Loading...
HomeMy WebLinkAboutENGINEERINGJ� ENGINEERING & TESTING, INC. Phone: (866) 781-6889 *Fax: (866) 784-8550 www.floiidaenginecringandtesting.com SCANNED 250 SM.13 Avenue BY Pompano Beach, FL 33069 DATE: 2/28/18 JOB ORDER #: 18-859 CLIENT: All Area Roofing ADDRESS: 3921 S. US Highway 1 Fort Pierce, Florida 34982 I PROJECT: Schwartz Residence EMAX Rib 29 GA. Steel Roof Panels ADDRESS: 656 SE Hidden River Drive Pt St Lucie, FL 34983 2017 FBC/ASCE-7 DESIGN PRESSURE CALCULATIONS Proiect Information: Mean Height = 10' Exposure: C Basic/Ultimate Wind Speed: V,,I =170 mph Length = 65' Category: II Nominal Wind Speed: V.d=V,,it*q0.6 Width = 45' Slope: 6/12 = 26.6° _ (asd = allowable strength design) Parapet Wall: N/A Residential KZ = 0.85, Kzt =1.0, Kd = 0.85 Design Calculations: Velocity Pressure: q = 0.00256*KZK,tKdV2 Velocity Pressure („ lt): q=0.00256(0.85)(1.0)(0.85)(170)2] = 53.45 psf Velocity Pressure (mod): q=0.00256(0.85)(1.0)(0.85)(170*�0.6)2] = 32.07 psf Width of Pressure Coefficient: 0.1(45') 0.4(10') Effective Wind Area: <1 Oft External Pressure Coefficient: 1) GCP1 = -0.9 2) GCP2 = -1.7 3) GCP3 = -2.6 Design Pressures Based on Vasd: , = 4.5' = 4.0' } use: 4'0" Internal Pressure Coefficient: 1) GCP; = 0.18 1) Field P1 = 32.07*[(-0.9) — (0.18)] = -34.6 psf 2) Perimeter P2 = 32.07* [(- 1.7) — (0.18)] = -60.3 psf 3) Corners P3 = 32.07* [(-2.6) — (0.18)] = -89.2 psf Qualay ;�`�A��i ✓lswirance 1 Page 2, 2/28/18, Job Urger #18-859 All Area Roofing Schwartz Residence EMAX Rib 29 GA. Steel Roof Panels 656 SE Hidden River Drive; Pt St Lucie, FL 34983: Attachment Requirements: F11,011IT3A Based on the requirements of Florida Product Approval # 17022.8 with maximum design pressures of -86psf for the field and-146psf for the perimeter and corner zones; the following are our recommended fastening patterns to attach the Extreme Metal Fabricators, LLC's EMAX Rib 29 GAS Steel Roof Panels to the 15/32" plywood or wood deck with #10xl-1/2" (min.) Hex Washer Head Wood Screw to penetrate 3/16" (min.) thru bottom of support spaced at 9"o.c. across panel width and on each side and panel overlap as follows: Field Perimeter & Corner Area (Method 1 Method 2) Maximum Total Uplift -86psf -146psf Design Pressure Fastener Row Spacing (Max.) 24" 12" Fastener Spacing Located Per 9''-9"-9"-9" 9"-9"-9"-9" Details(Along Rows Panel Side Laps Fastener 12" o.c. along panel length for all roof zones with Spacing 414x7/8" min. Hex -Washer Head Self -Drilling Screws Notes: Corners and perimeter (edge, hip, & ridge) area dimension shall not be less than a = 4'0" (Zone 2: Perimeter (including along ridges) is a 410" wide strip, Zone 3: Corners are 410" x 41011) Contractor to verify that the- fastening patterns meet manufacturer's requirements for issuance of a warranty (as applicable). All work shall be in compliance with the local building code product control notice of acceptance and manufacturer specifications and Florida Building Code 2017 Edition. Wind load calculations based on ASCE-7, 2017 FBC, and information provided by client. Client is responsible for verifying existing conditions as it pertains to the above provided product approval. All work shall be inspected by our field engineer (or authorized representative) or a building department inspector to verify compli c with \1l1efl/1 ` specifications. �i��N'/ Sincerely, :NS� ekwi,�� ®� No. 4 an ®=.' 2- .m Mark A. Mesianv�l,� STATE of Florida Engineerin',T c. ,� Florida Reg. No. 4 �.�+/ � G�� ®-Z Certificate of Author zAip M