SCOPE:
This Evaluation Report is issued under Rule
construction materials in the State of Florida
P.E. for use of the product under the Flori
products described herein have been evalu
sections noted herein.
DESCRIPTION: Boral Roof Underlayments
LABELING: Labeling shall be in accordance wi
herein.
CONTINUED COMPLIANCE: This Evaluation Report
Quality Assurance documentation changes, or I
this Evaluation Report by the named client c
changes or the referenced Quality Assurance d
Evaluation Report relative to updated Code req
ADVERTISEMENT: The Evaluation Report number
advertising literature. If any portion of the Eval
INSPECTION: Upon request, a copy of this entire
its distributors and shall be available for inspec
This Evaluation Report consists of pages 1
Prepared by:
Robert J.M. Nieminen, P.E.
Florida Registration No. 59166, Florida DCA ANE1983
BY
Offl ,101
;r DLII njNG T.'PJ?QT? EXTERIOR RESEARCH & DESIGN, LLC.
}$ CO;i :A NC Certificate of Authorization #/9503
i 3S3 CHRISTIAN STREET, UNIT#13
w2 OXFORD, CT 06478
�R)UT MST BE XEPT ON J033 (203) 262-9245
'TION WILL BE NIADE.
Evaluation Report M35710.12.10-R9
FL14317-R8
Date of Issuance:12/21/2010
f Revision 9:10/14/2017
ANYCOROpCS�D .
M-3 and the applicala e� fi118g �re^�Tg�y bg the use of
e documentation submitteT►fa3lip�+r�t,vlObert Nieminen,
Building Code and Florida Building C�11p��� ntial Volume. The
i for compliance with the 6th Edition (2017) Fa Building Code
h the requirements the J��� lity Assurance Agency noted
'�h�Tyf AEu SC�'��AC
valid until such time as threllateRM
8 'p referenced
rovisions of the Code that �� li�ceptance of
institutes agreement to notify Robert Niiemi P.E. if the product
mumentation changes. Trinityl ERD requires a complete review of this
lirements with each Code Cycle.
preceded by the words "Trinityl ERD Evaluated" may be displayed in
cation Report is displayed, then it shall be done in its entirety.
:valuation Report shall be provided to the user by the manufacturer or
ion at the job site at the request of the Building Official.
igh 7.
The facsimile seal appearing was authorized by Robert
Nieminen, P.E. on 10/14/2017. This does not serve as an
electronically signed document.
CERTIFICATION OF INDEPENDENCE:
1. Trinityl ERD does not have, nor does it intend to. acquire or will it acquire, a financial interest in any company manufacturing or
distributing products it evaluates.
2. Trinityl ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates.
3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for
which the evaluation reports are being issued.
4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the
product.
5. This is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any
project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained
specifically for that purpose.
File Copy
ROOFING COMPONENT EVALUATION:
1. SCOPE:
Product Category: Roofing
Sub -Category: Underlayment
Compliance Statement: Boral Roof Underlayments, as marketed by Boral Roofing, have demonstrated compliance
with the following sections of the 6th Edition (2017) Florida Building Code through testing in accordance with the
following Standards. Compliance is subject to the Installation Requirements and Limitations / Conditions of Use set
forth herein.
STANDARDS:
Section
Property
Standard
Year
1504.3.1
Wind Uplift
UL 1897
2012
1507.1.1, T1507.1.1, 1507.2.9.2
Physical
Properties
ASTM D1970
2015
1507.3.3
Physical
Properties
FRSA/TRI April 2012 (04-12)
2012
3. REFERENCES:
Entity
Examination
Reference
Date
ERD (TST 6049)
Physical Properties
M36790.07.11
09/30/2011
ERD (TST 6049)
Physical lProperties
640380.08.12
08/28/2012
ERD (TST 6049)
Tensile Adhesion / LTA
C41420.09.12-2
09/11/2012
ERD (TST 6049)
Adhesion
841940.09.12
09/13/2012
ERD (TST 6049) Tensile Adhesion / LTA B47390.07.14-1 07/31/2014
ERD (TST 6049) Tensile Adhesion / LTA 1347390.09.14 09/04/2014
PRI (TST 5878) ASTM D1970 NEI-031-02-02:REV 10/27/2010
PRI (TST 5878) ASTM D1970 NEI-029-02-01:REV 12/03/2010
PRI (TST 5878) Tensile Adhesion / LTA NEI-046-02-01REV 12/17/2010
PRI (TST 5878) FRSA/TRI April 2012 NEI-076-02-01 02/14/2011
PRI (TST 5878) ASTM D1970 NEI-034-02-02 01/29/2013
PRI (TST 5878) Wind Uplift BORR-001-02-01 03/17/2015
PRI (TST 5878) Wind Uplift BORR-005-02-01 06/24/2015
UL, LLC. (QUA 9625) Quality Assurance Service Confirmation Exp. 08/21/2020
4. PRODUCT DESCRIPTION:
4.1 Self -Adhering Underlayments:
4.1.1 Boral TileSeal° 50"T is a nominal 50-mil thick, polyester -surfaced, self -adhering SBS modified bitumen roof
u rla ment; meets ASTM D1970.
