Florida
Product Approval
USER: Public User
Product Approval Menu > Product or Application Search > Application List > Application Detail
" FL # FL2533-R19
Application Type Revision
Code Version 2017
Application Status Approved
ST. LUCIE COUNTY r
BUILDING DIVISION
Ev2r-- WED
FOR C✓OFriIPLI
SIVIMED BY
8�11'E 2�11-r
PLANS AND PER BAIT
MUST BE KEPT ON JOB On
NO INSPECTION WILL DE MADE
Comments
Archived (..i
Product Manufacturer CertainTeed Corporation-RooHUE QANS AND
AL - 170O ID WORK'
Address/Phone/Email 26 Moores Road
Malvern, PA 19355 ARE 8Ul:0ECT TO AP.IV c;ONRE0 10NI6
(6.10) 893-5400 �c r�
mark.d.harner@saint-gobairitto�iUIPiE�_I D FIL1.1I0 1��i�NEC OF16 r'HW
MAY Dr Nf:0ES8ARY IN ON-1)ERl TO
Authorized Signature Mark Harrier �p`4'�1��/ �lflsf�I A�� t�dl�Ipt�, ;Vw r,
mark.d.harner@saint-gobain�.ggm 1_1d/_H f1 ! 4F , S�jl
Technical Representative
Mark D. Harrier
Address/Phone/Email
18 Moores Road
Malvern, PA 19355
(610) 651-5847
Mark.D.Harner@saint-gobain.com
CONCEALED FASTENERS OR ATTACHMENTS
Quality Assurance Representative
Address/Phone/Email
ARE THE RESPONSIBILITY OF THE
CONTRACTOR OF RECORD
Category
Roofing
Subcategory
Modified Bitumen Roof System
Compliance Method
Evaluation Report from a Florida
Registered Architect or a Licensed
Florida Professional Engineer
ILA Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed
Robert Nieminen
the Evaluation Report
Florida License
PE-59166
Quality Assurance Entity
UL LLC
Quality Assurance Contract Expiration Date
03/09/2020
Validated By
John W. Knezevich, PE
Validation Checklist - Hardcopy Received
Certificate of Independence FL2533 R19 COI 2017 01 COI Nieminen.odf
Referenced Standard and Year (of Standard) Standard Year
ASTM D6162 2008
ASTM D6163 2008
ASTM D6164 2011
ASTM D6222 2011
ASTM D6509 2009
FM 4470 2012
FM 4474 2011 VAN
Equivalence of Product Standards ` , _ A r, 't �
Certified By
https://www.floridabuilding.org/pr/pr_app_dtl.aspx?param=wGEVXQwtDgvweIwRFXRv... 2/26/2018
Florida Building Code Online
Page 2 of 2
Sectionsfromfrom the
Product Approval Method
Date Submitted
Date Validated
Date Pending FBC Approval
Date Approved
Summary of Proi
Method 1 Option D
09/14/2017
09/15/2017
09/19/2017
12/12/2017
FL #
Model, Number or Name
Description
2533.1
Flintlastic Modified Bitumen
Modified Bitumen Roof Systems
Roof Systems
Limits of Use I
Approved for use in HVHZ: No
Approved for use outside HVHZ: Yes
Impact Resistant: N/A
Design Pressure: +N/A/-635
Other: 1.) Refer �o ER Section 5 for Limits of
Installation Instructions
FL2533 R19 II 2017 09 FINAL Al ER CERTAINTEED MODBIT FL2533-
R19.Ddf
Verified By: Robert Nieminen, PE PE-59166
Created by Independent Third Party: Yes
Evaluation Reports
Use. 2.) The design pressure noted in this
application relateslto one specific system.
FL2533 R19 AE 2017 09 FINAL ER CERTAINTEED MODBIT FL2533-
R19.Ddf
Refer to the ER Appendix for all systems and
max design pressdres.
