1. The truss design drawings referenced below have been prepared based on design criteria and requirements set forth in the
Construction Documents, as communicated by the Truss Manufacturer.
2. The engineer's signature on these drawings indicates professional engineering responsibility solely for the individual components
to be able to resist the design loads indicated, utilizing all the design parameter and materials indicated or referenced on each
individual design.
3. It is the Building Designer's responsibility to review the truss design drawings to insure compatibility with the Building design,
Refer to all notes on the individual truss design drawings.
2 Truss Design Drawing(s):
1-A1: SID 226069
2-A2: SID 226070
CEIVE
MAR 2, 72018
ST. Lucie County, Permitting
ComponerL, _.,IolutionsTM Important Infor(_ _,?ion & General Notes
.K fit
Symbols and Nomenclature
5X7 Plate size; the first digit is the plate width (perp. to the slots)
and the second digit is the plate length (parallel to the slots).
5X7-18 IA -18, -16S5 or -1 BS6 following the plate size indicates
different 18 ga plate types.
These symbols following the plate size indicate the direction
= I of the plate length (and tooth slots) for square and nearly
square plates.
10-3-14 Dimensions are shown in feet -inches -sixteenths (for this
example, the dimension is 10'-3 14/16").
Joints are numbered left to right, first along the top chord
and then along the bottom chord. Mid -panel splice joint
numbers are not shown on the drawing. Members are
identified using their end joint numbers (e.g., TC 2-3).
When this symbol is shown, lateral restraint is required
on the member near the location(s) indicated on the
\ graphic and in the Bracing Data Summary. See Note 3
\\\ under Handling, Installing, Restraint & Bracing for more
information.
Bearing supports (wall, beam or other), on which the
truss must completely bear. Bearing material is checked
for perpendicular -to -grain resistance only. The Building
Designer is responsible for all other bearing design
considerations.
Truss -to -Truss or Truss -to -Structural Element connections,
'Ll lr-3 which require a hanger or other structural connection (e.g.,
toe -nail) that has adequate capacity to resist the max.
reactions and uplifts shown in the Reaction Summary.
Design of the Structural Element and the connection of the
Truss to the Structural Element is by others.
Note: These symbols are for graphical interpretation only; they are not
intended to give any indication of the geometry requirements of the actual
item that is represented.
Materials and Fabrication
Design assumes truss is manufactured in accordance with the
TDD and the quality criteria in ANSI/TPI 1 Chapter 3, unless more
restrictive criteria are part of the contract specifications.
Unless specifically stated, lumber shall not exceed 19% moisture
content at time of fabrication or in service.
Design is not applicable for use with fire retardant, preservative
treated or green lumber unless specifically stated on the TDD.
Plate type, size, orientation and location indicated are minimum
plating requirements. Plates shall be embedded on both faces of the
truss at each joint.
Truss plates shall be centered on the joint unless otherwise
specified on the joint details.
Referenced Standards
ANSI/TPI 1: National Design Standard for Metal Plate Connected Wood
Truss Construction , a Truss Plate Institute publication (www.tpinst.org).
BCSI: Guide to Good Practice for Handling, Installing, Restraining &
Bracing Metal Plate Connected Wood Trusses, a joint publication of the
Truss Plate Institute (www.tpinst.org ) and the Structural Building
Components Association (www.sbcindustry.com ).
General Notes
1. Each Truss Design Drawing (TDD) provided with this sheet has been
prepared in conformance with ANSI/TPI 1. Refer to ANSI/TPI 1 Chapter 2 for
definitions of all capitalized terms and for the responsibilities of all parties
involved, which include but are not limited to the responsibilities listed on this
sheet.
2. TDDs should not be assumed to be to scale.
3. The Contractor and Building Designer shall review and approve the
Truss Submittal Package.
4. The suitability and use of the component depicted on the TDD for any
particular building design is the responsibility of the Building Designer.
5. The Building Designer is responsible for the anchorage of the truss at all
bearing locations as required to resist uplift, gravity and lateral loads, and for
all Truss -to -Structural Element connections except Truss -to -Truss
connections.
6. The Building Designer shall ensure that the supporting structure can
accommodate the vertical and/or horizontal truss deflections.
7. Unless specifically stated otherwise, each Design assumes trusses will
be adequately protected from the environment, including not being used in
locations where the sustained temperature is greater than 150°F.
8. Trusses are designed to carry loads within their plane. Any out -of -plane
loads must be resisted by the Permanent Building Stability Bracing.
