more layers, any
Prelim.
(min. nominal 60-
Mule -Hide EHD Plus Fasteners and
12
5.5
90.5
1.5
-37.5
o.c., side laps secured 24"
combination
Attach
mil) or TPO-c
Mule -Hide 2.4" PLUS Seam Plate
o.c. w/'/<"-14x1" long self-
EXTRA
tapping hex -head screw
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Mule -Hide EHD Fastener (steel only) or
SC-58
80 steel or min. 2,500 psi
more layers, any
Prelim.
Mule -Hide
HDP Fastener (concrete only) and Mule-
12
5.5
115
1.5
-37.5
structural concrete
combination
attach
EXTRA
or TPO-c EXXTRA
Hide 2.4" Seam Plate
Min. 22 ga., type B, Grade
40 steel; 6 ft spans; 5/8"
Min. 1-inch, one or
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener (steel only) or
SC-59
puddle welds 6" o.c. or
more layers, any
(min. 60-mil) or
HDP Fastener (concrete only) Fasteners
6.
5.5
138.5
1.5
-37.5
min. 2,500 psi structural
combination
attach
TPO-c EXTRA
and Mule -Hide 2.4" Seam Plate
concrete
Min. 22 ga., type B, Grade
33 steel, 6 ft span, 5/8"
SC-60
diameter puddle welds 6"
Min. 1-inch, one or
more layers, any
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener and Mule -Hide
6
o.c., side laps secured 24"
attach
or TPO-c EXTRA
2.4" Seam Plate
5.5
138.5
1.5
=45.0
o.c. w/'/<"-14x1" long self -
combination
tapping hex -head screw
Exterior Research and Design, I.I.C. d/b/a Trinity ) ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6'" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M15060.06.09-R5 for FL12772-RS
Revision 5: 09/11/2017
Appendix 1, Page 12 of 27
QOTRINITYIERD'
TABLE 2D: STEEL or STRUCTURAL CONCRETE DECKS - NEW CONSTRUCTION, REROOF (Tear -Off) or RECOVER
SYSTEM TYPED-1: INSULATED, MECHANICALLY ATTACHED ROOF COVER
System
Insulation Layer (Note 14)
Roof Cover
No.
Roof Deck
Type
Attach
Membrane
Fasteners
Fastener Spacing
Lap Width
Lap Spacing
Seam Weld
MDP
(psfl
inch
inch
inch
(inch)
Min. 22 a.,
g type B, Grade
Min. one or
Mule -Hide EHD Plus Fasteners and
SC-61
80 steel °r min. 2,500 psi
more layers, any
layers,
Prelim.
Mule -Hide TPO-c
Mule -Hide 2.4" PLUS Seam Plate (steel
12
5.5
115
1.5
-45.0
structural concrete
combination
attach
or TPO-c EXTRA
only) or HDP Fastener and Mule -Hide
2.4" Seam Plates
Min. 18 ga., type B, Grade
Min. 1.5-inch, one or
Mule -Hide EHD Fasteners (steel only) or
SC-62
33 steel or min. 2,500 psi
more layers, any
Prelim.
Mule -Hide
HDP Fastener (concrete only) and Mule-
12
5.5
115
1.5
-45.0 i
structural concrete
combination
attach
EXTRA RA
or TPO-c E
Hide 2.4" Seam Plates
Min. 22 ga., type B, Grade
33 steel, 6 ft span, 5/8"
Mule -Hide TPO-c
SC-63
diameter puddle welds 6"
Min. 1-inch, one or
more layers, any
Prelim.
(min. nominal 60-
Mule -Hide EHD Fastener and Mule -Hide
6
5.5
114.5
1.5
o.c., side laps secured 24"
attach
mil) or TPO-c
2.4" Seam Plate
-45.0
o.c. w/ Y4"-14x1" long self-
combination
EXTRA
tapping hex -head screw
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Mule -Hide EHD Fastener (steel only) or
SC-64
80 steel or min. 2,500 psi
more layers, any
Prelim.
Mule-Hc
HDP Fastener (concrete only) and Mule-
12
5.5
114.5
1.5
-45.0
structural concrete
combination
attach
EXTRA RA
or TPO-c E
Hide 2.4" Seam Plate
Min. 22 a.,
g type B, Grade
Min. one or
Mule -Hide EHD Plus Fasteners and
SC-65
steel min. psi
layers,
more layers, any
Prelim.
Mule -Hide TPO-c
Mule -Hide 2.4" PLUS Seam Plate (steel
12
5.5
91
1.5
45.0
l
structural concrete
structural to
combination
attach
or TPO-c EXTRA
only) or HDP Fastener and Mule -Hide
2.4" Seam Plates
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Mule -Hide EHD Fastener (steel only) or
SC-66
80 steel or min. 2,500 psi
more layers, any
Prelim.
HDP Fastener (concrete only) and Mule-
12
5.5
91
1.5
-45.0
structural concrete
combination
attach
or TPOideXTRA
or TPO-c EXTRA
Hide 2.4" Seam Plate
Min. 22 ga., type B, Grade
33 steel, 6 ft span, 5/8"
diameter puddle welds 6"
Min. 1-inch, one or
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener and Mule -Hide
SC-67
o.c., side laps secured 24"
more layers, any
attach
or TPO-c EXTRA
2.4" Seam Plate
6
5.5
66.5
1.5
45.0
o.c. w/'/<<"-14x1" long self -
combination
ation
tapping hex -head screw
Min. 22 ga., type B, Grade
33 steel, 6 ft span, 5/8"
Mule -Hide TPO-c
diameter puddle welds 6"
Min. 1-inch, one or
Prelim.
(min. nominal 60-
Mule -Hide EHD Plus Fasteners and
SC-68
o.c., side laps secured 24"
more layers, any
attach
mil) or TPO-c
Mule -Hide 2.4" PLUS Seam Plate
6
5.5
114.5
1.5
-52.5
%
o.c. w/ "-14x1" long self-
combination
EXTRA
tapping hex -head screw
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Mule -Hide TPO-c
SC-69
40 steel; 6 ft spans; 5/8"
more layers, any
Prelim.
(min. 60-mil) or
Mule -Hide EHD Fastener and Mule -Hide
6
5.5
114.5
1.5
-52.5
puddle welds 6" o.c.
combination
attach
TPO-c EXTRA
2.4" Seam Plate
Exterior Research and Design, I.I.C. d/b/a Trinity ) ERD Evaluation Report M15060.06.09-R5 for FL12772-RS
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVH2 EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 13 of 27
'TABLE 2D: STEEL or STRUCTURAL CONCRETE DECKS - NEW CONSTRUCTION, REROOF. (Tear -Off) or RECOVER
SYSTEM.TYPE D-1: INSULATED, MECHANICALLY ATTACHED ROOF COVER
System
Insulation Layer (Note 14)
Roof Cover
No,
Roof Deck
Type
Attach
Membrane
Fasteners
Fastener Spacing
Lap Width
Lap Spacing
Seam Weld
MDP
(psf)
(inch)
(inch)
(inch)
(inch)
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener (steel only) or
SC-70
33 steel or min. 2,500 psi
more layers, any
attach
or TPO-c EXTRA
HDP Fastener (concrete only) and Mule-
6
5.5
138.5
1.5
-52.5
structural concrete
combination
Hide 2.4" Seam Plate
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Prelim.
