HomeMy WebLinkAboutPRODUCT APPROVAL MODIFIED BITUMEN ROOF SYSTEMr Product Approval
k USER: Public User
Product Approval Menu > Product or Application Search > Application List > Application Detail
r,
w FL # FL16027-R2
Application Type Revision
Code Version
Application Status
Comments
Archived
Product Manufacturer
Address/Phone/Email
Authorized Signature
Technical Representative
Address/Phone/Email
1
Quality Assurance Representative
Address/Phone/Email
Category
Subcategory
Compliance Method
2017
Approved
PY
FILE. -CH
Tri-Built Materials Group, LLC
PO Box 70
Rutherford, NJ 07070
(800) 516-1485
david.ruiz@tribuiltmg.com
David Ruiz
david.ruiz@tribuiltmg,com
David Ruiz
250 Route 17 North
East Rutherford, NJ 07073
(201)842-2449
david.ruiz@tribuiltmateriaisgroup.com
C Richard Schurman
9050 Louisiana Street
Merrillville, IN 46410
rich.schurman@alliedbuilding.com
Roofing
Modified Bitumen Roof System
Evaluation Report from a Florida Registered Architect or;
Professional Engineer
Evaluation Report - Hardcopy Received
Florida Engineer or Architect Name who developed the Robert Nieminen
Evaluation Report
Florida License PE-59166
Quality Assurance Entity UL LLC
Quality Assurance Contract Expiration Date 10/06/2018
Validated By John W. Knezevich, PE
Validation Checklist - Hardcopy Received
Certificate of Independence FL16027 R2 COI 2017 01 COI Nieminen.pdf
:r
I
f�
Referenced Standard ana_ it (of Standard)Standard Yes
Equivalence of Product Standards
Certified By
Sections from the Code
Product Approval Method
Date Submitted
Date Validated
Date Pending FBC Approval
Date Approved
ASTM D6163 200
ASTM D6164 201
ASTM D6222 201
FM 4470 201
FM 4474 201
Method i Option D
09/25/2017
09/30/2017
10/08/2017
12/12/2017
FL # Model, Number or Name 1 Description
16027.1 TRI-BUILT Modified Bitumen Roof SBS and APP modified bitumen roof systems
Systems
Limits of Use
Approved for use in HVHZ: No
Approved for use outside HVHZ: Yes
Impact Resistant: N/A
Design Pressure: +N/A/-622.5
Other: 1.) The Design Pressure noted in this application refers
to one system, Refer to ER Appendix for all systems and max.
design pressures. 2.) Refer to ER Section 5 for Limits of Use.
Installation Instructions
FL16027 R2 II 2017 09 FINAL Al ER TRI
BUILT MODBIT FL16027-R2.odf
Verified By: Robert Nleminen PE-59166
Created by Independent Third Party: Yes
Evaluation Reports
FL16027 R2 AE 2017 09 FINAL ER TRI
BUILT MODBIT FL16027-R2 Ddf
Created by Independent Third Party: Yes
Bac#c ;Vent
Contact Us :: 2601 Blair Stone Road Tallahassee FL 32399 Phone: 850-467-1824
The State of Florida is an AA/EEO employer. Copyright 2007-2013 State of Florida.:: Privacy Statement :: Accessibility Statement :: ggl
Under Florida law, email addresses are public records. If you do not want your e-mail address released In response to a public -records request,
mail to this entity. Instead, contact the office by phone or by traditional mall. If you have any questions, please contact 850.487.1395. *PL
455.275(1), Florida Statutes, effective October 1, 2012, licensees licensed under Chapter 455, F.S. must provide the Department with an emai
one. The emails provided may be used for official communication with the licensee. However email addresses are public record. If you do not wi:
address, please provide the Department with an email address which can be made available to the public. To determine if you are a licensee un
please click here .
