HomeMy WebLinkAboutEVALUATION REPORTI T- SCANNED ', y TPjN1TY `= ERD i EVALUATION REPORT TRI- BUILT Materials Group, LLC PO Box 70 Rutherford, NJ 07070 (800) 516-1485 EXTERIOR.RESEARCH & DESIGN, LLC. Certificate of Authorization #19503 353 Christian Street Oxford, CT 06478 (203) 262-9245 Evaluation Report A42970.10.12-112 FL16027-R2 Date of Issuance:10/23/2012 Revision 2: 09/25/2017 SCOPE: This Evaluation Report is issued under Rule 61G20-3 and the applicable rules and regulations governing the use of construction materials in the State of Florida. he documentation submitted has been reviewed by Robert Nieminen, P.E. for use of the product under the Florida Building Code. The product described herein has been evaluated for compliance with the.6`h Edition (2017) Florida Building Code sections noted herein. DESCRIPTION: TRI-BUILT Modified Bitumen Roof Systems LABELING: Labeling shall be in accordance with the requirements the Accredited Quality Assurance Agency noted herein. CONTINUED COMPLIANCE: This Evaluation Report is valid until such time as the named product(s) changes, the referenced Quality Assurance documentation changes, or provisions of the Code that relate to the product change. Acceptance of this Evaluation Report by the named client Constitutes agreement to notify 'Robert Nieminen, P.E. if the product changes or.the referenced Quality Assurance documentation changes. Trinity I ERD requires a complete review of this Evaluation Report relative to updated Code requirements with each Code Cycle. ADVERTISEMENT: The Evaluation Report numbe' preceded by the words "Trinity I ERD Evaluated" may be displayed in advertising literature. If any portion of the Evaluation Report is displayed, then it shall be done in its.entirety. INSPECTION: Upon request, a copy of this entirei Evaluation Report shall be provided to the user by the manufacturer or its distributors and shall be available for inspection at the job site at the request of the Building. Official. This Evaluation Report consists of pages 1 th Prepared by: Robert J.M. Nieminen, P.E. Florida Registration No. 59166, Florida DCA ANE1983 4, plus a 26-page Appendix. The facsimile seal appearing was authorized by Robert Nieminen. P.E. on 09/25/2017. This does not serve as an electronically signed document. CERTIFICATION OF INDEPENDENCE: 1. Exterior Research & Design, LLC. d/b/a Trinity I ERD does not have, nor does it intend to acquire or will it acquire, a financial interest in any company manufacturing or distributing products it evaluates. 2. Exterior Research & Design, LLC. d/b/a Trinity ,I ERD is not owned, operated or controlled by any company manufacturing or distributing products it evaluates. 3. Robert Nieminen, P.E. does not have nor will acquire, a financial interest in any company manufacturing or distributing products for which the evaluation reports are being issued. 1 4. Robert Nieminen, P.E. does not have, nor will acquire, a financial interest in any other entity involved in the approval process of the product. S. This -is a building code evaluation. Neither Trinityl ERD nor Robert Nieminen, P.E. are, in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof, is/was used for permitting or design guidance unless retained specifically for that purpose. T.iv F January L, 2017 ST RE: Certification of Independence, TRINI RD wr;�EIVED i Certificate ofAuthorization #9503 B 28?018 County, Permitting a F.A.C. Rule 61'G20-3 To Whom It'May Concern: This letter: serves to document the following in accordance with Florida F.A.C. Rule 6I G20-3: 1. Exterior.=Research & Design, LLC. d/b/a rinity I ERD does not have, nor does itintend to acquire or will` it,acq'uire; ofinancial interest in any company manufacturing or distributing products it evaluates. 2. Exterior`Rese'arch & Design, LLC. d/b/a Trinity I .ERD is not owned; operated or controlled by any company.mariufacturing or distributing products it evaluates. 3. Robert ' Nieminen, P.E. does not have nor. will acquire, a financial" interest "in' any company manufacturing -or distributing products for which the evaluation reports are being. issued. 4 Robert Nieminen; P.E:.does not have, nor will acquire, a -financial interest in any, other entity involved in: the'approval'•process of -the product. r" n 5 gulding Code"Evaluations.issued:by Trinity{ERD and'•Robert Nieminen, P.E. are not, in anyway; to be f construed to mean or imply that TrinityyfRD or Robert Nieminen, P.E. are the Designer. of Record J for any project on -which the Evaluation eport is/was used for permitting or design guidance; unless retained specifically for that purpose ora given. project. Please contact our office with any questior Sincerely, Robert Nieminen; P.E. Florida'Reg No. 59166 ^O��eA1 EI Vice President' r1L Email: robertnieminen@trinityerd.com ARE Tf ST. LUCI►E COUNTY BUILD. ION REVIEWED FOR COMP REVIEWED DATE PLANS AND PERMIT MUST BE KEPT ON JOB OR NO INSPECTION WILL BE MADE FASTENERS OR ATTACHMENTS RESPONSIBILITY OF THE !TRACTOR OF RECORD THESE PLANS AND ALL PROPOSED WORK ARE SUBJECT TO ANY CORRECTIONS REQUIRED. BY FIELD INSPECTORS THAT MAY BE NECESSARY IN ORDER TO COMPLY WITH & APPMAIArk GODES. TM NITYi.CRD WA: ED, Via Ya t L.) CT: 4- n L' - Sep; t 1 to -Cx.( rd 4 a o 7 �5 4F 25 r 45 c a n::'. .2:2 r Z-92e? " SC: '! -. t4iu : SC 3 F. fen,% C-A.-:.'s' x� Illifll HI: 3c:a,5,_.,...a.•._4_7 .on.lu: .058.� .GS;53S-31:4 - .,L ._ S -3:4' FILE COPY - a ,'x TRINITY ` ERD I ROOFING, SYSTEMS EVALUATION: 1. SCOPE: Product Category: Roofing Sub -Category: Modified Bitumen Roof Systems Compliance Statement: TRI-BUILT Modified Bitumen Roof Systems, as produced by TRI-BUILT Materials Group, LLC, have demonstrated compliance with the following sections of the 6t' Edition (2017) Florida Building Code through testing in. accordance with the following Standards_ Compliance is subject to the Installation Requirements and Limitations /Conditions of Use set forth herein. 2. STANDARDS: Section PropertV Standard Year 1504.3.1 Wind FM 4474 2011 1504.7 Impact FM 4470 2012 1507.11.2 Physical Properties ASTM D6163 2008 1507.11.2 Physical Properties ASTM D6164 2011 1507.11.2 Physical Properties ASTM D6222 2011 3. REFERENCES: 9flibt Examination Reference Date ERD (TST6049) Physical Properties P10490.10.08-2 10/30/2008 ERD (TST6049) FM 4470/4474 P13760.09.09 09/10/2009 ERD(TST6049) FM 4470/4474 P13770.09.09 09/10/2009 ERD.(TST6049) FM 4470/4474 P30540.11.09-R1 11/30/2009 ERD (TST6049) FM 4470/4474 P30550.12.09 12/02/2009 ERD (TST6049) Physical Properties P33960.12.10 12/30/2010 ERD(TST6049) FM 4470/4474 P33970.03.11 03/15/2011 ERD (TST6049) ' Physical Properties P37590.03.13-3A 03/06/2013 ERD (TST6049) FM 4470/4474 P39680.03.13 03/04/2013 ERD (TST6049) Physical Properties P37590.03.13-1-R1 06/26/2013 ERD (TST6049) Physical Properties P37590.03.13-2-R1 07/01/2013 ERD (TST6049) Physical Properties P37590.07.13-2 07/01/2013 ERD (TST6049) Physical Properties P37590.03.13-5-R1 07/01/2013 ERD (TST6049) Physical Properties P37590.07.13-1 07/02/2013 ERD (TST6049) Physical Properties P45940.09.13 09/04/2013 ERD (TST6049) Physical Properties P44370.10.13 10/04/2013 FM Approvals (TST1867) FM 4470 2W7A7.AM 08/04/1994 FM Approvals (TST1867) FM 4470 0D3A3.AM 04/04/1997 FM Approvals (TST1867) FM 4470 2DOAO.AM 12/23/1998 FM Approvals (TST1867) FM 4470 2D5A9.AM 06/22/1999 FM Approvals (TST1867) FM 4470 3006646 01/04/2000. FM Approvals (TST1867) FM 4470 3001334 01/25/2000 FM Approvals (TST1867) FM 4470 3001334 02/15/2000 FM Approvals (TST1867) FM 4470 3000857 01/12/2000 FM Approvals (TST1867) FM 4470 3004091 01/12/2000 FM Approvals (TST1867) FM 4470 3006115 05/02/2001 fM Approvals,(TST1867) FM 4470 1 3012321 07/29/2002 FM'Approvals(TST1867) FM 4470 3014692 08/05/2003 FM Approvals (TST1867) FM 4470 3014751 08/27/2003 FM Approvals (TST1867) FM 4470 3007170 01/13/2004 FM Approvals(TST1867) FM 4470 3019317 06/30/2004 FM Approvals (TST1867) FM 4470 3020703 07/30/2004 FM Approvals (TST1867) FM 4470/4474 3018332 01/31/2006 FIVI Approvals (TST1867) FM 4470/4474 3023368 03/20/2006 FM Approvals (TST1867) FM 4470/4474 3024594 05/23/2006 Exterior Research and Design, LLC. Evaluation Report A42970.10.12-112 Certificate of Authorization #9503 C" EDITION (2017) FBC NON-HVH7 EVALUATION FL16027-112 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Revision 2: 09/25/2017 Page 2 of 4 Enifty Examination) FM Approvals(TST1867) FM 4470/4471 FM Approvals(TST1867) FM 4470/4474 FM Approvals (TST1867) FM 4470/4474 . PRI (TST5878) Physical Properties PRI (TST5878) Physical Properties PRI (TST5878) Physical Properties PRI (TST5878) Physical Properties Miami -Dade (CER1592) HVHZ Compliance Miami -Dade (CER1592) Proposal for Review UL LLC, (QUA9625) Quality Control UL LLC (QUA9625) Quality Control UL LLC- (QUA9625) Quality Control 4. PRODUCT DESCRIPTION: I This Evaluation Report covers TRI-BUILTModified Materials Group, LLC published installation instri following membranes make up the subject systems. 4 TRINITY ERD Reference Date 3023458 07/18/2006 3030668 09/12/2007 3032172 06/12/2009 PUSA-062-02-01 12/04/2007 PUSA-061-02-02 01/28/2008 PUSA-064-02-02 02/27/2008 PUSA-062-02-02 12/04/2008 Various NOAs Various 10-0823 10/12/2010 ML Agreement 02/27/2012 ML Correlation, R27202 08/20/2012 Service Confirmation, R14571 Exp. 10/06/2018 Bitumen Roof Systems installed in accordance with TRI-BUILT ctions and the Limitations / Conditions of Use herein. The x Table I Roll: Goo' s aX §forTRl BUILT Nlod�fied B�iymen�RoofSystemsti F s T e yp Product Specification Reference Grade Type SBS Membranes TriBuilt SA SBS Base ASTM D6163, Table 2 S I TriBuilt SBS Granular ASTM D6164. G I TriBuilt SA SBS Cap ASTM D6164 G I APP Membranes TriBuilt APP Smooth ASTM D6222 S I TriBuilt APP dranular ASTM D6222 G I TriBuilt SA APP Cap ASTM D6222 G I 5. LIMITATIONS: 5.1 This is a building code evaluation. Neither TrinityJERD nor Robert Nieminen, P.E. are; in any way, the Designer of Record for any project on which this Evaluation Report, or previous versions thereof; is/was used for permitting or design guidance unless retained specifically for that purpose. 5.2 This Evaluation Report is not for ise in FBC HVHZ jurisdictions. 5.3 Refer to a current Approved Roofing Materials Directory for fire ratings of this product. 5.4 For steeldeck installations, foam plastic insulation shall be separated from the building interior in accordance with FBC 2603.4 unless the except ions stated in FBC 2603.4.1 and 2603.6 apply. 5.5 The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of!the roof deck shall be documented through proper codified and/or FBC Approval documentation. 5.6 For recover installations, the existing roof shall be examined in accordance with FBC 1511. 5.7 For mechanically attached insulation or membrane or strip -bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 1.6. Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29; Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137, Assemblies marked With aln asterisk* carry the limitations set forth in Section 2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. Exterior Research and Design, LLC.' Evaluation Report A42970.10.12-R2 Certificate ojAuthori:ation #9503 6' EDITION (2017) FBC NON-HVHZ EVALUATION FL16027-R2 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Revision 2: 09/25/2017 i Page 3 of 4 5.8 5.9 5.10 5.11 �41`1 UNR Y I ERD For assemblies with all components fully bonded in place, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC Chapter 16. No rational analysis is permitted for ihese systems. For mechanically attached insul existing deck for withdrawal re! to the minimum requirements FX-1 or Testing Application Stai For bonded insulation or memb existing deck or existing roof su any surface conditions exist th< with ANSI/SPRI IA-1, ASTM E9C 124 shall be conducted on mocl ion or membrane over existing roof decks, fasteners shall be tested in the Lance. A qualified design professional shall review the data for comparison r the system. Testing and analysis shall be in accordance with ANSI/SPRI and TAS 105. ne over existing substrates in a re -roof (tear off) or recover installation, the ice shall be examined for compatibility with the adhesive to be installed. If bring system performance into question, field uplift -testing in accordance FM Loss Prevention Data Sheet 1-52 or Testing Application Standard TAS ips of the proposed new roof assembly. For bonded insulation or membrane over existing substrates in a recover installation, the existing roof system shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with ASTM E907, FM Loss Prevention Data Sheet 1-52;or Testing Application Standard TAS 124. 