HomeMy WebLinkAboutGENERAL INFORMATION_t
�li��fi�il�lraflLL�11��J�C•73/l�l�l�IL�T 1�4[+�_iirJi[+11G11f1�199J1�.r�cli1'1�:►�T1lnlJ�l'/�
Natural Gas
Natural gas is lighter than air. It is found in the gaseous state at
normal ambient temperatures and pressures. It is highly explosive
and can be ignited at the slightest spark. For that reason, fuel
lines must be free of leaks and adequate ventilation is absolutely
essential.
Local fuel/gas codes usually dictate the maximum pressure at
which natural gas can enter a structure. In order to reduce the
gas pressure to that required by law, a PRIMARY REGULATOR is
required.
LP Gas
Liquefied petroleum (LP) gas is heavier than air. The gas vapors
are explosive and, like natural gas, can be ignited by the slightest
spark.
LP tank pressure is dependent on the ambient temperature and can
be as high as 200 psi. A primary regulator is required at the tank to
reduce the pressure to the required five to 14 inches of water col-
umn for units less than 70kW, or 11 to 14 inches of water column
for units 70kW and larger.
i
114 THE NATURAL GAS SYSTEM
A typical natural gas system is shown in Figure 1.10. The maxi-
mum pressure at which the gas can enter a building is established
by code and may vary from area to area. A primary regulator is
required to reduce gas supply pressures to the required safe level
before the gas enters a structure.
The primary regulator may or may not be provided by the gas
supplier. The gas distribution company will usually provide piping
from the main distribution line to the generator site. It is the respon-
sibility of the gas supplier to ensure that sufficient gas pressure is
available to operate the primary regulator.
From the primary regulator, gas flows to the generator connection.
A flexible length of gas line is required between rigid piping and
the gas connection at the generator. The generator fuel system
consists of an electrical fuel shutoff valve/regulator assembly and
a gas actuator.
The secondary regulator reduces gas pressure to about five inches
of water column before the gas Is delivered to the actuator.
NOTE:
Gas pressure from the primary regulator (supplied by the
installing contractor) to the generator's fuel shutoff valve should
not exceed 14 inches of water column.
Follow the local codes on selecting the required AGA approved,
and UL listed, for NG application flexible portion of the fuel line
(supplied by the installing contractor).
This type of system utilizes the vapors formed above the liquid
fuel in the supply tank (see Figure 1.11). Approximately 10 to 20
percent of the tank capacity is needed for fuel expansion from
the liquid to the vapor state. Gas pressure requirements for an LP
vapor system at the frame of the generator are the same as those
listed for natural gas in "The Natural Gas System". See Table 1 for
information regarding the vapor capacity of LP tanks. The installer
should be aware of the following:
• When ambient temperatures are low and engine fuel consump-
tion is high, the vapor withdrawal system may not function
efficiently.
• Ambient temperatures around the supply tank must be high
enough to sustain adequate vaporization or the system will not
deliver the needed fuel volume.
• In addition to the cooling effects of ambient air, the vaporization
process itself provides an additional cooling effect.
116 GASEOUS FUEL SYSTEM PIPING
NOTE:
The information below is to assist in planning gaseous fuel
installation. In NO WAY should this information be interpreted
to conflict with applicable fuel gas codes. Contact the local
jurisdiction if questions arise.
The following general rules apply to piping used in gaseous fuel
systems:
• The piping should be of black iron, rigidly mounted and pro-
tected against vibration.
• Install the supplied length of flexible hose between the generator
connection point and rigid piping.
A CAUTIONI
AThe supplied flexible hose is not to be installed
underground or in contact with ground. The
flexible hose is for in -line installation only.
Bends, kinks or off -center in -line installation of
flexible hose is NOT allowed.
Piping must be of the correct size to maintain the required sup-
ply pressures and volume flow under varying conditions (see
Calculating volumetric Flow Rate and Pipe Size).
Installed piping must be properly purged and leak -tested, in
accordance with applicable codes and standards.
Use an approved pipe sealant or joint compound on all threaded
fittings, to reduce the possibility of leakage.
NOTE:
In the absence of local purging and leak test standards, NFPA
No. 54 may be used as a guide.