Mule-Hc
Mule -Hide EHD Fastener (steel only) or
SC-71
33 steel or min. 2,500 psi
more layers, any
HDP Fastener (concrete only) and Mule-
6
5.5
91
1.5
-52.5
structural concrete
combination
attach
or TPO-c E
EXTRA RA
Hide 2.4" Seam Plate
Min. 22 ga., type B, Grade
33 steel, 6 ft span, 5/8"
SC-72
diameter puddle welds 6"
Min. 1-inch, one or
more layers, any
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener and Mule -Hide
o.c., side laps secured 24"
attach
or TPO-c EXTRA
2.4" Seam Plate
6
5.5
90.5
1.5
-52.5
o.c. w/'/<"-14x1" long self -
combination
tapping hex -head screw
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener (steel only) or
SC-73
33 steel or min. 2,500 psi
more layers, any
HDP Fastener (concrete only) and Mule-
12
5.5
42.5
1.5
-52.5
structural concrete
combination
attach
or TPO-c EXTRA
Hide 2.4" Seam Plate
Min. 22 ga., type B, Grade
Min. 1-inch, one or
33 steel, 6 ft span, 5/8"
more layer's, any
SC-74
diameter puddle welds 6"
combination (optional
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener and Mule -Hide
o.c., side laps secured 24"
for recover) followed
attach
or TPO-c EXTRA
2.4" Seam Plate
6
5.5
138.5
1.5
-60.0
o.c. w/ %"-14x1" long self-
by 3/8-inch Insulfoam
tapping hex -head screw
R-Tech EPS or Fan -Fold
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Mule -Hide EHD Plus Fasteners and
SC-75
33 steel or min. 2,500 psi
p
more layers, an y
Prelim.
Mule -Hide TPO-c
Mule -Hide 2.4" PLUS Seam Plate (steel
6
5.5
138.5
1.5
-60.0
structural concrete
combination
attach
or TPO-c EXTRA
only) or HDP Fastener and Mule -Hide
2.4" Seam Plates
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Mule -Hide EHD Fastener (steel only) or
SC-76
80 steel or min. 2,500 psi
more layers, any
Prelim.
Mule -Hide TPO-c
HDP Fastener (concrete only) and Mule-
6
5.5
138.5
1.5
-60.0
structural concrete
combination
attach
or TPO-c EXTRA
Hide 2.4" Seam Plate
Min. 1.5-inch, one or
Min. 22 ga., type B, Grade
more layers, any
Mule -Hide EHD Fastener (steel only) or
SC-77
33 steel or min. 2,500 psi
combination followed
Loose
Mule -Hide TPO-c
HDP Fastener (concrete only) and Mule-
6
5.5
91
1.5
-60.0
structural concrete
by 3/8-inch Insulfoam
laid
or TPO-c EXTRA
Hide 2.4" Seam Plate
R-Tech EPS
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Mule -Hide EHD Fastener (steel only) or
SC-78
33 steel or min. 2,500 psi
more layers, any
Prelim.
Mule -Hide TPO-c
HDP Fastener (concrete only) and Mule-
12
5.5
54.5
1.5
-60;0
structural concrete
combination
attach
or TPO-c EXTRA
Hide 2.4" Seam Plate
Exterior Research and Design, LLC. d/b/a Trinity ) ERD
Certificate of Authorization #t9503
Prepared by: Robert Nieminen, PE-59166
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M15060.06.09-RS for FL12772-RS
Revision 5: 09/11/2017
Appendix 1, Page 14 of 27
TTRINITY I ERD
- ;TABLE, 2D: STEEL or STRUCTURAL CONCRETE DECKS - NEW CONSTRUCTION, REROOF (Tear -Off) or RECOVER
SYSTEM,TYPE D-1: INSULATED, MECHANICALLY -ATTACHED ROOF COVER
System
Insulation Layer (Note 14)
Roof Cover
No.
Roof Deck
Type
Attach
Membrane
Fasteners
Fastener Spacing
Lap Width
Lap Spacing
Seam Weld
MDP
(psf)
(inch)
(inch)
(inch)
(inch)
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener (steel only) or
SC-79
33 steel or min. 2,500 psi
P
la
an , ers more
Y Y
HDP Fastener (concrete only) and Mule-
6
5.5
90.5
1.5
-67.5
structural concrete
combination
attach
or TPO-c EXTRA
Hide 2.4" Seam Plate
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener (steel only) or
SC-80
80 steel or min. 2,500 psi
more layers, any
HDP Fastener (concrete only) and Mule-
9
5.5
54.5
1.5
-75'0
structural concrete
combination
attach
or TPO-c EXTRA
Hide 2.4" Seam Plate
1
Min. 22 ga., type B. Grade
Min. 1.5-inch, one or
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener (steel only) or
SC-81
33 steel or min. 2,500 psi
more layers, any
HDP Fastener (concrete only) and Mule-
6
5.5
42.5
1.5
-82.5
structural concrete
combination
attach
or TPO-c EXTRA
Hide 2.4" Seam Plate
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener (steel only) or
SC-82
80 steel or min. 2,500 psi
more layers, any
HDP Fastener (concrete only) and Mule-
6
5.5
54.5
1.5
-90.0
structural concrete
combination
attach
orTPO-c EXTRA
Hide 2.4" Seam Plate
SC-83
Min. 22 ga., type B, Grade
Min. 1.5-inch, one or
more layers, any
Prelim.
Mule -Hide TPO-c
Mule -Hide EHD Fastener and Mule -Hide
80 steel
combination
attach
or TPO-c EXTRA
2.4" Seam Plate
6
5.5
42.5
1.5
-112.5
Exterior Research and Design, I.I.C. d/b/a Trinity ) ERD Evaluation Report M15060.06.09-R5 for FL12772-RS
Certificate of Authorization #9503 6'" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 15 of 27
TABLE 2E; STEEL or STRUCTURAL CONCRETE DECKS'- NEW CONSTRUCTION, REROOF (Tear -Off) or RECOVER
SYSTEM TYPE D-2: INSULATED, MECHANICALLY ATTACHED ROOF COVER (RUSS Strips)
System
Deck
Insulation
Roof Cover
MDP
Type
Attach
Membrane
Fasteners
Attachment
No.
(Psf)
Min. 22 ga., type B,
One or more
Mule -Hide
Mule -Hide EHD Fastener (steel
TPO 10-inch Pressure -Sensitive RUSS strips are applied over the insulation
SC-84
Grade 80 steel or min.
layers, any
Prelim.
TPO-c or TPO-c
only) or HDP Fastener (concrete
spaced 138-inch o.c. The plates are centered over each strip and fastened 6-
-30.0
2,500 psi structural
combination
attached
EXTRA
only) and Mule -Hide 2.4" Seam
inch o.c. Roof cover adhered to each strip by first priming with TPO Tape
concrete
Plates
Primer at the strip location, then rolling into place with a hand roller.
Min. 22 ga., type B,
One or more
Mule -Hide
Mule -Hide EHD Fastener (steel
TPO 10-inch Pressure -Sensitive RUSS strips are applied over the insulation
SC-85
Grade 80 steel or min.
layers, any
Prelim.
TPO-c or TPO-c
only) or HDP Fastener (concrete
spaced 114-inch o.c. The plates are centered over each strip and fastened 6
-45.0.1-
2,500 psi structural
combination
attached
EXTRA
only) and Mule -Hide 2.4" Seam
inch o.c. Roof cover adhered to each strip by first priming with TPO Tape
concrete
Plates
Primer at the strip location, then rolling into place with a hand roller.