5.12, Metal edge attachment (except gutters), shall be designed and. installed for wind loads in accordance with FBC Chapter 16 and tested for resistance in accordance with ANSI/SPRI ES-1 or Roofing Application Standard RAS. 111, except the basic winld speed shall be determined from FBC Figure 1609.3(1), 1609.3(2) or 1609.3(3). 5.13- All products in the roof assembly shall have quality assurance in accordance with FAC Rule 61G20-3. 6. INSTALLATION: 6.1 TRI-BUILT Modified Bitumen Roof Systems shall be installed in accordance with TRI=BUILT Materials Group, LLC published installation instructions, subject to the Limitations / Conditions of Use noted below. 6.2 System attachment requirements for wind load resistance are set forth in Appendix 1. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads, and reflects the ultimate passing pressure divided by 2 (the 2 to 1 margin of safety per FBC 1504.9 has already been applied). Refer to FBC 1609 for determination of design wind loads. 7. BUILDING PERMIT REQUIREMENTS: As required by the Building Official or Authority Having Jurisdiction in order to properly evaluate the installation of this product. 8. MANUFACTURING PLANTS: I Contact the noted QA agency for information on product locations covered for F.A.C. Rule 611320-3 QA requirements. I 9. QUALITY ASSURANCE ENTITY: UL LLC—QUA9625; (314) 578-3406, k.chancellor@us.ul.com THE 26-PAGES THAT FOLLOW FORM PART OF THIS EVALUATION' REPORT - Exterior Research and Design, LLC. Evaluation Report A42970.30.12-R2 Certificate ofAuthorization #9503 CH EDITION (2017) FBC NON-HVH2 EVALUATION FL16027-RZ TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Revision 2: 09/25/2017 Page 4 of 4 TRINITY I ERD APPENDIX L, ,ATTACHMENT REQUIIiE(fnENTS,FOR WIND; UPLIFT RESI5I�ANCE ;:,, r '> � t "``'} Table Deck Application Type Description Page SA-1 Wood New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 4 1A-2 Wood New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 5 113 Wood New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 5 1C Wood New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 6 1D Wood New, Reroof (Tear -Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover 6 1E-1 Wood -New or Reroof (Tear -Off) E Non -Insulated, Mech, Attached Base Sheet, Bonded Roof Cover 7 1E-2 Wood_ __ New, Reroof (Tear -Off) or Recover E Non -insulated, Mech. Attached Bs eet, Bondedgoof-Gov_er _ 8_ 2A Steel or StruuEfurTconc'rete-'�-'I eew, Reroof (Tear -Off) or reecover — --T3 " "' Mech. Attached'RISs—el nsutattan, Bonded Top Insulation, Bon-ded`Roof Cover "� v 97 2B Steel or Structural concrete New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 9 2C Steel or Structural concrete New, Reroof (Tear -Off) or Recover D Prelim. Attached Insulation, Mech. Attached Base Sheet, Bonded Roof Cover 10 3A Structural concrete New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 11-14 - 3B-'- - Structural -concrete- -- -New or Reroof-(Tear-Off) - F--- --Non=Insulated,-Bonded-Rool`C-over 14- - -- 4A LWIC New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 15-16 4B LWIC New or Reroof (Tear -Off) A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 16 4C LWIC New or Reroof (Tear -Off) E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 17-19 SA CWF New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 20 5B CWF New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 21 5C CWF New, Reroof (Tear -Off) or Recover B Mech. Attached Base Insulation, Bonded Top Insulation, Bonded Roof Cover 22 5D CWF New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 22 5E CWF New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 22 6A Gypsum New or Reroof (Tear -Off) A-1 Bonded Insulation, Bonded Roof Cover 23 6B Gypsum New, Reroof (Tear -Off) or Recover A-2 Mech. Attached Anchor Sheet, Bonded Insulation, Bonded Roof Cover 24 6C Gypsum New, Reroof (Tear -Off) or Recover C Mech. Attached Insulation, Bonded Roof Cover 24 6D Gypsum New, Reroof (Tear -Off) or Recover E Non -Insulated, Mech. Attached Base Sheet, Bonded Roof Cover 24 7A Various Recover A-1 Bonded Insulation, Bonded Roof Cover 25-26 7B Various Recover F Non:Insulated, Bonded Base Sheet, Bonded Roof Cover 26 The following notes apply to the systems outlined herein: 1. The roof system evaluation herein pertains to above -deck roof components. Roof decks and structural members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. 'Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. 2. Insulation / base sheet fasteners shall be of sufficient length for the following deck engagement: Y Wood: Minimum 0.75-inch penetration. Y Steel: Minimum 0,75-inch penetration and engage the top flute of the steel deck. Y Structural concrete: Minimum 1-inch embedment into pilot hole in accordance with fastener manufacturer's published installation instructions. 3. Unless otherwise noted, insulation may be any one layer or combination of polyisocyanurate, polystyrene, wood fiberboard, perlite, gypsum -based roof board or mineral -wool roof board that meets the QA requirements of F.A.C. Rule 61G20-3 and is documented as meeting FBC 1505.1 and, for foam plastic, FBC Chapter 26, when installed with the roof cover. Exterior Research and Design, LLC. d/b/a Trinity ) ERD Evaluation Report A42970.10.12-R2 for FL16027-RZ Certificate of Authorization #9503 6r" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516.1485 Appendix 1, Page 1 of 26 r - Y TRIN9TY ERD 4. Minimum 200 psi, minimum 2-inch thick lightweight insulating concrete may be substituted for rigid insulation board for System Type D (mechanically attached base sheet, bonded roof cover), whereby the base sheet fasteners are Installed through the LWIC to engage the structural steel or concrete deck. The structural deck shall be of equal or greater configuration to the steel and concrete deck listings. Roof decks and structural, members shall be in accordance with FBC requirements to the satisfaction of the Authority Having Jurisdiction. Load resistance of the roof deck shall be documented through proper codified and/or FBC Approval documentation. S. Preliminary insulation attachment for System Type D: Unless otherwise, noted, refer to Section 2.2.10.1.3 of FM Loss Prevention Data Sheet 1-29 (January 2016). 6. Unless otherwise noted, insulation adhesive application rates are as follows. Ribbon or bead width is at the time of application; the ribbons/beads shall expand as noted in the manufacturer's published instructions. ➢ HA (HA): Full coverage at 25-30 Ibs/square. ➢ Dow INSTA STIK Quik Set Insulation Adhesive (D-IS): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c. Y Millennium One Step Foamable Adhesive (M-OSFA): Continuous 0.25 to 0.5-inch wide ribbons, 12-inch o.c. OMG OlyBond 500 (OB500): Continuous 0.75 to 1-inch wide ribbons, 12-inch o.c. (PaceCart or SpotShot). Note: OlyBond Green may be used where OlyBond 500 is referenced. Y OlyBond Classic (OB Classic): Full coverage at 1 gal/square. Y ICP Adhesive & Sealants CR-20: Continuous 2.5-3.5-inch wide ribbons, 12-inch o.c. ➢ Note: When multiple layers(s) of insulation and/or coverboard are installed in ribbon -applied adhesive, adhesive ribbons shall be staggered from layer -to -layer a distance of one-half the ribbon spacing. ➢ Note: The maximum edge distance from the adhesive ribbon to the edge of the insulation board shall be not less than one-half the specified ribbons spacing. _ 7. Unless otherwise noted, ail insulations. are flat stock or taper board of the minimum thickness noted. Tapered polyisocyanurate at the following thickness limitations maybe substituted with the following Maximum Design Pressure (MDP) limitations. In no case shall these values be used to 'increase' the MDP1istings in the tables; rather if MDP listing below meets or exceeds that listed for a particular system in the tables, then the thinner board listed below may be used as a drop -in for the equivalent thicker material listed in the table: ➢ Millennium One Step Foamable Adhesive (M-OSFA): MDP -157.5 psf (Min. 0.5-inch thick) Y OMG OlyBond 500 (OB500): MDP -45.0 psf (Min. 0.5-inch thick Multi -Max FA-3) ➢ OMG OlyBond 500 (OB500): MDP -187.5 psf (Min. 0.5-inch thick ISO 95+ GL) Y OMG OlyBond 500 (OB500): MDP -315.0 psf (Min. 0.5-inch thick ENRGY 3) Y OMG OlyBond 500 (OB500): MDP -487.5 psf (Min. 0.5-inch thick ACFoam II) Y ICP Adhesive & Sealants CR-20: MDP -117.5 psf (Min. 1.0-inch thick) 8. Bonded polyisocyanurate insulation boards shall be maximum 4 x 4 ft. 9. For mechanically attached components or partially bonded insulation, the maximum design pressure for the selected assembly shall meet or exceed the Zone 1 design pressure determined in accordance with FBC Chapter 16, and Zones 2 and 3 shall employ an attachment density designed by a qualified design professional to resist the elevated pressure criteria. Commonly used methods are ANSI/SPRI WD1, FM Loss Prevention Data Sheet 1-29, Roofing Application Standard RAS 117 and Roofing Application Standard RAS 137. Assemblies marked with an asterisk' carry the limitations set forth in Section .2.2.10.1 of FM Loss Prevention Data Sheet 1-29 (January 2016) for Zone 2/3 enhancements. 10. For fully bonded assemblies, the maximum design pressure for the selected assembly shall meet or exceed critical design pressure determined in accordance with FBC-Chapter 16, and no rational analysis is permitted. 1 11. For mechanically attached components over existing decks, fasteners shall be tested in the existing deck for withdrawal resistance. A qualified design professional shall review the data for comparison to the minimum requirements for the system. Testing and analysis shall be in accordance with ANSI/SPRI FX-1 or Testing Application Standard TAS 105. 12. For existing substrates in a bonded recover or re -roof installation, the existing roof surface or existing roof deck shall be examined for compatibility and bond performance with the selected adhesive, and the existing roof system (for recover) shall be capable of resisting project design pressures on its own merit to the satisfaction of the Authority Having Jurisdiction, as documented through field uplift testing in accordance with ANSI/SPRI IA-1, ASTM E907, FM Loss. Prevention Data Sheet 1-52 or Testing Application Standard TAS 124. 13. For Recover Applications using System Type D, the insulation is optional; however, the existing roof system shall be suitable for a recover application. 