Created by Independent Third Party: Yes
Back Next
Contact Us :: 2601 Blair Stone Road Tallahassee FL 32399 Phone: 850-487-1824
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida.:: Privacy Statement :: Accessibility Statement :: Refund Statement
Under Florida law, email addresses are public records. If you do not want your e-mail address released In response to a public -records request, do not send
electronic mail to this entity. Instead, contact the office by phone or by traditional mail. If you have any questions, please contact 850.487.1395. -Pursuant to
Section 455.275(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an email address if
they have one. The emeils provided may be used for official communication with the licensee. However email addresses are public record. If you do not wish to
supply a personal address, please provide the Department with an email address which can be made available to the public. To determine if you are a licensee under
Chapter 455, F.S., please click bffp_.
Product Approval Accepts:
19 M
Credit Card
Safe
https://www.floridabuildinlg.org/pr/pr_app_dti-aspx?param=wGEVXQwtDgvweIwRFXRv... 2/26/2018
(-")o
V I RINITY I ERD
APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE r -
Table
Deck
Application
Type
Description
Page
IA
Wood
New or Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
5-6
1B
Wood
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
7
1C
Wood
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
8-9
1D
Wood
New, Reroof (Tear -Off) or Recover
D
Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
10-12
lE-1
Wood
New, Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
13-15
1E-2
Wood
New, Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
16-17
1F
Wood
New or Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
17
2A
Steel or Structural Concrete
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
18-20
2B
Steel or Structural Concrete
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
21-25
2C
Steel or Structural Concrete
New, Reroof (Tear -Off) or Recover
D
Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
26-28
3A
Concrete
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
29-36
3B
Concrete
New or Reroof (Tear -Off)
A-3
Bonded Temp Roof/Vapor Barrier, Bonded Insulation, Bonded Roof Cover
36
3C
Concrete
New or Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
37
4A
LWIC
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
38-39
4B
LWIC
New or Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
40
4C
LWIC
New, Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
41-44
5A
CWF
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
45
5B
CWF
New or Reroof-(Tear-Off)
A=2-
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
46
SC
CWF
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
46
SD
CWF
New, Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
47
6A
Gypsum
Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
48-49
6B
Gypsum
Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
50
6C
Gypsum
Reroof (Tear -Off)
C
Mech. Attached Insulation, Bonded Roof Cover
51
61)
Gypsum
Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
51
7A
Various
Recover
A-1
Bonded Insulation, Bonded Roof Cover
52-57
7B
Various
Recover
F
Non -Insulated, Bonded Roof Cover
57
The following notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above -deck roof components. Roof decks shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the
roof deck shall be documented through proper codified and/or FBC Approval documentation. —
2. Unless otherwise noted, fasteners and stress plates for insulation attachment shall be as follows. Fasteners shall be of sufficient length for the following engagements:
➢ Wood Deck: OMG #14 Roofgrip with Flat Bottom Plate (Accutrac), CMG HD with OMG 3 in. Galvalume Steel Plate, Dekfast #14 with Hex Plate or 3" Round Insulation Plate, Trufast HD with Trufast 3"
Metal Insulation Plates or FlintFast #14 Fastener with FlintFast 3" Insulation Plates. Minimum 0.75-inch plywood penetration or minimum 1-inch wood plank embedment.
➢ Steel Deck: OMG #12 or #14 Roofgrip with Recessed or Flat Bottom Plate (Accutrac), CMG #12 Standard or HD with CMG 3 in. Galvalume Steel Plate, Dekfast #12 or #14 with Hex Plate or 3" Round
Insulation Plate, Trufast DP or HD with Trufast 3" Metal Insulation Plates or FlintFast #12 or #14 Fastener with FlintFast 3" Insulation Plates. Minimum 0.75-inch steel penetration and
engage the top flute of the steel deck.
➢ Structural Concrete: CMG #14 Roofgrip with Recessed or Flat Bottom Plate (Accutrac), OMG HD or CD-10 with OMG 3 in. Galvalume Steel Plate, Dekfast #14 or DekSpike with Hex Plate or 3" Round
Insulation Plate, Trufast HD or CF with Trufast 3" Metal Insulation Plates or FlintFast #14 Fastener -with FlintFast 3" Insulation Plates. Minimum 1-inch embedment. Fasteners installed
with a pilot hole in accordance with the fastener manufacturer's published installation instructions.