Primary Regulator
(Supplied by
Installing
Contractor)
Z—r—
Manual Shutoff
Valve
Figure 1.10 — Typical Natural Gas System
Generator Base
I
Flex Fuel Line
(Supplied
with Unit)
Gas Actuator
Figure 1.11— Typical LP Gas Vapor Withdrawal System
Fuel Shutoff/Regulator
Assembly
11 -14" Water Column
Recommended (> = 70kW)
5 -14" Water Column
Recommended (< 70kW)
— Manual Shutoff Valves
Generator Base
Gas Actuator
�— Fuel Shutoff/Regulator
Assembly
Flex Fuel Line
(Supplied
11 - 14" Water Column
with Unit)
Recommended (> = 70kW)
5 - 14" Water Column
Primary Regulator
Recommended (< 7okW)
(Supplied by
Fuel
Tank
Installing
Contractor)
9
1.9 CALCULATING VOLUMETRIC
FLOW RATE AND PIPE SIZE
If the Owner's Manual identifies the fuel consumption requirements
by a volumetric flow rate (units of ft3/hr), skip the next section and
go on to the section, Calculating Pipe Size. If the Fuel Consumption
requirements are given in units of Ib/hr, follow the next section,
Calculating Volumetric Flow Rate.
T
Since the fuel consumption requirements (from the owners
manual) are given as a mass flow (units of Ib/hr), the volumetric
flow rate (ft3/hr) must be identified before the appropriate pipe
size can be selected. The relationship between the mass flow rate
(lb/hr), density (lb/ft3), and volumetric flow rate (fts/hr) can be
described by Equation 1. According to Equation 1, the volumetric
flow rate can be calculated by dividing the mass flow rate by the
density. You may need to contact your fuel vendor to identify the
density or specific gravity for your fuel. If your vendor provides
the specific gravity (relative to air) Table 1 can be used to identify
the appropriate density. Since the density of natural gas and LP is
temperature dependant, the maximum temperature of the fuel (at
the fuel shutoff/regulator assembly) should be measured so the
fuel consumption requirements can be more accurately identified
for the generator. A sample calculation (Example 1) is included in
this section.
Equation 1:
m
v=-
P
Where:
iv = Volumetric Flow Rate (ft3/hr)
m = Mass Flow Rate (lb/hr)
p = Density from Table 1 - (r-so)
C
C = 11111 (for Natural Gas) or 3333 (for LP)
T = Temperature of the fuel into the fuel shut-off/regulator
Example 1: Determine the volumetric flow rate for a generator that
requires 91.34 Ib/hr of natural gas at 100% load.
Solution:
Specific gravity according to the local vendor: 0.5
Density of Natural Gas from Table 1: 0.0383 Ib/fts
Maximum Temperature of the fuel going into the generator: 90OF
C=11111 (for Natural Gas) from Equation 1
m = 91.34lb/hr
v = o and p = 0.0383 - (90160)
p = 0.0356 Ib/ft3
10
Thus:
91.34
v = 0.0356
And:
v = 2566 ft3/hr
LCULATING PIPE SIZ
Now that the volumetric flow rate has been identified, the mini-
mum pipe size can be determined by using Table 2. This table is
based on a specific gravity of 1.00 (specific gravity of air). For that
reason, a correction is required when the fuel used has a different
specific gravity. The fuel's specific gravity can be obtained from
the fuel supplier. The table is also based on a pressure drop of
0.3, which allows for a nominal amount of restrictions from bends,
fittings, etc. Example 2 illustrates how to calculate the pipe size for
the generator.
Example 2: Determine the iron pipe size for a generator that
requires 2566 ft3/hr of Natural. Gas. The unit is located 75 feet
from the fuel source.
Solution:
Specific gravity of natural gas according to the local vendor: 0.5
Multiplier for the given specific gravity from Table 1: 1.1
According to Table 2, a 2-1/2 inch pipe will deliver 1750 ft-3/hr
of air if it is located 75 feet from the fuel source. To determine the
I volumetric flow rate of natural gas, multiply the given flow rate by
the multiplier (from Table 1):
Natural gas flow rate = air flow rate (ft3/hr) * Multiplier
= 1750 ft3/hr * 1.10
Natural gas flow rate = 1925 ft3/hr
Since the flow rate through a 2-1/2 inch iron pipe is less than the
flow rate required by the generator (2430 ft3/hr), we must evaluate
the next larger pipe (3 inches) by the same method.