14. Lightweight Insulating Concrete (LWC) shall be cast in accordance with FBC Section 1917 to the satisfaction of the Authority Having Jurisdiction. For systems where specific LWC is referenced, refer to current LWC Product Approval for specific deck construction and limitations. For systems where specific LWC is not referenced, the minimum design mix shall be300 psi. In all cases, the minimum top -coat thickness is 2-inches. For LWC over structural concrete, reference is made to FBC Section 1917.4.1, Point 1. Exterior Research and Design, LLC. d/b/a Trinity) ERD Evaluation Report A42970.10.12-R2 for FL16027-RZ Certificate of Authorization #9503 6T'EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 2 of 26 f TRINITY ERD 15. Unless otherwise noted, refer to the following references for bonded base, ply or cap sheet applications. yY ' � TALE 1 stR1 BUILT Roo��CovERs„r, � x _ f � � k Reference Layer Material Application BP -AA Base Ply FBC Approved ASTM; D4601, Type 11 HA at.20-40 lbs/square Ply FBC Approved ASTN1p2178, Type IV or VI (Base and Ply sheets, Asphalt -Applied) SBS-AA Cap Ply Tr1Bullt SBS Granular HA at 20-40 Ibs/square (SBS, Asphalt -Applied) SBS-TA Cap Ply TriBuilt SBS Granular Torch -Applied (SBS, Torch -Applied) SBS-SA Base Ply TriBuilt SA SBS Base Self -Adhering Cap Ply TriBuilt SA SBS Cap (SBS, Self -Adhering) APP-TA Base Ply or Ply TriBuilt APP Smooth Torch -Applied Cap Ply TriBuilt APP Smooth; TriBuilt APP Granular (APP, Torch -Applied) APP-SA Cap Ply TriBuilt SA APP Cap Self -Adhering (APP, Self -Adhering) 16. Vapor barrier options for use over structural concrete deck followed by adhered • insulation carry the following Maximum Design Pressure (MDP) limitations. The lesser of the MDP listings below vs. those in Table 3A nnnlipc- VApbRBARft1EROPTIlN5,ST1tUCTURALGONGRETEDECK;AONEREbINSU[ATIdNpERjA8LE9A, Primer Vapor Barrier Insulation Adhesive MDP (psf)- Type YP Attach ASTM D41 TriBuilt SA SBS Base Self -Adhering Inta-Stik or CR-20, 12-inch o.c. -60.0 NB - ASTM D41 TriBullt SA SBS Cap Self -Adhering. Insta-Stik, 12-inch o.c. -75.0 ASTM D41 TriBuilt SA SBS Cap Self -Adhering Millennium One Step Foamable Adhesive, 12-inch o:c. -157:ASTM' D41 TriBuilt SA SBS Cap Self -Adhering CR-20, 12-inch o.c. -270.0 . ASTM D41 TriBuilt SA SBS Base Self -Adhering Millennium One Step Foamable Adhesive, Millennium PG-1 Pump Grade Adhesive, OlyBond 500 or CR-20, 12-inch o.c. 290.0 17. Dens Deck shall be field -primed with PG100 prior to self -adhering membrane application. Refer to tables herein for other priming requirements. 18. "MDP" = Maximum Design Pressure is the result of testing for wind load resistance based on allowable wind loads. Refer to FBC 1609 for determination of design wind loads. Exterior Research and Design, L-C. d/b/a Trinity i ERD Evaluation Report A42970.10.12-112 for FL16027-112 Certificate of Authorization 49503 6T" EDITION (2017) FBC NON-HVH2 EVALUATION Revision 2: 06/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 3 of 26 t. r TRINITY ER-D `TABLE 1A 1 :WOOD QECKS NEW CONSTRUCTION oR REROOF (TSAR Q`FF) � .:' SY5TEMTYPE�A2 MfrCWANIGALLYd�'1TACWED,AM1ICHOR'SWEET,Bf�NtlED'i1V$UI,ATION BON�EpR00FCDVERs �. System Deck A'nchorSheet Base Insulation Top Insulation 'Roof Cover (Note 15) MDR No. (Note 1) Type Fasteners Attach Type Attach Type Attach Base Ply Ply Cap Ply (psf) Min. 0.25-inch Dens Polyglass G2 Base,, 8-inch o.c. in 4- Deck, Dens Deck Prime, Min. 19/32- CertalnTeed Glasbase, 32 ga., 1-5/8- inch lap and 8- (Optional) FBC SECUROCK Gypsum - inch plywood Firestone MB Base, JM inch diameter inch o.c. in Approved, Fiber Roof Board, Min. (Optional) SBS-AA, W-1 max. Tamko tin caps with 11 three, equally ASTM C1289, HA 0.75-inch FescoBoard HA BP -AA BP -AA SBS-TA, -60.0 in inch spans spans GlassPermBasely. Glass Base or or a. annular ring g g spaced, P type II of iso- YP P Y {homogeneous) or min. APP-TA GAFGLAS k75 shank nails staggered cyanurate 0.5-inch Structodek center rows High Density Fiberboard Roof Insulation Polyglass G2 Base, 8-inch o.c. in 4- MIn.19/32- CertainTeedGlasbJse_ 32 ga., 1-5/8- Inch lap and 8- (Optional) FBC Win. D,25_inch__Dens (Optional) ---- - inch plywood Firestone MB Base, 1M -inch diameter— -inch-o.c.-in Approved;One Deck, Dens Deck Prime, or _SBS=SA,_ APP-SA, W-2 at max. 24- Perma-Ply 28, Tamko tin caps with 11 three, equally ASTM C1289, HA SECUROCK Gypsum- HA SBS-SA more SBS- SBS TA or -60.0 inch spans Glass Base or ga. annular ring spaced, type II polyiso- Fiber Roof Board SA or APP-TA GAFGLAS 1$75 shank nails staggered cyanurate APP TA center rows 32 ga., 1-5/8- 6-inch o.c. in 4- inch lap and 6- Min. 2-inch D-15, 08500, Min. 19/32- Polyglass Elastobase inch diameter inch O.C.in ACFoam 11, III, CR-20 or M- Min. 0.25-inch Dens D-IS, SBS-AA, W-3 inch plywood or Polyglass tin caps with 12 four; equally H-Shield, H- OSFA, atop Deck, Dens Deck Prime OB500, BP -AA (Optional) SBS-TA, -60.0* at max. 24- Elastobase PolyShield ga. annular ring spaced, CG, fastener or SECUROCK Gypsum- CR-20 or BP -AA APP-TA inch spans shank nails staggered Multi -Max FA3 rows, 7-inch Fiber Roof Board M-OSFA center rows or ENRGY-3 oc 6-inch o.c. in 4- Min. 2-inch D-IS, OB500, Min. 19/32- 32 ga., 1-5/8- inch. lap and-6- ACFoam II, III, CR-20 or M- D-IS, (Optional) SBS-SA, inch plywood Polyglass.Elastobase inch diameter inch o.c. in H- atop (Optional) Additional C B500' One or APP-SA, W 4 at max. 24 or Polyglass tin caps with 12 four, equally Shield CG, ShieH-Shld C PasteOSFA fastener ;layers of base insulation CR-20 or SBS-SA more SBS- SBS-TA or -6D.0* inch spans Elastobase Poly ga. annular ring spaced, Multi -Max FA3 rows, 7-inch M-OSFA SA or APP-TA shank nails staggered or ENRGY-3 oc APP TA center rows Exterior Research and Design, LLC. d/b/a Trinity ) ERD Certificate of Authorization k9503 Prepared by: Robert Nieminen, PE-59166 6T°' EDITION (2017) FBC NON-HVH2 EVALUATION TRI-BUILT Modified Bitumen Roof Systems; (800) S16-1485 Evaluation Report A42970.10.12-R2 for FL16027-RZ Revision 2: 09/25/2017 Appendix 1, Page 4 of 26 TRINITY I ERa TA6LEr1A-2 WOOD DECKS N W GONSTQ ION, t2EROOF (TeaR OFF) oR RECOVER E UCT 5YSTEIIA TYP:A 2 MfiCHANiCALLY ATTACHED ANGHOR SHEET, Bt?NCIr b;INSU�ATtON, BONDED GOVEft »OC#F „ t}„ _ .. y.., System. Deck Anchor Sheet Base Insulation. Top Insulation Roof Cover (Note 15) lyipp No. (Note i) Type Fasteners Attach Type Attach Type Attach Base Ply Ply Cap Ply (psf) 12-inch o.c. in 4- Min. 0.25-inch Dens Deck, Min. 19/32- Polyglass OMG Flat inch lap and 12- (Optional) FBC Dens Deck Prime, SECUROCK W-5 inch plywood Elastobase or Polyglass Bottom Plates inch o.c. in two, Approved, Gypsum -Fiber Roof Board, (Optional). SBS-AA, 585- at max. 24- Elastobase (square) with equally spaced, ASTM C1289, HA Min. 0.75-inch FescoBoard HA BP -AA BP -AA TA, APP-TA -60.0 inch spans Roofgrip #12 staggered center type II of iso yp y (homogeneous) or min. Poly cyanurate a inch Structodek High Density Density rows Fiberboard Roof insulation Min. 19/32- Polyglass OMG Flat 12-inch o.c. in 4- inch lap and 12- (Optional) FBC (Optional) inch plywood Elastobase or Bottom Plates inch o.c. in two, Approved, Min. 0.25-inch Dens Deck, One or SBS-SA, APP- W 6 at max. 244 Polyglass (square) with equally spaced, ASTM C1289, HA Dens Deck Prime, SECU ROCK HA SBS-SA more SBS- SA, SBS-TA -60.0 - - - _ incfi spar s Elastobase__ _ _ _ Roofgrip #12 ---type-Il-polyiso-- er staggered center -Gypsum-Fiber-Roof-Board -SA or APP— r-or— -- -- cyanurate TA rows System Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP No. Type Fasteners Attach Type Attach Base Ply Ply Cap Ply (psf) Min. 19 32-inch / Min. 1.5-inch Dekfast Hex with Min. 0.75-inch FescoBoard (Optional. if (Optional if using W-7 plywood at max. 24-inch ENRGY 3, H-Shield Dekfast #12 or TruFast 1 per Z (homogeneous) or min. 0.5-inch HA using AA Ply) AA Base) One or SBS-AA, SBS-TA, -60.0 spans or Polytherm MP-3 with TruFast DP . 133 ft Structoclek High Density Fiberboard BP -AA more BP -AA or APP-TA Roof Insulation APP-TA 7 Exterior Research and Design, I.I.C. d/b/a Trinity (ERD Evaluation Report A42970.10.12-R2 for Fi.16027-R2 Certificate of Authorization #9503 6'" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 5 of 26 i RECEIVED FEB 2 8 - 318 ST. Lucie county, Permitting TRINITY ERD - NSTRUCTI �TAB LE ON; RERPqFIT KAECOVERECK4NEWCO , SYSTEWTYP!� MECHANICALLYAT.rAHt WS L Nc-' ON P �Tfq, �A System. Base Insulation Top Insulation Layer Roof Cover (Note 15) MDP Type Fasteners Attach Base Ply Ply Cap Ply No. Deck (Note l) . Layer (Psf) Min. 19/32-inch (Optional) One or more layers, Min. 0.5-inch Structodek High'Density Fiberboard Roof Insulation or min. 0.25- Dekfast Galvalume 1 per 1.33 (Optional if (Optional if using AA SBS-AA, SBS-TA, APP- W-8 plywood at max. any combination, - Inch - Dens - Deck, DensDecIlk Prime or Steel Hex with ft, using AA Ply) Base) One or more BP -AA TA -82.5 24-Inch spans loose laid SECUROCK Gypsum -Fiber Roof Board Dekfast #12 DP BP -AA orAPP-TA Dekfast Galvalume Min. 19/32-inch (Optional) One or more layers, Min. 1.5-inch ENRGY 3, H-Shield or Steel Hex with Dekfast #12 DP or 1 per 1.33 SBS-SA (Optional) One or more SBS-SA, APP-SA, SBS- -82.5 W-9 plywood at max. any combination, Polytherm TruFast MP-3 with W SBS-SA or APP-TA TA or APP-TA 24-inch spans loose laid TruFast DP . . . . . . . . . . . . . . . ............. ION; &B 00110ECKV;l :lj7g TAU& AEW&(�E k4ffl', MTN'. System insulation Layer(s) Base Sheet Roof Cover (Note 15) MDP No. Deck (Note 1) Type Attach Base Fasteners Attach Base Ply Cap Ply (Psf) Polyglass Elastobase, Polyglass OVIG Flat Bottom Plates Min. 19/32-inch Elastobase Poly, Polyglass G2 Base, (square) with Roofgrip 12-inch o.c. in 4-inch lap and 12- (Optional) One SBS-AA, W-10 plywood at max. one or more layers, Prelim. Certain'reed Glasbase, Firestone MB 414, Dekfast Hex with inch o.c. in two, equally spaced, or more BP -AA SBS-TA, -52.5 24-inch spans any combination Attached Base, JM Perma-Ply 28, Tamko Glass Dekfast N14 or TruFast staggered center rows orAPP-TA APP-TA Base or GAFG LAS #75 MP-3 with TruFast HD SBS-SA, Min. 19/32-inch one or more layers, Prelim. Polyglass Elastobase or Polyglass Dekfast Hex with Dekfast 12-inch o.c. in 4-inch lap and 12- One or more APP-SA, W-11 plywood at max. any combination Attached Elastobase Poly with poly top surface #14 or TruFast MP-3 with inch o.c. in two, equally spaced, SBS-SA SBS-TA or -52.5 24-inch spans TruFast HD staggered center rows APP-TA Min. 19/32-inch one or more layers, Prelim. Polyglass Elastobase or Polyglass OMG FlatBottomPlates 12-inch o.c. in 4-inch lap and 12- Inch o.c. in two, equally spaced, (Optional) one or more BP -AA SBS-AA, SBS-TA, -60.0 W-12 plywood at max. any combination Attached Elastobase Poly (square) with Roofgrip #12 staggered center rows or APP-TA APP-TA 24-inch spans SBS-SA, Min. 19/32-inch One or more layers, Prelim. Polyglass Elastobase or Polyglass OMG Flat Bottom Plates 12 -inch o.c. in 4-inch lap and 12- inch o.c, in two, equally -spaced, One or more APP-SA, -60.0* W-13 plywood at max. any combination Attached Elastobase Poly with poly top surface (square) with Roofgrip # 12 staggered center rows SBS-SA SBS-TA or 24-Inch spans APP-TA Exterior Research and Design, I.I.C. d/b/a Trinity I ERD Evaluation Report A42970.10.12-R2 for FL16027-R2 Certificate of Authorization #9503 6 M EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nierninen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 6 of 26 ERD • �' TABLE 1E 1, WOOdrdECKS `NEW COPISTRUts`CION oRRERQQF(TeAR OFF}; SYSTEtVI TYP NON tN5ULATECi, IVIECEIANiCAlt;S!