HomeMy WebLinkAboutGENERATOR CONCRETE PAD1i N 0 �ENG11A �\ \ GENERATOR i PAD - \ 1�j- THICKNESS _ P P,0 BEN TC 11M CTO T/"` \/T C1111 PAD DIMENSIONS: CONCRETE PAD GENERATOR r-a = GENERATOR UNIT BY o SEPARATE SUBMITTAL 3 (SEE SCHEDULE FOR m MINIMUM WEIGHT REQUIRED) 54" LENGTH PLAN VIEW - - - ----- �- I - - --CONCRETE PAD-- ROAD MESH MASTERFIBER •3 MAC100 GROUND AMERICAST GENERATOR CONCRETE PAD GENERATOR TABLE: (ON -GRADE APPLICATIONS ONLY) �� �N�E® St Lucie County AMERICAST wron emerFcastlna mm '�iAIIID INAMIDRIOA:• FED TM d"^""Tt= LICH7-=d59-=S0167 3300 PJmemo Ave. FOn Pieroe, FL 3002 id. 7-971-102 Fmc 773-{64ASOD Ewtk HVHZ OR NON-HVHZ RISK EXPOSURE (EXP) RISK EXPOSURE (EXP) RISK EXPOSURE (EXP) COUNTY C D II C, -pII"•, {II III- . 11;C L5 I I P. BEACH 15O MPH 30.44 Psf 36.94 Psf 170 MPH 39.09 Psf 47.44'Psf- 180 MPH- 43.83,Psf-.53.19'PYf BROWARD 156 MPH 32.92 Psf 39.95 Psf 170 MPH 39.09 Psf 47.44 Psf_.180`MPH` '43:83.Fsf. 53:19 Psf MIAMI-DADE 165 MPH 36.83 Psf 44.69 Psf 175 MPH 41.43 Psf 50.28 Psf 186 MPH 46.80 Psf 56.80 Psf BRAND & MODEL CAPACITY WIDTH LENGTH -HEIGHf-'WEIGHT /ALLOWABLE ? PRESSURE COMMENTS Generac 005871 & 005883 10 KW 25.00 ; 48:00_:_ -29i00:" 387 Ibs '41.43 Psf EXP C 175 MPH & D 156 MPH Generac 005872 & 005884 14 KW 25.00'; 48;00�'` `29,00 " 439;Ibsf " �47:44 Psf EXP C 186 MPH & D 156 MPH Generac 6459, 6461, 6462 16 KW 25.00 " -48.00 "_ 29.00 ". - 513 Ibs ``47A4 Psf Generac 006721 16 KW 25.00 " 48.00" 29:00._' _448 Ibs 47.44 Psf Generac 005873 & 005885 17 KW 25.00"_ 48.00 "_ _ 29.00" _ 455_Ibs_ _- 47.44 Psf___ Generac 005874 & 005886 17 KW 25.00 ' t 48 00_ , 129 00 `_ "421 Ibs 47:44 Psf ` _ Generac 005875 & 005887 20 KW 25.00 " •48:00,'Sy ;p29:00•" ; 451•lbs­ :.l v 47:44,,Psf Generac 006729 & 006730 20 KW 25.00" + -48.00 "' ' 29.00 " s 516 Ibs- I `= -47.44 Psf Generac 006551 & 006552 22 KW 25.00 " 48.00 " 29.00 " 526 Ibs 47.44 Psf Kohler 14RES & 20RES 14-20 KW 26.00 " 48.00 " 29.00 " 500 Ibs 47.44 Psf GE 40323GE & 40324GE 13 KW 35.00 " 39.40 " 39.00 " 540 Ibs 39.09 Psf EXP C 170 MPH & D 156 MPH GE 04038215KW 15 KW 33.00 " 48.00 " 30.50 " 484 Ibs 43.83 Psf EXP C-180 MPH & D 156 MPH GE 04037817KW 17 KW 33.00 " 48.00 " 30.50 " 484 Ibs 43.83 Psf GE 40330GE & 40331GE 20 KW. _- _33.00= 48.00 " -30.50 " 600 Ibs 43.83 Psf Briggs & Stratton 040243-0 10 