HomeMy WebLinkAboutDESIGN PRESSURE CALCULATIONSENGINEERING & TESTING, INC. SCANNED BY St Lucie C®untY DATE: 2/22/18 RECE7VEDPhone: (866) 781-6889 *Fait: (866) 784-8550 lvww.floridaengineering,tndtesting.com FEB �, 250 S.W.13th Avenue Pompano Beach, FL 33069 ST. Lucia Coy ER #: 18-812 CLIENT: All Area Roofing ADDRESS: 3921 S. US Highway 1 Fort Pierce, Florida 34982 PROJECT: Smolarek Residence Sunlast Metal 5V Crimp Roof Panels ADDRESS: 5331 Montego Circle Fort Pierce, Florida 2017 FBC/ASCE-7 DESIGN PRESSURE CALCULATIONS Proiect Information: Mean Height < 15' Exposure: D Basic/Ultimate Wind Speed: V,,tt=170 mph Length = 39' Category: R Nominal Wind Speed: V.d=Vwt*40.6 Width = 22' Slope: 3/12 =14' (asd = allowable strength design) Parapet Wall: N/A Residential KZ =1.03, Kzt =1.0, Kd = 0.85 Design Calculations: Velocity Pressure: q = 0.00256*K7KztKdV2 Velocity Pressure (,,It): q=0.00256(1.03)(1.0)(0.85)(170)2] = 64.77 psf Velocity Pressure (.d): q=0.00256(1.03)(1.0)(0.85)(170*40.6)2] = 38.86 psf Width of Pressure Coefficient: 0.1(22') 0.4(15') Effective Wind Area: <1 Of 2 External Pressure Coefficient: 1) GCP 1 = -0.9 2) GCP2 = -1.7 3) GCP3 = -2.6 Design Pressures Based on Vasa: = 2.2' = 6.0' } use: 3'0" Internal Pressure Coefficient: 1) GCP; = 0.18 1) Field P1 = 38.86*[(-0.9) — (0.18)] = -42.0 psf 2) Perimeter P2 = 38.86*[(-1.7) — (0.18)] = -73.1 psf 3) Corners P3 = 38.86* [(-2.6) — (0.18)] = -108.0 psf �0A ath I�'Q 14 QualityA01 dls Trance ` Page 2, 2/22/18, Job Order #18-812 All Area Roofing Smolarek Residence Sunlast Metal 5V Crimp Roof Panels 5331 Montego Circle; Fort Pierce, FL: Attachment Requirements: FLO A Based on the requirements of Florida Product Approval # 21423.7 with maximum design pressures of-78.5psf for the field and-189.25psf for the perimeter and corner zones; the following are our recommended fastening row spacing (located across panel per Install Details on page 4 of 4) to attach the Sunlast Metal 26GA 5V Crimp Roof Panels (24" width) to the 15/32" APA plywood deck (attached to structural supports per product approval) with Wood-Zac XG fasteners with Neoprene Washers or equivalent # 10 Hex Head to penetrate 3/16" minimum through plywood in the following spacing: Area Field Perimeter & Corner Maximum Design Pressure -78.5psf -189.25psf Fastener Row Spacing 16" o.c. 8" o.c. Fastener Size #10 #10 Notes: Corners and perimeter (edge, hip, & ridge) area dimension shall not be less than a = TO" (Zone 2: Perimeter (including along ridges) is a 3'0" wide strip, Zone 3: Corners are 310" x 31011) Contractor to verify that the fastening patterns meet manufacturer's requirements for issuance of a warranty (as applicable). All work shall be in compliance with the local building code product control notice of acceptance and manufacturer specifications and Florida Building Code 2017 Edition. Wind load calculations based on ASCE-7, 2017 FBC, and information provided by client. Client is responsible for verifying existing conditions as it pertains to the above provided product approval. All work shall be inspected by our field engineer (or authorized representative) or a building department inspector to verify compliance with specifications. Sincerely, ` I z��� Z• �L Mark A. Mesiano, j: No. 48202 - ••%0 Florida Engineerirg &'Vesting, Inc. Florida Reg. No. �2; STATE OF : ty Certificate of Authca ip%n,� 6$ OR% �'/'i/ /ONAL �a\N III