`ATTACI£d �A5E SHEET BONdECkROQF CV R System Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP No. Base Fasteners Attach Base Ply Gap Ply (Psf) Min. IS/32-inch- W-14' plywood at max. 24- Polyglass Elastobase Simplex MAXX Cap 9-inch o.c, at 2-inch lap and 18-inch o.c. in t two, onaor (Optional) BP-AA'BS-AA, SBS-TA S�` -45.0 inch spans equally spaced, staggered center rows APP-TA or APP-TA Min. 15/32-inch W-15 plywood at max. 24- Polyglass Elastobase Simplex MAXX Cap 9-inch o.c. at 2-inch`lap and 12-inch o.c. in two, (Optional) BP -AA or SBS-AA, SBS-TA -52.5 inch spans equally spaced, staggered center rows APP-TA or APP-TA Min. 19/32-inch Polyglass Elastobase, Polyglass Elastobase W-16 plywood at max. Poly, Polyglass G2 Base, CertainTeed 32 ga., 1-5/8-inch diameter tin caps. B-inch o.c. in 4-inch lap and 8-inch o.c. in three, (Optional) One or SBS-AA, SBS- 24-inch spans Glasbase, Firestone MB Base,1M Perma- with 11 ga. annular ring shank nails equally spaced, staggered center rows more BP -AA or TA, APP-TA -60.0 Ply 28, Tamko Glass Base or GAFGLAS 475 APP-TA W-17 Min. 19 32-inch � --- -- plywood at max. =Pol Iass-Elastobase-or Pol lass yg yg _ �2- a., 1-5 8-Inch diameter tinn ca s g - / - P —8=inch o.c. in 4=inch lap and-8=inch o.c. inii�ree, —(Optional)-One-or--SBS-SA,-APP--------- 24-inch inch spans Elastobase Poly with poly top surface with 11 ga. annular ring shank nails equally spaced, staggered center rows .more SBS-SA or moreAPP�S SA, SBS-TA or -60.0 APPSBS Min. 15/32-inch W-18 plywood at max. 24- Polyglass Elastobase Simplex MAXX Cap 6-inch d .c, at 2-inch lap and 6-inch o.c. in two, (Optional) BP -AA or 585-AA, SBS-TA 90.0 inch spans equally spaced, staggered center rows APP-TA or APP-TA W-19 Min. 19/32-inch plywood at max. Polyglass Elastobase or Polyglass 32 ga., 1-5/8-inch diameter tin caps 4-inch o.c. in 4-inch lap and 4-inch o.c. in four, (Optional) One or ` SBS-SA, APP- 24-inch spans Elastobase Polywith of to surface poly p with 11 a. annular ring shank nails, g g equally spaced, staggered center rows q y gg more SBS-SA or SA, SBS-TA or -97.5 .p APP-TA APP-TA Min. 15/32-inch W-20 plywood at max. 24- Polyglass Elastobase Simplex MAXX Cap 6-inch o.c. at 2-inch lap and 6-inch o.c. in three, (Optional) BP -AA or SBS-AA, SBS-TA 105.0 inch spans equally spaced, staggered center rows APP-TA or APP-TA W-21 Min. 19/32-inch plywood at max. y Polyglass Elastobase or Polyglass 32 ga., 1-5/8-inch diameter tin caps 6-inch o.c. in 4-inch lap and 6-inch o.c. in four, (Optional) One or SBS-AA, SBS- 2 24-inch spans Elastobase Poly with 11 ga. annular ring shank nails equally spaced, staggered center rows more BP -AA or TA, APP-TA 112.5 APP-TA Min. 19/32-inch 32 ga., 1-5/8-inch diameter tin caps W-22 plywood at max. Polyglass Elastobase or Polyglass yg yg with 11 a, annular ring shank nails. g g 6-inch o.c, in 4-Inch la and 6-inch o.c. in four, P (Optional) One or SBS-SA, APP- 24-inch spans Elastobase Poly with poly top surface Note: Tin caps are to be primed with equally spaced, staggered center rows more APP-TA SA, S85-TA or -112.5 ASTM D41 primer. APP-TA Exterior Research and Design, I.I.C. d/b/a Trinity(ERD Evaluation Report A42970.10.12-112 for F1.16027-112 Certificate of Authorization #9503 6"'EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 7 of 26 4' TABLE 1E 2 WGbI7 ElECKS NEW.'CONSTRUCTION REROOF'(TEAe OFF) oR REegvER 5`lS7EMTYPEE `NON (fVSULAT[}MECHANICALLY,ATiACIEDBISESHEE��BQNDED,fiOgFCC17ER } System Base Sheet Roof Cover (Note 15) MDP No. Deck (Note 1) Base Fasteners Attach Base Ply Cap Ply (psf) Min. 19/32-inch Polyglass Elastobase;. Polyglass Elastobase OMG Flat Bottom Plates (square) with 12-inch o.c. in 4-inch lap and 12-inch (Optional) One or W-1 plywood at max. Poly, Polyglass G2 Base, CertainTeed Roofgrip q14, Dekfast Hex with Dekfast ##14 o.c. in two, equally spaced, staggered more BP -AA or SBS-AA, SBS- -52.5 24-inch spans Glasbase, Firestone MB Base, 1M Perma- or TruFast MP-3 with TruFast HD center rows APP TA TA, APP-TA Ply 28, Tamko Glass Base or GAFGLAS 1#75 Min. 19/32-inch Polyglass Elastobase or Polyglass Dekfast Hex with Dekfast #14 or TruFast MP- 12-inch o.c. in 4-Inch lap and 12-inch One or more SBS- SBS-SA, APP- W-2 plywood at max. o.c. in two, equally spaced, staggered SA, SBS-TA or -52.5 „ 24-inch spans Elastobase Poly with poly top surface 3 with TruFast HD center rows SA APP-TA Min. 19/32-inch Polyglass Elastobase or Polyglass OMG Flat Bottom Plates (square) with 12-inch o.c. in 4-inch lap and 12-inch (Optional) One or SBS-AA, SBS- W-3 plywood at max. o.c. in two, equally spaced, staggered more BP -AA or -60.0 24-inch spans Elastobase Poly Roofgrip f#12 center rows . APP-TA TA, APP-TA Min. 19/32-inch Polyglass Elastobase or-Polyglass— -- -OtVlGflat-Bottom PIa�(square) with —12=inch-o:c—in-4-inch-lap-and in-4-inch-lap-and-1-2-inch — One or more SBS- -SBS=SA, APP- - W-4 plywood at max. Elastobase Poly with poly top surface Roofgrip t#12 o.c. In two, equally spaced, staggered SA SA, SBS-TA or -60.0" 24-inch spans center rows APP-TA TABLE o WOOD DECS NEW CON5TitUC710N o I�IlE Udt (TIcdR QFF} { > T .. 5Y5TRN1 TYPE_, NON. INSULAI f D; BgNdEC1 ROOD R �QV System Roof Cover (Note 15) MDP No. Deck Primer (Psf . Joint Trea t B se PI I C p Ply W-5 Min 15/32,i4ch plywood rattmaxt24.inchtspans F AST1M D1 :� "' 'u' '�" Non1- " ` `n SBS-SA (Optional)tSBS-SAto'r . SBS-SA, APP-SA, SBS TA 90.0 $(O[a6) _ or AP.P-TrA W 6 Min. 32-inch plywood _ (Optional) ASTM D41 Plywood joints are covered with 4-inch wide strips of TriBuilt SA TriBuilt SA SBS Base (Optional) SBS-SA or SBS-SA, APP-SA, SBS-TA 97.5 at max. 24-inch spans SBS Base, rolled Into place to create continuous bond. APP-TA or APP-TA Exterior Research and Design, LLC. d/b/a Trinity I ERD Evaluation Report A42970.10.12-R2 for FL16027-R2 Certificate of Authorization /#9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516.1485 Appendix 1, Page 8 of 26 \T .i e. TRINITY Y ERD i TABLE2A_STEELC�R`5TRUCTGRALCOfWCRETEOECKS NEWCONSTRUCTIfJN REROOF TEaIz=OFF o`RECOVER . ,. SYSTEM,TYPE:: MECfA[d►CAttw'A[TACHED BASE INUtl7ION, �ONdECJjpp INULAtiN BOI�nE[? ROCiF CC+.VER ..� System Deck (Note 1), Base Insulation Layer To lnsulationLa Layer p Roof Cove ; .�_. .. ...;:.: r (Note 15) MDP No, Type Fasteners Attach Type Attach Base, Ply Ply Cap Ply (psf) Min. 22 ga., type B, Min. 1.5-inch Dekfast Hex with Dekfast #14, Trufast Min. 0.75-inch FescoBoard (Optional,if using ' SC-1. Grade 33 steel or AGFoam II, ENRGY MP-3 with Trufast HD or 1 per 2 ftZ (homogeneous) or min. 0.5-inch HA (Optional if using AA Base) One or . SBS-AA, SBS- min. 2,500 psi p structrual concrete • 3, H-Shield or Polytherm y OMG 3-inch Galv Plate Structodek High Density AA Ply) BP -AA more BP -AA or TA, APP-TA 45.0 * with OMD HD Fiberboard Roof Insulation APP-TA Min. 22 a., type B, g yP Min. 2-inch Dekfast Hex with Dekfast #14, Trufast Min. 0.75-Inch FescoBoard (Optional if using SC-2. Grade 33 steel or ACFoam II, ENRGY MP-3 with Trufast HD or 1 per 4 ftZ (homogeneous) or min. 0.5-inch HA (Optional if using AA Base) One or SBS-AA, SBS- min. 2,500 psi structrual concrete 3, H-Shield or Polytherm y OMG 3-inch Galy Plate Structodek High Density AA Ply) BP -AA more BP -AA or TA, APP-TA -45.0* with OMD HD Fiberboard Roof Insulation APP-TA -- Min. 22 ga., type B, - ----.- Grade 33 steel or Min, -1-5-inch - .- - = ex Dekfast-Hex-with- - Min. 0.75-inch FescoBoard -(Optional-if-using- - SC-3. ENRGY 3, H-Shield Dekfast #14 or TruFast 1 per 1.33 (homogeneous) or min. 0.5-inch HA (Optional if using AA Base) One or SBS-AA, SBS- min. 2,500 psi structrual concrete or Polytherm MP-3 with Truast HD F ft, Structodek High Density AA Ply) BP -AA more BP -AA or TA, APP-TA -90.0 Fiberboard Roof Insulation APP-TA SC-4. Min. 22 ga., type B, Grade 33 steel or Min. 1.5-inch Dekfast Hex withru 1 per 1.33 Min. 0.75-inch FescoBoard (homogeneous) or min. 0.5-inch BP -AA (Top surface One or more SBS-SA, APP- min. 2,500 psi ENRGY 3, H-Shield Dekfast #14 or TruFast ast ftZ Structodek High Density HA primed with ASTM layers, SBS-SA or SA, SB5-TA -90.0 structrual concrete or Polytherm MP-3 with TruFast HD Fiberboard Roof Insulation D41 primer) APP-TA or APP-TA 57EELTABLE49i,CSTRUT.URALCQNCRETEDECk9:, CN CTI d+REndFs TEAO ( t A y �LSAT�IOU 3.VER System Deck (Noe . t1) Base Insulation Top Insulation Layer Roof Cover (Note 15) MDP No. La Layer y Type Fasteners Attach Base Ply Ply Cap Ply (psf) Min. 22 ga., type S, (Optional) One or SC-5. Grade 33 steel or more layers, any Min. 0.5-inch SECUROCK Gypsum- OMG 3-inch Galvalume Steel 1 per 1.78 (Optional if (Optional if using AA SBS-AA, SBS- min. 2,500 psi combination, loose Fiber Roof Board Plate with OMG #14 HD W using AA Ply) Base) One or more BP- TA, APP-TA -75.0 structrual concrete laid BP -AA AA or. APP-TA Min. 0.5-inch Structodek High Min. 22 ga., type B, One or more layers, Density Fiberboard Roof Dekfast Galvalume Steel Hex with SC-6. Grade 33 steel or any combination, Insulation or min. 0.25-inch Dens Dekfast H12 (steel only) or #14 or 1 per 1.33 (Optional if (Optional if using AA SBS-AA, SBS- min. 2,500 psi loose laid Deck, Dens Deck Prime or TruFast MP-3 with TruFast DP z ft using AA Ply) Base) One or more BP- TA, APP-TA -82.5 structrual concrete SECUROCK Gypsum -Fiber Roof. (steel only}. or HD BP -AA AA or APP-TA Board Min. 22 ga.; type B, (Optional) Dekfast Galvalume Steel Hex with SBS-AA, SBS= SC-7. Grade 33 steel or One or more layers, Min. 1.5-inch ENRGY 3, H-Shield Dekfast #12 (steel only) or #14 or 1 per 1.33 (Optional) One or more TA,,SBS-SA, min. 2,500 psi any combination, or Polytherm TruFast MP-3 with TruFast DP ft2 SBS-SA SBS-SA or APP-TA APP-TA, APP- 82 5 structrual concrete loose laid (steel only) or HD SA Exterior Research and Design, I.I.C. d/b/a Trinity IERD Certificate of Authorization #9503 Prepared by: Robert Nieminen, PE-59166 6r" EDITION (2017) FBC NON-HVHZ EVALUATION TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Evaluation Report A42970.10.12-112 for FL16027-RZ Revision 2: 09/25/2017 Appendix 1, Page 9 of 26 1 TR1N1 ■ ■ i E, \V TABlE2C STEELOR�STRUCTl1RALCONCRETEDECKS NEWCON$TR<]C710N,RERf}dF(TIArt=OFF}oRRECOVER ::., ;. SYSTEM TYPE PRELIM(NAItILY ATTACHED {N5ULATION" MECHANICALLY-�tTTAGHED dSE SHEET. B B ONtSE@ROOF COVER :NOTE INSULATIONIS,OPTIONAL„FOF RECQVERAPpLtCATIQNS System Deck (Note 1) Insulation Layer(s) Baseee Sheet, Roof Cover (Note 15) MDP No. Type Attach Base Fasteners Attach Base Ply Cap'Ply (Psf) Min. 22 ga., type B, Grade 33 steel or min. One or more Prelim. Polyglass Elastobase, Polyglass OMG Flat Bottom Plates (square). 12-inch o.c. in 4-inch lap (Optional) One or SC-8. 2,500 psi structrual layers, any Attached Elastobase Poly or JM Perma- with Roofgrip #14, Dekfast Hex with Dekfast #14 or TruFast MP-3 and 18-inch o.c. in two, equally spaced, staggered more BP -AA or APP- SBS-AA, SBS- -45.0* concrete combination ply 28 TA TA, APP-TA with TruFast HD center rows Polyglass Elastobase, Polyglass Min. 22 ga., type B, One or more Elastobase Poly, Polyglass G2 OMG Flat Bottom Plates (square) 12-inch o.c. in 4-inch lap SC-9. Grade 33 steel or min. layers, any Prelim. Base, CertainTeed Glasbase, with Roofgrip #14, Dekfast Hex and 12-inch o.c. in two, (Optional) One or SBS-AA, SBS- 2,500 psi structrual combination Attached Firestone MB Base, JM Perma- with Dekfast #14 or TruFast MP-3 equally spaced, sta q y p ggered more BP -AA or APP- TA; APP-TA -52.5 concrete Ply 28, Tamko Glass Base or with TruFast HD center rows TA T GAFGLAS #75 __ T Min. 22 ga., type B, One or more Polyglass Elastobase or OMG Flat Bottom Plates (square) 12-inch o.c. in 4-inch lap SC-10. Grade 33 steel or min. layers, any Prelim. Polyglass Elastobase Poly with with Roofgrip #14, Dekfast Hex and 12-inch o.c. in two, SBS-SA, APP- 2,500 psi structrual combination Attached poly top surface with Dekfast #14 or TruFast MP-3 equally spaced, staggered q y ace p O One or more SBS-SA SA, SBS-TA -52.5* concrete with TruFast HD center rows or APP-TA Min. 22 ga., type B, Grade 33 steel or min, One or more Prelim. Polyglass Elastobase or yg OMG Flat Bottom Plates (square) 12-inch o.c. in 4-inch la p (Optional) One or SC-11, 2,500 psi structrual layers an y y Attached Polyglass Elastobase Poly yg y with Roofgrip #12 (steel only) or and 12-inch o.c. in two, equally spaced, staggered more BP -AA or APP- SBS-AA, SBS- TA, -60.0 concrete combination #14 TA APP-TA center rows Min. 22 ga., type B, Grade 33 steel or min. One or more Prelim. Polyglass Elastobase or OMG Flat Bottom Plates (square) (q ) 12-inch o.c. in 4-inch lap SBS-SA, APP- SC-12, 2,500 psi structrual layers, any Attached Polyglass Elastobase Poly with with Roofgrip #12 (steel only) or and 12-inch o.c. in two, One or more SBS-SA SA, SBS-TA -60.0* concrete combination poly top surface #14 equally spaced, staggered or APP-TA center rows Min. 22 ga., type B, SC-13. Grade 80 steel or min. One or more layers, any Prelim. TriBuilt APP Smooth Dekfast isofast IF-2.375-AT Plates 12.-inch o.c. in the 5-inch SBS-TA, APP- 2,500 psi structrual p combination Attached with Dekfast #15 HS wide, heat -welded side lap (Optional) APP-TA TA -82.5 concrete Min. 22 ga., type B, SC-14. Grade 80 steel or min. One or more layers, any Prelim. TriBuilt APP Smooth Trufast 2.4 in. Barbed Seam .c. 12-inch oin the 6-inch SBS-TA, APP- 2,500 psi structrual p combination Attached Plates with TrufastEHD Fasteners wide, heat -welded side lap (Optional) APP-TA TA 82.5 concrete Min. 22 ga., type B, Grade 33 steel or min. One or more Prelim. Dekfast Hex with Dekfast #14 or 12-inch o.c. in the 4-inch � SC-15. 