Product Approval Accepts:
IM '° W OR Im
t'C11.I"Li1tA3i 1'I3I("4
�� �1R4y1
� TRINITY1 ER®
Table
Deck
Application
Type
Description
1A-1
Wood
New or Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
page
4
1A-2
Wood
New, Reroof (Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet; Bonded Insulation, Bonded Roof Cover
5
16
Wood
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
5
1C
Wood
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
6
1D
Wood
New, Re &(3ea*Gff) or Recover
D
Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover
6
Er'
1E-2
Ultood
Wood
litevu o Reroof (Tear -Off)
New, Reroof (Tear -Off) or Recover
E
E
on-Insu led, Mech. Attached Base Sheet, Bonded Roof Cover
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
g
1F
Wood
New or Reroof (Tear -off)
F
Non -Insulated, Bonded Roof Cover
8
2A
Steel or Structural concrete
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
9
2B
Steel or Structural concrete
New, Reroof (Tear -Off) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
9
2C
Steel or Structural concrete
New, Reroof (Tear -Off) or Recover
D
Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover
10
3A
Structural concrete
New or Reroof (Tear -off)
A-1
Bonded Insulation, Bonded Roof Cover
11-14
3B
Structural concrete
New or Reroof (Tear -Off)
F
Non -Insulated, Bonded Roof Cover
14
4A
LWIC
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
15-16
48
LWIC
New or Reroof (Tear -Off)
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
16
4C
LWIC
New or Reroof (Tear -Off)
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
17-19
5A
CWF
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
20
5B
CWF
New, Reroof (Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover
21
5C
CWF
New, Reroof (Tear -Off) or Recover
B
Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover
22
5D_ _
CWF
New, Reroof (Tear -Off) or Recover
C
Mech. Attached insulation, Bonded Roof Cover
22
5E
CWF
New, Reroof (Tear -Off) or Recover
E
Non -insulated, Mech. Attached Base Sheet, Bonded Roof Cover
22
6A
Gypsum
New or Reroof (Tear -Off)
A-1
Bonded Insulation, Bonded Roof Cover
23
6B
Gypsum
New, Reroof (Tear -Off) or Recover
A-2
Mech. Attached Anchor Sheet, Bonded insulation, Bonded Roof Cover
24
6C
Gypsum
New, Reroof (Tear -Of) or Recover
C
Mech. Attached Insulation, Bonded Roof Cover
24
6D
Gypsum
New, Reroof (Tear -Off) or Recover
E
Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover
24
7A
Various
Recover
A-1
Bonded Insulation, Bonded Roof Cover
25-26
7B
Various
Recover
F
Non -insulated, Bonded Base Sheet, Bonded Roof Cover
26
The following notes apply to the systems outlined herein:
1. The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction.
Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation.
Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement:
➢ Wood: Minimum 0.75-inch penetration.
➢ Steel: Minimum 0.75-inch penetration and engage the top flute of the steel deck.
➢ Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions.
Unless otherwise noted, insulation may be any one layer or combination of polylsocvanurate, polystyrene, wood fiberboard, perlite, gypsum -based roof board or mineral -wool roof board that meets the CIA
requirements of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover.
Exterior Research and Design, LLC. d/b/a Trinity ) ERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6' EDITION (2017) FBC NON-HVHZ EVALUATION
TRI-BUILT Modified Bitumen Roof Systems; (800) 516-14SS
Evaluation Report A42970.10.12-R2 for F1.16027-112
Revision 2: 09/25/2017
Appendix 1, Page 1 of 26
TRINITY I ERD
Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover), whereby the base
sheet fasteners are installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and
structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC
Approval documentation.
Preliminary insulation attachment for System Type D: Unless otherwise noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016).
6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published instructions.
➢ HA (HA): Full coverage at 25-30 Ibs/square.
➢ Dow iNSTA STIK Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1-inch wide ribbons,l2-Inch o.c
➢ Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c.
➢ OMG OlyBond 500 (OB500): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c (PaceCart or SpotShot). Note: Olyflond Green may be used where OlyBond 500 is referenced.
➢ OlyBond Classic (OB Classic): Full coverage at 1 gal/square.
➢ ICP Adhesive & Sealants CR-20: Continuous 2.5-3.5-inch wide ribbons,12-inch o.c.
➢ Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, adhesive ribbons shall be staggered from layer -to -layer a distance of one-half the ribbon spacing.
➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing.