9. Design dead loads must account for all materials, including self -weight.
The TDD notes will indicate the min. pitch above which the dead loads are
automatically increa sed for pitch effects.
10. Trusses installed with roof slopes less than 0.25/12 may experience
(but are not designed for) ponding. The Building Designer must ensure that
adequate drainage is provided to prevent ponding.
Handling, Installing, Restraint & Bracing
The Contractor is responsible for the proper handling, erection, restraint
and bracing of the Trusses. In lieu of job -specific details, refer to BCSI.
ANSI/TPI 1 stipulates that for trusses spanning 60' or greater, the
Owner shall contract with any Registered Design Professional for the design
and inspection of the temporary and permanent truss restraint and bracing.
Simpson Strong -Tie is not responsible for providing these services.
Trusses require permanent lateral restraint of chords and certain web
members (when indicated) at the locations or intervals indicated on the TDD.
This shall be accomplished in accordance with: standard industry lateral
restraint/bracing details in BCSI-133 or BCSI-137, supplemental bracing details
referenced on the TDD, or as specified in a project -specific truss permanent
bracing plan provided by the Building Designer.
Additional building stability permanent bracing shall be installed as
specified in the Construction Documents.
Special end wall bracing design considerations may be required if a flat
gable end frame is used with adjacent trusses that have sloped bottom
chords (see BCSI-133).
Do not cut, drill, trim, or otherwise alter truss members or plates without
prior written approval of an engineer, unless specifically noted on the TDD.
Piggyback assemblies shall be braced as per BCSI-133 unless otherwise
specified in the Construction Documents.
DSB-89 Recommended Design Specification for Temporary Bracing of
Metal Plate Connected Wood Trusses, a Truss Plate Institute publication
(www.tpinst.org).
NDS: National Design Specification for Wood Construction published by
American Forest & Paper Association and American Wood Council.
ESR-2762 Simpson Strong -Tie® AS Truss Plates are covered under
ESR-2762 published by the International Code Council Evaluation Service
(www.icc-es.org ).
TD-GEN-0003A 612015
Truss: Al
Project (Same: 00271-Shed City: 7
Customer: Ron Lafferty -
Truss Mfr. Contact: Rick Mills
PA 5-0-8 5-0-8 �8-Q
5-0-8 l 10-1-0
4/12 4x4= -4/12
N op
O I
t 3-15 3x4= 3x� 3-15 ri'
N ry
2x31I
3.5" 3.5"
5-0-8 5-0-8
5-0-8 l 10-1-0
1 4
10-1-0
Plates -- Simpson Strong -Tie 20 ga (AS20) or 18 ga (AS1811S, AS18S5, or AS18S6) indicated by '-18'
Code/Design: FBC-2017/TPI-2014
PSF Live Dead Dur Factors
TC 20.0 7.0 Live Wind Snow
BC 0.0 10.0 I= 1.25 1.60 N/A
Total 37.0 Plt 1.25 1.60 N/A
Spacing: 2-00-00 o_c. Plies: 1
Repetitive Member Increase: Yes
Green Lumber: No Wet Service: No
Fab Tolerance: 20% Creep (Kcr) = 2.0
OH Soffit Load: 2.0 PSF
Material Summary
TC 2x4 SP (ALSC6-2013) #2
BC 2x4 SP (ALSC6-2013) #2
Webs 2x4 SP (ALSC6-2013) #2
Member Forces Summary
..Mem...
Ten
Comp
-CSI_
TC OH- 1
14
2
0.05
1- 2
930
784
0-52
2- 3
912
775
0.52
3-OH
14
0
0.05
BC 1- 4
577
706
0.30
3- 4
577
706
0.30
Web 2- 4
210
26
0.04
-----------Snow Load Specs-----------
ASCE7-10 Ground Snow (Pg) = N/A
Risk Cat: II Terrain Cat: C
Roof Exposure: Sheltered
Thermal Condition: All Others
Unobstructed Slippery Roof: No
Low -Slope Minimums (Pfmin): No
Unbalanced Snow Loads : No
Rain Surcharge: No Ice Dam Chk: No
----------Wind Load Specs----------
ASCE7-10 Wind Speed (V) = 160 mph
Risk Cat: II Exposure Cat: C
Bldg Dims: L = 0.0 ft B = 0.0 ft
M.R.H (h) = 15.0 ft Kzt = 1.0
Bldg Enclosure: Partially Enclosed
Wind DL (psf) : TC = 5.0 BC = 5.0
End Vertical Exposed: L - Yes R = Yes
Wind Uplift Reporting: HybridMW
Reaction Summary
------------- Reaction Summary (Lbs)--------------
Jnt--X-Loc- React -Up- --Width- -Regd -Mat PSI
1 01-12 411 431 03-08 00-09 SPF 470
3 9-11-04 411 421 03-08 00-09 SPF 470
Max Horiz = -45 / +13 at Joint 1
Loads Summary
This truss has been designed for the effects of an unbalanced top chord
live load occurring at [50008] using a 1.00 Full and 0.00 Reduced load
factor.