2,500 psi structrual layers, any Attached ' TriBuilt APP Smooth OMG Flat Bottom Plates with lap and 18 inch o.c. in two,. (Optional) BP -AA or SBS-AA, SBS- -112.5 combination OMG Roofgrip #14 a uall s q Y paced, staggered APP-TA TA, APP-TA concrete center rows Exterior. Research and Design, I.I.C. d/b/a Trinity ) ERD Certificate of Authorization #9503 Prepared by: Robert Nieminen, PE-59166 6T" EDITION (2017) FBC NON-HVH2 EVALUATION TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Evaluation Report A42970.10.12-R2 for FL16027-R2- Revision 2: 09/25/2017 Appendix 1, Page 10 of 26 Y N'�;„ ,. 'f TABLE 3A' STRUCTU AL CONCRETE DECKS NI;W CONSTRUCTION oR REROOF (TEAKpFP} a &YSTEM,TYPE A 1' BONbEL� INS111LATlpt�l, BONDED ROOF CdIIER S6ENOTE&6.FORVAPORBARRIEROPTIONS ". ` System Deck Primer Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP No. Type Attach Type Attach Base Ply Ply Cap Ply (psf) SELF=AbHRING;$YSTENtSUVITH BA$E!INS"ULATIQN'ANDORTIONA6,TOP1N$UU1TItlN�pfTHEANiE_•�YPE >_sjt C 1 Structural (Optional) Min. 1.5-inch H-Shield or Multi -Max (Optional) additional layers(s) of (Optional) One or more SBS SA, APP SA, concrete ASTM D41 FA3 D-IS base insulation D-IS SBS-SA SBS-SA or APP-TA SBS-TA or APP-TA -67.5 C 2 Structural (Optional) Min. 1.5 inch ACFoam II or ENRGY 3 D-IS (Optional) additional layers(s) of D-IS SBS-SA (Optional) One or more SBS-SA, APP-SA, concrete ASTM D41 base insulation SBS-SA or APP-TA SBS-TA or APP-TA 135.0 C-3 Structural None Min. 1.5-inch, min. 1.5 pcf Insulfoam D-IS (Optional) additional layers of base D-IS SBS-SA (Optional) One or more SBS-SA, APP-SA, concrete insulation SBS-SA or APP-TA SBS-TA or APP-TA 157.5 C-4 Structural None Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) additional layers of base OB500 SBS-SA (Optional) One or more SBS-SA, APP-SA, -120.0 concrete _ _ _ insulation _S.BS=SA.or-AP_P-TA _SBS=TA-or_AP_B-TA _ _ _ __ C-5 Structural None Min.1.5-inch OB500 (Optional) additional layers(s) of OB500 S85-SA (Optional) One or more SBS-SA, APP-SA, 127.5 concrete base insulation SBS-SA or APP-TA SBS-TAorAPP-TA C 6 Structural None Min. 1.5-inch ACFoam II or H-Shield OB500 (Optional) additional layers(s) of OB500 SBS-SA (Optional) One or more SBS-SA, APP-SA, 150.0 concrete base insulation SBS-SA or APP-TA SBS-TA or APP-TA C 7 Structural None Min. 1.5-inch ACFoam II, ENRGY 3, H- M-OSFA (Optional) additional layers(s) of (Optional) One or more SBS-SA, APP-SA, concrete Shield or Multi -Max FA3 base insulation M-OSFA SBS-SA SBS-SA or APP-TA SBS-TA or APP-TA 232.5 C 8 Structural None Min. 1.5-inch, min. 2,0 pcf Insulfoam CR-20 (Optional) additional layers of base CR-20 SBS-SA (Optional) One or more SBS-SA, APP-SA, 240.0 concrete insulation SBS-SA or APP-TA SBS-TA or APP-TA C 9 Structural None Min. 1.5-inch ACFoam II, ACFoam III, ENRGY 3, H-Shield, H-Shield CG Multi- CR-20 (Optional) additional layers(s) of CR-20 SBS-SA (Optional) One or more SBS-SA, APP-SA, concrete , Max FA3 or ISO 95+ GL base Insulation SBS-SA or APP-TA SBS-TA or APP-TA -270.0 C-10 Structural None Min. 2-inch ACFoam II or H-Shleld OB Classic (Optional) additional layers(s) of OB Classic SBS-SA (Optional) One or more SBS-SA, APP-SA, -270.0 concrete (FULL) base insulation (FULL) SBS-SA or APP-TA SBS-TA or APP-TA C-11 Structural ASTM D41 Min. 1.5-inch ACFoam 11, ACFoam Ill, ENRGY 3, H-Shield, H-Shield CG or HA (Optional) additional layers(s) of HA SBS-SA (Optional) One or more SBS-SA, APP-SA, concrete Multi -Max FA3 base insulation SBS-SA or APP-TA SBS-TA or APP-TA -480.0 EIF-ADHEPINtl$YSTEMS;WITHBASEINSULAIDi�dNDCOV�RBtlARD ar �4nd s% C-12 Structural None Min. 1.5-inch Multi Max FA3 D-IS Min, 0.25-Inch SECUROCK Gypsum- D-IS SBS SA (Optional) One or more SBS-SA, APP-SA, -67.5 concrete Fiber Roof Board SBS-SA or APR -TA SBS-TA or APP-TA C-13 Structural None Min. 1.5-Inch, min. 2.0 pcf Insulfoam D-IS Min. 0.25-inch Dens Deck, Dens D-IS SBS-SA (Optional) One or more SBS-SA, APP-SA, -120.0 concrete Deck Prime SBS-SA or APP-TA SBS-TA or APP-TA C-14 Structural None Min. 2-inch ACFoam II, ENRGY-3 or H- D-IS Min. 0.25-Inch SEW ROCK Gypsum-' (Optional) One or more SBS-SA, APP-SA, concrete Shield Fiber Roof Board D-IS SBS-SA SBS-SA or APP-TA SBS-TA or APP-TA -247.5 C-15 Structural None Min1 . .5 inch ENRGY 3 OB500 Min. 0.25-inch Dens Deck, Dens. OB500 SBS-SA (Optional) One or more SBS-SA,'APP-SA, 127.5 concrete Deck Prime SBS-SA or APP-TA SBS-TA or APP-TA Exterior Research and Design, LLC. d/b/a Trinity IERD Certificate of Authorization 99503 Prepared by: Robert Nieminen, PE-59166 6T"EDITION (2017) FBCNON-HVHZ EVALUATION TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Evaluation Report A42970.10.12-R2 for F1.16027-132 Revision 2: 09/25/2017 Appendix 1, Page 11 of 26 ,t TRINITY, ERD TABLE 3A STRUCTURAL CONCRETE DECKS NEW CONSTftUCTIQN oR REROOF (TEAR OFF) SYSTEyVi TYPE A' 1 BONDED INSULATION, BONDED GOOF COV9R SeE NOTE ZG F.OR VAPOR BARRIER OPTIONS System Base Insulation Layer . Top Insulation Layer Roof Cover (Note 15) MOP No. Deck Primer Type Attach Type Attach Base Ply Ply Cap Ply (psi) Structural Min. 1.5-inch ACFoam 11, H-Shield or. Min. 0.25-inch Dens Deck, Dens (Optional) One or more SBS-SA, APP-SA, C-16 concrete None ISO 95+GL OB500 Deck Prime 08500 SBS-SA SBS-SA or APP-TA SBS-TA or APP-TA 150.0 Structural Min. 2-inch ACFoam II, ENRGY-3 or H- Min. 0.25-inch SECUROCK Gypsum- (Optional) One or more SBS-SA, APP-SA, C-17 concrete None -Shield 06500 Fiber Roof Board OB500 SBS-SA SBS-SA or APP-TA SBS-TA or APP-TA 247.5 Structural Min. 1.5-inch ACFoam 11, ENRGY 3, H- Min. 0.25-inch SECUROCK Gypsum- (Optional) One or more SBS-SA, APP-SA, C-18 concrete None Shield or Multi -Max FA3 M-OSFA Fiber Roof Board" M-OSFA SBS-SA SBS-SA or APP-TA -TA or APP-TA -232.5 Structural Min. 2-inch ACFoam II, ENRGY-3 or H- Min. 0.25-inch SECUROCK Gypsum- (Optional) One or more SBS-SA, APP-SA, C 19 concrete None Shield M•OSFA Fiber Roof Board M-OSFA SBS-SA SBS-SA or APP-TA SBS-TA or APP-TA 247.5 --C-20 Structural-__. ___ _--_ None _ _ Min. 1.5-inch,, min 2.0 pcflnsulfoam CR-20 Min_0.25=inch_Oens_Deck,_Dens _ CR-£0 SBS-SA _(O.ptionalone_or-more-_SBS=SA,_APPSA,--_ 24D.0 concrete Deck Prime SgS-SA or APP-TA SBS-TA or APP-TA Min. 1.5-inch Ultra -Max or Multi -Max Structural FA-3, min. 1.3-inch ACFoam III or min. Min. 0.25-Inch SECUROCK Gypsum- (Optional) One or more SBS-SA, APP-SA, C-21 concrete None 1.0-inch ISO 95+GL, H-Shield, H-Shield CR-20 Fiber Roof Board CR-20 S8S-SA SBS-SA or APP-TA SBS-TA or APP-TA 240.0 CG or ENRGY 3 Structural Min. 2-inch ACFoam II, ENRGY-3 or H- Min. 0.25-inch SECUROCK Gypsum- (Optional) One or more SBS-SA, APP-SA, C 22 concrete None Shield CR 20 Fiber Roof Board CR-20 SBS-SA SBS-SA or APP-TA SBS-TA or APP-TA -247.5 Structural OB Min. 0.25-inch SECUROCK Gypsum- OB (Optional) One or more SBS-SA, APP-SA, C-23 None Min. 2-inch ACFoam II or H-Shield Classic Classic SBS-SA -350.0 concrete Fiber Roof Board SBS-SA or APP-TA SBS-TA or APP-TA (FULL) (FULL) Min. 1.5-inch ACFoam II, ACFoam III, Structural Min. 0.25-inch SECUROCK Gypsum- (Optional) One or more SBS-SA, APP-SA, C-24 ASTM D41 ENRGY 3, H-Shield, H-Shield CG or HA HA SBS-SA -350.0 concrete Multi -Max FA3 Fiber Roof Board SBS-SA or APP-TA SBS-TA or APP-TA A$PIAITAlYO .... ., .3 A .3 x dRTORCH►APPl1EDSYS£M5 S 7 .�_.. .. ,. ,. _... ..._. v...,_ ,,. .% ... .•.^ 5:3..'. v: 4. ..La t. .-F, ac4� .:t. fn•}:c .. .. ... ..._ .. x c xx.. u.... :E 1 X q 5:-. j s.RA$ n :.. :.n.., Q.�.e .r.x . i. �..f., _ .. is .. .... .K w .b ....:ram..:. Structural Min. 0.25-inch SECUROCK Gypsum- (Optional) One or more " C-25 None Min. 2-inch ACFoam II or H-Shield D-IS D-IS BP -AA SBS -AA 225.0 concrete Fiber Roof Board BP AA Structural Min. 0.25-inch SECUROCK Gypsum- (Optional) One or more C-26 None Min. 2-Inch ACFoam 11 or D-IS D-IS APP-TA APP-TA -232.5 concrete .H-Shield Fiber Roof Board APP TA Structural Min. 0.25-inch SECUROCK Gypsum- (Optional) one -or more C-27 None Min. 2-inch ACFoam 11 or H-Shield OB500 OB500 BP -AA " SBS-AA -225.0 concrete Fiber Roof Board BP -AA Structural Min. 0.25-inch SECUROCK Gypsum- (Optional).One or more C-28 None Min. 2-Inch ACFoam II or H-Shield OB500 OB5o0 APP-TA APP-TA -232.5 concrete I Fiber Roof Board APP-fA Structural Min. 0.25-inch SECUROCK Gypsum- (Optional) One or more C-29 None Min. 2-inch ACFoam II or H-Shield M-OSFA M-05FA BP=AA SBS-AA 225.0 concrete Fiber Roof Board BP -AA Structural Min. 0.25-inch SECUROCK Gypsum- (Optional) One or more C-30 concrete None Min. 2-inch ACFoam II or H-Shield M-OSFA Fiber Roof Board WOSFA APP-TA APP-TA APP-TA -232.5 Exterior Research and Design, I.I.C. d/b/a Trinity )ERD Evaluation Report A42970.10.12-R2 for FL16027-RZ Certificate of Authorization #9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 12 of 26 �S d I TRINITY i ERA %TABLE 3A STJtUCTUNAL CONCRETE QECKS NiN CONSTRUCTION oR REROOF (TEaR OFF), :' ON,Ba FCdVER SVSTEMT�1pE NDED INSULATI NDED ROQ ? k S' NOTE 16 FOR VAOPTIONS i System Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP No. Deck Primer Type Attach Type Attach Base Ply Ply Cap Ply (psf) Min. 1.5-inch Ultra -Max or Multi -Max Structural FA-3, min. 1.3-inch ACFoam III or min. Min. 0.25-inch SECUROCK Gypsum (Optional) One or more C-31 concrete None 1.0-inch ISO 95+GL, H-Shield, H-Shield CR 20 Fiber Roof Board CR-20 BP -AA BP AA SBS-AA 225.0 CG or ENRGY 3 Min. 1.5-inch Ultra -Max or Multi -Max _ Structural FA-3, min. 1.3-inch ACFoam III or min. Min. 0.25-inch SECUROCK Gypsum- (Optional) One or more C-32 concrete None 1.0-inch ISO 95+GL, H-Shield, H-Shield CR-20 Fiber Roof Board CR-20 APP-TA APP-TA APP-TA 232,5 CG or ENRGY 3 -- Structural __(Optional) Min. 2--inch ACFoam.11_or_H— OB _ Classic _Min.-0.25=inch.SECUROCK-Gypsum OB _(Optional) -One -or -more-- SBS-AA C=33— concrete None Shield Fiber Roof Board Classic BP -AA BP AA -225.0 (FULL) (FULL) Structural (Optional) Min. 2-inch ACFoam II or H- OB Min. 0.25-inch SECUROCK Gypsum- OB (Optional).One or more C-34 concrete None Shield Classic Fiber Roof Board Classic APP-TA APP-TA APP-TA 232.5 (FULL) (FULL) Min. 1.5-inch ACFoam II, ACFoam III, C-35 Structural ASTM D41 ENRGY 3, H-Shield, H-Shield CG or HA Min. 0.25-Inch SECUROCK Gypsum- HA BP -AA (Optional) One or more SBS-AA -225.0 concrete Multi -Max FA3 Fiber Roof Board BP AA Structural Min. 1.5-inch ACFoam II, ACFoam III, Min. 0.25-inch SECUROCK Gypsum- (Optional) One or more C-36 ASTM D41 ENRGY 3, H-Shield, H-Shield CG or HA HA APP-TA APP-TA -232.5 concrete Multi -Max FA3 Fiber Roof Board APP-TA (Optional if (Optional if using AA C-37 Structural ASTM D41 Min. 0.75-inch FescoBoard HA None N/A using AA Ply) Base) One or more BP- SBS-AA, SBS-TA, -277.5 concrete (homogeneous) One or more APP TA BP AA AA or APP-TA Min. 1.5-inch ACFoam II, ACFoam III, (Optional if (Optional if using AA C-38 Structural ASTM D41 ENRGY 3, H-Shield, H-Shield CG or HA Min. 0.75-inch Fesco Board HA using AA Ply) Base) One or more BP- SBS-AA, SBS-TA, -290.0 concrete Multi -Max FA3 One or more AA or APP-TA APP TA BP AA (Optional if (Optional if using AA C 39 Structural ASTM D41 Min. 0.5-inch Structodek High Density HA None N/A using AA Ply) Base) One or more BP- SBS-AA, SBS-TA, 285.0 concrete Fiberboard Roof Insulation One or more APP TA AA or APP-TA BP -AA Min. 1.5-inch ACFoam II; ACFoam III, (Optional if. (Optional if using AA' Structural Min. 0.5-inch Structodek High using AA Ply) SBS-AA, SBS-TA, C-40 concrete ASTM D41 . ENRGY 3, H-Shield, H-Shield.CG or HA Density Fiberboard Roof Insulation HA One or more Base) One or more BP- APP=TA -480,0 Multi -Max FA3 AA or APP-TA BP -AA Exterior Research and Design, I.I.C. d/b/a Trinity I ERD Evaluation Report A42970.10.12-R2 for FL16027-R2 Certificate of Authorization #9503 GT" EDITION (2017) FBC NON-HVH2 EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 13 of 26 . ; TRINITY' ERID :• :. WC Cf tFAiiSCfIF} CpNe»�iETE DEC�fS NE 0N5TRQ IqN DFt RE(�pOti t SyTEM 8b ]:1 gtlNLlffp INS4fLAr1ON, BODED R6tltK!