Min. 22 ga., type B,
One or more
Mule -Hide
Mule -Hide EHD Fastener (steel
TPO 10-inch Pressure -Sensitive RUSS strips are applied over the insulation
SC-86
Grade 80 steel or min.
layers, any
Prelim.
TPO-c or TPO-c
only) or HDP Fastener (concrete
spaced 90-inch o.c. The plates are centered over each strip and fastened 6-
-52.5
2,500 psi structural
combination
attached
EXTRA
only) and Mule -Hide 2.4" Seam
inch o.c. Roof cover adhered to each strip by first priming with TPO Tape
concrete
Plates
Primer at the strip location, then rolling into place with a hand roller.
Min. 22 ga., type B,
One or more
Mule -Hide
Mule -Hide EHD Fastener (steel
TPO 10-inch Pressure -Sensitive RUSS strips are applied over the insulation
SC-87
Grade 80 steel or min.
layers, any
Prelim.
TPO-c or TPO-c
only) or HDP Fastener (concrete
spaced 120-inch o.c. The plates are centered over each strip and fastened 6-
-60.0
2,500 psi structural
combination
attached
EXTRA
only) and Mule -Hide 2.4" Seam
inch o.c. Roof cover adhered to each strip by first priming with HP-250
concrete
Plates
Primer at the strip location, then rolling into place with a hand roller.
Min. 22 ga., type B,
One or more
Mule -Hide
Mule -Hide EHD Fastener (steel
TPO 10-inch Pressure -Sensitive RUSS strips are applied over the insulation
SC-88
Grade 80 steel or min.
layers, any
Prelim.
TPO-c or TPO-c
only) or HDP Fastener (concrete
spaced 60-inch o.c. The plates are centered over each strip and fastened 12-
-60.0
2,500 psi structural
combination
attached
EXTRA
only) and Mule -Hide 2.4" Seam
inch o.c. Roof cover adhered to each strip by first priming with HP-250
concrete
Plates I
Primer at the strip location, then rolling into place with a hand roller.
Exterior Research and Design, L-C. d/b/a Trinity ( ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 36S-3111
Evaluation Report M15060.06.09-R5 for FL12772-RS
Revision 5: 09/11/2017
Appendix 1, Page 16 of 27
TABLE 3A: STRUCTURAL CONCRETE;DECKS — NEW CONSTRUCTION OR REROOF (TEAR -OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED ROOF COVER
REFER TU NOTE 19 FOR VAPOR BARRIER OPTIONS"
System
Roof Deck
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 16)
MDP
No.
(Note 1)
Type Attach
Type Attach
Membrane Application
(psf)
MULE -HID ETPO-CAPPLICATIONS: - '.,, • " -
(Optional) Min. 1.5-inch Poly ISO 1, H-Shield,
C-1.
Min. 2,500 psi
structural concrete
Polyiso HP-H, Poly ISO 2, ACFoam II, H-Shield
HELIX
Min. 0.25-inch Dens Deck Prime
HELIX
Mule -Hide TPO-c
Aqua Base 120 BA
-127.5
CG, SecurShield
',:-2.
Min. 2,500 psi
Min. 1.5-inch Poly ISO 1, H-Shield, Polyiso HP-H,
structural concrete
Poly ISO 2, ACFoam ll, H-Shield CG, SecurShield
HELIX
(Optional) Additional layers of base insulation
HELIX
Mule -Hide TPO-c
Aqua Base 120 BA
127.5
(Optional) Min. 1.5-inch Poly ISO 1, H-Shield,
C-3.
Min. 2,500 psi
structural concrete
Polyiso HP-H, Poly ISO 2, ACFoam II, H-Shield
HELIX
Min. 0.25-inch Dens Deck Prime
HELIX
Mule -Hide TPO-c
TPO-c BA
-195.0
CG, SecurShield
(Optional) Min. 1.5-inch Poly ISO 1, H-Shield,
C-4.
Min. psi
Polyiso HP-H, Poly ISO 2, ACFoam II, H-Shield
HELIX
Min. Dens Deck Prime or SECUROCK
HELIX
Mule -Hide TPO-c
TPO-c BA or Aqua
-195.0
u
structural
structural concrete
CG, SecurShield
minch
Gypsum -Fiber Roof Board
Base 120 BA
C-5.
Min. 2,500 psi
Min. 1.5-inch Poly ISO 1, H-Shield, Polyiso HP-H,
HELIX
(Optional) Additional layers of base insulation
HELIX
Mule -Hide TPO-c
TPO-c BA
-232.5
structural concrete
Poly ISO 2, ACFoam 11, H-Shield CG, SecurShield
C-6.
Min. 2,500 psi
Min. 1.5-inch ACFoam II, H-Shield, ENRGY 3 or
structural concrete
Poly ISO 1, Poly ISO 2
CR-20
(Optional) Additional layers of base insulation
CR-20
Mule -Hide TPO-c
Aqua Base 120 BA
-127.5
C 7
Min. 2,500 psi
(Optional) Min. 1.5-inch ACFoam II, H-Shield,
structural concrete
ENRGY 3 or Poly ISO 1, Poly ISO 2
CR-20
Min. Y.-inch Dens Deck or Dens Deck Prime
CR-20
Mule -Hide TPO-c
Aqua Base 120 BA
-127.5
C 8
Min. 2,500 psi
Min. 1.5-inch ACFoam II, H-Shield, ENRGY 3 or
CR-20
(Optional) Additional layers of base insulation
CR-20
Mule -Hide TPO-c
TPO-c BA
-232.5
structural concrete
Poly ISO 1, Poly ISO 2
Min. 2,500 psi
(Optional) Min. 1.5-inch ACFoam Il, H-Shield,
C 9
structural concrete
ENRGY 3 or Poly ISO 1, Poly ISO 2
CR-20
Min. Y.-inch Dens Deck or Dens Deck Prime
CR-20
Mule -Hide TPO-c
TPO-c BA
-232.5
\ ` 10
Min. 2,500 psi
Min. 1.5-inch Poly ISO 1, H-Shield, H-Shield CG
OB500
Min. 0.25-inch SECUROCK Gypsum -Fiber Roof
OB500
Mule -Hide TPO-c
TPO-c BA
-120.0
structural concrete
Board
C-11.
Min. 2,500 psi
Min. 1.5-inch ACFoam II, H-Shield, ENRGY 3 or
OB500
(Optional) Additional layers of base insulation
OB500
Mule -Hide TPO-c
Aqua Base 120 BA
127.5
structural concrete
Poly ISO 1, Poly ISO 2
C-12.
Min. 2,500 psi
(Optional) Min. 1.5-inch ACFoam II, H-Shield,
structural concrete
ENRGY 3 or Poly ISO 1, Poly ISO 2
OB500
Min. Y.-inch Dens Deck or Dens Deck Prime
OB500
Mule -Hide TPO-c
Aqua Base 120 BA
-127.5
C-13.
Min. 2,500 psi
Min. 1.5-inch ACFoam II, H-Shield, ENRGY 3 or
OB500
(Optional) Additional layers of base insulation
OB500
Mule -Hide TPO-c
TPO-c BA
-150.0
structural concrete
Poly ISO 1, Poly ISO 2
C-14.
Min. 2,500 psi
(Optional) Min. 1.5-inch ACFoam II, H-Shield,
structural concrete
ENRGY 3 or Poly ISO 1, Poly ISO 2
OB500
Min. Y.-inch Dens Deck or Dens Deck Prime
OB500
Mule -Hide TPO-c
TPO-c BA
-150.0
C-15.