7. Unless otherwise noted, all insulations are fiat stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations may be substituted with the following Maximum
Design Pressure (MDP) limitations. In no case shall these values be used to 'increase the MDP listings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then
the thinner board listed below may be used as a drop4n for the equivalent thicker material listed in the table:
➢ Millennium One Step Foamable Adhesive (M-OSFA): MDP -157.5 psf (Min. 0.5-inch thick)
➢ OMG OlyBond 500 (OB500): MDP -45.0 psf (Min. 0.5-inch thick Multi -Max FA-3)
➢ OMG OlyBond 500 (06500): MDP -187.5 psf (Min. 0.5-inch thick ISO 95+ GL)
➢ OMG OlyBond 500 (OB500): MDP -315.0 psf (Min. 0.5-inch thick ENRGY 3)
➢ OMG OlyBond 500 (OB500): MDP -487.5 psf (Min. 0.5-inch thick ACFoam 11)
➢ ICP Adhesive & Sealants CR-20: MDP -117.5 psf (Min.1.0-inch thick)
8. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft.
9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC
Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD3, FM Loss
Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk; carry the limitations set forth in Section 2.2.10.1 of FM Loss
Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements.
10. For fully bonded assemblies, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16, and no rational analysis is permitted.
11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the
minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105.
12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing
roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with
ANSI/SPRI IA-1, ASTM E907, FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS 124.
13. For Recover Applications using System Type D, the insulation is optional; however, the existing roof system shall be suitable for a recover application.
14. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC Is referenced, refer to current LWC
Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be 300 psi. In all cases, the minimum top -coat thickness is 24nches.
For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1.
Exterior Research and Design, LLC, d/b/a Trinity) ERD
Certificate of Authorization 49503
Prepared by: Robert Nleminen, PE-59166
eEDITION (2017) FBC NON-HVHZ EVALUATION
TRI-BUILT Modified Bitumen Roof Systems; (900) 516-148s
Evaluation Report A42970.10.12-R2 for FL160Z7-R2
Revision 2: 09/25/2017
Appendix 1, Page 2 of 26
15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications.
TRIM Y' ESQ
I
e }� 1ti ,1�a. 1, n y-i ... it � :� �, `.,.: .5f, ti _.: '2�.. �:� 1 -t..f L '(wi':� J i".;✓.:..; ,. ...`,4�.:ti -1. � b .'1 `y. L^` - y-' t 1: `^.
Reference
Layer
Material
Application
BP -AA
Base and PI sheets, Asphalt-Applied)HA
( Y
Base Ply
FBC Approved ASTM D4601, Type II
at 20-40 Ibs/square
Ply
FBC Approved ASTM D2178, Type IV or VI
SBS-AA
(SBS, Asphalt -Applied)
Cap Ply
TriBuilt SBS Granular
HA at 20-40 lbs/square
SBS-TA
(SBS, Torch -Applied)
Cap Ply
TriBuilt SBS Granular
Torch -Applied
SBS-SA
(SBS, Seff-Adhering)
Base Ply
TriBuilt SA SBS Base
Self -Adhering
Cap Ply
TriBuilt SA SBS Cap
APP-TA
(APP, Torch -Applied)
Base Ply or Ply
TriBuilt APP Smooth
Torch -Applied
Cap Ply
TriBuilt APP Smooth, TriBuilt APP Granular
APP-SA
(APP, Self -Adhering)
Ca P PIY
TriBuilt SA APP Cap
Self -Adhering
16. Vapor barrier options for use over structural concrete deck followed by adhered insulation carry the following Maximum Design Pressure (MDP) limitations. The lesser of the MDP listings below vs. those in Table 3A
applies:
• t _ : t - ,w . 1.itTT.Yt�:� a. �9 . t Kink".
Option #
Primer
Vapor Barrier
Insulation Adhesive
MDP (psf)
Type
Attach
VB-1.
ASTM D41
TriBuift SA SBS Base
Self -Adhering
Inta-Stik or CR-20,12-inch o.c.
-60.0
VB-2.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
Insta-Stik,12-inch o.c.
_75,0
VB-3.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
Millennium One Step Foamable Adhesive,12-inch o.c.
-157.5
VB-4.