KW 31.00 " 32.00 " 34.00 " 430 Ibs 43.83 Psf Briggs & Stratton 040302-2 12 KW 33.75 " 50.00 " 31.60 " 507 Ibs 41.43 Psf EXP C 175 MPH & D 156 MPH Briggs & Stratton 040303-1 15 KW 33.75 " 49.00 " 31.60 " 562 Ibs 43.83 Psf EXP C 180 MPH & D.156 MPH Briggs &Stratton 040304-1 18 KW 33.75 " 49.00 " 31.60 " 568 Ibs 44.00 Psf Briggs & Stratton 040305-1 20 KW 33.75 " 49.00 " 31.60 " 570 Ibs 44.00 Psf Generac 7035, 7036, 7037 16 KW 25.00 " 48.00 " 29.00 " 406 Ibs 47.44 Psf EXP C 186 MPH & D 156 MPH Generac 007038 & 007039 20 KW 25.00 " 48.00 " 29.00 " 448 Ibs 47.44 Psf Generac 007042 & 7043 22 KW 25.00 " 48.00 " 29.00 " 466 Ibs 47.44 Psf 54r;. ji " v� -L--GENERATOR MOUNTING CONFIGURATION: GENERATOR GENERATOR ATTACHMENT BASE OR SIMPSON A24 ANGLE BRACE W/ (4) #10 SS 316 SELF -DRILLING T(v Q T-1- T_ F GENERATOR x I x I (SEE CONCRETE PAD w_ U.1 SCHEDULE FOR DIMENSIONS & WEIGHT = REQUIRED) 4" I L� I)� + 32" WIDTH -� 54" LENGTH I SIDE VIEW FRONT VIEW (SEE GENE_W 3v THICK GALV, FEB A WIND DESIGN REQUIREILENTRIe county, Perm (BASED ON ASCE 7-10 & FLORIDA BUILDING CODE SIXTH EDITION ZITrr)j- AT-GRADESIGN METHOD ULTIMATE DESIGN WIND SPEED, Vult = 186 mph NOMINAL DESIGN WIND SPEED,Vasd = 144 mph RISK CATEGORY = III INTERNAL PRESSURE COEF = N/A EXPOSURE CATEGORY = D WIND DIRECTIONALITY FACTOR Kd= 0.85 ENCLOSURE CATEGORY = N/A HEIGHT H = AT GROUND GUST EFFECT FACTOR = 0.85 PRESSURE AT HEIGHT H qh = 77.56 Ib/ft2 FORCE COEFFICIENT Cf = 1.44 , WIND PRESSUREI: P = qh G Cf = 56.80 Ib/ft2 (ASD) GENERAL NOTES ANCHOR TO PAD SCHEDULE: SUBSTRATE DESCRIPTION CONCRETE: (2)-3/8"0 TITEN HD (6000 PSI OR EQUIVALENT, MIN.) 2-3/4" FULL EMBED 0 CONCRETE, 3" MIN EDGE DISTANCE, 6" MIN. SPACING TO ANY ADJACENT ANCHOR. NOTES: 1. ANCHOR QUANTITY PER LONG SIDE 2.,_EMBEDMENT AND EDGE DISTANCE EXCLUDES:FI� _NISHES IF - -.APPLICABLE: - 3.-_ ENSURE -MINIMUM EDGE DISTANCE AS'NOTED-IN ANCHOR SCHEDULE. 4,. ENSURE`MINIMUMSPACING TO -ANY ADJACENT ANCHORS. ! - y_5. jFOL`LOW MANUFACTURER'S INSTALLATION INSTRUCTIONS TO `--INSTALL ANCHORS. v=t'� j�• GENERATOR= tII' ATTACHMENT BASE,- y a VARIES WffH`MODE 1v SEE GENERATOR SPECS } r -" Vie" SIMPSON TITEN HD, SEE ANCHOR SCHEDULE 2"x3"x3/s" GALV. STEEL - WASHER RUBBER VIBRATION PAD - VIBRATION PAD I- = c- f 1 CONCRETE PAD - _'•. �. 