Exterior Research and Design, U.C. d/b/a Trinity IERD Evaluation Report 3520.03.04-R20 for FL2533-1119
Certificate of Authorization #9503 CH EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/14/2017
Prepared by: Robert Nieminen, PE-59166 CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5847 Appendix 1, Page 1 of 57
\1 TRINITY I ERD
3. Unless otherwise noted, insulation may be any one layer or combination of polyisocya nu rate, polystyrene, wood fiberboard, perlite, GlasRoc Roof Board or gypsum -based roof board that meets the CA requirements
of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover.
4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for, or installed beneath rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover),
whereby the base sheet screws and plates are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck
listings. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper
codified and/or FBC Approval documentation.
5. Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016).
6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published instructions
➢
Hot asphalt (HA):
Full coverage at 25-30 Ibs/square
➢
-Ashland Pliodeck (A-PD):
Continuous 0.75 inch wide ribbons, 12-inch o.c. Ribbons ofsubsequent layers shall be perpendicular to those in the layer below.
➢
Dow INSTA-STIK Quik Set Insulation Adhesive (D-IS):
Continuous 0.75 to 1 inch wide ribbons, 12-inch o.c.
➢
Millennium One Step Foamable Adhesive (M-OSFA):
Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.
➢
Millennium PG-1 Pump Grade Adhesive (M-PGI):
Continuous 0.5 to 0.75-inch wide ribbons,12-inch o.c.
➢
OMG OlyBond 500 or OlyBond Green (OB500):
Continuous 0.75-inch wide ribbons, 12-inch o.c. (PaceCart or SpotShot)
➢
ICP Adhesives CR-20:
Continuous 2.5 to 3-inch wide ribbons, 12-inch o.c.
➢
Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, boards shall be staggered from layer -to -layer.
➢
Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
7. Unless otherwise noted, all insulations are flat -stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following Maximum
Design Pressure (MDP) limitations. In no case shall these values be used to 'increase' the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then
the thinner board listed below may be used as a drop -in for the equivalent thicker material listed in the table:
➢
Ashland Pliodeck (A-PD) @ 12-inch o.c.
MDP
-105.0 psf
(Min. 1.0-inch)
➢
Ashland Pliodeck (A-PD) @ 6-inch o.c.
MDP
-277.5 psf
(Min. 1.0-inch)
➢
Dow INSTA-STIK Quik Set Insulation Adhesive (D-IS):
MDP
-120.0 psf
(Min. 1.0-inch)
➢
Millennium One Step Foamable Adhesive (M-OSFA):
MDP
-157.5 psf
(Min. 1.0-inch)
➢
Millennium PG-1 Pump Grade Adhesive (M-PG1):
MDP
-157.5 psf
(Min. 1.0-inch)
➢
OMG OlyBond 500 (OB500):
MDP
-45.0 psf
(Min. 0.5-inch Multi -Max FA3)
➢
OMG OlyBond 500 (OB500):
MDP
-187.5 psf
(Min. 0.5-inch ISO 95+ GL)
➢
OMG OlyBond 500 (OB500):
MDP
-315.0 psf
(Min. 0.5-inch ENRGY 3)
➢
OMG OlyBond 500 (OB500):
MDP
-487.5 psf
(Min. 0.5-inch ACFoam II)
➢
ICP Adhesives CR-20:
MDP
-117.5 psf
(Min. 1.0-inch)
8-Bonded polyisocyanurate-insulation-boards-shall-be-maximum-4-x-4-ft
9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC
Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss
Prevention Data Sheet 1-29 and Roofing Application Standard RAS 117. Assemblies marked with an asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for
Zone 2/3 enhancements.
10. For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no
rational analysis is permitted.
11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TA5105.
Exterior Research and Design, LLC. d/b/a Trinity I ERD Evaluation Report 3520.03.04-R20 for FL2533-1119
Certificate of Authorization #9503 O EDITION (2017) FBC NON-HVHZ EVALUATION Revision 20: 09/14/2017
Prepared by: Robert Nieminen, PE-59166 CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5847 Appendix 1, Page 2 of 57
�VTRRINITYJERD
12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing
roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with
ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13. For Concrete Deck or Recover Applications using System Type D, the insulation is optional.
14. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to current LWC
Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness is 2-inches.
For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1
15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications.
CERTAINTEED FLINTLASTIC® MODIFIED BITUMEN COMPONENTS 8t APPLICATION METHODS
Reference
Layer
Material
Application
Bp -AA
(Base and Ply sheets, Asphalt -Applied)
Base
Glasbase; All Weather/Empire Base; Flexiglas Base; Flintlastic Base 20
Hot asphalt at 20-40 Ibs/square
ply
One or more Flintglas Ply 4; Flintglas Premium Ply 6
BP-AA2
Base
Yosemite Venting Base
Hot asphalt in 24-inch diameter spots in 30-
(Base, Spot -Asphalt -Applied)
inch grid pattern
BP-AA3
Base
Yosemite Venting Base
Hot asphalt in 9-inch diameter spots in grid
(Base, Spot -Asphalt -Applied)
pattern noted herein.
BP-AA4
Base
Yosemite Venting Base
Hot asphalt in 9-inch wide ribbons spaced
(Base, Strip -Asphalt -Applied)
as noted herein.
BP-CA2
Base/Ply
Glasbase; All Weather/Empire Base; Flexiglas Base; Flintlastic Base 20
Henry #903 Adhesive at 1.5 gal/square
BP-CA3
Base/Ply
Glasbase; All Weather/Empire Base; Flexiglas Base; Flintlastic Base 20
Millennium Hurricane Force Membrane
Adhesive, beads spaced 6-inch o.c.
Base
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
SBS-AA
(SBS, Asphalt -Applied)
Hot asphalt at 20-40 Ibs/square
Ply
One or more Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
Cap
Flintlastic Cap 30; Flintlastic Cap 30 CoolStar; Flintlastic FR Cap 30; Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual
Cap; Flintlastic FR-P; Flintlastic FR-P CoolStar; Flintlastic Premium FR-P; Flintlastic Premium FR-P CoolStar;
Flintlastic GMS; Flintlastic GMS CoolStar
Base
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
SBS-CAI
(SBS, Cold -Applied)
FlintBond Brush or Karnak No. 81 Cold
Process Modified Bitumen Adhesive Brush
Grade at 1 gal/square
Note:
Base ply cures overnight prior to application of the ply or cap ply.
Ply
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
Cap
Flintlastic FR Cap 30; Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual Cap; Flintlastic FR-P; Flintlastic FR-P CoolStar;
Flintlastic Premium FR-P; Flintlastic Premium FR-P CoolStar; Flintlastic GMS; Flintlastic GMS CoolStar
Base
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
SBS-CA2
(SBS, Cold -Applied)
Henry #903 Adhesive at 1.5 gal/square.
Ply
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
Cap
Flintlastic Cap 30; Flintlastic Cap 30 CoolStar; Flintlastic FR Cap 30; Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual
Cap; Flintlastic FR-P; Flintlastic FR-P CoolStar; Flintlastic Premium FR-P; Flintlastic Premium FR-P CoolStar;
Flintlastic GMS; Flintlastic GMS CoolStar
Exterior Research and Design, LLC. d/b/a Trinity[ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
C" EDITION (2017) FBC NON-HVH2 EVALUATION
CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5847
Evaluation Report 3520.03.04-R20 for FL2533-11119
Revision 20: 09/14/2017
Appendix 1, Page 3 of 57
�I TRINITY I ERD
" CERTAINTEED Ft1NTLASTIC' MODIFIED BITUMEN COMPONENTS'B'�APPUCATION:MEM0D5,(CONDNUED) " -
Reference
Layer
Material
Application
Base
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
SBS-CA3
(ses,Cold-Applied)
Ply
Flintlastic Base 20; Flintlastic Poly SMS Base; Flintlastic Ultra Poly SMS Base
Millennium Hurricane Force Membrane
Adhesive, beads spaced 6-inch o.c.