Natural gas flow rate = air flow rate (ft3/hr) * Multiplier
= 3000 ft3/hr * 1.10
Natural gas flow rate = 3300 ft3/hr
A 3 inch pipe is required at the given distance of 75 feet. Pressure
drop does not have to be considered unless an unusual number
of fittings, bends or other restrictions are used. In such unusual
cases, the fuel supplier will usually specify which multiplier is
applicable.
NOTE:
The installed piping system shall be capable of providing the
Fuel Consumption requirements as identified in the specifica-
tions section of the Owners Manual.
Specific
Gravity(1)
Multiplier
Density lb/f13
Specific
Gravity(1)
Multiplier
Density Ib/f13
Pressure Drop
Multiplier
0.5
1.1
0.0383
1
0.775
0.0765
0.1
0.577
0.55
1.04
0.0421
1.2
0.707
0.0918
0.2
0.815
0.6
1
0.0459
1.4
0.655
0.1072
0.3
1
0.65
0.962
0.0497
1.5
0.633
0.1148
0.5
1.29
0.7
0.926
0.0536
1.7
0.594
0.1301
1
1.83
0.8
0.867
0.0612
1.9
0.565
0.1454
2
2.58
0.9
0.817 T
0.0689
.2.1
0.535
0.1607
5
4.08
Note 1: Relative to air at 30 inches Hg, 60T
Length of Pipe
(in Feet)
Iron Pipe Size (IRS
Inches)
1/2"
3/4"
1"
1-1/4"
1;1/2"
2"
1 2-1/2"
3"
4"
6"
8"
15
76
172
345
750
1220
2480
3850
0500
13880
38700
79000
30
52
120
241
535
650
1780
2750
4700
9700
27370
55850
45
43
99
199
435
700
1475
2300
3900
7900
23350
45600
60
38
86
173
380
610
1290
2000
3450
6800
19330
39500
75
77
155
345
545
1 1120
1750
3000
'6000
17310
35300
90
70
141
310
490
1000
1560
2700
5500
15800
32250
105
65
131
285
450
920
1430
2450
5100
14620
29850
120
120
270
420
860
1340
2300
4800
13680
27920
150
109
242
380
780
1 1220
2090
4350
12240
25000
180
100
225
350
720
1120
1950
4000
11160
22800
210
92
205
320
660
1030
1780
3700
10330
21100
240
190
300
620
970
1680
3490
9600
19740
270
1
178
1 285
580
910
1580
3250
9000
18610
300
1
170
270
545
860
1490
3000
8500
17660
450
140
226
450
710
1230
2500
7000
14420
600
119
192
390
600
1030
2130
6000
1 12480
11
mur-c u — unrun unrnun r uv vnurnnc u►unnuL mornu
To Use: Go to the First column and pick the required kW load and then pick the minimum ambient temperature (400, 200 or 0° F) that the
generator would be operating in. The third column (tank capacity) will give the required tank size to continually produce the given fuel flow.
Operating
Max kW
Minimum
Hours @
Tank Capacity
Length
Dia
Overall
Vapor
Temp
Max kW
Gallons
Inches
Inches
Ht. Inches
30
40
24
20
20
35
120
57
24
33
10
0
67
35
40
26
25
20
36
i150
68
24
33
12
0
72
60
40
26
40
20
38
250
94
30
39
20
0
74
80
40
26
50
20
40
1325
119
30
39
25
0
77
100
40
31
60
20
51
500
119
37
46
30
0
100
150
40
35
100
20
53
1850
165
41
50
50
0
105
170
40
36
120
20
51
�1000
192
41
50
60
0
103
Propane storage tanks can provide either a liquid or a vapor supply to jthe generator. The above chart is for vapor withdrawal only and provides
the kW output or amount of vapor that can be withdrawn at a given temperature while keeping the temperature of the liquid above the boiling
point. If the withdrawal rate is too high, the LP temperature goes below the boiling point, the pressure drops to zero and no vapor can be with-
drawn. A primary regulator is also required at the tank to reduce the line pressure to the generator to 5-14 inches of water column.
Propane Conversions: 36.38 ft3 = 90,500 btu = 1 gal • 11b = 21,500 btu'= 8.56 ft3
Propane Storage Tank
12
1.10 ELECTRICAL CONNECTIONS
1 GROUNDING THE GE
A GROUNDING LUG is provided on the generator mounting base
for the purpose of grounding the frame and the external electrically
conductive parts of this equipment to an approved earth ground
and/or grounding rods where required by the National Electrical
Code (Figure 1.12). Consult a qualified electrician for. grounding
requirements in the area. Grounding procedures must meet local
regulations.