4. Boral TileSeal® Is nominal 160-mil thick, polyester -surfaced, self -adhering SBS modified bitumen roof
derl ASTM D1970 and FRSA/TRI 04-12.
4.1.3 GatorSeal® is a nominal 55-mil thick, granular -surfaced, fiberglass reinforced, self -adhering SBS modified
bitumen roof underlayment; meets ASTM D1970.
4.1.4 Citadel® Plus is a nominal 48-mil thick, fabric -surfaced, fiberglass reinforced, self -adhering SBS modified
bitumen roofing underlaymentfor use as a base -layer in two-ply underlayment systems; meets ASTM
D1970.
S. LIMITATIONS:
5.1 This is a building code evaluation. Neither Trinity IERD nor Robert Nieminen, P.E. are, in any way, the
Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was
used for permitting or design guidance unless retained specifically for that purpose.
5.2 This Evaluation Report is not for, use in FBC HVHZ jurisdictions.
Exterior Research and Design, I.I.C. Evaluation Report M35710.12.10-R9
Certificate ofAuthori:ation #9503 eH EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-118
Boral Roof Underlayments; (602) 269-2288 Revision 9:10/14/2017
Page 2 of 7
T�RINITY]ERD
5.3 Fire Classification is not part of this Laboratory Report; refer to current Approved Roofing Materials
Directory for fire ratings of this product.
5.4 Boral Roof Underlayments may be used with any prepared roof cover where the product is specifically
referenced within FBC approval documents. If not listed, a request may be made to the Authority Having
Jurisdiction for approval based on this evaluation combined with supporting data for the prepared roof
covering.
5.5 Allowable Roof Covers: Table 1 pertains to use of each listed underlayment by -itself beneath the stated
roof covers. Refer to the installation instructions and Table 2 for two-ply underlayment options.
Underlayment Asphalt Nail -On Tile Adhesive set Metal Wood Shakes Slate
Shingles Tile & Shingles
Bo i e e 15 "T 71
"Yes No SNo -Yes, Yes Ves
z yes an
Boral TileSeal"T�Yes Yes Yet Yes_
GatorSeal
5.5.1 "Adhesive -set Tile" is limited to use of following Approved tile adhesives / underlayment combinations.
TABLE SA MLLOyUABI:E TILE ADHESIVEI UNpERLAYMENT COMBINATIONS)
Adhesive
Florida Product Approval
Underlayments
DAP Foam Touch'n Seal StormBond Roof Tile Adhesive
FL14506
Boral TileSeal"T
Dow TILE BOND'" Roof Tile Adhesive
FL22525
Boral TileSeal"T
ICP Adhesives Polyset® AH-160
FL6332
Boral TileSeal"T
ICP Adhesives Polyset® RTA-1
FL6276
Boral TileSeal"T
5.6 Allowable Substrates:
5.6.1 Direct -Bond to Deck:
Citadel Plus, Boral TileSeal 50iT, Boral TileSeal"T or GatorSeal:
➢ Plywood (unprimed or primed with ASTM D41 primer).
Boral TileSeal"T:
➢ OSB primed with ASTM Di 1 primer.
Note: Refer to Section 5.6.4 for uplift limitations associated with direct -deck underlayment installations
where the overlying roof cover is adhesive -set the roofing
5.6.2 Bond to Base Laver Underlayment:
Citadel Plus, Boral TileSeal 50iT, Boral TileSeal"T or GatorSeal:
➢ ASTM D226, Type II felt; Citadel Plus.
For installations under mechanically attached prepared roof coverings, base layer shall be attached per
minimum codified requirement's. For installations under adhesive -set tile systems, base layer shall be
attached per minimum requirements of FRSA/TRI April 2012 (04-12), Appendix A, Table 1, or as listed in
Section 5.6.4 herein, or as tested in accordance with FBC 1504.3.1.
1 Refer to Tile Manufacturer's or Adhesive Manufacturer's Florida Product Approval for Overturning Moment Resistance Performance.