6,000 PSI LIGHTWEIGHT x CONCRETE MIX ` CONCRETE..PAD" . ,- E 6WEI PSI --1 I MASTERFIBER MAC 100 LIGHTWEIGHT ?CONCRETEIMIX 7 " y ¢' ?, 'I '' & ROAD MESH _._NOTES: " s% _ FOAM CORE 1., - Y DISTANCE DEPEND=ON''GENERATOR BASE LENGTH, NO LESS THAN 2". 2. X DISTANCE 3" FROM UNIT EDGE TO CLIP. 3. Z DISTANCE DEPEND ON GENERATOR BASE WIDTH, NO LESS THAN ANCHOR REQUIREMENTS 1. THIS SYSTEM HAS BEEN DESIGNED AND SHALL BE FABRICATED IN ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA BUILDING CODE SIXTH EDITION (2017). 2. REQUIRED WIND LOAD DESIGN PRESSURES CALCULATED FOR USE WITH THIS SYSTEM SHALL BE DETERMINED UNDER SEPARATE CERTIFICATION ON A JOB -SPECIFIC BASIS IN ACCORDANCE WITH THE GOVERNING CODE. SITE -SPECIFIC LOAD REQUIREMENTS AS DETERMINED. IN ACCORDANCE WITH THE APPLICABLE BUILDING CODE'SHALL BE LESS THAN OR EQUAL TO THE DESIGN PRESSURE "ASD" CAPACITY -VALUES LISTED HEREIN FOR ANY ASSEMBLY'AS.SHOWN. 3. DIMENSIONS ANO; WEI&T;OF-UNITS SHALL`•:CONF.ORM•TO SPECIFICATIONS STATED HERE_'IN: Ir ' 4. UNITS MUST BE CENTERED-ON.PAD•WITH OPPOSITE SIDES HAVING EQUAL CLEARANCE:;�A.MINIM UM DISTANCE•FROM UNIT TO PAD EDGE IS SPECIFIED..._ 5. CALCULATIONS MADE USING LIGHTWEIGHT`CONCRETE'125 PCF 6. THE AREA UNDER CONCERETE SLAB ON.GROUND SHALL HAVE ALL VEGETATION, STUMPS, ROOTS,.Ak,FOREIGN MATERIALS REMOVED PRIOR TO INSTALLATION ON COMPACTED SOIL AS VERIFIED BY OTHERS. :1 NI ° `I�,,• • rj`az 7. RESISTANCE TO.SL'IDING OF;T.HEPAD. OTHE,GROUND:IStNOT PART OF THIS DOCUMENT AS SOIL CHARACTERISTICS. AND PAD PLACEMENT VARIES'.---- 8. ELECTRICAL GROUND, WHEN REQUIRED, TO BE DESIGNED & INSTALLED BY OTHERS. ALL MECHANICAL SPECIFICATIONS (CLEAR SPACE, TONNAGE, ETC.) SHALL BE AS PER MANUFACTURER RECOMMENDATIONS AND ARE THE EXPRESS RESPONSIBILITY_O F_TH E-CONTRACTOR- -9. ENGINEER SEAL AFFIXED HERETO VALIDATES STRUCTURAL DESIGN AS SHOWN ONLY. USE OF THIS SPECIFICATION BY CONTRACTOR, et. al. INDEMNIFIES & SAVES HARMLESS THIS ENGINEER FOR ALL COST & DAMAGES INCLUDING LEGAL FEES & APPELLATE FEES RESULTING FROM MATERIAL FABRICATION, SYSTEM ERECTION, CONSTRUCTION PRACTICES BEYOND THAT WHICH IS CALLED FOR BY LOCAL, STATE, & FEDERAL CODES & FROM DEVIATIONS OF THIS PLAN. 10. WATER -TIGHTNESS OF EXISTING FINISHES SHALL BE THE FULL RESPONSIBILITY OF THE INSTALLING CONTRACTOR. CONTRACTOR SHALL ENSURE THAT ANY REMOVED OR ALTERED WATERPROOFING MEMBRANE IS RESTORED AFTER FABRICATION AND INSTALLATION OF STRUCTURE PROPOSED HEREIN. THIS ENGINEER SHALL NOT BE RESPONSIBLE FOR ANY WATERPROOFING OR LEAKAGE ISSUES WHICH MAY OCCUR AS WATER -TIGHTNESS SHALL BE THE FULL RESPONSIBILITY OF THE INSTALLING CONTRACTOR. 