®Do not connect the ground wire to any pipe that
carries a flammable or explosive substance
FIRE or an EXPLOSION may result.
Proper grounding helps protect personnel against electrical shock
in the event of a ground fault condition in the generator or in con-
nected electrical devices. In addition, grounding helps dissipate
static electricity that often builds up in ungrounded devices.
Figure 1.12 — Generator Grounding Lug (typical)
UNDING
LUG
1.10.2 BATTERY CHARGER CONNECTION
The generator has been equipped with a battery charger integrated
in the control panel. Power leads for the charger have been run to
the connection box (Figure 1.13). Connect the power leads for the
battery charger to the 120 VAC T1/LINE connection and the neutral
lead to the NEU connection. This is a 15 Amp circuit supplied by
the customer.
(Refer to the Connection Diagrams section in this manual, or the
wiring diagram in the Owner's Manual that is supplied with the
unit.)
Figure 1.13 — Battery Charger Connection
1.11 ,BATTERY INSTALLATION
F11 bl
AStandby generators installed with automatic
transfer switches will crank and start automati-
cally when NORMAL ,(UTILITY) source voltage is
removed or is below an acceptable preset level.
To prevent such automatic start-up and pos-
sible injury to personnel, do not connect battery
cables until certain that normal source voltage
at the transfer switch is correct and the system
is ready to be placed into operation.
j ®Storage batteries give off explosive hydrogen
gas. This gas can form an explosive mixture
around the battery for several hours after
charging. The slightest spark can ignite the.gas
and cause an explosion. Such an explosion can
shatter the battery and cause blindness or other
injury. Any area that houses a storage battery
must be properly ventilated. Do not allow smok-
ing, open flame, sparks or any spark producing
tools or equipment near the battery.
Battery electrolyte fluid is an extremely caustic
sulfuric acid solution that can cause severe
burns. Do not permit fluid to contact eyes, skin,
clothing, painted surfaces, etc. Wear protective
goggles, protective clothing and gloves when
handling a battery. If fluid is spilled, flush the
i
affected area immediately with clear water.
ADo not dispose of the battery in a fire. The bat-
tery is capable of exploding.
ADo not open or mutilate the battery. Released
electrolyte can be toxic. and harmful to the skin
and eyes.
13
QThe battery represents a risk of high short
circuit current. When working on the battery,
always remove watches, rings or other metal
objects, and only use tools that have insulated
handles.
MIUMVI! UPI J.1111 _; .
A CAUTIONI
AThe electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically
conductive and corrosive. The following proce-
dures are to be observed:
• Wear full eye protection and protective clothing,
• Where electrolyte contacts the skin, wash it off immediately
with water,
• Where electrolyte contacts the eyes, flush thoroughly and
immediately with water and seek medical attention, and
• Spilled electrolyte is to be washed down with an acid -
neutralizing agent. A common practice is to use a solution
of one pound (500 grams) bicarbonate of soda to one gallon
(4 liters) of water. The bicarbonate of soda solution is to be
added until the evidence of reaction (foaming) has ceased.
The resulting liquid is to be flushed with water and the area
dried.
ALead acid batteries present a risk of fire
because they generate hydrogen gas. The fol-
lowing procedure are to be followed:
• DO NOT SMOKE when near batteries,
• DO NOT cause flame or spark in battery area, and
• Discharge static electricity from body before touching batter-
ies by first touching a grounded metal surface.
Servicing of batteries is to be performed or supervised by person-
nel knowledgeable of batteries and the required precautions. Keep
unauthorized personnel away from batteries.
For recommended batteries, see the "Specifications" section in
the Owner's Manual. All batteries must be at 100 percent state -of -
charge before they are installed on the generator.
When using maintenance -free batteries, it is not necessary to
check the specific gravity or electrolyte level. Have these proce-
dures performed at the intervals specified in the "Maintenance"
section in the Owner's Manual. A negative ground system is used.
Battery connections are shown on the wiring diagrams. Make
sure all batteries are correctly connected, and terminals are tight.
Observe battery polarity when connecting batteries to the genera-
tor set.
NOTE:
Damage will result if the battery connections are made in
reverse.