~11�gj - ,' R VAPPR $ ER BARRIUpTIQt�S EQ NOTE 16;Fo a System Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) No. Deck Primer Type Attach ' Type Attach Base Ply Ply Cap Pi (psi) Structural ' Min 1.5 Inch ACFoam ]I,' ACFoam III, (optlonal if .' using AA Ply) (Optional If using AA SBS-AA, SBS-TA, C-41 ASTM D41 ENR6Y 3, H=Shield, H=Shield CG or HA Min. 0'.25-Inch Dens Deck Prime HA One or more 138se) One or more BP- APP-TA -480.0 concrete Multi -Max FA3 BP AA AA or APP•TA (Optional if (Optional if using AA C-42 Structural ASTM D41 Min. 0.25-inch Dens Deck Prime HA None N/A using AA Ply) Base) One or more BP- SBS-AA, SBS-TA, APP TA 510.0 concrete. One or more AA or APP-TA BP -AA 7 6 bd pE C}Q� (CEyif Ce p{ a '' s TAB �i3B' tS UG1 E!.pA! 6kopi46.'ECKS NEW Gb S[TppWf;4,1 BoiVngd sAsrF `sNt;�T, Roof Cover (Note 1s) IVIDP System No. Deck Primer (psf) Base Ply Ply Cap Ply C-43 Structural concrete ASTM D41 S.BS-SA (Optional) SBS-SA or APP-TA SBS-SA, APP-SA, SBS-TA or APP-TA -315.0 C-44 Structural concrete ASTM D41 BP -AA (Optional If using asphalt applied Ply) (Optional if using asphalt applied -Base) BP -AA or APP-TA SBS-AA, SBS-TA, APP-TA -622.5 Werlor Research and Design, I.I.C. d/b/a Trinity-JERD Evaluation Report A42970.10.12-R2 for FL16027-RZ Certificate of Authorization 49503 GTn EDITION (2017)• FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 14 of 26 TRINI71�IERD t CDTIGNdR'�t�ifO�IF'(1'FAROFFj 1'ABf:E4A;LIGHSTTWh�1I7GYNPTECC+,1NC,'BR(ETE�ECKiV�1AfCON$TN[iG��A _. ,., ... � System Deck Llghtwelght Base insulation Layer Coverboard , Roof Cover (Note'15) MDP Type - _-Attach Type Attach Base Ply Ply. _, Cap PlyEd No.- (Note 1) Concrete (Note 14) (psf) SELF �AbHE{i1N0SY8T�M5N(ITH gASEfN3UIJIT(OMF}NFid'PTIQNA6T_O,PINSULArtItl�{OF�TFiESAME.TYPE ....; ., ;. .- :.�, �3.% .n..,,... •• „ _3.. .. LWC-1 Structural Min, 200 psi, min 2- Min. 1.5-Inch, min. 2.6 pcf Insulfoam OB500 (Optional) Additional OB500 SBS-SA (Optional) One or SBS-SA, APP 120.0 concrete inch Elastizell.. layers of base insulation more SBS-SA SA (Optional) One or SBS-SA, APP LWC-2 Structural Min. 200 psi, min 2- Min. 1.5-inch ACFoam II, ENRGY 3, ISO 95+ GL 06500 (Optional) Additional OB500 SBS-SA more SBS-SA or SA, SBS-TA -225.0 concrete Inch Elastizell or H-Shield layers of base insulation APP-TA or APP-TA LWC-3 Structural Min. 200 psi, min. Min. 2.0 Insulfoam CR-20 (Optional) Additional CR-20 SBS-SA (Optional) One or SBS-SA, APP- =180.0 . concrete 2-inch Elastizel_I pcf layers of base insulation more SBS-SA SA Structurai min. Min. 1.5-inch ACFoam II, ACFoam III, ENRGY 3, {Optional) Additional (Optional) One or SBS-SA, APP- LWC_4 Min. 200 psi, 95+GL, H-Shield, H-ShieldMulti-Max_ _CR_20- _ -of -base CR-20 _ 5BS_SA more SBS,SA or. SA, SBS-TA- _ 180.0 _ APP-TA concrete _ 2 IncFf Elastizell _ FA3 _ nISO layers Insulation-- y or APP-TA Structural Min. 200 psi,'min. 0 tional Additional ( P ) CR-20 SBS-SA (Optional One or ) SBS-SA, APP- 222.5 LWC-5 concrete 2-Inch Celcore or Min. 2.0 pcf Insulfoam CR-20 layers of base insulation more SBS-SA SA Mearlcrete Min. 200 psi; min. Min. 1.5-inch ACFoam il, ACFoam III, ENRGY 3, (Optional) Additional (Optional) One or' SBS-SA, APP- Structural LWC-6 2-Inch Celcore or ISO 95+ GL, H-Shield, H-Shield CG, Multi -Max CR-20 layers of base insulation CR-20 SBS-SA more SBS-SA or SA, SBS-TA -222.5 concrete Mearlcrete FA3 APP-TA arAPP-TA SELF A4FjERING`SYSTfMS:WRH,�KSLIMSUTAT(Ot�A�t1gCOVER8QAH4t• fl � � (Optional) One or SBS-SA APP- LWC-7 Structural. Min. 200 psi, min 2- Min. 1.5-Inch, min. 2.0 pcf Insulfoam 08500 Min. 0.25-Inch SECUROCK OB500 SBS-SA more SBS-SA or SA, S85-TA 120.0 concrete inch Elastizell Gypsum -Fiber Roof Board APP-TA or APP TA ne or SBS-SA, APP- Structural Min. 200 psi, min 2- Min. 1.5-inch ACFoam il, ENRGY 3, ISO 95+ GL OB500 Min. 0:25-inch SECUROCK OB500 SBS SA oreSS=S-S more B SA or SA, SBS TA 225.0 LW.C-8 concrete inch Elastizell or H-Shleld Gypsum -Fiber Roof Board APP-TA or APP-TA Structural MIn..200 Psi,.min.. Min.1.5-Inch ACFoam ll, ACFoam III, ENRGY 3, ISO 95+GL, H-Shield, H-Shield CG, Multi -Max Cit-20 Min 0.25-inch'SECUROCK CR-20 SBS-SA (Optional) One or, more SBS-SA or SBS-SA; APP- SA, 565-TA -180.0 LWC-9 concrete 2-inch Elastizell FA3 or min, 2.0 pcf Insulfoam Gypsum -Fiber Roof Board APP-TA or ARp-TA Min. 200 psl, min. MIh.1:5-Inch ACFoam ll, ACFoam III, ENRGY 3 . Min. 0,25-inch SECUROCK (Optional),,One or SBS=SA, APP- LWC-10 Structural 2-inch Celcore or ISO 95+ GL, H-Shield, H-Shield CG, Muitl-Max 'CR-20 o f Boar Gypsum Fiber Roof CR-20 SBS-SA more SBS=SA or SA, SBS-TA -222.5 concrete Mearlcrete FA3 or min 2.0 pcf Insulfoam AP A p� orA Pp TA • ,. ......,.. � � r s a,..s.: :sr � y{1 vrT ySBS `�Y < (Optional) One oir Structural. ,Min, 200 psi, min .2- Min LS-inch.ACFoam II, ENRGY 3 ISO'95+ GL OB500 Min 0:25-Inch SECUROCK OB500 BP -AA 'more BP; AA or APP- AA SBS- 225,0 LWC-11,•: ,' cohcrefe : , . inch Elastizeli or H-Shield Gypsum -Fiber Roof Board APP-TA TA 1A, APP-TA Min.1.5=fich ACFoam II, ACFoam lll,'ENRGY 3, . _ Min 0.25=Inch SECUROCK - BP -AA, (Optlona.l) One or SBS-AA, SBS- L1NC 12 Structural Min. 200 psi, min. ISO 95+GL, H-Shleld, H-Shield CG,.Multl-Max CR 20 Gypsum -Fiber Roof Board CR-20 APP-TA More BP -AA or APP TA, APP-TA 180.0 concrete 2-Inch Elastizell FA3 or min. 2.0 pcf Insulfoam TA Exterior Research and DesignJI.C, d/b/a. Trinity l ERD Evaluation Report A42970.10.12-R2 for FLt.6027-RZ Certificate of Authorization'09503 GM EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by, Robert Nieminen, PE-59166 TRI-BUILT Modlfied:.Biturnen Roof Systems; (800) 516-1485 Appendix 1, Page 15 of 26 t� Y` fk�t ..J TRINITY 1 ERD TABLE 4A ,LIGHTWEIGHT CONCRETE PECKS NEW CQNSTRUCTION oR�REROOF (TSAR OFsj';, "' SYST�IV!'fyPEA 1 P!PNI ED RsUL'ATICit�,BOND�b'ttO0FCE7 ER System Deck Lightweight Base Insulation.Layer Coverboard . Roof Cover (Note 15) No. (Note 1) Concrete (Note 14) Type Attach Type Attach Base Ply Ply MDP Cap Ply (psf) Structural Min. 200 psi, min. Min. 1.5-inch ACFoam II, ACFoam III, ENRGY 3, (Optional) One or LWC-13 concrete 2-inch Ceicore or 150 95+ GL, H-Shield, H-Shield CG; Multi -Max CR-20 Min. 0.25-inch SECUROCK CR-20 BP -AA, re BP -AA or APP SBS-AA, SBS- 2 22.5 Mearlcrete FA3 or min. 2.0 pcf Insulfoam Gypsum -Fiber Roof Board APP TA TA TA, APP-TA T LE48 LIGHTVVEIGHTCON�RETEUECKS N UIlGONSTRUC[IONd n ON RUC ERR O>4Fj 'r ; Sys'f�nrtTyp�q 2_ yz �MECHANiC1iLLV �lT ACHED ANCWCIR $iiEfT,�#Q IREb (NSAN;f�kyi t 3EQ RQOF CODER' >u.... ,_ . System Deck Lightweight Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) No. Concrete MDP (Note 1) (Note 14) Type Fasteners Attach Type Attach Type Attach Base Ply Ply Cap Ply (psf) Min.1.5-inch Min. 22 ga., 7-inch o.c. at (Optional) Min. The�maroof Composite, p Type B, Min. 300 psi 4-inch lap and 1.5-inch Polytherm Composite or (Optional if LWC-14 vented steel Approved GAFGLAS OMG CR 7-inch o.c. in ACFoam II, H- HA min. 0.5-inch Structodek (Optional if using AA Base) SBS-AA, SBS- at max. 5 ft cellular LWC #75 BSF two, equally Shield, Multi- High Density Fiberboard g y HA using AA Ply) One or more TA, APP-TA -45.0 spans spaced center Max FA3 or Roof Insulation or min. BP -AA BP -AA or APP- rows Polythene 0.75-inch FescoBoard TA (homogeneous) Min, 22 ga., 7-inch o_c. at Min. 1.5-inch LWC-15 Type B, vented steel Min. 300 psi Approved GAFGLAS CMG CR 4-inch lap and 7-inch o.c. in ACFoam I1, H- (Optional) One SIRS -SA, APP- at max. 5 ft cellular LWC #75 BSF two, tequally Shield, Multi- HA None N/A SBS-SA or more SBS-SA SA, SBS-TA -45.0 spaced center Max FA3 or or APP-TA or APP-TA spans p Pl otherm y rows Exterior Research and Design, LLC. d/b/a Trinity IERD Certificate of Authorization 49503 Prepared by: Robert Nieminen, PE-59166 6r" EDITION (2017) FBC NON-HVHZ EVALUATION TRI-BUILT Modified Bitumen Roof Systems; (900) 516-1485 Evaluation Report A42970.10.12-R2 for FL16027-R2 Revision 2: 09/25/2017 Appendix 1, Page 16 of 26 TRIM 1 Y `ERD TABLE AC L16HTWEIGHT C(iNCRfTE QECKS IVW CONSTRUCTION oR itER00F (TSAR OFF► SYSTEM TYF�E E' IiIlEC41ANICALLY ATTACHEC3 BASE 54EE f, BONfJE1�RE)E1F CCi1lER _... ,.. .... r......,. System Deck Base Sheet (Note A below) Roof Cover (Note 15) Type No. (Note 1) Lightweight Concrete (Note 14) MDP (Note A). Fasteners Attach Base Ply Cap Ply (psf) GENERIC CELLtlIAR.LiGIiTWE1GHTINS6. N'GCQNCREjE, j Min. 300 psi, min. 2-inch thick cellular Min. 22 ga., type B steel LWC. Note: To qualify the. LWIC under this 7-inch o.c. in a 3-inch lap and 7-inch o.c. in (Optional) LWC-16 at max 5 ft spans or assembly, an OMG CR BPF shall achieve B3 OMG CR BPF two, equally spaced, staggered rows in the One or more SBSB S-AA, APP- -45.0 structural concrete an average withdrawal of53 lbf when field of the sheet BP -AA TA tested per TAS 105 or ANSI/SPRI FX-1 CEi CORE CELLULAR k LIGNT1N61G11T INSULATING COfCRE CE } Min. 0.0179-inch Tensilform S-75 or min. 8-inch o.c. in a 3-inch lap and 16-inch o.c. in -LWC=17--- -0:0205=inch Tensilfo'rm --- -Min 200 psi; min: 2=inch thick-Celcore -g1-gr, 5g or B7 IrufastFM=90_or -One or -more-- SBS-AA -37.5 two, equally spaced, staggered rows in the 75 at max. 5 ft spans or OMG CR BPF field of the sheet BP -AA structural concrete Min. 22 ga., type B steel Trufast FM-90 or 7-inch o.c. in a 3-inch lap and 7-inch o.c. in One or more LWC-18 at max 5 ft spans or Min. 200 psi, min. 2-inch thick Celcore Bi through B12 two, equally spaced, staggered rows in the SBS-AA -45.0 structural concrete OMG CR BPF field of the sheet BP AA Min. 26 ga., type HF B1, B2, B3, B4, 9-inch o.c. in a 3-inch lap and 9-inch o.c, in LWC 19 steel at max 5 it spans Min. 225 psi, min. 2-inch thick Celcore MF B7, B8, B10, B11 OMG CR BPF two, equally spaced, staggered rows in the One or more SB5-AA -45.0 or structural concrete or B12 field of the sheet BP AA Min. 22 ga., type B steel BI, B2, B3, B4, 7-inch o.c. in a 3-inch lap and 14-inch o.c. in LWC-20 at max 6 ft spans or Min. 225 psi, min. 2-inch thick Celcore MF B7, B8, B10, 611 OMG CR BPF two, equally spaced, staggered rows in the One or more SBS-AA -45.0 structural concrete or B12 field of the sheet BP AA Min. 22 ga., type B steel B1, B2, B3, B4, 9-inch o.c. in a 3-inch lap and 9-Inch o.c, in LWC-21 at max 6 ft spans or Min. 225 psi, min. 2-Inch thick Celcore MF B7, B8, B10, B11 OMG CR BPF two, equally spaced, staggered rows in the One or more SBS-AA -45.0 structural concrete or B12 field of the sheet BP AA Min. 22 ga., type B steel Trufast Twin Loc- 9-inch o.c. in a 4-Inch lap and 18-inch o.c. in One or more SBS-AA, SBS- LWC-22 at max 5 ft spans or Min. 225 psi, min. 2-inch thick Celcore MF Bl or B2 two, equally spaced, staggered rows in the BP -AA or APP- -45.0 structural concrete Nail field of the sheet TA TA or APP-TA Min. 22 ga., type B steel 82 (with poly- Trufast Twin Loc- 9-inch o.c. in a 4-inch lap and 18-inch o.c. in One or more SBS-SA, APP- LWC-23 at max 5 ft spans or Min. 225 psi, min. 2-Inch thick Celcore MF film top surface) Nail two, equally spaced, staggered rows in the SBS-SA or SA, SBS-TA -45.0 structural concrete field of the sheet APP-TA or APP-TA Min. 22 ga., type B steel LWC-24 at max 5 ft spans or Min. 300 psi, min. 2-inch thick Celcore MF B2 Trufast FM-90 8-inch o.c. in a 4-inch lap and 8-Inch o.c. in BP -AA or APP- SBS AASBS , -60.0 structural concrete three equally spaced, staggered center rows TA TA or APP-TA Min. 22 ga., type B steel B2 (with poly- 8-inch o.c. In a 4-inch lap and 8-inch o.c, in One or more SBS-SA,'APP- LWC-25 at max 5 ft spans or Min, 300 psi, min. 2-inch thick Celcore MF Trufast FM-90 SBS-SA or SA, SBS-TA -60.0 structural concrete film top surface) three equally spaced, staggered center rows APP-TA or APP-TA Exterior Research and Design, I.I.C. d/b/a Trinity(ERD Certificate of Authorization #9503 Prepared by: Robert Nieminen, PE-59166 6T" EDITION (2017) FBC NON-HVH2 EVALUATION TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Evaluation Report A42970.10.12-R2 for FL16027-RZ Revision 2: 09/25/2017 Appendix 1, Page 17 of 26 TRINITY = ERD TA • , , BLE4C LIGWTWEIGHT CONCRETE DECKS :NEW CONS'[RUCTIQN oR REROOF TEAR OFF} 5YSTENI TYpE E;: ME 'HANICALLY`ATTA"' ' I BASE HEFT, BAND 11g00 coVER System 'Deck Base Sheet (Note A below) Roof Cover (Note 15) Type No. (Note 1) Lightweight Concrete (Note 14) MDP (Note A) Fasteners Attach Base Ply Cap Ply (Psf) Min.