See Loadcase Report for loading combinations and additional details.
Dead Loads may be slope adjusted: > 12.0/12
Notes
Plates designed for Cq at 0.80 and Rotational Tolerance of 10.0
degrees
Plates located at TC pitch breaks meet the prescriptive minimum size
requirement to transfer unblocked diaphragm loads across those joints.
SID: 0000226069
TID: 63211
Date: 03/21/18
Page: 1 of 1
-------Additional Design Checks------
10 psf Non -Concurrent BCLL: Yes
20 psf BC Limited Storage: Yes
200 lb BC Accessible Ceiling: No
300 lb TC Maintenance Load: No
2000 lb TC Safe Load: No
Unbalanced TCLL: Yes
Deflection Summary
TrussSpan Limit Actual(in) Location
Vert LL L/360 L/999(-0.02) 4- 3
Vert CR L/240 L/999(-0.04) 4- 3
Herz LL 0.75in ( 0.01) @Jt 3
Herz CR 1.25in ( 0.02) @it 3
Vert CR and Herz CR are the vertical and
horizontal deflections due to live load
plus the creep component of deflection
due to dead load, computed as Defl LL +
(Kcr - 1) x Defl_DL in accordance with
ANSI/TPI 1.
Bracing Data Summary
------------ Bracing Data ------------
Chords; continuous except where shown
Web Bracing -- None
Plate offsets (X, Y):
(None unless indicated below)
i
Z.* : No. 76864
._ � Q •• ST ♦
111,11111115
COA #30003 3/2 1 /20 1 8
NOTICE A copy of this design shall be furnished to the erection contractor. The design of this individual truss is based on design criteria and requlromont8 supplied by lh Component Solutions
Truss Manufacturer and relies upon the accuracy and completeness of the information set forth by the Building Designer. Aseal on this drawing Indicates acceptance of Truss Studio V
professional engineering responsibility solely for the truss component design shown. See the cover page and the 'Important Information & General Notes' page for 2017.7 -1-21
additional information. All connector plates shall be manufactured by Simpson Strong -Tie Company, Inc in accordance with ESR-2762. All connector plates aro 20 gouge Helpdesk: 1-866-252-8606
unless the specified plate size is followed by a •-18' which indicates an 18 gauge plate, or'S# 18", which indicates a high tension 18 gauge plate. CSHolp@strongtie.com
Truss: A2
Project [lame: 00271Shed Qty: 2
Customer. Ron Lafferty
Truss Mfr. Contact: Rick Mills
PA5-0-8
( 4 5-0-8 A
5-0-8 1 2 3 -1-0 5
4/12 4x4= -4/12
(V 00
I I
O
N 3-15 3x� x 3-15 1
r4
3.5•' 3.5"
Typical plate: 2x3
5-0-8 5-0-8
5-0-8 10-1-0
1 6 7 8
10-1-0
Plates -- Simpson Strong -Tie 20 ga (AS20) or 18 ga (AS1811S, AS1BS5, or AS18S6) indicated by '-18'
Code/Design: FBC-2017/TPI-2014
PSF Live Dead Dur Factors
TC 20.0 7.0 Live Wind Snow
BC 0.0 10.0 I= 1.25 1.60 N/A
Total 37.0 Plt 1.25 1.60 N/A
Spacing: 2-00-00 o.c. Plies: 1
Repetitive Member Increase: Yes
Green Lumber: No Wet Service: No
Fab Tolerance: 20% Creep (Kcr) = 2.0
OH Soffit Load: 2.0 PSF
Material Summary
TC 2x4 SP (ALSC6-2013) #2
BC 2x4 SP (ALSC6-2013) #2
Webs 2x4 SP (ALSC6-2013) 12
Member Forces Summary
..Mem...
Ten
Comp
.CSI.