Before connecting the battery, make certain that normal utility volt-
age at the transfer switch is correct and the system is ready to be
put into operation.
Check the engine oil, the coolant level, belt tension, and if so
equipped, the gearbox oil (Figure 1.14).
14
Figure 1.14 — Check Engine Oil
Check the battery to make sure it is fully charged before install-
ing.
Follow all safety procedures detailed in the Owner's Manual and
observe polarity when connecting the battery. Make sure all termi-
nal connections are tight (Figure 1.15).
Figure 1.15 — Check Terminal Connections
1.12 GENERATOR ACTIVATION
When battery power is applied to the generator during the installa-
tion process, the controller will light up. However, the generator still
needs to be activated before it will automatically run in the event
of a power outage.
Activating the generator is a simple one time process that is guided
by the controller screen prompts. Once the product is activated,
the controller screen will not prompt you again, even if you discon-
nect the generator battery.
After obtaining your activation code, please complete the follow-
ing steps at the generator's control panel in the Activation Chart
(shown on the following page).
CHOOSE LANGUAGE
TROUBLESHOOTING
Display
Reads:
Use ARROW keys to scroll to desired language.
If the wrong language is chosen, it can be
Press ENTER to select.
changed later using the "edit" menu.
Language
- English +
Escape . . Enty
Display
Reads:
Press ENTER to begin the activation process.
If ESCAPE is pressed instead of ENTER, your
generator will only run in manual mode (for
Activate me (ENT) or
test purposes) and NOT ACTIVATED will be dis-
ESC to run in manual
!
played. You will need to remove the generator
!
control panel fuse AND disconnect the T1, N1,
N2 connector in the external connection box (if
Escape �0 ��
equipped) or disconnect the utility input (main
breaker) to the transfer switch for 3-5 seconds.
!
Reconnect and start over with step 1.
Display Reads:
If you do not have your activation code, go to
www.activategen.com or call 1-888-9ACTIVATE
Activate go to
(922 8482).
(WA'wmactivategen.com
If you already have your activation code, wait 3-5
seconds for the next display.
Escape �� Enty
ENTER ACTIVATION CODE (Passcode)
TROUBLESHOOTING
Display
Reads:
Use ARROW keys to scroll and find the first num-
ber of your Activation Code.
Ser�123456789
Press ENTER to select.
Pas
Repeat this step until all digits have been entered.
Use ESCAPE to correct previous digits.
Eseape . . Enty
Display Reads:
Activation is complete when all digits are entered
What happens if "Wrong Passcode Try Again"
above and your screen shows this display.
appears?
"SELECT HOUR (0-23)"
Follow the controller prompts to continue setting
Reenter the activation code. If a second attempt
- 6 +"
the time function. Refer to your Owner's Manual
is unsuccessful, check the number against the
with questions.
code given on activategen.com. If it is correct
and the generator will not accept it, contact
Eseape�� Ewer
1-888-9ACTIVATE (922-8482).
15
i
2.1 TRANSFER SWITCH
The - generator system should be used in conjunction with a
matched automatic transfer switch. The NEMA 3R enclosure is
weather proof and can be used indoors or outdoors.
2.2 UNPACKING
Carefully unpack the transfer switch. Inspect closely for any dam-
age that might have occurred during shipmentAThe purchaser
must file with the carrier any claims for loss or damage incurred
while in transit.
Check that all packing material is completely removed from the
switch prior to installation.
Attach ahy lifting device to the transfer switch mounting holes or
brackets only. DO NOT LIFT THE SWITCH AT ANY OTHER POINT.
Always inspect the transfer switch for shipping damage.
i
2.3 MOUNTING
Mounting dimensions for the transfer switch enclosure can be
found in the transfer switch owner's manual..Enclosures are typi-
cally wall -mounted.
The transfer switch must be mounted vertically and must be level
and plumb.
ACAUTIONI
Handle transfer switches carefully when install-
ing. Do not drop the switch. Protect the switch
against impact at all times, and against con-
struction grit and metal chips. Never install a
transfer switch that has been damaged.
Install the transfer switch as close as possible to the electrical
loads that are to be connected to it. Mount the switch vertically
to a rigid supporting structure. To prevent switch distortion, level
all mounting points. If necessary, use washers behind mounting
holes to level the unit. Never install the switch where water or any
corrosive substance might drip into the enclosure.