Min. 2,500 psi
Min. 2-inch Poly ISO 1, H-Shield, H-Shield CG
OB500
Min. 0.25-inch SECUROCK Gypsum -Fiber Roof
OB500
Mule -Hide TPO-c
TPO-c BA or Aqua
-247.5
structural concrete
Board
Base 120 BA
MULE-.HIDETPO-C,FLEECE$ACKAPP.LICATIONS: - • - -• ,. -- .. - •, ..
Exterior Research and Design, LLC. d/b/a Trinity I ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M15060.06.09-RS for FL12772-RS
Revision 5: 09/11/2017
Appendix 1, Page 17 of 27
QOTRINITYIERD
TABLE 3A: STRUCTURAL CONCRETE DECKS — NEW CONSTRUCTION OR REROOF (TEAR -OFF)
SYSTEM TYPE A-1: BONDED INSULATION, BONDED. ROOF COVER -
REFER TO NOTE 19 FOR' VAPOR BARRIER OPTIONS
System
Roof Deck
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 16)
MDP
No.
(Note 1)
Type
Attach
Type
Attach
Membrane
Application
(Psf)
C-16.
Min. 2,500 psi
Min. 1.5-inch Poly ISO 1, H-Shield, Polyiso HP-H,
Min. 0.5-inch Poly ISO 1-HD, H-Shield HD,
Mule -Hide TPO-c
structural concrete
Poly ISO 2, ACFoam II, H-Shield CG, SecurShield
HELIX
SecurShield HD Plus
HELIX
Fleece Back
HELIX (FULL)
-165.0
Min. psi
Min. inch Poly ISO 1, ld, Polyiso HP-H,
Min. 0.25-inch Dens Deck Prime, DEXcell FA Glass
Mule -Hide TPO-c
C-17.
structural
structural concrete
SO
Poly ISO 2, ACFoam II, H-Shield CG, SecurShield
Meld
HELIX
Mat Roof Board, SECUROCK Gypsum -Fiber Roof
HELIX
Fleece Back
HELIX (FULL)
-195.0
\
Board or min. 7/16-inch DEXcell Cement Roof Board
„s 18
Min. 2,500 psi
Min. 1.5-inch Poly ISO 1, H-Shield, Polyiso HP-H,
HELIX
(Optional) Additional layers of base insulation
HELIX
Mule -Hide TPO-c
HELIX (FULL)
-322.5
structural concrete
Poly ISO 2, ACFoam II, H-Shield CG, SecurShield
Fleece Back
MULE-HIDESA-TPOAPPUCATIONS: - - -
Min. 2,500 psi
(Optional) One or more layers, min. 1-inch
HELIX, 4-
HELIX, 4-
Mule -Hide SA-
_T
C-19.
structural concrete
Insulfoam I, II, IX, Vill, XIV or XV
inch o.c.
Min. 2-inch Insulfoam SP
inch o.c.
TPO
Self -adhered
315.0
TABLE 3B:.•STRUCTURAL CONCRETE.DECKS.- NEW, CONSTRUCTION, REROOF (Tear -Off) or RECOVER
SYSTEM TYPE G.2: MECHANICALLY ATTACHED INSULATION, PLATE -BONDED ROOF COVER
System
Deck
Insulation Layer
Attachment
Roof Cover
MOP
Fasteners
Density
No.
(Note 1)
(psf)
1 per 5.33 ftZ
Min. 2,500
Min. 1-inch thick, one or more
Mule -Hide DHP Fastener and RhinoBond Plate
(6 parts per 4 x 8 ft board)
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
C-20.
psi structural
layers, any combination.
- TPO or RhinoBond Treadsafe Plate - TPO
Per FM Loss Prevention Data
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-45.0
concrete
per manufacturer's instructions.
Sheet 1-29; Note A
1 per 4 ft2
Min. 2,500
Min. 1-inch thick, one or more
Mule -Hide DHP Fastener and RhinoBond Plate
(8 parts per 4 x 8 ft board)
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
r-21.
psi structural
layers, any combination.
- TPO or RhinoBond Treadsafe Plate - TPO
Per FM Loss Prevention Data
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-60.0
-
concrete
per manufacturer's instructions.
Sheet 1-29; Note A
1 per 2 ft'
Min. 2,500
Min. 1.5-inch thick, one or more
Mule -Hide DHP Fastener and RhinoBond Plate
(16 parts per 4 x 8 ft board)
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
C-22.
psi structural
layers, any combination. Note B.
- TPO or RhinoBond Treadsafe Plate - TPO
Per FM Loss Prevention Data
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-97.5
concrete
per manufacturer's instructions.
Sheet 1-29
Min. 2,500
Min. 1.5-inch thick, one or more
Mule -Hide DHP Fastener and RhinoBond Plate
Mule -Hide TPO-c (minimum 60-mil) bonded to RhinoBond
C-23.
psi structural
layers, any combination, prelim
- TPO or RhinoBond Treadsafe Plate - TPO
12-inch o.c. in rows 120-inch o.c.
Plate - TPO or RhinoBond Treadsafe Plate - TPO with
-30.0
concrete
attach (Note 14)
RHINOBOND tool per manufacturer's instructions.
Min. 2,500
Min. 1.5-inch thick, one or more
Mule -Hide DHP Fastener and RhinoBond Plate
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
C-24.
psi structural
layers, any combination, prelim
- TPO or RhinoBond Treadsafe Plate - TPO
6-inch o.c. in rows 120-inch o.c.
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-37.5
concrete
attach (Note 14)
per manufacturer's instructions.
Exterior Research and Design, LLC. d/b/a Trinity I ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6TH EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M15060.06.09-R5 for FL12772-RS
Revision 5: 09/11/2017
Appendix 1, Page 18 of 27
Q0TRINITYIERD
TABLE 3B:' STRUCTURAL CONCRETE DECKS - NEW CONSTRUCTION, REROOF.(Tear-Off) or RECOVER
SYSTEM TYPE C-2: MECHANICALLY ATTACHED INSULATION, PLATE -BONDED ROOF COVER
System
'No.
Deck
Insulation Layer
Attachment
Roof Cover
MDP
Fasteners
Density
(Note 1)
(psf)
Min. 2,500
Min. 1.5-inch thick, one or more
Mule -Hide DHP Fastener and RhinoBond Plate
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
C-25.
psi structural
layers, any combination, prelim
- TPO or RhinoBond Treadsafe Plate - TPO
12-inch o.c. in rows 60-inch o.c.
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-37.5
concrete
attach (Note 14)
per manufacturer's instructions.
Min. 2,500
Min. 1.5-inch thick, one or more
Mule -Hide DHP Fastener and RhinoBond Plate
Mule -Hide TPO-c (minimum 60-mil) bonded to RhinoBond
C-26.
psi structural
layers, any combination, prelim
- TPO or RhinoBond Treadsafe Plate - TPO
12-inch o.c. in rows 60-inch o.c.
Plate -TPO or RhinoBond Treadsafe Plate - TPO with
-45.0
concrete
attach (Note 14)
RHINOBOND tool per manufacturer's instructions.
Min. 2,500
Min. 1.5-inch thick, one or more
Mule -Hide DHP Fastener and Rh d Plate
Mule -Hide TPO-c (minimum 60-mil) bonded to RhinoBond
C-27.
psi structural
layers, any combination, prelim
ra- T
TPO or RhinoBond Treadsafe Plate te TPO
6-inch o.c. in rows 120-inch o.c.