Exterior Research and Design, I.I.C. Evaluation Report M35730.12.10-R9
Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-R8
Boral Roof Underlayments; (602) 269-2288 Revision 9: 10/14/2017
Page 3 of 7
QOTRIN'ITYIERD
5.6.3 Bond to Other Substrate Types:
Citadel Plus, Boral TileSeal 50 T, Boral TileSeal"T or GatorSeal:
➢ ASTM D41 primed metal (e.g., flashing metal, valley metal, etc).
Boral TileSeal"T:
➢ Huber Zip Deck (unprimed or primed with ASTM D41 primer); Dens Deck Prime.
Note: For installation under mechanically attached prepared roof coverings, insulation shall be attached
per minimum requirements of the prepared roof covering manufacturer's Product Approval.
5.6.4 Wind Resistance for Underlayment Systems in Adhesive -set Tile Applications: FRSA/TRI April 2012 (04-12)
does not address wind uplift resistance of all underlayment systems beneath adhesive -set tile systems,
where the underlayment forms part of the load -path. The following wind uplift limitations apply to
underlayment systems that are not addressed in FRSA/TRI April 2012 (04-12) and are used in adhesive -set
tile applications. * Maximum Design Pressure is the result of testing for wind load resistance based on
allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety
per FBC 1504.9 has already been applied). Refer to FRSA/TRI April 2012 (04-12), Appendix A, Table 1A or
FBC 1609 for determination of design wind loads
#1 Maximum Design Pressure = -105 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Base Ply: (Optional) Citadel Plus, self -adhered
Underlayment: Boral TileSeal"T, self -adhered and back -nailed within the selvedge -edge side laps using
12 ga. x 1W ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c.
#2 Maximum Design Pressure = -120.0 psf:
Deck: Min. 15/32-i�ch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Primer: ASTM D41 to the plywood deck
Base Ply: Citadel Plus, self -adhered
Cap Sheet: Boral TileSeal"T, self -adhered, and back -nailed within the selvedge -edge side laps using
12 ga. x 1%" ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch o.c.
#3 Maximum Design Pressure = -202.5 psf:
Deck: Min. 15/32-inch plywood to meet project requirements to satisfaction of Authority
Having Jurisdiction.
Primer: ASTM D41 to the plywood deck
Base Ply: None
Cap Sheet: Boral TileSeaIHT, self -adhered, and back -nailed within the selvedge -edge side laps using
12 ga. x I%" ring shank nails through 32 ga., 1-5/8" diameter tin caps spaced 12-inch D.C.
#4 Maximum Design Pressure = -120.0 psf:
Deck: Min. 2,500 psi structural concrete to meet project requirements to satisfaction of
Authority Having Jurisdiction.
Primer: ASTM D41 to,the concrete deck
Base Ply: (Optional) Citadel Plus, self -adhered
Cap Sheet: Boral TileSeal;"T, self -adhered
5.6.4.1 Note: For adhesive -set tile systems, if there is a base ply or mid -ply of Citadel Plus in the system, the
project design pressure requirements may not exceed -120 psf.
Exterior Research and Design, I.I.C. Evaluation Report M35710.12.10-R9
Certificate of Authorization #9503 6T" EDITION .(2017) FBC NON-HVHZ EVALUATION FL14317-118
Boral Roof Underlayments; (602) 269-2288 Revision 9:10/14/2017
Page 4 of 7
i
C-JiCTRINITY I ERD
5.7 Exposure Limitations:
GatorSeal shall not be left exposed for longer than 30-days after installation, prior to placement of final
roof cover.
Boral TileSeal 50"T and Boral TileSealHT shall not be left exposed for longer than 180-days after
installation, prior to placement of final roof cover.
Citadel Plus, for use as a base -I yer in a two-ply underlayment system, shall not be left exposed for longer
than 180-days after installation prior to placement of subsequent underlayment layer.
5.8 Tile Slippage Limitations (FRSAITRI April 2012 (04-12)1:
When loading roof tiles on the Iunderlayment in direct -deck tile assemblies, the maximum roof slope shall
be as follows. These slope limitations can only be exceeded by using battens during loading of the roof
tiles.
TABLE 2..'TILEISUPPAG
LIMIrQ1IONS L bR;LiiRECT DECK TILE (NSTACLt1tfONS ;,' ,..,.. -.
Underlayment
Tile Profile
Stagging Method Maximum Slope
Boral TileSeal"T
Flat
Max. 10-tile stack 6:12
Lugged
Max. 10-tile stack 6:12
6. INSTALLATION:
6.1 Boral Roof Underlayments shall be installed in accordance with Boral Roofing published installation
instructions subject to the Limitiations set forth in Section 5 herein and the specifics noted below.