11. THE ROLE OF THIS ENGINEER FOR THIS PROJECT IS THAT OF SPECIALTY ENGINEER AND NOT THE ENGINEER OF RECORD. CONSEQUENTLY, THE ARCHITECT/ENGINEER OF RECORD SHALL BE RESPONSIBLE FOR THE INTEGRITY OF ALL SUPPORTING SURFACES TO THIS DESIGN WHICH SHALL BE COORDINATED BY THE PERMITTING CONTRACTOR. 12. THIS DOCUMENT IS'GENERIC AND DOES NOT PERTAIN TO ANY SPECIFIC PROJECT SITE: INFORMATION,CONTAINED'HEREIN IS NTRACTOR SUP'PCIED DATA AND ME S BASED ON CO - - A UREMENTS. ENGINEERING EXPRESS.SHALL NOT BE HELD RESPONSIBLE OR LIABLE IN ANY WAY FOR -ERRONEOUS OR INACCURATE DATA - OR MEASUREMENTS. DIMENSIONS ARE SHOWN TO ILLUSTRATE DESIGN FORCES AND16THER DESIGN CRITERIA.�T'HEYMAY `T VARY SLIGHTLY, BUT-MUSTREMAIN'WITHIN THE-L:IMITATIONS l SPECIFIED HEREIN. WORK'SHALL BE FIELD VERIFIED BY J{ OTHERS PRIOR TO CONSTRUCTION: ENGINEERING EXPRESS SHALL BE NOTIFIED AND GIVEN;AN OPPORTUNI_TYTO• REEVALUATE OUR WORK UPON�DISCOVERY OFANY;i ; ; �2"� INACCURATE INFORMATION'PRIOR'TO-MODIFICATION OF ` EXISTING FIELD CONDITIONS AND+FABRICA'TION AND, INSTALLATION OF MATERIALS': ALTERATIONS ORADDITIONS TO THIS DOCUMENT ARE NOT PERMITTED AND INVALIDATE OUR CERTIFICATION. 13. EXCEPT AS EXPRESSLY PROVIDED HEREIN, NO ADDITIONAL CERTIFICATIONS OR AFFIRMATIONS ARE INTENDED. BENNARDO, P.E. L BENNARDO, P.E. SIGNATURE ON SHEET 1, THIS SHEET IS PART OF DIGITALLY SIGNED FILE, SHALL REMAIN IN DIGITAL FORMAT, & PRINTED COPIES OF THIS DOCUMENT ARE NOT CONSIDERED SIGNED AND SEALED. IF THERE IS NO DIGITAL SIGNATURE ON SHEET 1 OR THIS SHEET DOES NOT CONTAIN AN ENGINEER'S ORIGINAL SIGNATURE & SEAL, � N Z M® W Cn , V F LL VLA wHJWOw WIn iLV) _XU) WW OLLj 1: CZ ZrnR F>< a:Lu U11 <QW�w0� m zZ WW Cf ON_jMWWV V N wo- �LL �z �t'ffi Wsw oW%D ,1 0 O d z O_ (D oY J w C7 Ld Y LL � N x Ukq��W _ ul C,� .� _j o:i lL w a a�^ M U)O z U LU o g Z L M O^ M LL N Y cL F- n � .+In cc) a w Q O U_ O o 0 g U' m coo.hi�F ILL LL 3 0 og 0 0 5 a " o �"6ylow� Nm 0 0 pw Qp ro, ,0 Q S2 � 2 C LL 0 �In po ~ a6 M r COPYRIGHT ENGINEERING EXPRESS 17-3961.1 SCALE: NTS UNLESS NOTED 0