Plate -TPO or RhinoBond Treadsafe Plate - TPO with
-52.5
concrete
attach Note 14
( )
RHINOBOND tool per manufacturers instructions.
Min. 2,500
Min. 1.5-inch thick, one or more
Mule -Hide DHP Fastener and RhinoBond Plate
Mule -Hide TPO-c bonded to RhinoBond Plate - TPO or
C-28.
psi structural
layers, any combination, prelim
TPO or RhinoBond Treadsafe Plate - TPO
6-inch o.c. in rows 60-inch o.c.
RhinoBond Treadsafe Plate - TPO with RHINOBOND tool
-67.5
concrete
attach Note 14
( )I
per manufacturers instructions.
Notes: A. The plate/fastener combination offset 12 inch from adjacent rows.
B. For these assemblies each row of insulation is staggered by 1 foot.
TABLE 3C: STRUCTURAL CONCRETE DECKS"= NEW CONSTRUCTION OR REROOF,(TkAR-OFF)
SYSTEM TYPE F: "NON -INSULATED, BONDED ROOF.COVER
System
No.
Deck
Primer
Roof Cover
s
MDP (P o
Type
Attach
C-29.
Structural concrete
I None
I Mule -Hide SA-TPO
I Self -adhered
-425.0
Exterior Research and Design, I.I.C. d/b/a Trinity ( ERD Evaluation Report M15060.06.09-R5 for FL12772-RS
Certificate of Authorization #9503 6'" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 19 of 27
TABLE 4A: LIGHTWEIGHT.CONCRETE DECKS - NEW CONSTRUCTION or REROOF (Tear -Off)
SYSTEM TYPE A -IA: BONDED INSULATION, BONDED ROOF COVER
System
Deck (Note i)
Lightweight Concrete (Note 15)
Base Insulation Layer
Coverboard
Roof Cover (Note 16)
MDP
Type
Attach
Type
Attach
-No.
(psf)
LWC-1
Structural
Min. 200 psi, Min. 2-inch thick,
Min. 1-inch Poly ISO 1 or
(Optional) Additional layers base
concrete
Elastizell Range II LWIC
H-Shield
CR-20
insulation
CR-20
Mule -Hide TPO c /TPO-c BA
-180.0
LWC-2
Structural
Min. 200 psi, Min. 2-inch thick,
Min. 1-inch Poly ISO 1 or
(Optional) Additional layers base
concrete
Celcore MF Cellular Concrete
H-Shield
CR-20
insulation
CR-20
Mule-Hide-c/TPO-cBA
222.5
LWC-3
Structural
Min. 200 psi, Min. 2-inch thick,
Min. 1-inch Poly ISO 1 or
(Optional) Additional layers base
concrete
Mearlcrete
H-Shield
CR-20
insulation
CR-20
Mule -Hide TPO-c/TPO-c BA
-240.0
LWC-4
Structural
Min. 250 psi, Min. 2-inch thick,
Min. 1-inch Poly ISO 1 or
(Optional) Additional layers base
concrete
Elastizell Range II LWIC
H-Shield
OB500
insulation
OBS00
Mule -Hide TPO-c/TPO c BA
-225.0
TABLEAB-1: LIGHTWEIGHT CONCRETE.OVER STEEL DECK - NEW CONSTRUCTION OR RE -ROOF: (TEAR OFF) "
SYSTEM TYPE F: NON -INSULATED; BONDED ROOF COVER ,
Lightweight Concrete (Note 15)
Roof Cover (Note 16)
System
No
Deck (Note i)
MDP
Surface
Supplemental Attachment
Type
Treatment
Type
Attach
(psf)
Fasteners
Density
Min. 22 ga., Type B, Grade 33 steel
Min. 36 pcf wet cast density, min. 200 psi, min. 2-
LWC-5_
at max. 6 ft spans attached 6-inch
inch thick Celcore MF Cellular Concrete (cast with
None
None
N/A
Mule -Hide
TPO-c BA or Aqua
-60.0
O.C.
or without min. 1" EPS holey board). Note A.
TPO c
Base 120 BA
Min. 22 ga., Type B, Grade 33 steel
Min. 38 pcf wet cast density, min. 200 psi, min.
LWC-6
at max. 4 ft spans attached 6-inch
1.625-inch thick Celcore MF Cellular Concrete
Celcore PVA
None
N/A
Mule -Hide
TPO-c BA
-67.5
followed by min. 1-inch EPS holey board with min.
TPO-c
O.C.
2.0-inch thick top coat. Note A.
LWC-7
Min. 22 a., Type B, Grade 33 steel
g YP
Min. 36 pcf wet cast density, min. 200 psi, min. 2-
inch thick Celcore MF Cellular Concrete (cast with
None
Mule -Hide HDP Fastener
Z
1 per 9 ft
Mule -Hide
TPO-c BA or Aqua
-67.5
at max. 6 ft spans 6-inch o.c.
or without min. 1" EPS holey board). Note A.
with 3" Insulation Plate
-
TPO-c
Base 120 BA
Note B
LWC-8
Min. 22 a., Type B, Grade 33 steel
g YP
Min. 36 pcf wet cast density, min. 200 psi, min. 2-
inch thick Celcore MF Cellular Concrete (cast with
None
Mule -Hide HDP Fastener
1 per 1 ftZ
Mule -Hide
BA orAqua
at max. 6 ft spans 6-inch" o.c.
or without min. 1" EPS holey board). Note A.
with 3" Insulation Plate
TPO-c
BaseTPO-
Base 120 BA
Note B
Note 8
Note A.) If the type of LWC to be used on the project is unknown, as in a re -roof (tear -off) condition, compressive strength and fastener withdrawal resistance testing shall be conducted. Compressive strength testing shall
be in accordance with ASTM C495 (for new pour) or ASTM C109 (for existing) and shall yield a minimum 200 psi result. Field withdrawal resistance testing in accordance with TAS 105 or ANSI/SPRI FX-1 and shall yield an
average withdrawal performance not less than 55 lbf with a Trufast FM-90 Base Sheet Fastener. If question exists as to the adhesion to the LWC surface, field testing in accordance with ASTM E907 or FM Loss Prevention
Data Sheet 1-29 is recommended. All testing shall be performed by an accredited testing agency acceptable to the Authority Having Jurisdiction.
Note B.) Linear interpolation between supplemental attachment at 1 per 9 ftz for -67.5 psf and 1 per 1 ftz for -120.0 psf is permissible. Such interpolation shall be performed by a qualified design professional to the
satisfaction of the Authority Having Jurisdiction.
Exterior Research and Design, I.I.C. d/b/a Trinity ( ERD Evaluation Report M15060.06.09-RS for FL12772-RS
Certificate of Authorization #9503 6" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 20 of 27
QOTRINITYIERD
TABLE 46-2: LIGHTWEIGHT CONCRETE OVER, STRUCTURAL CONCRETE - NEW CONSTRUCTION
SYSTEM TYPE F: NON -INSULATED; BONDED ROOF COVER
System
Deck (Note 1)
Lightweight Concrete (Note 15)
Roof Cover (Note 16)
MDP
Membrane
Application
• No.