ASTM D41
TriBuilt SA SBS Cap
Self -Adhering
CR-20,12-Inch o.c.
-270.0
VB-S.
ASTM D41
TriBuilt SA SBS Base
Self -Adhering
Millennium One Step Foamable Adhesive, Millennium PG-1 Pump Grade
Adhesive, OlyBond 500 or CR-20,12-inch o.c.
-290.0
17. Dens Deck shall be field -primed with PG300 prior to self -adhering membrane application. Refer to tables herein for other priming requirements.
18. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads.
Exterior Research and Design, LLC. d/b/a Trinity IERD Evaluation Report A42970.10.12-R2 for FL16027-RZ
Certificate of Authorization #9503 6TM EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017
Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems, (800) 516-1485 Appendix 1, Page 3 of 26
TR1NffY '1 ERD
:+•.Y. l�'. �. .r„ ,1. 1^s r .. : M'.y ,>� �� .'{ ,_ f✓ -/.W J' i- +:'-_ ..,,s c .� :.0 @��p l:' .i� ^F .p` x.; t ,,'L� T } .A Y' i !-. , .y..
}y,: :6 j
'.N:...i:. "`.,�.^ i
' F" 'S1 1 '4
.....,..,... : •. ,r ... M ,y. ... .. { �. ., ., .. .c ,.. ,!�:y _J i ;d,. e .,:._i. «... .,-(�.. � ,...: n.. / •Vx - .+•. <. . ,a. -
,,,_.,• ..{..L--�'F,t d. �-. s,,?s-.. ..,..,Xi,.....:•s.. ve; , ...;. �..._ s� '- -."`. .. E b: ,:: .,• �o� -:P., J: .a: xl;:, +'e
.. .,-: rx.... . .. v .( � l „^ t*..... -..:.. �.., �,. A;( _.e.0 ry.4 i..�..., ..,.,, �,.....,.snR•' `1 :.i'>, ^. `2•.. p' .Y< 4 t 4 ✓,sy, n "t '4 .. �. S L y�1
/!�]({ /(/�k,r�•y 3.. �:1 ,;..0 t "S y9;�z .3 s;: X v3.Y Y "� � 4 ? ""'
...-: ..a. .. •:. a.. y,F
5 nx. ke„..:F } 'fj ��. t�,x � }. J`:. �.��k:�y■y �q yin -��[� ���p h �qt {7f?
-,:. ' -1R1 (t■.',�(�ly� 9. 'IM{�(7FLI:'�+ ��••�+ u �} •��+� bl��y 6�.•"l i h. �.
T,-K ��'7�1��IV IiLV `
..�.:. .,C.. ,.n •. h,.,..: ...^ I�►F11�P/TY�i/if1i� }� _ VCiJJG 3 C'. 4.a
� ti.;•LB. t1VQ��Q��k 4 rf J '1:Y
System Base Sheet
Deck (Note 1) Roof Cover (Note 15) MDP
No.
Base
Fasteners
Attach
Base Ply
Cap Ply
(ps"
Min. 15/32-inch
W-14
plywood at max. 24-
Polyglass Elastobase
Simplex MAXX Cap
9-Inc6h o.c. at 2-inch lap and 18 inch o.c in two,
(Optional) BP -AA or
SBS AA, SBS TA
inch spans
equally spaced, sta eyed center rows
P staggered
APP TA
or APP TA
-0S.0 ;
Min. 15/32-inch
W-15
plywood at max. 24-
Polyglass Elastobase
Simplex MAXX Cap
9-inch o.c. at 2-inch lap and 12-inch o.c. in two,
(Optional) BP -AA or
SBS-AA, SBS-TA
inch spans
equally spaced, staggered center rows
APP TA
or APP TA
-52.5
Min.19/32-inch
Polyglass Elastobase, Po lass Elastobase
W-
plywood at max
Poly, Polyglass G2 Base, C-ertainFee
Giasb' i�restone
32 1-5/8-inch diameter tin caps
11
8-inch o.c. in 4-inch la and 8-inch o.c. in three,
(Optional) One or
more BP -AA
BS-
T
24-inch spans
E MB Base, JM Perma-
with ga. annular ring shank nails
equally spaced, staggered center rows
or
APP-TA
T
-60.0
28, Tamko Glass Base or GAFGIAS #75
Min.19/32-inch
W-17
plywood at max.