Cap
Flintlastic Cap 30; Flintlastic Cap 30 CoolStar; Flintlastic FR Cap 30; Flintlastic FR Cap 30 CoolStar; Flintlastic FR Dual
Cap; Flintlastic FR-P; Flintlastic FR-P CoolStar; Flintlastic Premium FR-P; Flintlastic Premium FR-P CoolStar;
Flintlastic GMS; Flintlastic GMS CoolStar
Base
Flintlastic Ultra Poly SMS Base; Flintlastic Base 20 T
SBS-TA
(SBS,Torch-Applied)
Ply
One or more Flintlastic Ultra Poly SMS Base; Flintlastic Base 20 T
Torch -Applied
Cap
Flintlastic FR Cap 30 T; Flintlastic FR Cap 30 T CoolStar; Flintlastic GTS; Flintlastic GTS CoolStar; Flintlastic GTS-FR;
Flintlastic GTS-FR CoolStar; FlintClad
Base
One or more Flintlastic APP Base T; Flintlastic STA; Flintlastic STA Plus
APP TA
(APP,Torch-Applied)
Torch -Applied
pp
Cap
Flintlastic STA; Flintlastic STA Plus; Flintlastic GTA; Flintlastic GTA CoolStar; Flintlastic GTA-FR; Flintlastic GTA-FR
CoolStar
SBS-SA-H
(58S, Self -Adhering, Hybrid Systems)
Base/Ply
Black Diamond Base Sheet; Flintlastic Ultra Glass SA
Self -Adhering
Base
Flintlastic SA PlyBase; Flintlastic SA Mid Ply
SBS-SA
(585,SeY-Adhering)
I Self -Adhering
Ply
Flintlastic SA PlyBase; Flintlastic SA Mid Ply
Cap
Flintlastic SA Cap; Flintlastic SA Cap CoolStar; Flintlastic SA Cap FR; Flintlastic SA Cap FR CoolStar
16. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads.
Exterior Research and Design, LLC. d/b/a Trinity IERD
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION
Prepared by: Robert Nieminen, PE-59166 CertainTeed Flintlastic® Modified Bitumen Roof Systems; (610) 651-5847
Evaluation Report 3520.03.04-R20 for FL2533-1119
Revision 20: 09/14/2017
Appendix 1, Page 4 of 57
ME
\J TRINITY
ERD
:.TABLE 1Ei2: WOOD DECKS -NEW CONSTRUCTION,-REROOF (TEAR-3") oR'RECOVER-
SYSTEfV! TYPE Et ;NOWINSUi:ATED, MECHANICALLY ATTACHED.BASESHEET, BONDED:ROOF COVER
System
Deck
Base Sheet
Roof Cover (Note 14)
MOP
No.
(Note 1)
(psf)
Base
Fasteners .
Attach
Ply
Cap
W-89
MIn.15/32-Inch I
p plywood
Glasbase; Flexiglas Flintiastic
Base 20; Poly SMS Base; Ultra
Fllntfast 3 In. Insulation Plates with
FIIntFast #12 or #14, Trufast 3" Metal
6-inch o.c, at 4-Inch lap and 6-inch mc, in three
(Optional) BP-
AA, SBS-AA,
SBS-AA, SBS-
at max 24-Inch spans
Poly SMS Base; Yosemite
Insulation Plates with DP or HD, OMG 3
(3), equally spaced, staggered center
SBS-TA or
TAor APP-TA
-97.5
in. Round Metal Plates with OMG #14 HD
APP-TA
rw-40
Min.15/32-Inch plywood
Flintlastic APP Base T
OMG 3 in. Round Metal Plates with OMG
6-inch o.c. at 4-inch lap and 6-Inch o.c. in three
QL
}
at max 24-Inch spans
#14 HD
(a), equally spaced, staggered center rows.
APP-TA
APP-TA
-97.5
�!