FITS and HTS switches are open transition switches. Because load
circuits can only be connected to one power supply at a time,
open transition switches prevent electrical feedback between utility
circuits and generator circuits (Figure 2.1).
Figure 2.1— Connect Power Leads
16
3.1 BASIC STANDBY ELECTRIC
SYSTEM
Figure 3.1 shows a schematic diagram of a basic standby electric
system. Both the UTILITY power supply and the STANDBY (GEN-
ERATOR) output are connected to an approved transfer switch.
The transfer switch is required by electrical code and serves the
following functions:
• Allows the LOAD circuits to be connected to only one power
supply at a time.
• Prevents electrical backfeed between the generator and the
UTILITY power circuits.
Figure 3.1— Basic Standby Electric System
unun
Po11FR
SUPHY
snumer
sos
MM uxe
CINCUff DRUM
ORCUrr BRUHR
Notice that both the STANDBY and the UTILITY power supplies to
the transfer switch are protected against overload by a main line
circuit breaker.
3.2 STANDBY CIRCUIT ISOLATION
METHOD
This prevents overloading the generator by keeping electrical
loads below the wattage/amperage capacity of the generator. If the
generator is powering only designated loads, within the wattage/
amperage capacity, during utility power outages, consider using
the emergency circuit isolation method.
Designated electrical loads are grouped together and wired into a
separate "Standby Distribution Panel." Load circuits powered by
that panel are within the wattage/amperage capacity of the genera-
tor set. When this method is used, it is difficult to overload the gen-
erator. The transfer switch must meet the following requirements:
- It must have an ampere rating equal to the total amperage rating
of the standby distribution panel circuit.
• Have it installed between the building's main distribution panel
and the standby distribution panel.
The generator powers only designated loads that are grouped
together and wired into a separate emergency distribution panel.
The transfer switch is installed between the main distribution panel
(A) and the emergency distribution panel (E) (Figure 3.1).
The amperage rating of the transfer switch must be equal to, or
greater than, the highest amperage rating of the utility and genera-
tor breakers feeding the switch.
Figure 3.1= Standby Isolation
3.3 TOTAL CIRCUIT ISOLATION
METHOD
When a generator capable of powering all electrical loads in the
circuit is to be installed, use the "Total Circuit Isolation Method." It
is possible for the generator to be overloaded when this isolation
method is employed. The following apply to the transfer switch in
this type of system.
• Ampere rating of the transfer switch must equal the ampere
rating of the normal incoming utility service.
• The transfer switch is installed between the utility service
entrance and the building distribution panel.
The generator will be backing up all electrical loads within the
circuit, so the amperage rating of the transfer switch must be
equal to, or greater than, the amperage rating of the normal utility
service.
Unless a service entrance rated transfer switch is used, a main
service disconnect (D) must be located before the transfer switch.
The transfer switch is installed between the utility service entrance
and the building distribution panel (A) (Figure 3.2).
Figure 3.2 — Total Circuit Isolation
3.4 ALL TRANSFER SWITCH
INSTALLATIONS
Power wiring, control wiring and wiring for the 15 or 20 Amp cir-
cuit required for the 2-Amp smart charger should be in separate
conduit.
In all installations, a ground wire will run through the power conduit
from the generator connection panel to the transfer switch (Figure
3.3).
Figure 3.3 — Ground Wire
In any three-phase application, the phase rotation of the generator
power lines must match the phase rotation of the utility power lines
at the transfer switch (Figure 3.4).
17
Figure 3 4 — Match Phase Rotation
While supporting the lugs, use a torque wrench to tighten the lugs
on the generator circuit breaker and the transfer switch. Torque
specifications are in the Transfer Switch, Owner's Manual (Figure
3.5).
Consult the Technical Manual that comes with the transfer switch
for. wiring diagrams and any product changes, "modifications or
updates.
Figure 3.5 — Torque Lugs
3.5 NEXUS TRANSFER SWITCHES
Generators equipped with the Nexus Digital Controller will be
matched to a Nexus or RTS transfer switch.
N = Normal Utility Supply
E = Generator Connection Panel
T = Load Distribution Panel
3.6 CONNECTION DIAGRAMS
All wiring in the standby electric power system must be in strict
compliance with applicable codes, standards and regulations.
Such wiring must be properly supported, routed, and connected.
In addition, wiring must be properly sized to carry the maximum
load current to which is will be subjected.