Polyglass Elastobase or Polyglass
32 ga.,1-5/8-inch diameter tin caps
8-inch o.c. in 4-inch lap and 8-inch o.c. in three,
(Optional) One or
SBS-SA, APP-
24-inch spans
Elastobase Poly with poly top surface
with 11 ga. annular ring shank nails
equally spaced, staggered center rows
more SBS-SA or
SA, SBS-TA or
-60.0
APP-TA
APP-TA
Min. 15/32-Inch
W-18
plywood at Max. 24-
Polyglass Elastobase
Simplex MAXX Cap
6-inch o.c. at 2-inch lap and 6-Inch o.c. in two,
(Optional) BP -AA or
SBS-AA, SOS -TA
inch spans
equally spaced, staggered center rows
APP-TA
or APP-TA
-90.0
Min.19/32-inch
W-19
plywood at max.
Polyglass Elastobase or Polyglass
32 ga.,1-5/8-inch diameter tin caps
4-inch o.c. in 4-inch lap and 4-inch o.c. in four,
(Optional) One or
SBS-SA, APP-
24-inch spans
Elastobase Poly with poly top surface
with 11 ga. annular ring shank nails.
equally spaced, staggered center rows
more SBS-SA or
SA, SBS-TA or
-97,5
APP-TA
APP TA
Min.15/32-inch
-' - -` - -
W-20
plywood at max. 24-
Polyglass Elastobase
Simplex MAXX Cap
6-inch o.c, at 2-inch lap and 6-inch o.c. in three,
(Optional) BP -AA or
SBS-AA, SBS-TA
inch spans
equally spaced, staggered center rows
APP-TA
or APP TA
-105.0
Min.19/32-inch
W-21
plywood at max.
Polyglass Elastobase or Polyglass
32 ga.,1-5/8-inch diameter tin caps
P
6-inch O.C.in 4-inch la and 6-inch o.c. in four,
P
(Optional) One or
SBS-AA, SBS-
24-inch spans
Elastobase Poly
with 11 ga. annular ring shank nails
equally spaced, staggered center rows
more BP -AA or
TA, APP TA
-112.5
APP-TA
Min.19/32-inch
32 ga.,1-5/8-inch diameter tin caps
W-22
plywood at max.
Polyglass Elastobase or Polyglass
with 11 ga. annular ring shank nails.
64nch o.c. In 44nch lap and 6-inch o.c. in four,
(Optional) One or
585 , APPSA-
-SA
24-inch spans
Elastobase Poly with poly top surface
Note: Tin caps are to be primed with
equally spaced, staggered center rows
more APP TA
SA, SBS-TA or
-112.5
ASTM D41 primer.
APP TA
Exterior Research and Design, LLC. d/b/a Trinity IERD
Certificate of Authorization #9503
Prepared by: Robert Nieminen, PE-59166
6' EDITION (2017) FBC NON-WHZ EVALUATION
TRI-BUILT Modified Bitumen Roof Systems; (800) 526-1485
Evaluation Report A42970.10.12-R2 for FL36027-R2
Revision 2: 09/25/2017
Appendix 1, Page 7 of 26
",,,,",]TRINITY IERD.
' - k•'� � _ s� "" • 6L�. ��ry�; � 4,f� MI��` ���• l�r��
• :c.,. � x .' k.. „r ':,,_. dt'^ .. .. . .....:... ..,..;..,Y�EE,. NONtNSf3�1�D Af)E
iliac=
.• � 4,.. �:.`. 4. .;uir:.: v a,i4. .. .,.Y':,5 v. ssK.n.At�..::.
System
Dedc (Note 1)
Base Sheet
Roof Cover (Note 15)
MOP
No.
Base
Fasteners
Attach
Base Ply
Cap Ply
(pso
Min.19/32-inch
Poly, ss Elastobase, Polyglass Elastobase
P
Poly, Polyglass G2 Base, CertainTeed
OMG Hat Bottom Plates (square) with
12-inch o.c. in flinch lap and 12-inch
(Optional) One or
W-1
plywood at max.