W-91
Min.15/32-inch plywood
Glasbase; Flexlglas; Flintlastic
Base 20; All Weather/ Empire
Flintfast 3 in. Insulation Plates with
8-inch o.c. at 4-inch lap and S-Inch o.c. at three
(OptlonaQ.BP-
SBS-AA
at max 24-Inch spans
Bose; Poly SMS Base; Ultra Poly
FIIntFast #14; Trufast 3" Metal insulation
Plates with Trufast HD
(3} equally spaced, staggered center rows
AA, SBS-AA or
or
S85-TA
-97.5
SMS Base; Yosemite
SBS•TA
W-92
Min,19/32-Inch plywood I wood
Glasbase; Flexiglas; Flintlastic
Base 20; Poly SMS Base; Ultra
Note 2
7-Inch o.c. at 3-Inch lap and 7-inch o.c. in three
SP-AA, SBS-
SBS-AA, SBS-
atmax 24 Inch spans
Poly SMS Base; Yosemite
(3), equally spaced, staggered center rows
AA, SBS-TA APP-TA
TA or APP-TA
-105.0
W-93
Min.19/32-Inch plywood
at max 24-Inch spans
Filntlastic APP Base T
OMG 3In, Round Metal Plates with OMG
#14 HD or Dekfast Hex Plate with DekfastAPP-TA
7-Inch o.c. at 3-Inch lap and 7-Inch o.c, in three
APP-TA
-105,0
#14
{3}, equally spaced, staggered center rows
W-94
Min1532-Inch . plywood
/ p
Glasbase; Flexiglas; Filntlastic
Base 20; Poly SMS Base, Ultra
Flintfast 3 In. insulation Plates with
FIIntFast #12 or #14; Trufast 3" Metal
6-inch o.c.. at 4-Inch lap and 6-Inch o.c. In four
{Optional) BP-
AA, SOS -AA,
SBS-AA, SBS-
at max 24-Inch spans
Poly SMS Base; Yosemite
insulation Plates with DP or HO; OMG 3
(4), equally spaced, staggered center rows
SBS-TA or
TA or APP-TA
.1276
In. Round Metal Plates with OMG #14 HD
APP TA
W-95
Min.15/32-Inch plywood
Flintlastic APP Base T
OMG 3 in. Round Metal Plates with OMG
6-Inch o.c. at 4-inch lap and 6-inch o.c. In four
at max 24-Inch spans
#14 HD
(4), equally spaced, staggered center rows.
APP-TA
APP-TA
-127.5
C0Lb-APPl1E0.5ti13TEMSI
Glasbase; Flexiglas Base;
iW-96
Min.15/32-Inch plywood
p Y
Flintiastic Base 20, All Weather /
Empire Base; Yosemite Venting
Flintfast 3 In. Insulation Plates with
FllntFast #12 or #14, Trufast 3" Metal
at 4-Inch lap and In three
(Optional)
at max 241nch spans
Base; Flintlastic Poly SMS Base;
Insulation Plates with DP or HD
all
(3), equally d center
r r
(3), equally spaced, staggered center rows
SOS-CNi
SBS•CA1
-52.5
Flintlastic Ultra Poly SMS Bass
i 'gBl, �FtfR pit CON9TRt0N,d�R 1�ERQD6i �3
' �aSY&s101�kilr4FE1,8WNfRtl
System
No.
Deck
(Note 1)
Primer
Roof Cover (Note 14)
MDIP (psf}
Base
Ply
Cap
W-97
Min.15/32-inch plywood at max 24-Inch spans
F1intPrlme orFlintPrlme $A
SBS-SA-H
(Optional) SBS-TA, APP-TA
SBS-TA, APP-TA
I
-112A
W-98
Min.15/32-Inch plywood at,max 24-Inch spans
FIIntPrime or FlintPrime SA
SBS-SA
(Optional) SOS -SA
SBS-SA
-127.5
Exterior -Research and Design, LLC. d/b/a Trinity I ERD
Certificate of Authorization #9503
Prepared by; Robert Nieminen, PE-59166
6r"EDITION (2017) FBC NON-HVHZ EVALUATION
CertainTeed Flintiastic° Modified Bitumen Roof Systems; (610) 651-5847
Evaluation Report 3520.0344-1120 for F1.2533-1119
Revision 20; 09/14/2017
Appendix 1, Page 17 of 57