PAD DIMENSIONS:
CONCRETE GENERATOR
Fa
GENERATOR UNIT BY
o SEPARATE SUBMITTAL
3 (SEE SCHEDULE FOR
N I MINIMUM WEIGHT
REQUIRED)
54" LENGTH
PLAN VIEW -
CONCRETE PAD
ROAD MESH al f
MASTERFIBER '3 MIN
MAC100 4" MINA
GROUNDS
GENERATOR TAB
AMERICAST GENERATOR CONCRETE PAD
(ON -GRADE APPLICATIONS ONLY)
AMERICAST
s`\
.M1 WllINAMHRIM;• _
FEDTAXA20-9252711 LICBNSH it540.20050i63 ,I
SM Wa%Wo AY F-n Pump Fl. M992
T,L "3.971 109 FM 772�6/-0500
EmriE til tie,4n.N�_-•mia eh•AtedIE2001Q_t. = _ _ r; • �,`.` `t
HVHZ OR NON-HVHZ
RISK
EXPOSURE (EXP)
RISK
EXPOSURE (EXP)
RISK
EXPOSURE (EXP)
COUNTY
C
D
II
C
i'c-D;!
I s III hVI'I
GCS ,i
P. BEACH
150 MPH
30.44 Psf
36.94 Psf
170 MPH
39.09 Psf
47.44 Psf
180 MPH
43 83,Psf
513.19. Psf
BROWARD
156 MPH
32.92 Psf
39.95 Psf
170 MPH
39.09 Psf
47.44 Psf.
;18OW PH-
43:83 Psf:
5319;Pef,
MIAMI-DADE
165 MPH
36.83 Psf
44.69 Psf
175 MPH
41.43 Psf
50.28 Psf
186 MPH
46.80 Psf
56.80 Psf
BRAND & MODEL
CAPACITY
I
WIDTH
LENGTH
i
HEIGHT --WEIGHT
\
/`ALLOWABLE
PRESSURE
COMMENTS
Generac 005871 & 005883
10 KW
25.00
4800 1
-29;00,"
387 Ibs
',41.43 Psf
EXP C 175 MPH & D 156 MPH
Generac005872&005884
14KW
25.00'1
48.00"`-29.00'.'
4391b's/^�47':44Psf
EXP C 186 MPH & D 156 MPH
Generac 6459, 6461, 6462
16 KW
25.00"
48.00 "
'29.00'.'
-513 Ibs-
v_-47:44 Psf
Generac 006721
16 KW
25.00 "
48. 00 "
29:00.'.;
_448'Ibs
47.44 Psf
Generac 005873 & 005885
17 KW
25.00-".
48.00_"
_ 29.01J"
_ 455 Ibs
47.44 Psf
Generac 005874 & 005886
17 KW
25 00 'l
48 00 T
l 29.00 +,
'421'Ibs
` i i47 44 Psf
Generac 005875 & 005887
20 KW
25.00 "
748:00,',i
,;29:00"-
; 451-Ibs-
a � 47:44,Psf
Generac 006729 & 006730
20 KW
25.00 " -
-48:00
29.00 "
(5161bs
=47.44 Psf
Generac 006551 & 006552
22 KW
25.00 "
48.00 "
29.00 "
526 Ibs
47.44 Psf
Kohler 14RES & 20RES
14-20 KW
26.00 "
48.00"
29.00 "
500 Ibs
47.44 Psf
GE 40323GE & 40324GE
13 KW
35.00 "
39.40 "
39.00 "
540 Ibs
39.09 Psf
EXP C 170 MPH & D 156 MPH
GE 04038215KW
15 KW
33.00 "
48.00 "
30.501,
484 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
GE;04037817KW
17 KW
33.00 "
48.00 "
30.50 "
4841bs
43.83 Psf
.6E 40330GE & 40331GE
20 KW
33.00 "
48.00"
30.50 "
600 Ibs
43.83 Psf
Briggs &-Stratton-040243-0
- 10 KW- -
-31.00=-
-32.00 _'_
-34.00 "_
_430 Ibs
43.83 Psf
Briggs & Stratton 040302-2
12 KW
33.75 "
50.00 "
31.60 "
507 Ibs
41.43 Psf
EXP C 175 MPH & D 156 MPH
Briggs & Stratton 040303-1
15 KW
33.75 "
49.00 "
31.60"
562 Ibs
43.83 Psf
EXP C 180 MPH & D 156 MPH
Briggs & Stratton 040304-1
18 KW
33.75 "
49.00 "
31.60 "
568 Ibs
44.00 Psf
Briggs & Stratton 040305-1
20 KW
33.75 "
49.00 "
31.60 "
570 Ibs
44.00 Psf
Generac 7035, 7036, 7037
16 KW
25.00 "
48.00 "
29.00 "
406 Ibs
47.44 Psf
EXP C 186 MPH & D 156 MPH
Generac 007038 & 007039
20 KW
25.00 "
48.00 "
29.00 "
448 Ibs
47.44 Psf
Generac:007042 & 7043
22 KW
25.00 "
48.00 "
29.00 "
466 Ibs
47.44 Psf
`-`'`-GENERATOR MOUNTING CONFIGURATION:
GENERATOR
GENERATOR ATTACHMENT BASE
OR SIMPSON A24 ANGLE BRACE
W/ (4) #10 SS 316 SELF -DRILLING
Q
T_
= I I = GENERATOR
(SEE CONCRETE PAD
w I w SCHEDULE FOR
_ = I DIMENSIONSREQUIRED)WEIGHT
4"
32" WIDTH I 54" LENGTH -+
i
SIDE VIEW
FRONT VIEW
GENERA
(SEE GENERAT(
V THICK GALVAN
WIND DESIGN REOUIREMENTS-
(BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION (2017))
AT -GRADE SIGN METHOD
ULTIMATE DESIGN WIND SPEED, Vult = 186 mph
NOMINAL DESIGN WIND SPEED Vasd = 144 mph
RISK CATEGORY = III INTERNAL PRESSURE COEF = N/A
EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd= 0.85
ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND
GUST EFFECT FACTOR = 0.85 PRESSURE AT HEIGHT H qh = 77.56 Ib/ft2
FORCE COEFFICIENT Cf = 1.44
WIND PRESSURE,
P = qh G Cf = 56.80 Ib/ft2 (ASD)
GENERAL NOTES
1
2.