TC OH- 1
14
2
0.05
1- 3
930
784
0.52
3- 5
912
775
0.52
5-OH
14
0
0-05
BC 1- 7
577
706
0.30
5- 7
577
706
0-30
Web 3- 7
210
26
0.04
-----------Snow Load Specs-----------
ASCE7-10 Ground Snow (Pg) = N/A
Risk Cat: II Terrain Cat: C
Roof Exposure: Sheltered
Thermal Condition: All Others
Unobstructed Slippery Roof: No
Low -Slope Minimums (Pfmin): No
Unbalanced Snow Loads : No
Rain Surcharge: No Ice Dam Chk: No
----------Wind Load Specs----------
ASCE7-10 Wind Speed (V) = 160 mph
Risk Cat: II Exposure Cat: C
Bldg Dims: L = 0.0 ft B - 0.0 ft
M.R.H (h) = 15.0 ft Kzt - 1.0
Bldg Enclosure: Partially Enclosed
Wind DL (psf) : TC = 5.0 BC = 5.0
End Vertical Exposed: L = Yes R - Yes
Wind Uplift Reporting: HybridMW
Reaction Summary
------------- Reaction Summary (Lbs)--------------
Jnt--X-Loc- React -Up- --Width- -Regd -Mat PSI
1 01-12 411 431 03-08 00-09 SPF 470
5 9-11-04 411 421 03-08 00-09 SPF 470
Max Horiz - -45 / +13 at Joint 1
Loads Summary
This truss has been designed for the effects of an unbalanced top chord
live load occurring at [50008] using a 1.00 Full and 0.00 Reduced load
factor.
See Loadcase Report for loading combinations and additional details -
Dead Loads may be slope adjusted: > 12.0/12
Notes
Gable webs are attached with min. lx3 20 ga- plates. The max. rake
overhang = 1/2 the truss spacing- If this truss is exposed to wind
loads perpendicular to the plane of the truss, it must be braced
according to a standard detail matching the wind criteria shown, or
according to the Construction Documents and/or BCSI -B3.
Plates designed for Cq at 0.80 and Rotational Tolerance of 10.0
degrees
Plates located at TC pitch breaks meet the prescriptive minimum size
requirement to transfer unblocked diaphragm loads across those joints.
SID: 0000226070
TID: 63211
Date: 03/21/18
Page: 1 of 1
-------Additional Design Checks------
10 psf Non -Concurrent BCLL: Yes
20 psf BC Limited Storage: Yes
200 lb BC Accessible Ceiling: No
300 lb TC Maintenance Load: No
2000 lb TC Safe Load: No
Unbalanced TCLL: Yes
Deflection Summary
TrussSpan Limit Actual(in) Location
Vert LL L/360 L/999(-0.02) 7- 5
Vert CR L/240 L/999(-0.04) 7- 5
Horz LL 0.75in ( 0.01) @it 5
Horz CR 1.25in ( 0.02) @Jt 5
Vert CR and Horz CR are the vertical and
horizontal deflections due to live load
plus the creep component of deflection
due to dead load, computed as Defl_LL +
(Kcr - 1) x Defl_DL in accordance with
ANSI/TPI 1-
Bracing Data Summary
------------ Bracing Data -----------
Chords; continuous except where shown
Web Bracing -- None
Plate offsets (X,1):
(None unless indicated below)
* : No. 76864
ID
Al-
Jil
'' ST
COA #30003 / i t3/21 /2018
NOTICE A copy of this design shall be furnished to the erection contractor. The design of this individual truss is based on design criteria and requirements supplied by th Component Solutions
Truss Manufacturer and relies upon the accuracy and completeness of the information set forth by the Building Designer. A seal on this drawing indicates acceptance of Truss Studio V
professional engineering responsibility solely for the truss component design shown. See the cover page and the 'Important Information & General Notes page for 2017.7.1.21
additional information. All connector plates shall be manufactured by Simpson Strong -Tie Company, Inc in accordance with ESR-2762. All connector plates are 20 gauge Helpdesk: 1-866-252-8606
unless the specified plate size is followed by a "A8• which indicates an 18 gauge plate, or'S# 18", which indicates a high tension 18 gauge plate. _ CSHelp@strongtie.com
,SIMPSON
Strong -Tie
GABLE STUI_ 'RACING DETAIL -130 MPH (NO; ;JAL), I TD-GBL-0006B
160 MPH (ULTIMATE)
NOTES:
1. This detail provides bracing/reinforcement options for the gable studs to
resist the out -of -plane wind loading. Refer to the individual truss design
drawing for bracing/reinforcement requirements for resisting the vertical
(in -plane) loads assumed in the design of the gable end frame.
Additional bracing/reinforcement at the end of the building and/or at the
gable end wall may be required. Refer to the Building
Designer/Construction Documents for all gable end frame and roof
system bracing requirements. For additional information, see BCSI-B3.