•22 ga., type B steel Trufast FM-40 -7-inch o.c. in a 3-inch lap and 7-inch o.c. in LWC-26 at max 5 ft spans or Min. 300 psi, min. 2-inch thick Celcore BS through B12 or two; equally spaced, staggered rows in the One or more SBS-AA -75.0 structural concrete OMG CR BPF field of the sheet BP -AA Min. 22 ga., type B steel LWC-27 at max 5 ft spans or Min. 300 psi, min. 2-Inch thick Celcore MF Polyglass Trufast FM-260 10-inch o.c. in a 4-inch lap and 10-inch o.c. in (Optional) BP- SBS-AA, SBS- structural concrete Elastobase Poly Y three equally spiced, staggered q Y P center rows AA or APP-TA TA, APP-TA -90.0 EtasrtzELLGetIULARLIGN7WEIGFiTINSUlATiNGCONCR�TE .77 4... Min. 0.0179-inch Tensilform S-75 or min. Min. 200 psi, min. 2-inch thick Elastizell Trufast FM-90 or 7.5-inch o.c. in a 3-inch lap and 7.5-inch o.c. One or more LWC-28 ---- 0.0205-Inch Tensilform -Range II-- - _ _ _ _ _B1-throu h.B12—_ g -- OMG CR BPFggered —in-two,-equally-spaced, sta rowsin the— BP=AA or APP= SBS=AA,.SBS- -_ _ _ 30.0 75 at max. 5 ft spans or field of the sheet TA TA or APP-TA structural concrete Min. 0.0179-inch Tensilform S-75 or min. Min. 200 psi, min. 2-inch thick Elastizell B2 (with poly- Trufast FM-90 or 7.5-inch o.c. in a 3-inch lap and 7.5-inch o.c. One or more SBS-SA, APP- LWC-29 0.0205-inch Tensilform Range II film top surface) OMG CR BPF in two, equally spaced, staggered rows in the SBS-SA or SA, SBS-TA -30.0 75 at max. 5 ft spans or field of the sheet APP-TA or APP-TA structural concrete LWC-30 Min. 22 ga., type B steel at max 5 ft s spans or Min. 200 psi, min. 2-Inch thick Elastizell Trufast FM-90 or 7-inch o.c. in a 3-inch lap and 7-inch o.c. in r One omore SBS-AA, SBS- P Range II Bl through B12 OMG CR BPF two, equally spaced, staggered rows in the BP -AA or APP- -45.0 structural concrete field of the sheet TA TA or APP-TA Min. 22 ga., type B steel Min. 200 psi, min. 2-inch thick Elastizell B2 (with poly- Trufast FM-90 or 7-inch o.c. In a 3-inch lap and 7-inch o.c. in One or more SBS-SA, APP- LWC-31 at max 5 ft spans or Range II g film top surface) OMG CR BPF two, equally spaced, staggered rows in the SBS-SA or SA, SBS-TA -45.0 structural concrete field of the sheet APP-TA or APP-TA Min. 22 a., e B steel g type Min. 350 psi, min. 2-Inch thick Elastizell with Zell -Crete Fibers, supple -mentally Trufast Twin Loc- 6-inch o.c. In a 4-inch lap and 6-inch o.c. in SBS-AA, SBS- LWC-32 at max 5 ft spans or P attached with Roofgrip #21 and 3-inch B2 Nails (min. 1.8- three, equally spaced, staggered rows in the One or more TA, SBS-SA, -60.0 structural concrete plates at 1 per 8 ft2 inch) field of the sheet BP -AA APP-TA or APP-SA Min. 22 a., type B steel Min. 350 psi, min. 2-inch thick Elastizell g with Zell -Crete Fibers, supple -mentally B2 (with poly- Trufast Twin Loc- 6-inch o.c. in a 4-inch lap and 6-inch o.c. in SBS-SA, APP- LWC-33 at max 5 ft spans or P attached with Roofgrip #21 and 3-Inch film top surface) Nails (min. 1.8- three, equally spaced, staggered rows In the SBS-SA or SA, SBS-TA -60.0 structural concrete plates at 1 per 8 ft2 inch) field of the sheet APP-TA or APP-TA MFARLCREr�k'ftLfjLA IIGHTWEIGfITIfVSUU1TIFIGCONCRETE :`• `Y' r. Min. 24 ga., type B steel Trufast FM-90 7.5-inch o.c. in a 3-inch lap and 10-inch o,c. LWC-34 at max 5 ft spans or Mln. 200 psi, min. 2-inch thick Mearlcrete 81 through B12 or _ in two, equally spaced, staggered rows In the One or more SBS-AA 30.0 structural concrete OMG CR BPF field ofthe sheet BP -AA Exterior Research and Design, LLC. d/b/a Trinity IERD Certificate of Authorization #9503 Prepared by: Robert Nleminen, PE-59166 6M EDITION (2017) FBC NON-HVHZ EVALUATION TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Evaluation Report A42970.10.12-112 for FL16027-RZ Revision 2: 09/25/2017 Appendix 1, Page 18 of 26 TRINITYERa TABLE AC LIGHTWEIGN TO ONCRETE DECKS NEW CONSTRUCTION oR REROOF (TEaa OFF):. -S'iST M TYpE E MECHANICALLY`ATTACFIEC� BASS Sf�EE C, BONbED R00f�C01lER T;• R System Deck Base Sheet (Note A below) Roof Cover (Note 15) Type No. (Note 1) Lightweight Concrete (Note 14) MD (Note A) Fasteners Attach Base Ply Cap Ply (psf) Min. 22 ga,, type B steel Trufast FM-90 7-inch o.c. in a 4-inch lap and 7-inch o.c. in One or more LWC-35 at max 5 ft spans or Min. 300 psi, min. 2-inch thick Mearlcrete B1, 82 or B12 or two, equally spaced, staggered rows in the BP -AA or APP- SBS-AA, SBS- -45.0 structural concrete OMG CR BPF field of the sheet TA TA or APP-TA LWC-36 Min. 22 ga., type B steel at max 5 ft spans or P Min. 300 psi, min. 2-inch thick Mearlcrete P B2 (with poly- Trufast FM-90 or 7-inch o.c. in a 4-inch lap and 7-inch o.c. in two, equally spaced, staggered rows in the One or more SBS SA SBS-SA, APP- structural concrete film top surface) OMG CR BPF field of the sheet or APP-TA SA, SBS-TA or APP-TA 45.0 Min. 22 ga., type B steel B3, 82, B3, 87 or Trufast FM-90 or 7-inch o.c. in a 4-inch lap and 7-inch o.c. in One"or more LWC-37 at max 5 ft spans or P Min. 300 psi, min. 2-inch thick Mearlcrete P 611 two, equally spaced, staggered rows in the BP -AA or APP- SBS-r A, SBS- -52.5 structural concrete OMG CR BPF field of the sheet TA TA or APP-TA LWC-38 - - Min. 22 ga., type B steel -at-max 5-ft s ans or P _ _ -Min. 300 si, min. 2-inch thick Mearlcrete P 32 (with poly--- — -Trufa3t FM=90 or — _7-inch-o.c_ina-4-inch-lap and-7-inch o:c. in-- two, equally spaced, staggered rows in the One -or more- SBS-SA or -SBS=SA, APPT SA, SBS-TA structural concrete film top surface) OMG CR BPF field of the sheet APP-TA or APP-TA -52.5 A. Base Sheets options are coded as follows: Bl: Polyglass G2 Base; 132: Polyglass Elastobase or Polyglass Elastobase Poly; 83: GAFGLAS #75; 84: GAFGLAS Stratavent Noilable Venting Base Sheet; 65: GAFGLAS Ply 4; 66: GAFGLAS FlexPly 6; B7: JM Perma Ply No. 28; 138: JM Vensulation; B9: JM GlasPly IV; B10: JM GlasPly Premier, B11: Tamko Glass -Base; B12: Tamko Vapor -Chan Exterior Research and Design, LLC. d/b/a Trinity I ERD Evaluation Report A42970.10.12-R2 for FL16027-R2 Certificate of Authorization #9503 6'" EDITION (2017) FBC NON-HVH2 EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 19 of 26 TRINITY f ERD c !AkE& CEMENTITIOUSWOOfjFIBE(tbECK5 .NEW,GONSTRUCTfONQtt;REROOF(TEAROFF) SYSTEM TYPE &I BONOEa INSiJLAfION, t 0NDE6ROOF Cb1iER ' System Deck Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP No. (Note 1) Type. Attach Type Attach Base Ply Ply Cap Ply (psf) Min. 1.5-inch ACFoam II, "Min. 0.25-inch Dens Deck, Dens Deck Prime, CWF-1 Min. 2.5-inch Tectum ISO ld, D-IS or SECUROCK Gypsum -Fiber Roof Board or min. 0.5- D-IS or (Optional) One or 585-AA, SBS-TA, Plank or Tectum LS Plank therm, ENRG Polytherm, ENRGY-3 OB500 inch Structodek High Density Fiberboard Roof OB500 BP -AA more BP -AA or APP- APP TA -45.0 Insulation CWF-2 Min. 2.5-inch Tectum Min. 1.5-inch ACFoam II, ISO 95+GL, H-Shield, D-IS or Min. 0.25-inch Dens Deck, Dens Deck Prime, D-IS.or SBS-SA or (Optional) One or SBS-TA, SBS-SA; Plank or Tectum LS Plank Polytherm, ENRGY-3 OB500 SECUROCK Gypsum -Fiber Roof Board OB500 APP-TA more SBS-SA or APp_TA, APP-SA -45.0 APP-TA Min. 2.5-inch Tectum Min. 1.5-inch ACFoam 11, Min. 0.25-inch Dens Deck, Dens Deck Prime, (Optional) One or CWF-3 Plank or Tectum LS Plank ISO CR-20 SECUROCK Gypsum -Fiber Roof Board or min. 0.5- inch Structodek High Density Fiberboard Roof CR-20 BP -AA more BP -AA or APP- SBS-AA, SBS-TA, 52.5 therm, ENRGH-Shl-3 Polytherm, ENRGY3 TA APP TA Insulation -_------_------ _-- _-- --- - _ - - - CWF-4 — - --- - — Min. 2.5-inch Tectum Min.1.5-inch ACFoamll, ISO 95+GL, H-Shield, CR-20 Min. 0.25-inch Dens Deck, Dens Deck Prime, SBS-SA or (Optional) One or SBS-TA, SBS-SA, Plank or Tectum LS Plank Polytherm, ENRGY-3 SECUROCK Gypsum -Fiber Roof Board CR-20 APP-TA more SBS-SA or gpp_TA, APP=SA 5I APP-TA Exterior Research and Design, I.I.C. d/b/a Trinity)ERD Certificate of Authorization 49503 Prepared by: Robert Nieminen, PE-59166 6'" EDITION (2017) FBC NON-HVHZ EVALUATION TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Evaluation Report A42970.10.12-R2 for FL16027-RZ Revision 2: 09/25/2017 Appendix 1, Page, 20 of 26 @ ERA TRINITY TABLE`$B CEMENTITIOUS WOOD FI¢ER DECKS NEW EONSTRUCLION oR REROOF(teAR OFF); SYSTEMTYP6A 2 MEGWANICAf LY`ATTA CHED ANC14! SHEET, BONDED If�SU(AjION�i30ND6D ROCrFCOVER .. ,. System Deck Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP No. (Note 1) Type Fastener Attach Type Attach Type Attach Base Ply Ply' Cap Ply (PA Min. 0.25-inch Dens Deck, Dens Min. 2.5-inch Polyglass 9-inch o.c. in 4-inch Min. 1.5-inch ACFoam II, ACFoam Deck Prime, SECUROCK Gypsum (Optional) Elastobase, Trufast lap and 12-Inch o.c. Fiber Roof Board, Min. 0.75-inch SBS-AA, CWF-5 Tectum Plank Polyglass Inuldek in two, equally III, H- HA FescoBoard (homogeneous) or HA BP -AA One A more SBS-TA, -30.0* or Tectum LS Elastobase Poly, Loc-Nail spaced, staggered ShieIS0ld, ENGL, Shield, ENRGY 3, min. 0.5 fnch Structodek High BP -AA or APP TA Plank Polytherm or Multi- APP TA Polyglass G2 Base center rows Density Fiberboard Roof Max FA3 Insulation Polyglass 9-Inch o.c. in 4-inch Min. 1.5-Inch Min. 2.5-inch Elastobase, Trufast lap and 12-inch o.c. , ACFoam 11ACFoam Min. 0.25-inch Dens Deck, Dens SBS-SA (Optional) SBS-TA, CWF-6 Tectum Plank Polyglass Inuldek in two, equally III, 1S095+GL, H- HA Deck Prime, SECUROCK Gypsum- HA or APP- One or more SBS-SA, -30.0* or Tectum LS Elastobase.Poly,- Loc_Nail_.___spaced, staggered —_ ShieldENRGY 3 , , _ _ __— _Fiber Roofeoard---- --- TA ---------- SBS-SA or ------- APP-TA, - - - - - Plank- -- __ Polyglass G2 Base center rows Polytherm or Multi- APP-TA APP-SA Max FA3 Min. 0.25-inch Dens Deck, Dens Min. 2.5-inch Polyglass 9-inch o.c. in 4-inch Min. 1.5-inch ACFoam II, ACFoam Deck Prime, SECUROCK Gypsum - (Optional) Elastobase, Trufast lap and 18-Inch o.c. Fiber Roof Board, Min. 0.75-inch SBS-AA, CWF-7 Tectum Plank Polyglass Twin in two, equally III, H-, HA FescoBoard (homogeneous) or HA BP -AA One more SBS-TA, -45.0* or Tectum LS Elastobase Poly, Loc-Nail spaced, staggered , ENRGY 3GL, Shield, min. 0.5-Inch Structodek High BP -AAA or APP-TA Plank Polyglass G2 Base center rows Polytherm or Multi- Density Fiberboard Roof APP-TA Max FA3 Insulation Polyglass 9-inch o.c. in 4-inch Min. 1.5-inch Min. 2.5-inch Elastobase, Trufast lap and 18-inch o.c. , ACFoam 11ACFoam Min. 0.25-inch Dens Deck, Dens SBS-SA (Optional) SBS-TA, CWF-8 Tectum Plank Polyglass Twin in two, equally III, 15095+GL, H HA Deck Prime, SECUROCK Gypsum- HA or APP- One or more SBS-SA, -45.0* or Tectum LS Shield ENRGY 3, SBS-SA or APP-TA, Plank Elastobase Poly, Loc-Nail spaced, staggered Polytherm or Multi- Fiber Roof Board TA APP-TA APP-SA Polyglass G2 Base center rows Max FA3 Exterior Research and Design, LLC. d/b/a Trinity IERD I Evaluation Report A42970.10.12-R2for FL16027-R2 Certificate of Authorization k9503 6Tri EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2; 09/25/2017 Prepared by; Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 21 of 26 k TRINITY ERD 1ABLE SC .CEMENTITIOUSWOOdFlBER DECKS NEW CbNSTRUCTION REROOF, �TPAtt QFF) oR RECOVER - SYSTEM TYPE B:r BASE_(NSUEAj ION BOfUCtEb Tap INSUTAT(ON` BOND:E17 006 < ;MECHANICALLY-ATTAGWED !