6.2 Re -fasten any loose decking panels, and check for protruding nail heads. Sweep the substrate thoroughly
to remove any dust and debris prior to application, and prime the substrate (if applicable).
6.3 Install self -adhering underlayment when ambient and surface temperatures are minimum 407 and rising.
6.4.1 Citadel Plus is limited to use as a base or mid -layer in multi -ply underlayment systems beneath Boral
TileSeal 50"T, Boral TileSeal "T or GatorSeal.
6.4.2 Slope limitations are those assol fated with the top -layer underlayment.
6.4.3 Direct to Deck:
Cut the membrane into manageable lengths, typically 10 to 12 ft. Align the membrane parallel to the roof
edge, extending over by %-inch, Fold the membrane away from the edge onto itself. Remove the release
sheet. Place the membrane witk the exposed rubberized asphalt onto the deck, pressing firmly into place.
Roll into place with a weighted roller.
Boral recommends fastening of the top edge of the sheet to the deck with roofing nails, nails & tin -tags or
1-inch diameter plastic or steel cap nails spaced 24-inch o.c. for slopes below 7:12 and 12-inch o.c. for
slopes 7:12 and greater. Overlap successive courses minimum 2 inches (horizontal lap) and minimum 4"
end (vertical) laps.
Install final underlayment layer atop Citadel Plus per 'direct -to -deck' instructions for Boral TileSeal 50"T,
Boral TileSeal"T or GatorSeal.
6.4.4 To Base Sheet:
Install base sheet of ASTM D226, Type II felt in accordance with Code requirements or install base ply of
Citadel Plus in accordance with Boral Roofing published installation instructions and Section 6.4.3 and
when used as part of a multi -ply system.
Install optional Citadel Plus as a mid -ply in accordance with Boral Roofing published installation
instructions and Section 6.4.3.
Install final underlayment layer atop Citadel Plus per 'direct -to -deck' instructions for Boral TileSeal 50"T,
Boral TileSeal"T or GatorSeal. ;
Exterior Research and Design, I.I.C. Evaluation Report M35730.12.30-R9
Certificate of Authorization #9503 6T" EDITIONI(2017) FBC NON-HVHZ EVALUATION FL14317-RB
Boral Roof Underlayments; (602) 269-2288 Revision 9: 10/14/2017
Page 5 of 7
Note: For adhesive -set tile systems, if there is a base ply or mid -ply of Citadel Plus in the system, the
project design pressure requirements may not exceed -120 psf.
6.5.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.5.2 Do not use Boral TileSeal 50"T onl roof pitches less than 2:12.
6.5.3 Non -Tile Applications, Direct to Deck:
6.5.4
Cut the membrane into manageable lengths, typically 10 to 12 ft. Align the membrane parallel to the roof
edge, extending over by X-inch. Fold the membrane away from the edge onto itself. Remove the release
sheet. Place the membrane with the exposed rubberized asphalt onto the deck, pressing firmly into place.
Roll into place with a weighted roller.
Boral recommends fastening of the black selvedge edge to the deck with roofing nails, nails & tin -tags or 1-
inch diameter plastic or steel cap nails spaced 24-inch o.c. for slopes below 7:12 and 12-inch o.c. for slopes
712 and greater. Overlap successive courses the width of the black -selvedge area, minimum 3-inch.
Seal under end (vertical) laps using approved mastic, or use Joined and Folded Seam or Inverted Sheet
Seam method detailed in Boral Roofing published installation instructions.
Install ASTM D226, Type II felt in accordance with Code requirements or install Citadel Plus in accordance
with Boral Roofing published installation instructions and Section 6.4.
Install Boral TileSeal 50"r in accordance over ASTM D226, Type II felt or Citadel Plus with Boral Roofing
published installation instructions and Section 6.5.3, except end (vertical) laps, described below.
Apply SIBS Mastic under all end (vertical) laps or any other laps where the self -adhering bituminous
underside is in contact with the fabric top surface, rolling the interface into place with a weighted roller.
6.6.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared) roof covering to be installed.
6.6.2 Do not use GatorSeal on roof pitches less than 2:12.
6.6.3 Non -Tile applications. Direct to Deck:
Cut the membrane into manageable lengths, typically 10 to 12 ft. Align the membrane parallel to the roof
edge, extending over by X-inch. Fold the membrane away from the edge onto itself. Remove the release
sheet. Place the membrane with the exposed rubberized asphalt onto the deck, pressing firmly into place.
Roll into place with a weighted roller.