3.
ANCHOR TO PAD SCHEDULE: 4,
SUBSTRATE I DESCRIPTION I
CONCRETE: (2)-3/W0 TITEN HD
(6000 PSI OR EQUIVALENT;
MIN.) 2-3/4" FULL EMBED
O CONCRETE, 3" MIN
EDGE DISTANCE, 6"
MIN. SPACING TO ANY
ADJACENT ANCHOR.
5.
6.
7
8.
NOTES:
1. ANCHOR QUANTITY PER LONG SIDE
2,,_EMBEDMENT AND EDGE DISTANCE
9
EXCLUDES FINISHES IF
APPLICABLE.. -
3 ENSURE MINIMUM EDGE DISTANCE
AS`NOTED IN ANCHOR SCHEDULE.
4. ENSURE'.MINIMUM'SPACING TO
-. ANY ADJACENT ANCHORS.
i ( $ IFOLLOW MANUFACTURER'S
'IN STALLATIONINSTRUCTIONS TO
I"'--•-
z -�-INSTALL ANCHORS '`
10.
w-
�:,;�
f GENERATORS 1 g L
ATTACHMENT BASE S G,
VARIES WIT] DEL
i' ,I
GENERATOR
SEE SPECS"
11.
SIMPSON TITEN HD,
SEE ANCHOR SCHEDULE
2"x3"x3/B" GALV. STEEL
WASHER
RUBBER VIBRATION PAD
12.
vviAonorta-rtu000rt-
VIBRATION
Z
CONCRETE PAD -
j
6,000 PSI
LIGHTWEIGHT
CONCRETE.PAD
Y
CONCRETE MIX tr
6,000 PSI
LIGHTWEIGHT
` MASTERFIBER MAC 100 -!
„,'CONCRETEIMIX I'
&ROAD MESH
NOTES a ,`
FOAM CORE
_ 1•.r. Y'DISTANCE DEPEND_ON'GENERATOR BASE LENGTH, NO LESS THAN 2".
2. X DISTANCE 3" FROM UNIT EDGE TO CLIP.
3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN
ANCHOR REQUIREMENTS
13.
THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED
IN ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA
BUILDING CODE SIXTH EDITION (2017).
REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR
USE WITH THIS SYSTEM SHALL BE DETERMINED UNDER
SEPARATE CERTIFICATION ON A JOB -SPECIFIC BASIS IN
ACCORDANCE WITH THE GOVERNING CODE. SITE -SPECIFIC
LOAD REQUIREMENTS AS DETERMINED IN ACCORDANCE WITH
THE APPLICABLE BUILDING CODE-SHALL_BE LESS THAN OR
EQUAL TO THE DESIGN PRESSURE "ASD" CAPACITYNALUES
LISTED HEREIN FOR ANY ASSEMBLY AS -SHOWN.
DIMENSIONS AND WEIGHT,OF UNITSi SHALL•CONFORM TO
SPECIFICATIONS ,STATED- HEREIN -` 1 _,
UNITS MUST BE CENTERED -ON PAD_WITH OPPOSITE SIDES
HAVING EQUAL CLEARANCE: A MINIMUM DISTANCE•FROM UNIT
TO PAD EDGE IS SPECIFIED._'
CALCULATIONS MADE USING -LIGHTWEIGHT CONCRETE ] 25 PCF
THE AREA UNDER CONCERETE SLAB.ON GROUND SHALL HAVE
ALL VEGETATION, STUMPS, ROOTS,,AND FOREIGN MATERIALS
REMOVED PRIOR TO INSTALLATION ON COMPACTED SOIL AS
VERIFIED BY OTHERS. 7 Kam^ p Ipt, G k m l+ ' I I-- ;,
RESISTANCE TO_SLIDING.;O.FITHE'PAD_ ONITHE;GROUND'IS;NOT
PART OF THIS DOCUMENT,AS-SOIL CHARACTERISTICS AND PAD
PLACEMENT VARIESr' = r'
ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED &
INSTALLED BY OTHERS. ALL MECHANICAL SPECIFICATIONS
(CLEAR SPACE, TONNAGE, ETC.) SHALL BE AS PER
MANUFACTURER RECOMMENDATIONS AND ARE THE EXPRESS
RESPONSIBILITY OF THE CONTRACTOR.
ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL
DESIGN AS SHOWN ONLY. USE OF THIS SPECIFICATION BY
CONTRACTOR, et. al. INDEMNIFIES & SAVES HARMLESS THIS
ENGINEER FOR ALL COST & DAMAGES INCLUDING LEGAL FEES
& APPELLATE FEES RESULTING FROM MATERIAL FABRICATION,
SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT
WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES &
FROM DEVIATIONS OF THIS PLAN.
WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL
RESPONSIBILITY OF THE INSTALLING CONTRACTOR.
CONTRACTOR SHALL ENSURE THAT ANY REMOVED OR ALTERED
WATERPROOFING MEMBRANE IS RESTORED AFTER
FABRICATION AND INSTALLATION OF STRUCTURE PROPOSED
HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY
WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS
WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF
THE INSTALLING CONTRACTOR.
THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF
SPECIALTY ENGINEER AND NOT THE ENGINEER OF RECORD.
CONSEQUENTLY, THE ARCHITECT/ENGINEER OF RECORD SHALL
BE RESPONSIBLE FOR THE INTEGRITY OF ALL SUPPORTING
SURFACES TO THIS DESIGN WHICH. SHALL BE COORDINATED
BY THE PERMITTING CONTRACTOR, - - -
THIS DOCUMENT IS GENERIC.AND-DOES NOT PERTAIN TO ANY
SPECIFIC PROJECT SITE. INFORMATION CONTAINEDrI EREIN IS
ACT BASED ON CONTROR-SUPPGIED.DATA AND..MEASUREMENTS.
ENGINEERING EXPRESS SHALL NOT BE HELD RESPONSIBLE OR
LIABLE IN ANY WAY FOR -ERRONEOUS OR INACCURATE DATA
OR MEASUREMENTS DIMENSIONS ARE SHOWN JO ILLUSTRATE
DESIGN FORCES AND OTHER'DESIGN CRITERIA::THEY'MAY
VARY SLIGHTLY, BUT -MUST REMAIN'WITHIN THE-L-IMITATIONS
SPECIFIED HEREIN. WORK -SHALL BE FIELD VERIFIED BY
OTHERS PRIOR TO CONSTRUCTION:' ENGINEERING EXPRESS
SHALL BE NOTIFIED AND, GIVEN AN OPPORTUNITY TO _
REEVALUATE OUR WORK UPON DISCOVERY OFANYi+I i
INACCURATE INFORMATION'PRIOR TO MODIFICATION OF
EXISTING FIELD CONDITIONS AND fABRICATION AND
INSTALLATION OF MATERIALS! ALTERATIONS OR'ADDITIONS
TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE
OUR CERTIFICATION.
EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL
CERTIFICATIONS OR AFFIRMATIONS ARE INTENDED.
BENNARDO, P.E.
01
KED, CENTIFlTNG P.E. AMMS BELOW
L. BENNARDO, P.E.
SIGNATURE ON SHEET 1, THIS
SHEET IS PART OF A DIGITALLY
SIGNED FILE, SHALL REMAIN IN
DIGITAL FORMAT, & PRINTED
COPIES OF THIS DOCUMENT
ARE NOT CONSIDERED SIGNED
AND SEALED. IF THERE IS NO
DIGITAL SIGNATURE ON SHEET 1
OR THIS SHEET DOES NOT
CONTAIN AN ENGINEER'S
ORIGINAL SIGNATURE & SEAL,
U %D N
O
.-1 0
Z � 0
,y. ® W M ,., U 2:LL v
uiHMouwiy.
WU) u071= MaNrn
W' 1 1 V1 x 4
ZQ 0 _ZI
rF-->ULL�xa
'<awgL.uu
ZX Orm -Ez�
WW 0 _juj MLuwu
LL v -1
(/I la 2 W
0 Ul w
o a z
C9 O_
J ~
I^ z Lu
v/ Q LL O Y w
N N ItU °-w�' INS I-
_ I j c .1 D6 W En
Lu W
O , � O
Lu a1^ pzu
C I'I O g
G o w 2� D
a L Y LU
w �
Lr) on
(D
O
a?�g
Noy
o
0 0
0
g�0
"53�
=
LL 0]
U J
m
J
0
()
� LL
LL
z
(�.2�cQi
g
F
z
3000
oioo�w
io
io !
K
¢
U
0
o
w
R'
Z 2_
COPYRIGHT ENGINEERING EXPRESS
17-3961.1
SCALE: NTS UNLESS NOTED
L
0