2. This detail does not apply to structural gables.
3. Connection requirements between the gable end frame and the wall to
be specified by the Building Designer.
4. The gable end frame must match the profile of the adjacent trusses. Do
not use a gable end frame with a flat bottom chord next to trusses with
sloped bottom chords, such as scissor or vaulted trusses.
Date:06/11/2014 1 Rev:B I Pg. 1 of 1
Diagonal Bracing
@ 4'-0" O.C. Max. Gable Stud Bracing
(24" O.C. Max)
'Diagonal braces not
shown for clarity. See
Section A -A.
La A
GABLE END WITH STUD BRACING/REINFORCEMENT
MINIMUM GABLE
MAX.
WITHOUT
L-
SCAB
DIAGONAL
BRACING
DIAGONAL
BRACING
STUD SIZE,
GABLE
BRACE
REINFORCEMENT'REINFORCEMENT'
@ MID -SPAN z
@ 1/3 POINTS
SPECIES & GRADE
STUD
SPACING
MAXIMUM STUD LENGTH 3
12' O.C.
4-0-4
6-10-4
8-0-12
8-0-12
12-1-4
2X4 SPF STUD
16" O.C.
3-7-0
5-11-4
7-2-0
7-2-0
10-9-0
or STANDARD
24" O.C.
1 2-11-0
4-10-4
1 5-10-4
5-10-4
8-9-4
1. L- and Scab Reinforcements shall be minimum 2x4 stud grade and must be a minimum of 90% of the gable
stud length. Fasten the reinforcement member to the gable stud with 10d nails @ 6" o.c.
2. Attach horizontal reinforcing member at mid -span (or 1/3 points as required) of the longest stud and install
diagonal bracing @ 4' o.c. (max) as shown in Section A -A.
3. Tabulated maximum stud lengths are based on components and cladding wind pressures using the wind
design parameters listed in the detail limitations. Gable stud deflection criteria is U240.
5-8d nails connecting Min. 2x4 #2 blocking between
sheathing to first 2 trusses (min) as shown.
blocking (Typ.)� Toe -nail blocking to trusses
Roof Sheathing with 2-10d nails at each end.
2-10d Toe -nails
(TYp•)
Trusses @ 24"
Bracing at ; O.C. Max.
1/3 points as
required
(See Table) '
2x6 diagonal brace at 48" O.C. (max
Attach to gable stud with 4-16d nails
and to blocking with 5-10d nails.
Horizontal L-reinforcement (located
at mid -span or 1/3-points of longest
End Wall stud as required per table.)
SECTION A -A
10d nails GABLE �`-10d nails
6" o.c. @ 6" o.c.
GABLE3�:
L-REINFX. STUD SCAB
STUDREINF.
SECTION B-B SECTION C-C
Gable Stud
Fasten diagonal
brace to gable stud
with 4-16d nails
2-10d nails into top reinf.
member (Typ. ea stud)
4-10d nails into
bottom reinf. member -
(Typ. ea stud)
2x6 Diagonal Brace
(Approx. 45-degrees
to roof diaphragm)
Fasten L-reinforcement
members together with
16d nails @ 6" O.C.
"-Min. 2x6
Min. 2x4
NOTE: Diagonal braces over 6-3" require a 2x4 T-brace
attached to one narrow edge. Diagonal braces over
12'-6" require 2x4s attached on both narrow edges. The
braces must cover 90% of the diagonal brace and shall
be fastened to the narrow edge with 10d nails at 6" o.c.
(min. 3" end distance). When attached on both narrow
edges, stagger the nails on each side by 3".
i DETAIL LIMITATIONS: Wind Speed Equivalent Nail Dimension
I Max. Mean Roof Height: 30' Nominal Ultimate 16d = 3.5" x 0.162"
Category: II 130 mph (160 mph) 10d = 3" x 0.148"
Exposure: B or C 8d = 2.5" x 0.131"
Load Duration Factor: 1.6
Wind Speed: 130 mph Nominal
\\`\>>tllllll///i /`
,CENT
* No.76864
°^ S
AL.
COA il30003 111, 3/21 /2018
This detail is to be used only for the application and conditions indicated herein, and its suitability for any particular truss/project shall be verified (by others). This detail is not intended to Simpson Strong -Tie Company
supersede any project -specific details provided in the Construction Documents. Truss configurations shown are for illustration only. Refer to the truss design drawing(s) accompanying
this detail for specific truss design information. Simpson Strong -Tie Inc. is not responsible for any deviations from this design.