The connections between the generator and transfer switch will
vary depending on the equipment ordered. In each case there are
two types of interconnections, load wiring and control wiring.
QMake sure to turn OFF both the NORMAL
(UTILITY) and STANDBY (EMERGENCY) power
supplies before trying to connect power source
and load lines to the transfer switch. Supply
voltages are extremely high and dangerous.
Contact with such high voltage power supply
lines causes extremely hazardous, possibly
lethal, electrical shock.
A CAUTIONI.
ABe.sure to maintain proper electrical clearanc-
es between live electrical parts and grounded
metal. Allow at least one-half inchof clearance
circuits up to 400 amps.
AExtremely high and potentially lethal supply
voltages are present at the transfer switch when
verifying phase rotation. This operation should
only be performed by a trained electrician.
3.6.1 NEXUS CONTROLLER TO A RTS/NEXUS SMART
The Nexus controller generator consists of an AUTO/OFF/ MANUAL
switch and a 2-line LCD display. See Figure 3.6 for an interconnec-
tion diagram. See "Control Wiring" for control wire sizing recom-
mendations.
OMake sure to turn OFF the NORMAL (UTILITY)
power supply before trying to connect the Utility
1 and Utility 2 control wires. Supply voltages
are extremely high and dangerous. Contact with
such high voltage power supply lines causes
extremely hazardous, possibly lethal, electrical
shock.
A CAUTIONI
When installing these switches, terminals 178 and 183 (2-wire Terminals 178 and 183 in the generator AC con-
nection box are not used in this application.
start) are not used. Connection of any wires to these terminals may
result in unwarrantable damage to the control
board.
18
J
UTILITY SUPPLY FROM
QT SERIES ENGINE GENERATOR SERVICE DISCONNECT
CONNECTION PANEL
® O O O
w
z
ZZHz �nn LOAD SHED
NUMB IIII am IIIIIIIIII IIIII MODULE
MATCH WIRE
TO
TERMINAL NUMBERS
�Nmm� O
E1 E2 ® NEUTRAL BLOCK
0
GROUND
GROUND
RTS TRANSFER SWITCH
11
006 eee00
000 000
000 00
Dm oo00
ooe00
oe
2
NEUTRAL BLOCK
N1ITEi CUSTOMER LOAD
POWER LEADS AND TRANSFER SWITCH LEADS (DISTRIBUTION PANEL)
III BE RUN IN TWO DIFFERENT CONDUITS,
LIQUID COOLED INSTALLATI❑N
The load wires consist of wires run between the generator main
circuit breaker and the transfer mechanism, and a neutral wire. See
"Wire Recommendations/Sizing" for load wire sizing information.
3.6.2 BLOCK HEATER CONNECTIONS
Block heater kits can be purchased at the authorized dealer.
The block heater will not function unless it is plugged into the AC
outlet and the outlet is properly wired to an AC power supply (by'
the installer) (Figure 3.7).
Figure 3.7 — AC Outlet for Block Heater and Battery
Charger (to be wired by installer)
FRAME RAIL
3.7 WIRE RECOMMENDATIONS/
SIZING (SEE TABLE 4)
3.7.1 CONTROL WIRING
Control system interconnections on a Nexus Series controlled
generator consist of N1 and N2, T1, NEU, and leads 23 and 194.
Control system interconnection leads must be run in a conduit that
is separate from the AC power leads. Recommended wire gauge
size depends on the length of the wire:
Max. Cable Length
Recommended Wire Size
460 feet (140m)
No.18 AWG.
461 to 730 feet (223m)
No. 16 AWG.
731 to 1,160 feet (354m)
No.14 AWG.
1,161 to 1850 feet (565m)
No. 12 AWG.
I 312 LOAD WIRING
b b I 12OVAC SUPPLY TO BATTERY Power source and load line conductors must be properly sup-
omo a CHARGER, ANB BLOCK HEATER ported, of approved insulative qualities, and of the correct wire
gauge size.
20A, 120VAC When connecting power, source, and load lines remove surface
GFCI OUTLET oxides from stripped ends of conductors with a wire brush. Apply
joint compound to stripped ends of conductors. Tighten terminals
to the specified torque value, as given in the owner's manual for
the transfer switch.
Recommended wire gauge size depends on the current rating of
the generator main circuit breaker.