(Psf)
Min. 2,500 psi structural
LWC-9
concrete
Min. 250 psi, Min. 2" thick, Elastizell Range II LWIC
Mule -Hide TPO-c
Aqua Base 120 BA
-67.5
Min. 2,500 psi structural
LWC-10
Min. 250 psi, Min. 2" thick, Elastizell Range II LWIC (EPS board optional)
Mule -Hide TPO-c
TPO-c BA
-240.0
concrete
Min. 2,500 psi structural
LWC-11
Min. 300 psi, Min. 2" thick, Elastizell Range II LWIC (no EPS board)
Mule -Hide TPO-c
TPO-c BA
-495.0
concrete
"-WC-12
Min. 2,500 psi structural
Min. 300 psi, Min. 2" thick, Celcore Cellular Concrete
Mule -Hide TPO-c
Aqua Base 120 BA
-82.5
concrete
Min. 2,500 psi structural
LWC-13
Min. 300 psi, Min. 2" thick, Celcore Cellular Concrete
Mule -Hide TPO-c
TPO-c BA
-135.0
concrete
Min. 2,500 psi structural
Min. 36 pcf wet cast density, min. 200 psi, min. 2-inch thick Celcore MF Cellular Concrete (cast with
LWC-14
concrete
or without min. 1" EPS holey board). Note A.
Mule -Hide TPO-c
Aqua Base 120 BA
-217.5
Min. 2,500 psi structural
Min. 36 pcf wet cast density, min. 200 psi, min. 2-inch thick Celcore MF Cellular Concrete (cast with
LWC-15
concrete
or without min. 1" EPS holey board). Note A.
Mule -Hide TPO-c
TPO-c BA
-480.0
Note A.) If the type of LWC to be used on the project is unknown, as in a re -roof (tear -off) condition, compressive strength and fastener withdrawal resistance testing shall be conducted. Compressive strength testing shall
be in accordance with ASTM C495 (for new pour) or ASTM C109 (for existing) and shall yield a minimum 200 psi result. Field withdrawal resistance testing in accordance with TAS 105 or ANSI/SPRI FX-1 and shall yield an
average withdrawal performance not less than 5S Ibf with a Trufast FM-90 Base Sheet Fastener. If question exists as to the adhesion to the LWC surface, field testing in accordance with ASTM E907 or FM Loss Prevention
Data Sheet 1-29 is recommended. All testing shall be performed by an accredited testing agency acceptable to the Authority Having Jurisdiction.
Exterior Research and Design, LLC. d/b/a Trinity I ERD Evaluation Report M15060.06.09-RS for FL12772-RS
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 21 of 27
r
TABLE SA: GYPSUM, DECKS — REROOF (Tear -Off)
WSTEM^TYPE .A-1: BONDED INSULATION, BONDED ROOF COVER
System
Deck (Notes 1 & 12)
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 16)
MDP
No.
Type
Attach
Type
Attach
Type
Application
(Psf)
G-1.
Existing sound gypsum or
Min. 1.5-inch ACFoam II, H-Shield, ENRGY 3 or Poly ISO 1,
(Optional) Additional layers
gypsum plank
Poly ISO 2
CR-20
of base insulation
CR-20
Mule -Hide TPO-c
Aqua Base 120 BA
-127.5
G 2.
Existing sound gypsum or
(Optional) Min. 1.5-inch ACFoam II, H-Shield, ENRGY 3 or
Min. X-inch Dens Deck or
gypsum plank
Poly ISO 1, Poly ISO 2
CR 20
Dens Deck Prime
CR-20
Mule -Hide TPO-c
Aqua Base 120 BA
127.5
Existing sound gypsum or
Min. 1.5-inch ACFoam II, H-Shield, ENRGY 3 or Poly ISO 1,
(Optional) Additional layers
gypsum P lank
Poly ISO 2
Y
CR-20
of base insulation
CR-20
Mule -Hide TPO-c
TPO-c BA
-232.5
G-4.
Existingsound
gypsum or
(Optional) Min. 1.5-inch ACFoam II, H-Shield, ENRGY 3 or
Min.'/< -inch Dens Deck or
gypsum plank
Poly ISO 1, Poly ISO 2
CR-20
Dens Deck Prime
CR-20
Mule -Hide TPO-c
TPO-c BA
-232.5
Exterior Research and Design, LLC. d/b/a Trinity ( ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M15060.06.09-R5 for FL12772-R5
Revision 5: 09/11/2017
Appendix 1, Page 22 of 27
QOTR-INITYIERD
TABLE 6A: RECOVER APPLICATIONS
SYSTEM TYPE A-1: BONDED INSULATION; BONDED ROOF COVER
System
Substrate
Base Insulation Layer
Top Insulation Layer
Roof Cover (Note 16)
MDP
'No.
(Notes 1 & 12)
Type
Attach
Type
Attach
Type
Application
(Psf)
Existing asphaltic BUR or
Min. 1.5-inch ACFoam II, H-Shield, ENRGY 3 or Poly
(Optional) Additional layers of base
Mule -Hide
R-1
mineral surface cap sheet
ISO 1, Poly ISO 2
CR-20
insulation
CR 20
TPO-c
Aqua Base 120 BA
-127.5
Existingasphaltic BUR or
P
(Optional) Min. inch ACFoam II, H-Shield,
Min. A -inch Dens Deck or Dens Deck
Mule -Hide
R 2
mineral surface cap sheet
ENRGY 3 or Poly ISO 1, Poly ISO 2
IS
CR-20
Prime or SECUROCK Gypsum -Fiber
CR-20
TPO-c
Aqua Base 120 BA
-127.5
Roof Board
Existing asphaltic BUR or
Min. 1.5-inch ACFoam II, H-Shield, ENRGY 3 or Poly
(Optional) Additional layers of base
Mule -Hide
3
}
mineral surface cap sheet
ISO 1, Poly ISO 2
CR-20
insulation
CR-20
TPO-c
TPO-c BA
-232.5
Existingasphaltic BUR or
P
(Optional) Min. inch ACFoam II, H-Shield,
Min. Y.-inch Dens Deck or Dens Deck
Mule -Hide
R-4
mineral surface cap sheet
IS
ENRGY 3 or Poly ISO 1, Poly ISO 2
CR-20
Prime or SECUROCK Gypsum -Fiber
CR-20
TPO-c
TPO-c BA
-232.5
Roof Board
Existing asphaltic BUR or
Min. 1.5-inch ACFoam II, H-Shield, ENRGY 3 or Poly
(Optional) Additional layers of base
Mule -Hide
TPO-c BA or Aqua Base
R-5
mineral surface cap sheet
ISO 1, Poly ISO 2
OB500
insulation
OB500
TPO-c
120 BA
120.0
Existing asphaltic BUR or
(Optional) Min. 1.5-inch ACFoam II, H-Shield,
X.-inch Dens Deck,
Min. Dens Deck
Mule -Hide
TPO-c BA or Aqua Base
R-6
mineral surface cap sheet
ENRGY 3 or Poly ISO 1, Poly ISO 2
OB500
Prime or SECUROCK Gypsum -Fiber
OB500
TPO-c
120 BA
-120.0
Roof Board
Exterior Research and Design, LLC. d/b/a Trinity ( ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6T" EDITION (2017) FBC NON-HVHz EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M15060.06.09-R5 for FL12772-RS
Revision 5: 09/11/2017
Appendix 1, Page 23 of 27
\P TRINITY
I ERD
TABLE 6B: STEEL -RECOVER
SYSTEM TYPE C-2: PLATE -BONDED ROOF COVER
All areas where the existing metal panels do not lay flush on the underlying purlin shall have a a25-inch diameter pilot hole pre -drilled into the panel prior to driving the Purlin Fastener into the purlin
System
Substrate
Insulation Layer
Attachment
Roof Cover /Adhesive
MDP (psf)
Fasteners (Note 11)
Spacing
No.