Boral recommends fastening of the black selvedge edge to the deck with roofing nails, nails & tin -tags or f-
inch diameter plastic or steel cap nails spaced 24-inch o.c. for slopes below 7:12 and 12-inch o.c. for slopes
7:12 and greater. Overlap successive courses the width of the black -selvedge area, minimum 3-inch.
Seal end (vertical) laps using SBS Mastic under all side (vertical) laps or any other laps where the self -
adhering bituminous underside is 'in contact with the granular or mineral top surface, rolling the interface
into place with a weighted roller; or using the Inverted Sheet Seam detailed in Boral Roofing published
installation instructions.
6.6.4 Non -Tile Applications, to Base Sheet:
Install ASTM D226, Type II felt in accordance with Code requirements or install Citadel Plus in accordance
with Boral Roofing published installation instructions and Section 6.4.
Install GatorSeal over ASTM D226, Type II felt or Citadel Plus in accordance with Boral Roofing published
installation instructions and Section 6.6.3 except end (vertical) laps, described below.
Apply SIBS Mastic under all side (vertical) laps or any other laps where the self -adhering bituminous
underside is in contact with the granular top surface, rolling the interface into place with a weighted roller.
Exterior Research and Design, I.I.C. Evaluation Report M35710.12.10-119
Certificate of Authorization #9503 6r" EDITION (2017) FBC NON-HVHZ EVALUATION FL14317-118
Boral Roof Underlayments; (602) 269-2288 Revision 9: 10/14/2017
Page 6 of 7
6.7.1 Shall be installed in compliance with the requirements for ASTM D1970 underlayment in FBC Table
1507.1.1 for the type of prepared roof covering to be installed.
6.7.2 Do not use Boral TileSeal HT on roof pitches less than 2:12.
6.7.3 Non -Tile Applications, Direct to Deck:
For OSB substrate, prime with ASTM D41 primer and allow to dry prior to installation. Cut the membrane
into manageable lengths, typically 10 to 12 ft. Align the membrane parallel to the roof edge, extending
over by %-inch. Fold the membrane away from the edge onto itself. Remove the release sheet. Place the
membrane with the exposed ruIbberized asphalt onto the deck, pressing firmly into place. Roll into place
with a weighted roller.
Boral recommends fastening of the black selvedge edge to the deck with roofing nails, nails & tin -tags or 1-
inch diameter plastic or steel cap nails spaced 24-inch D.C. for slopes below 7:12 and 12-inch o.c. for slopes
7:12 and greater. Overlap successive courses the width of the black -selvedge area, minimum 3-inch.
Seal under end (vertical) laps Using approved mastic, or use Joined and Folded Seam or Inverted Sheet
Seam method detailed in Boral RI oofing published installation instructions.
6.7.4 Non -Tile Applications. to Base Sheet:
Install ASTM D226, Type II felt in accordance with Code requirements or install Citadel Plus in accordance
with Boral Roofing published installation instructions and Section 6.4.
11
Install Boral TileSeal "T over ASTM D226, Type II felt or Citadel Plus in accordance with Boral Roofing
published installation instructions and Section 6.7.3, except end (vertical) laps, described below.
Apply SBS Mastic under all end (vertical) laps or any other laps where the self -adhering bituminous
underside is in contact with the fabric top surface, rolling the interface into place with a weighted roller.
6.7.5 Tile Applications:
Reference is made to FRSA/TI
instructions noted above as a gi
For mechanically fastened tile
sheet(s), Base Sheet fastening s
For adhesive -set tile applicatior
Note: For adhesive -set tile sys
project design pressure require
Refer to Section 5.8 for tile stE
TileSeal HT with roof pitches of
battens are required.
April 2012 (04-12) Installation Manual and Table 1 herein, using the
deline.
)offing over 2-ply system, consisting of Base Sheet and self -adhering top
all be not less than FRSA/TRI April 2012 (04-12), Table 1.
refer to Section 5.6.4 herein.
!ms, if there is a base ply or mid -ply of Citadel Plus in the system, the
ents may not exceed -120 psf.
ng limitations. Battens must be used for all tile installations atop Boral
%2 to less than 3:12. Boral Roofing's Elevated Batten System or counter
7. BUILDING PERMIT REQUIREMENTS:
As required by the Building Official or Authi ority Having Jurisdiction in order to properly evaluate the installation of
this product.
8. MANUFACTURING PLANTS:
Brentwood, NH
9. QUALITY ASSURANCE ENTITY:
UL, LLC. — QUA9625; (631) 546-2458; I<anchi.Asrawala-Dokaniagul.com
- END OF EVALUATION REPORT -