20
TABLE 4 - ALLOWABLE AMPACITIES OF INSULATED CONDUCTORS RATED 0-2000 VOLTS, 60° TO 90° C (140° TO ' 194° F),
NOT MORE THAN THREE CONDUCTORS IN RACEWAY OR CABLE OR EARTH (DIRECTLY BURIED), BASED ON
SIZE
TEMPERATURE
RATING OF CONDUCTOR
SIZE
600 C
750 C
900 C I
600 C
750 C
900 C
1400 F
1670 F
1940 F
1400 F
1670 F
194- F
TYPES
TYPES
TYPES
TYPES
TYPES
TYPES
TWY, UFY
FEPWY
TA, TBS, SA
TWY
RHY, RHWY
TA, TBS
RHY, RHWY
SIS, FEPY
UFY
THHWY
SA, SIS,
AWG
THHWY
FEPBY '
THWY
THHNY
AWG
kcmil
THWY
RHHY, RHW2
THWNY
THHWY
THWNY
THHNY, THHWY
XHHWY
THW2, THWN2
XHHWY
THW2, THWN2
USEY
RHHY, RHW2
USEY, ZWY
USE2, XHH
USE2
XHHWY
XHH, XHHW
,
XHHW2 ZW2
L
XHHW2 ZW2
COPPER I
ALUMINUM
OR COPPER CLAD
ALUMINUM
18
—
—
14
—
—
—
—
16
—
—
18
—
—
—
—
14
20Y
20Y
25Y
—
—
—
—
12
25Y
25Y
30Y
20Y
20Y
25Y
12
10
30
35Y
40Y !
25
30Y
35Y
10
8
40
50
55
30
40
45
8
6
55
65
75
40
50
60
6
4
70
85
95
55
65
75
4
3
85
100
110
65
75
85
3
2
95
115
130
75
90
100
2
1
110
160
150
85
100
115
1
1 /0
125
150
170
100
120
135
1 /0
2/0
145
175
195
115
135
150
2/0
3/0
165
200
225
130
155
175
3/0
4/0
195
230
260
150
180
205
4 0
250
215
255
290
170
205
230
250
300
24
285
320
190
230
255
300
350
260
310
350
210
250
280
350
400
280
335
380
225
270
305
400
500
320
380
430
260
310
350
'500
600
355
42
475
285
340
385
600
700
385
460
520
310
375
420
700
750
400
475
535
320
385
435
750
800
410
490
555
330
395
450
800
900
435
520
585
355
425
480
900
1000
455
545
615 1
375
445
500
1000
1250
495
590
665 -
405
485
545
1250
1500
520
625
705
435
520
585
1500
1750
545
650
735
455
545
615
1750
2000
560
665
750
470
560
630
2000
Unless otherwise specifically permitted in the NEC, the over current protection for conductor types marked with an Y shall not exceed 15 amperes for No.
14, 20 amperes for No.12, and 30 amperes for No. 10 copper; or 15 amperes for No.12 and 25 amperes for No. 10 aluminum and copper -clad aluminum
after any correction factors for ambient temperature and number of conductors have been applied.
21
UTILITY SUPPLY FROM
SERVICE DISCONNECT
QT SERIES ENGINE GENERATOR
CONNECTION PANEL
® O O OLl
w CUSTOMER SUPPLIED
Z NEUTRAL WIRE
jz) LOAD SHED
-oJ= -Z MODULE
ZZH
NOTE,
MATCH WIRE
NUMBERS TO
TERMINAL NUMBERS
El E2 ® NEUTRAL BLOCK
Q
NEUT 00
I I -,I\ e - mCU
O
O B
GROUND
L
POWER LEADS AND
TRANSFER SWRQH
LEADS j= BE
RUN IN TWO
DIFFEREM OONDURS.
REVISION: H-7539-C
DATE: 9/24/10 PAGE 1 OF 2
GROUP G
RTS TRANSFER SWITCH
"dmw A
FW
NEUTRAL BLOCK
GROUND
CUSTOMER LOAD
(DISTRIBUTION PANEL)
EXPLODED VIEW:
RTS INTERCONNECTION DIAGRAM
DRAWING #: OH7453
EXPLODED VIEW: RTS INTERCONNECTION DIAGRAM
DRAWING #: OH7453
APPLICABLE TO:
GROUP G
THIS PAGE IS LEFT INTENTIONALLY BLANK
l
REVISION: H-7539-C
DATE: 9/24/10 PAGE 2 OF 2