(Note 1)
Existing standing seam or lap seam metal
roof covers having min. 16 gauge (0.0598
One or more layers, any
Mule -Hide Purlin Fastener and
Mule -Hide TPO-c (minimum 60-mil) bonded to
R-7
inch), 50 ksi or min. 12 gauge (0.105 in.), 36
combination,
RhinoBond Plate - TPO are fastened
12-inch o.c. along purlins
RhinoBond Plate - TPO with RHINOBOND tool
-30.0
ksi steel purlins spaced max.120-inch o.c.
preliminarily fastened
through to purlins
per manufacturer's instructions.
}
Existing standing seam or lap seam metal
roof covers having min. 16 gauge (0.0598
One or more layers, any
Mule -Hide Purlin Fastener and
Mule -Hide TPO-c bonded to RhinoBond Plate -
r8
inch), 50 ksi or min. 12 gauge (0.105 in.), 36
combination,
RHINOBOND Insulation Plate (TPO)
6-inch o.c. along purlins
TPO with RHINOBOND tool per manufacturer's
-37.5
ksi steel purlins spaced max. 120-inch o.c.
preliminarily fastened
are fastened through to purlins
instructions.
Existing standing seam or lap seam metal
roof covers having min. 16 gauge (0.0598
One or more layers, any
Mule -Hide Purlin Fastener and
Mule -Hide TPO-c bonded to RhinoBond Plate -
R-9
inch), 50 ksi or min. 12 gauge (0.105 in.), 36
combination,
RHINOBOND Insulation Plate (TPO)
12-inch o.c. along purlins
TPO with RHINOBOND tool per manufacturer's
-37.5
ksi steel purlins spaced max. 60-inch o.c.
preliminarily fastened
are fastened through to purlins
instructions.
Existing standing seam or lap seam metal
One or more layers, any
Mule -Hide Purlin Fastener and
Mule -Hide TPO-c (minimum 60-mil) bonded to
R-10
roof covers having min. 16 gauge (0.0598
inch), 50 ksi or min. 12 gauge (0.105 in.), 36
combination,
RHINOBOND Insulation Plate (TPO)
12-inch o.c. along purlins
RhinoBond Plate -TPO with RHINOBOND tool
-45.0
ksi steel purlins spaced max. 60-inch o.c.
preliminarily fastened
are fastened through to purlins
per manufacturer's instructions.
Existing standing seam or lap seam metal
One or more layers, any
Mule -Hide Purlin Fastener and
Mule -Hide TPO-c (minimum 60-mil) bonded to
R-li
roof covers having min. 16 gauge (0.0598
inch), 50 ksi or min. 12 gauge (0.105 in.), 36
combination,
RHINOBOND Insulation Plate (TPO)
6-inch o.c. along purlins
RhinoBond Plate - TPO with RHINOBOND tool
-52.5
ksi steel purlins spaced max. 120-inch o.c.
preliminarily fastened
are fastened through to purlins
per manufacturer's instructions.
Existing standing seam or lap seam metal
One or more layers, any
Mule -Hide Purlin Fastener and
Mule -Hide TPO-c bonded to RhinoBond Plate -
R-12
roof covers having min. 16 gauge (0.0598
inch), 50 ksi or min. 12 gauge (0.105 in.), 36
combination,
RHINOBOND Insulation Plate (TPO)
6-inch o.c. along purlins
TPO with RHINOBOND tool per manufacturers
-67.5
ksi steel purlins spaced max. 60-inch o.c.
preliminarily fastened
are fastened through to purlins
instructions.
Exterior Research and Design, LLC. d/b/a Trinity I ERD Evaluation Report M15060.06.09-R5 for FL12772-RS
Certificate of Authorization #t9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 24 of 27
\J TRINITY
ER®
TABLE6C: STEEL -RECOVER
SYSTEM TYPE D-1: INSULATED, MECHANICALLY` ATTACHED ROOF COVER
(All areas where the existing metol panels do not lay flush on the underlying purlin shall have a 0.25-inch diameter pilot hole pre -drilled into the panel prior to driving the Purlin Fastener into the purlin:)
System
Deck (Note 1)
Insulation
Roof Cover
MDP
Type
Attach
Membrane
Fasteners (Note 11)
Attachment
No.
(Psf)
Existing standing seam or lap seam metal roof covers
One more layers,
Prelim.
Mule -Hide
Mule -Hide Purlin Fastener
-12-inch o.c. within 5.5-inch wide laps spaced
R-13
having min. 16 ga. (0.0598-inch) to max. 3/16-inch
any combination
o
attach
or TPO-c EXTTRARA
and 24 Seam Plate
max. 138.5-inch o.c. to engage steel purlin.
-30.0
thick steel purlins spaced max. 138.5-inch o.c.
Laps sealed with 1.5-inch heat weld.
Existing standing seam or lap seam metal roof covers
One or more layers,
Prelim.
Mule -Hide TPO-c
Mule -Hide Purlin Fastener
12-inch o.c. within 5.5-inch wide laps spaced
14
having min. 16 ga. (0.0598-inch) to max. 3/16-inch
any combination
attach
or TPO-c EXTRA
and 2.4 Seam Plate
max. 115-inch o.c. to engage steel purlin. Laps
-45.0
thick steel purlins spaced max. 115-inch o.c.
sealed with 1.5-inch heat weld.
Existing standing seam or lap seam metal roof covers
One or more layers,
Prelim.
Mule -Hide TPO-c
Mule -Hide Purlin Fastener
12-inch o.c. within 5.5-inch wide laps spaced
R-15
having min. 16 ga. (0.0598-inch) to max. 3/16-inch
any combination
attach
or TPO-c EXTRA
and 2.4 Seam Plate
max. 54.5-inch o.c. to engage steel purlin. Laps
-60.0
thick steel purlins spaced max. 54.5-inch o.c.
sealed with 1.5-inch heat weld.
Existing standing seam or lap seam metal roof covers
One more layers,
Prelim.
Mule-Hc
Mule -Hide Purlin Fastener
6-inch o.c. within 5.5-inch wide laps spaced
R-16
having min. 16 ga. (0.0598-inch) to max. 3/16-inch
o
any combination
attach
or TPO-c EXTRA
E
and 2.4 Seam Plate
max. 138.5-inch o.c. to engage steel purlin.
-60.0
thick steel purlins spaced max. 138.5-inch o.c.
Laps sealed with 1.5-inch heat weld.
Existing standing seam or lap seam metal roof covers
One or more layers,
Prelim.
Mule -Hide TPO-c
Mule -Hide Purlin Fastener
6-inch o.c. within 5.5-inch wide laps spaced
R-17
having min..16 ga. (0.0598-inch) to max. 3/16-inch
any combination
attach
or TPO-c EXTRA
and 2.4 Seam Plate
max. 90.5-inch o.c. to engage steel purlin. Laps
-67.5
thick steel purlins spaced max. 90.5-inch o.c.
sealed with 1.5-inch heat weld.
Existing standing seam or lap seam metal roof covers
One more layers,
Prelim.
Mule -Hide
Mule -Hide Purlin Fastener
9-inch o.c. within 5.5-inch wide laps spaced
R-18
having min. 16 ga. (0.0598-inch) to max. 3/16-inch
o
any combination
attach
or TPO-c EXTTRARA
and 24 Seam Plate
max. 114.5-inch o.c. to engage steel purlin.