Glasbase, Firestone MB Base, JM Perma-
Roofgrip #14, Dekfast Hex with Dekfast #14
o.c. in two, equally spaced, staggered
more BP -AA or
SBS-AA, SBS-
-525
i
24-inch spans
Ply 28, Tamko Glass Base or GAFGLAS #75
or TruFast MP-3 with TruFast HD
center rows
APP-TA
TA, APP TA
W-2
Min.19/32-inch
plywood at max.
Po
Polyglass Elastobase or Polyglass
Dekfast Hex with Dekfasi #14 or TruFast MP-
12-inch o.c, in 4-inch lap and 12-inch
One or more SBS-
SBS-SA, APP-
24-inch spans
Elastobase Poly with poly top surface
3 with TruFast HD
O.C. in two, equally spaced, staggered
SA
SA, SBS-TA or
-52.5'
center rows
APP-TA
W 3
Min.19/32-inch
at
Polyglass Elastobase or Polyglass
OMG Fiat Bottom Plates (square) with
12-inch o.c. in 4-inch lap and 12-inch
(Optional) One or
SBS-AA,
plywood max.
24-inch spans
Elastobase Poly
Roofgrip #12
o.c. in two, equally spaced, staggered
more BP -AA or
565-
TA, APP-TA
-60.0
center rows
APP-TA
W 4
Min. 19/32 inch
plywood at max
Polyglass Elastobase or Polyglass
OMG Flat Bottom Plates (square) with
(q )
12-inch o.c. in 4-inch lap and 12-inch
One or more SBS
SBS-SA, APP-
24-inch spans
Elastobase Poly with poly top surface
Roofgrip #12
o.c. in two, equally spaced, staggered
SA, SBS-TA or
-60.0°
center rows
APP-TA
�"'�+' X .,,:.'.rs,x � �' k'� , z-' a.•, �',.. 'M. �s t _.,.t r � a � `- . . �,_ -. ; . n.. .-s. :;�,:;.
( . ,ti�.f.. �:. � .. M1 4.... :.'u: .: .S 5,. •. i,....,sn. n 1 ,,,,,.%... �,...,: Y r., .:.�._ .. y....{,, ,{, . h $ .� f h �5k'. �., �, ..��e
:>:.;�t a,�... ^� 1� � '1~ �...� Q k►.1N + x j� �S �y � 4 � r ,_�
i#' (,.s
p .., ,?, .::._ ��t .: '.�� �. � � �u;. -.�.- . , .�" 4 � � d` 5 }�,l �'�. v_
. ., 5��7#�l?gP�N�ti�l►Q��' �Q�(��.»„rx �s .,y,� r'�'" � .�n -:'x y.'r
_ , , -.. ..*. �' -. .,,. ,,......>.. . .. ,<2^:: ,.r. ,°t ... _,� P!�
System
Roof Cover (Note 15j
No.
Deck
Primer
MDP
Joint Treatment
Base ply
Ply
Cap Ply
(psf)
Min. 15/32-inch plywood
W-5
(Optional) ASTM D41
None
SBS-SA
(Optional) SBS-SA or
SBS-SA, APP-SA, SBS-TA
at max. 24 inch spans
APP TA
orAPP-TA
-90.0
W-6
Min.15/32-inch plywood
(Optional) ASTM D41
Plywood joints are covered with 4-inch wide strips of TriBuilt SA
(Optional) SBS-SA or
SBS-SA, APP-S SBS-TA
A'
at max 24-inch spans
SBS Base, rolled into place to create continuous bond.
TriBuiit SA SBS Base
APP-TA
or APP-l'A
-97 5
Exterior Research and Design, LLC. d/b/a Trinity IERD
Certificate of Authorization #9503 -
Prepared by: Robert Nieminen, PE-59166
e EDMON (2017) FBC NON-HVHZ EVALUATION
TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485
Evaluation Report A42970.10.12-112 for FL16027-R2
Revision 2: 09/25/2017
Appendix 1, Page 8 of 26