ENGINEERING & TESTING, INC.
Phone: (866) 781-6889 *Fax: (866) 784-8550
www.floiidaenginecringandtesting.com
SCANNED 250 SM.13 Avenue
BY Pompano Beach, FL 33069
DATE: 2/28/18 JOB ORDER #: 18-859
CLIENT: All Area Roofing
ADDRESS: 3921 S. US Highway 1 Fort Pierce, Florida 34982
I
PROJECT: Schwartz Residence EMAX Rib 29 GA. Steel Roof Panels
ADDRESS: 656 SE Hidden River Drive Pt St Lucie, FL 34983
2017 FBC/ASCE-7 DESIGN PRESSURE CALCULATIONS
Proiect Information:
Mean Height = 10' Exposure: C Basic/Ultimate Wind Speed: V,,I =170 mph
Length = 65' Category: II Nominal Wind Speed: V.d=V,,it*q0.6
Width = 45' Slope: 6/12 = 26.6° _ (asd = allowable strength design)
Parapet Wall: N/A Residential KZ = 0.85, Kzt =1.0, Kd = 0.85
Design Calculations:
Velocity Pressure: q = 0.00256*KZK,tKdV2
Velocity Pressure („ lt): q=0.00256(0.85)(1.0)(0.85)(170)2] = 53.45 psf
Velocity Pressure (mod): q=0.00256(0.85)(1.0)(0.85)(170*�0.6)2] = 32.07 psf
Width of Pressure Coefficient: 0.1(45')
0.4(10')
Effective Wind Area: <1 Oft
External Pressure Coefficient:
1)
GCP1
= -0.9
2)
GCP2
= -1.7
3)
GCP3
= -2.6
Design Pressures Based on Vasd: ,
= 4.5'
= 4.0' } use: 4'0"
Internal Pressure Coefficient:
1) GCP; = 0.18
1) Field P1 = 32.07*[(-0.9) — (0.18)] = -34.6 psf
2) Perimeter P2 = 32.07* [(- 1.7) — (0.18)] = -60.3 psf
3) Corners P3 = 32.07* [(-2.6) — (0.18)] = -89.2 psf
Qualay ;�`�A��i ✓lswirance
1
Page 2, 2/28/18, Job Urger #18-859
All Area Roofing
Schwartz Residence
EMAX Rib 29 GA. Steel Roof Panels
656 SE Hidden River Drive; Pt St Lucie, FL 34983:
Attachment Requirements:
F11,011IT3A
Based on the requirements of Florida Product Approval # 17022.8 with maximum design
pressures of -86psf for the field and-146psf for the perimeter and corner zones; the
following are our recommended fastening patterns to attach the Extreme Metal
Fabricators, LLC's EMAX Rib 29 GAS Steel Roof Panels to the 15/32" plywood or wood
deck with #10xl-1/2" (min.) Hex Washer Head Wood Screw to penetrate 3/16" (min.)
thru bottom of support spaced at 9"o.c. across panel width and on each side and panel
overlap as follows:
Field
Perimeter & Corner
Area
(Method 1
Method 2)
Maximum Total Uplift
-86psf
-146psf
Design Pressure
Fastener Row Spacing (Max.)
24"
12"
Fastener Spacing Located Per
9''-9"-9"-9"
9"-9"-9"-9"
Details(Along Rows
Panel Side Laps Fastener
12" o.c. along panel length for all roof zones with
Spacing
414x7/8" min. Hex -Washer Head Self -Drilling Screws
Notes: Corners and perimeter (edge, hip, & ridge) area dimension shall not be less
than a = 4'0" (Zone 2: Perimeter (including along ridges) is a 410" wide
strip, Zone 3: Corners are 410" x 41011)
Contractor to verify that the- fastening patterns meet manufacturer's
requirements for issuance of a warranty (as applicable).
All work shall be in compliance with the local building code product control
notice of acceptance and manufacturer specifications and Florida Building
Code 2017 Edition.
Wind load calculations based on ASCE-7, 2017 FBC, and information
provided by client. Client is responsible for verifying existing conditions as it
pertains to the above provided product approval.
All work shall be inspected by our field engineer (or authorized
representative) or a building department inspector to verify compli c with
\1l1efl/1 ` specifications.