-75.0
thick steel purlins spaced max. 114.5-inch o.c.
Laps sealed with 1.5-inch heat weld.
Existing standing seam or lap seam metal roof covers
One or more layers,
Prelim.
Mule -Hide TPO-c
Mule -Hide Purlin Fastener
6-inch o.c. within 5.5-inch wide laps spaced
R-19
having min. 16 ga. (0.0598-inch) to max. 3/16-inch
any combination
attach
or TPO-c EXTRA
and 2.4 Seam Plate
max. 42.5-inch o.c. to engage steel purlin. Laps
-82.5
thick steel purlins spaced max. 42.5-inch o.c.
sealed with 1.5-inch heat weld.
Existing standing seam or lap seam metal roof covers
One more layers,
Prelim.
Mule -Hide
Mule -Hide Purlin Fastener
6-inch o.c. within 5.5-inch wide laps spaced
R-20
having min. 16 ga. (0.0598-inch) to max. 3/16-inch
any combination
o
attach
or TPO-c EXTTRARA
and 24 Seam Plate
max. 114.5-inch o.c. to engage steel purlin.
-90.0
thick steel purlins spaced max. 114.5-inch o.c.
Laps sealed with 1.5-inch heat weld.
Exterior Research and Design, LLC. d/b/a Trinity I ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M35060.06.09-R5 for FL12772-RS
Revision 5: 09/11/2017
Appendix 1, Page 25 of 27
TRINITY
ER®
TABLE 6D: RECOVER APPLICATIONS
SYSTEM TYPE E-1:. NON -INSULATED, MECHANICALLYATTACHED ROOF COVER
System
Deck
Roof Cover
No.
(Note 1)
Membrane
Fasteners (Note 11)
Fastener Spacing
Lap Width
Lap Spacing
Seam Weld
MDP (psf)
(inch)
(inch)
(inch)
(inch)
R-21
Existing steel deck
Mule -Hide TPO-c
Mule -Hide EHD Fastener and Mule -Hide 2.4" Seam Plates installed
12
5
139
Fleece Back, 60-mil
through to engage existing deck (Field W/D a 6951bl)
1.5
-30.0
Existing steel deck,
Mule -Hide TPO-c
Mule -Hide EHD Fastener and Mule -Hide 2.4" Seam Plates installed
R 22
min. Grade 80
Fleece Back
through to engage existing deck (Field W/D> 695lbf)
12
5.5
139
1.5
-30.0
�`I-23
Existing steel deck
Mule -Hide TPO-c
Mule -Hide EHD Plus Fasteners and Mule -Hide 2.4" PLUS Seam Plate
6
5
f
Fleece Back, 60-mil
installed through to engage existing deck (Field W/D> 434lbf)
139
1.5
-37.5
Existing steel deck,
Mule -Hide TPO-c
Mule -Hide EHD Fastener and Mule -Hide 2.4" Seam Plates installed
R-24
min. Grade 80
Fleece Back
through to engage existing deck (Field W/D> 4341bj)
6
5.5
139
1.5
-37.5
R-25
Existing steel deck
Mule -Hide TPO-c
Mule -Hide EHD Plus Fasteners and Mule -Hide 2.4" PLUS Seam Plate
12
5
Fleece Back, 60-mil
installed through to engage existing deck (Field W/D> 719lbf)
115
1.5
-37.5
Existing steel deck,
Mule -Hide TPO-c
Mule -Hide EHD Plus Fasteners and Mule -Hide 2.4" PLUS Seam Plate
R-26
min. Grade 80
Fleece Back
installed through to engage existing deck (Field W/D> 719lbf)
12
5.5
115
1.5
-37.5
Existing steel deck,
Mule -Hide TPO-c
Mule -Hide EHD Fastener and Mule -Hide 2.4" Seam Plates installed
R 27
min. Grade 80
Fleece Back
through to engage existing deck (Field W/D 2:455lbf)
6
5.5
91
1.5
-60.0
Existing steel deck,
Mule -Hide TPO-c
Mule -Hide EHD Plus Fasteners and Mule -Hide 2.4" PLUS Seam Plate
R 28
min. Grade 80
Fleece Back, 60-mil
installed through to engage existing deck (Field W/D> 9101bf)
12
5
91
1.5
-60.0
Existing structural
Mule -Hide TPO-c
Mule -Hide HDP Fastener and Mule -Hide 2.4" Seam Plates installed
R 29
concrete
Fleece Back
through to engage existing deck (Field W/D> 695lbf)
12
5.5
139
1.5
-30.0
Existing structural
Mule -Hide TPO-c
Mule -Hide HDP Fastener and Mule -Hide 2.4" Seam Plates installed
R-30
concrete
Fleece Back
through to engage existing deck Plates (Field W/D>_434lbf)
6
5.5
139
1.5
37.5
Existing structural
Mule -Hide TPO-c
Mule -Hide HDP Fastener and Mule -Hide 2.4" Seam Plates installed
R-31
concrete
Fleece Back
through to engage existing deck (Field W/D> 719lbf)
12
5.5
115
1.5
-37.5
Existing structural
Mule -Hide TPO-c
Mule -Hide HDP Fastener and Mule -Hide 2.4" Seam Plates installed
l.,-32
concrete
Fleece Back
through to engage existing deck (Field W/D>455lbfl
6
5.5
91
1.5
60.0
Existing structural
Mule -Hide TPO-c
Mule -Hide HDP Fastener and Mule -Hide 2.4" Seam Plates installed
R-33
concrete
Fleece Back, 60-mil
through to engage existing deck (Field W/D > 910lbf)
12
5
91
1.5
-60.0
Exterior Research and Design, I.I.C. d/b/a Trinity I ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6T" EDITION (2017) FBC NON-HVHZ EVALUATION
Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111
Evaluation Report M15060.06.09-R5 for FL12772-RS
Revision 5: 09/11/2017
Appendix 1, Page 26 of 27
QOTRINITYIERD
` TABLE 6E: RECOVEWAPPLICATIONS
SYSTEM TYPE F-2: NEW LIGHTWEIGHT CONCRETE OVER EXITISTINGROOF; BONDED, ROOF COVER
System
Substrate (Notes 1 & 12j
Roof Cover (Note 16)
No.
Lightweight Concrete (Note 1S)
MDP (psi
Deck
Existing Roof
Type
Attach
R-34
Structural
Existing asphalt BUR or smooth- or granule -surface
Min. 250 psi, Min. 2-inch thick, Elastizell Range II LWIC
concrete
SBS modified bitumen
(EPS board optional)
Mule -Hide TPO-c
Aqua Base 120 BA
-67.5
R-35
Structural
Existing asphalt BUR or granule -surface SBS modified
Min. 250 psi, Min. 2-inch thick, Elastizell Range II LWIC
concrete
bitumen
(EPS board optional)
Mule -Hide TPO-c
TPO-c BA
-302.5
R-36
Structural
Existing asphalt BUR or smooth -surface SBS modified
Min. 250 psi, Min. 2-inch thick, Elastizell Range II LWIC
concrete
bitumen
(EPS board optional)
Mule -Hide TPO-c
TPO-c BA
342.0
Exterior Research and Design, LLC. d/b/a Trinity I ERD Evaluation Report M15060.06.09-RS for FL12772-RS
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 5: 09/11/2017
Prepared by: Robert Nieminen, PE-59166 Mule -Hide TPO-c Single Ply Roof Systems; (608) 365-3111 Appendix 1, Page 27 of 27