_........, .,_... t. - _ �. COVER ti.. System Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP No. Type Fasteners Attach Type ttach Base Ply Ply Cap Ply (psf) Min. 2.5-inch Min. 2-inch H- OMG Polymer GypTec Plate Min. 0.5-inch Structodek fHA (Optional if using AA SBS-AA, CWF-9 m TectuPlank or Shield or with Polymer GypTec or TruFast 1 per 4 ft2 High Density Fiberboard (Optional if using Base) One or more BP -AA SBS-TA, -45.0* Tectum LS Plank Polytherm TL 3 in. Plate with TL Fastener Roof Insulation AA Ply) BP -AA or APP-TA APP-TA t . .. :` TP(BL 5D 'GEMENfi111dU5Ir000D 1,110ER6E KS , NIEW OiVSTRUCT)bN :RERbE7F TEAR Os R V T :; r MECHAf�iCAMYtON; BONdE6 System Deck (Note 1) Base Insulation Layer Top Insulation Layer Roof Cover (Note 15). MDP ,Y Type Fasteners Attach Base Ply Ply Cap Ply No. (psf) Min. 2.5-inch (Optional) One or Min. 0.25-inch Dens Deck, Dens Deck Prime WF-10-- Tectum Plank -or- molayers, any re orSECUROCK Gypsum -Fiber Roof_Board-or Trufast Twin-Loc-Nails— -2--(Optional-if-using-- (Optional if using AA SBS=All, -- Tectum LS Plank combination, loose min. 0.5-inch Structodek Hi h High y (min. 1-inch embedment) 1 per 2 ft AA Ply) BP -AA Base) One or more BP -AA SBS-TA, -45.0* laid Fiberboard Roof Insulation or APP-TA APP-TA ' TABLE 5E CEMENTITVIf 1OUS OQD FIBER,4ECK5; ;VIEW Co , STRUGTIOQR,REROOF TEAR OfE SYSf EM;� YPE E'; N N�( IS I fATt D, M CWdh)I�AL�;Y AT'f EiED BRVSE-S IEET SONOEd aC OP G(1VE 'u 1 System Deck (Note 1) Base Sheet Roof Cover (Note 15) MDP Base Fasteners Attach Base Ply Cap Ply No. (psf) CWF-11 Min. 2.5-inch Tectum Plank Polyglass Elastobase, Polyglass Elastobase Trufast Inuldek 9-inch o.c. in 4-Inch lap and 12-Inch o.c. in two, (Optional) One or SBS-AA, SBS-TA, or Tectum LS Plank Poly, Polyglass G2 Base Loc-Nail equally spaced, staggered center rows more BP -AA or APP-TA APP-TA -30.0* CWF-12 Min. 2.5-inch Tectum Plank Polyglass Elastobase, Polyglass Elastobase Trufast Twin Loc- 9-Inch o.c. in 4-Inch lap and 18-Inch o.c. in two, (Optional) One or SBS-AA, SBS-TA, or Tectum LS Plank Poly, Polyglass G2 Base Nails equally spaced, staggered center rows more BP -AA or APP-TA APP-TA 45,0* Exterior Research and Design, I.I.C. d/b/a Trinity (ERD Evaluation Report A42970.10.12-R2 for FL16027-R2 Certificate of Authorization k9503 6M EDITION (2017) FBC NON-HVH2 EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 22 of 26 r t TRINTY ERD >`TABLE 6A GYPSUM DECKS REROAF (TEAR=QFF� _ - ;. SYSTEM;TVPEA 1 gdNbED INSULATIdN, BdNDED RdOFCOVER System Deck (Notes 1 & 12) Base Insulation Layer Top Insulation Layer Roof Cover Note 15 Type Attach Type Attach Base Ply Ply Cap Ply No. (psf) G-1 Existing, sound poured gypsum Min. 2.0 pcf, Insulfoam OB500 (Optional) additional layers(s) of base OB500 SBS-SA (Optional) One SBS-$A, APP-SA -112.5 or gypsum plank deck insulation or more SBS-SA G-2 Existing, sound poured gypsum' Min. 1.5-inch ACFoam 11, ENRGY 3 or (Optional) additional layers(s) of base (Optional) One SB5-SA, APP-SA, or gypsum plank deck H-Shield OB500 insulation 08500 SBS-SA or more SBS-SA SB5-TA or APP-TA -112.5 or APP-TA G-3 Existing, sound poured gypsum Min. 1.5-inch ACFoam 11 ENRGY 3 or Min. 0.25-inch SECUROCK Gypsum- (Optional) One SBS-SA, APP-SA, or gypsum lank deck p H-Shield or min. 2.0 pcf, Insulfoam p OB500 Fiber Roof Board OB500 SB5-SA or more SBS SA SB5-TA or APP-TA 112.5 or APP-TA G-4 Existing, sound poured gypsum Min. 1.5-inch ACFoam 11, ENRGY 3, (Optional) additional layers(s) of base (Optional) One SBS-SA, APP-SA, or gypsum plank deck H-Shield or Multi -Max FA3 M-OSFA insulation and/or min. 0.25-Inch M-OSFA SBS-SA or more SBS-SA SB5-TA or APP-TA -202.5 _ SECUROCK Gypsum -Fiber Roof Bo.ard__ _ _ ------or-APP-TA - ---- -- G 5 Existing, sound poured gypsum or deck Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers of base CR-20 SBS-SA (Optional) One SBS-SA, APP-SA 240.0 gypsum plank insulation or more SBS-SA G-6 Existing, sound poured g p gypsum or gypsum lank deck Min. 1.5-inch, min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum- CR-20 SBS-SA (Optional) One or more SBS-SA SBS-SA, APP-SA, -240.0 P Fiber Roof Board SBS-TA or APP-TA or APP-TA Min. 0.25-inch Dens Deck, Dens (Optional (Optional if using G 7 Existing, sound poured gypsum Deck Prime or SECUROCK Gypsum- CR-20 None N/A if using AA Base) One or SB5-AA, SBS-TA, or sum lank deck gyp p Fiber Roof Board AA Ply) more BP -AA or APP-TA -245.0 BP -AA APP-TA Existing, sound poured gypsum Min. 1.5-inch ACFoam II, ACFoam III, (Optional) additional layers(s) of base (Optional) One G-8 or gypsum plank deck ENRGY 3, H-Shield, H-Shield CG or CR-20 insulation and/or min. 0.25-inch CR-20 SBS-SA or more SBS-SA SBS-SA, APP-SA, -257.5 Multi -Max FA3 SECUROCK Gypsum -Fiber Roof Board or APP-TA SBS-TA or APP-TA Exterior Research and Design, I.I.C. d/b/a Trinity IERD Certificate of Authorization #9503 Prepared by: Robert Nleminen, PE-59166 GM EDITION (2017) FBC NON-HVHZ EVALUATION TRI-BUILT Modified Bitumen Roof Systems; (800) 516-149S Evaluation Report A42970.10.12-R2 for FL36027-112 Revision 2: 09/25/2017 Appendix 1, Page 23 of 26 TRINITY ERD V,TABLE 66 GYPSUM DECKS.466615, T y' EM PE" 01 D A-2 E, Anchor Sheet Base Insulation Top Insulation Roof Cover (Note 15) MDP System Deck No. (Note 1) -type Fasteners Attach -Type Attach Type Attach Base Ply Ply Cap Ply (psf) (Note 11) Min. 0.25-inch Dens Deck, Dens Polyglass 9-inch o.c. in 4-' Min. 1.5-inch Deck Prime, SECUROCK Gypsum- Existing, sound Trufast FM- Inch lap and 18- ACFoam 11, ACFoam (optional) Elastobase, Fiber Roof Board, Min. 0.75-inch SBS-AA, G-9 poured gypsum Polyglass 75 or FM- Inch o.c. in.two, III, IS095+GL, H- HA FescoBoard (homogeneous) or HA BP -AA One or more SBS-TA, -45.0* or gypsum Elastobase Poly, 90 or Twin equally spaced, Shield, ENRGY 3, min. 0.5-inch Structodek High BP -AA or APP-TA plank deck Polyglass G2 Base Loc-Nails staggered center Polytherm or Multi- Density Fiberboard Roof APP-TA rows Max FA3, Insulation EARVFF 011; Kt V.s. F. WK T "A System Base Insulation Top Insulation Layer Roof Cover (Note 15) MD_ No. Deck (Note 1) Layer (Psf) Type Fasteners (Note 11) Attach Base Ply Ply Cap Ply . Min. 0.25-inch Dens Deck, Dens Deck ) one or (Optional) Existing sound Prime or SECUROCK Gypsum -Fiber Trufast Twin Loc- (optional If G-10 poured gypsum or more layers, any Roof Board or min. 0.5-inch . Nails (min. 1-inch I. per 2 ft' using AA Ply) (optional if using AA Base) one SBS-AA, SBS- -45.0* combination, loose or more BP -AA or APP-TA TA, APP-TA gypsum plank deck Structodek High Density Fiberboard embedment) BP -AA laid Roof Insulation bidi Uk k(W 64 F x4 MI.' ­RT xx' System Base Sheet Roof Cover (Note 15) MD Deck (Note 1) No. Base Fasteners (Note 11) Attach Base Ply Cap Ply (psf) Existing sound poured Polyglass Elastobase, Polyglass Elaitobase Trufast FM-75 or FM _90jo, 9-inch h .c. in 4-inch lap and 18-inch o.c. in 9 (optional) One or more` SBS-AA, SBS-TA, G-11 gypsum or gypsum Poly, Polyglass G2 Base Twin Loc-Nails two, equally spaced, staggered center rows BP -AA or APP-TA APP-TA -45.0* plank deck Exterior Research and Design, I.I.C. d/b/a Trinity I ERD Evaluation Report A42970.10.12-R2 for FL16027-RZ Certificate of Authorization k9503 6T" EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 24 of 26 TRINITY . ERD TABLE 7At:`RECOVER?APPLICATI6NS _ • :,SYS TYKE A 4 ON, BONDEb F(60 CdUER TEM . - .. ;BONDEDINSUlATI System Substrate Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MID No. Type Attach Type Attach Base Ply Ply Cap Ply (psf) Existing (Optional) additional layers(s) of base (Optional) One or more SBS-SA, APP-SA, R-1 as haltic roof Min. 1.5-inch Multi -Max FA3 D-IS insulation and/or min. 0.2S-inch D-IS SBS-SA SBS-SA -67.5 p SECUROCK Gypsum -Fiber Roof Board or APP-TA SBS-TA or APP-TA R 2 Existing Min. 2.0 pcf Insulfoam D-IS (Optional) additional layers(s) of base D-IS SBS-SA (Optional) One or more SBS-SA, APP-SA -90.0 asphaltic roof insulation SBS-SA R-3 Existing Min. 1.5-inch ACFoam II or ENRGY 3 or min. Min. 0.25-inch SECUROCK Gypsum -Fiber (Optional) One or more SBS-SA, APP-SA, asphaltic roof 2.0 pcf Insulfoam D IS Roof Board D-IS SBS-SA SBS-SA or APP-TA SBS-TA or APP-TA 90.0 Existing (Optional) additional layers(s) of base (Optional) One or more SBS-SA, APP-SA, R-4 asphaltic roof Min. 1.5-inch ACFoam II or ENRGY 3 DAS insulation and/or min. 0.25-inch D-IS SBS-SA -90.0 SECUROCK Gypsum -Fiber. Roof Board 585-SA or APP-TA SBS-TA or APP-TA R-5 Existing Min. 1.5-inch, min. 2.0 pcf Insulfoam OB500 (Optional) additional layers of base OB500 SBS-SA (Optional) One or mare SBS-SA, APP-SA -120.0 asphaltic roof insulation SBS-SA R-6 Existing Min. 1.S-inch, min. 2.0 pcf Insulfoam OB500 Min. 0.25-inch SECUROCK Gypsum -Fiber OB500 SBS-SA (Optional) One or more SBS-SA, APP-SA, -120.0 asphaltic roof Roof Board SBS-SA or APP-TA SBS-TA or APP-TA R Existing Min. 1.5-inch ACFoam II, ENRGY 3 or H- (Optional) additional layers(s) of base (Optional) One or more SBS-SA, APP-SA, 7 asphaltic roof p Shield OB500 insulation and/or min. 0.25-inch OB500 SBS-SA SBS-SA or APP-TA SBS-TA or APP-TA -127.5 SECUROCK Gypsum -Fiber Roof Board Existing Min. 1.5-inch ACFoam II, ENRGY 3, H- M- (Optional) additional layers(s) of base M (Optional) One or more SBS-SA, APP-SA, R 8 asphaltic roof Shield or Multi -Max FA3 OSFA insulation and/or min. 0.25-inch OSFA SBS-SA SBS-SA or APP-TA SBS-TA or APP-TA -157.5 SECUROCK Gypsum -Fiber Roof Board R-9 Existing Min. 2.0 pcf Insulfoam CR-20 (Optional) additional layers(s) of base CR-20 SBS SA (Optional) One or more SBS-SA, APP-SA 240.0 asphaltic roof insulation SBS-SA R-10 Existing Min. 2.0 pcf Insulfoam CR-20 Min. 0.25-inch SECUROCK Gypsum -Fiber CR-20 SBS-SA (Optional) One or more SBS-SA, APP-SA, -240.0 asphaltic roof Roof Board SBS-SA or APP-TA SBS-TA or APP-TA Min. 1.5-inch Ultra -Max or Multi -Max FA-3, Existing min. 1.3-inch ACFoam III or min, 1.0-inch (Optional) additional layers(s) of base (Optional) One or more SBS-SA, APP-SA, R-11 asphaltic roof ISO 95+GL, H-Shleld, H-Shield CG or ENRGY CR-20 insulation and/or min. inch CR-20 SBS-SA SBS'-SA or APP-TA SBS-TA or APP-TA 240.0 3 SECUROCK Gypsum -Fiber Roof er0.Roof Board (Optional) additional layers(s) of base R-12 Existing Min. 2-inch ACFoam II, ENRGY-3 or H-Shleld CR-20 insulation and/or min. 0.25-inch CR-20 SBS-SA (Optional).One or more SBS-SA, APP-SA, -247.5 asphaltic roof SECUROCK<Gypsum-Fiber Roof Board SBS SA orAPP-TA SBS-FA or APP-TA Min. 0.25-inch Dens Deck, Dens Deck R-13 Existing Min. 1.5-inch Multi -Max FA3 D-IS Prime or SECUROCK Gypsum -Fiber Roof D-IS BP -AA SBS= (Optional) One or more SBS-AA, SBS-TA or 67,5 asphaltic roof Board SA, APP-TA BP -AA or APP-TA APP-TA Existing Min. 1.5-inch ACFoam II or ENRGY 3 or min. Min. 0.25-inch'Dens Deck, Dens Deck BP -AA SBS- (Optional), One or more SBS-AA, SBS-TA or R-14 asphaltic roof 2.0 pcf Insulfoam D-IS Prime or SECUROCK Gypsum -Fiber Roof D-IS SA, APP-TA BP -AA or APP-TA APP-TA g0:0 Board- - Exterior Research and Design, I.I.C. d/b/a Trinity IERD Evaluation Report A42970,10.12-R2 for FL16027-112 Certificate of Authorization 90503 6T" EDITION (2017) FBC NON-HVH2 EVALUATION Revision 2: 09/2S/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-1485 Appendix 1, Page 25 of 26 �r S { TRINITYRD TABLE 7A :RECOVERAPPL(CATIONS _. SYSTEMTYP v.BONDS.DINSULATION,#PNDEDR00FCO , System Substrate Base Insulation Layer Top Insulation Layer Roof Cover (Note 15) MDP No. Type Attach Type Attach Base Ply Ply Cap Ply (psf) R-15 Existing Min. 15-inch ACFoam II, ENRGY 3, H-Shield Min. 0.25-inch Dens Deck, Dens Deck BP -AA SBS- (Optional) One or more SBS-AA, SBS-TA or asphaltic roof or ISO 95+GL OB500 Prime or SECUROCK Gypsum -Fiber Roof OB500 SA, APP-TA BP -AA or APP-TA APP-TA -127.5 Board R-16 Existing Min. 1.5-inch ACFoam II, ENRGY 3, H-Shield M- Min. 0,25-inch SECUROCK Gypsum -Fiber M- BP AA SBS- (Optional) One or more SBS-AA, SBS-TA or asphaltic roof or Multi -Max FA3 OSFA Roof Board OSFA SA, APP-TA BP -AA or APP-TA APP-TA -157.5 Min. 1.5-inch Ultra -Max or Multi -Max FA-3, R-17 Existing min. 1.3-inch ACFoam III or min. 1.0-inch Min. 0.25-inch SECUROCK Gypsum -Fiber (Optional) One or more asphaltic roof ISO 95+GL, H-Shield, H-Shield CG or ENRGY CR-20 Roof Board CR-20 BP -AA BP -AA SBS-AA -225.0 3 or min. 2.0 pcf Insulfoam _ Min. 1.5-inch Ultra -Max or Multi -Max FA-3, R-18 Existing min. 1.3-Inch ACFoam III or min. 1.0-inch CR-20 Min. CL- 5-Inch SECUROCK-Gypsum-FibeP (Optional) One-ormore-TA asphaltic roof ISO 95+GL, H-Shield, H-Shield CG or ENRGY Roof Board CR-20 APP-TA APP-TA TA 232.5 3 or min. 2.0 pcf Insulfoam IAgLE7B RE COVERAPPLICA�IONS t ' { SfSTENI TYPE F+ � r ; ' , ,,. _,.. ..:. : , • . _. , - ,. ;'.' -;� , L NOAI°1NSl1LATEDwBONOE[��BASESHEETv8OM1i0�0ROQF�CON�Ft � � r System Deck Primer I Roof Cover (Note 15) MOP IBase Ply Ply Cap Ply No. (psf) R-19 Existing asphaltic roof ASTM D41 BP -AA (Optional if using asphalt applied Ply) (Optional if using asphalt applied Base) BP -AA or APP-TA SBS-AA, SBS-TA, APP-TA -45.0 Exterior Research and Design, I.I.C. d/b/a Trinity ) ERD Evaluation Report A42970.10.12-R2 for FL16027-R2 Certificate of Authorization #9503 6rn EDITION (2017) FBC NON-HVHZ EVALUATION Revision 2: 09/25/2017 Prepared by: Robert Nieminen, PE-59166 TRI-BUILT Modified Bitumen Roof Systems; (800) 516-148S Appendix 1, Page 26 of 26